Plan Review Details - Permit 06050449
Plan Review Stops For Permit 06050449
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By lursu Date 2006-05-15 Time 14:53 Rev Time 0.00
Received By lursu Date 2006-05-15 Time 14:52 Sent To  
Notes
2006-05-15 00:00:00CREATE EXT# 0012 FOR THE UNIT #146 UNDER
 THE MAIN ADDRESS 550 S ROSEMARY AVE

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-06-28 Cont ID  
Sent By lursu Date 2006-06-28 Time 09:05 Rev Time 0.00
Received By lursu Date 2006-05-10 Time 10:49 Sent To  
Notes
2006-05-10 00:00:00EXT REQUIRED FOR STE #146

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-31 Cont ID  
Sent By alange Date 2006-10-31 Time 13:16 Rev Time 0.00
Received By alange Date 2006-10-31 Time 12:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-28 Cont ID  
Sent By alange Date 2006-06-28 Time 09:13 Rev Time 0.00
Received By alange Date 2006-06-28 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-05-24 Cont ID  
Sent By alange Date 2006-05-24 Time 09:37 Rev Time 2.00
Received By alange Date 2006-05-24 Time 09:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-02-18 Cont ID  
Sent By dpalmer Date 2007-02-18 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2007-02-18 Time 16:22 Sent To  
Notes
2007-02-18 16:34:32ELEC OK,STAMPED

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-12-10 Cont ID  
Sent By dpalmer Date 2006-12-10 Time 09:07 Rev Time 0.00
Received By dpalmer Date 2006-12-10 Time 08:33 Sent To  
Notes
2006-12-10 09:08:43******* UNSAT5TH REVIEW********
  
 ** PLEASE KNOW THIS IS THE FIFTH TIME PLANS HAVE BEEN
 REVIEWED, HOWEVER ONLY THE SECOND TIME ACTUALLY UNDER
 PERMIT APPLICATION. PLEASE SEE NOTE BELOW WITH RESPECT
 TO FLORIDA STATUTES WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEWS WHICH
 STILL NEED TO BE ADDRESSED.
  
  
  
 1) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
 PLEASE SEE LOAD SHOWN ON TRANSFORMER PLACES LOAD AT
 44.97KVA ON PREVIOUS PLANS AND NOW 47.92 WHICH
 INDICATES LOADS EXCEEDING TRANSFORMER AS SHOWN. PLEASE
 SEE ABOVE NOTES, AS CONTINUOUS LOADS WILL PLACE THIS
 LOAD OVER RATING OF SAID 45KVA UNIT.
 PLEASE CLARIFY WHAT APPEARS TO BE ADDITIONAL LOAD ON
 "PA"? HOW, ARE THESE LOADS DIFFERENT OF THAT ON "DP"?
 PLEASE SHOW COMPLETE LOAD CALCULATIONS PER ABOVE AND
 220.3, 220.10, 220.11, 220.13
 ETC. AND 215.3, 230.42 ETC
  
 2) NOTE:PREVIOUS NOTES BELOW WHICH HAVE NOT BEEN
 ADDRESSED. PLEASE SEE RESPONSE LETTER MENTIONS
 OCCUPANCY SENSORS WERE ADDED HOWEVER THIS DOES NOT
 COMPLETE COMMENTS FROM PREVIOUS REVIEWS.
 PLEASE SEE MISSING SCHEDULING.
 PLEASE SEE MAXIMUM TIMES FOR DEVICES.
 PLEASE SEE TIME CLOCK STILL SHOWN, HOWEVER NO
 CIRCUITING ETC.
 PLEASE SEE NO LIGHTING POWER DENSITIES?
 PLEASE KNOW BASED ON INFORMATION AS SUBMITTED A
 COMPLETE REVIEW CAN NOT BE DONE.
 ** PLEASE SEE 700.12E AS ALL EM/ EXT LTS SHALL BE
 INDICATED AHEAD OF ANY OC/TIMER TYPE DEVIE.
  
 ** PREVIOUS REVIEW NOTES FROM THE TWO PREVIOUS REVIEWS
 ALONE. **
 NO, PLEASE SEE CONTROLS FOR ALL SEPARATE SPACES DO NOT
 SEEM TO BE INDICATED.(BATHRM) PLEASE SEE "S" ARE BEING
 NOTED IN RESPONSE LTR AND SHOWN AS OC , HOWEVER IF
 THESE DEVICES ARE LOCATED BEHIND WALL WHICH SEPARATES
 STORAGE/BACK AREA FROM STORE SALES AREAS, HOW WOULD
 THESE OCSENSOR TYPE SWITCHES BE EFFECTIVE. PLEASE
 INDICATE THE NORMAL SCHEDULING TIME OF DAY. PLEASE
 CLARIFY WHERE THE MAX TIMES PERMITTED ON THE DEVICES AS
 CHOSEN IS LOCATED ON PLANS? (OC TYPE 30MINS) (TIMER
 TYPE 4HRS MAX).
 PLEASE SEE MISSING THE PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.2.ABC.1, TABLES, 415.2.C.1, 415.2.B.1
 PLEASE SHOW A BREAK DOWN ON MAX LIGHTING POWER
 DENSITIES.
  
 ** PREVIOUS REVIEW NOTES**
 PLEASE SEE FBC 2004 CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2, AND .1.3.
 PLEASE SEE SPACE IS IN A BUILDING GREATER THAN 5000 SQ
 FT AND CONTROLS FOR LIGHTING WILL BE REQUIRED (SHOWN),
 HOWEVER PLEASE SEE .1.2, AND .1.3 AS CONTROLS FOR
 SEPARATE SPACES WITH FLR TO CEILING PARTITIONS ARE
 REQUIRED. PLEASE SEE PERMITTED TYPE OF DEVICES AS
 "TIMER" TYPE OVER RIDES ARE ONLY PERMITTED TO OVER RIDE
 NORMAL SCHEDULING A MAX OF 4HRS. PLEASE SEE ANY
 OCCUPANCY SENSOR(S) TYPE DEVICES SHALL ONLY PERMIT A
 MAX OF 30 MINS. PLEASE SHOW LOCATION OF THESE OVER
 RIDES DEVICES AND PLEASE SEE THESE ARE REQUIRED AT THE
 POINT OF ENTRANCE INTO SPACE SO THE OCCUPANT CAN
 VISUALLY SEE LTS BEING CONTROLLED. PLEASE SEE EXCEPTION
 FOR OCC SENSORS. PLEASE SEE BATH R, STOCK RM ETC,,,
 IT IS NOTED BY THIS OFFICE THAT A TIME CLOCK IS BEING
 PROVIDED, HOWEVER PLEASE SEE ABOVE FOR OTHER
 REQUIREMENTS.
  
 3) NOTE: PLEASE SEE NOTE #1, BASED ON THE UNCERTAINTY
 OF LOADS ON THE TRANSFORMER, THE RISER MAY BE NEEDING
 TO BE REVISED AS STATED ON PREVIOUS REVIEWS. THE
 TRANSFORMER WAS CHANGED ONCE TO 75 KVA WHICH WAS OK,
 HOWEVER NOT ALL AREAS OF PLANS WERE REVISED TO
 CORRELATE WITH THIS.
  
 4) NOTE:PLEASE SEE AS NOTED ON PREVIOUS REVIEWS, DO
 NOT USE THE "RUBBER STAMP" WHICH CONTAINS THE WORDING
 OF "CERTIFICATE" FOR SEAL. IT IS NOTED THAT A RAISED
 SEAL IS BEING PLACED OVER THIS RUBBER STAMP.
 THE RUBBER STAMP FOR USE IN THE STATE OF FLORIDA IS NOT
 PERMITTED AND SEEING THAT IT WORDING IS NO LONGER
 VALID, PLEASE DO NOT USE.
 FAC 61G15-23.001, FS 471.025
 AS PREVIOUSLY NOTED.
  
 5) NOTE: PLEASE SEE AS NOTED ABOVE, PLEASE SEE FLORIDA
 STATUTES 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE AS THIS IS ONLY THE 2ND REVIEW UNDER PERMIT
 APPLICATION THE FEE AS MENTIONED IN THE ATTACHED SHEET
 IS NOT ASSESSED, HOWEVER IF PLANS COME BACK WITH ANY OF
 THE ITEMS IN THE NOTES ABOVE NOT ADDRESSED, A 4X FEE IS
 ASSESSED TO THE DESIGN PROFESSIONAL BASED ON THE
 PORTION OF BASE PERMIT FEE ATTRIBUTED TO PLAN REVIEW.
 *** PLEASE KNOW AT THIS TIME, ONE SET OF ME PLANS WILL
 BE RETAINED AND HELD IN FILE FOR POSSIBLE REVIEW BY THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS AND LEGAL
 COUNSEL TO THE BOARD.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 19:18 Rev Time 0.00
Received By dpalmer Date 2006-10-28 Time 18:27 Sent To  
Notes
2006-10-28 19:18:36******* UNSAT ********
  
 ** PLEASE SEE THIS IS THE FIRST REVIEW UNDER PERMIT.
  
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE:OK.
  
 4) NOTE: OK.
  
 5) NOTE:NO/ OK, PLEASE SEE TRANSFORMER SIZE NOW SEEMS
 TO HAVE BEEN CHANGED, HOWEVER PLEASE SEE ME-2.0 WHICH
 STILL INDICATES A 45KVA UNIT (NOTE #11).
 PLEASE SEEMIN OCP WHICH IS REQUIRED AS THE LOAD AT
 277/480V IS BEING SHOWN AT 75KVA, PLEASE SEE @THIS,
 THE OCP WOULD BE JUST OVER 90A'S WHICH IS BEING SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125%. 215.3,230.42 ETC.
 PLEASE SEE LOADSHOWN ON TRANSFORMER
 PLACES LOAD AT 44.97KVA. PLEASE SEE
 ABOVE NOTES, AS CONTINUOUS LOADS WILL
 PLACE THIS LOAD OVER RATING OF SAID
 45KVA UNIT.
 PLEASE CLARIFY WHAT APPEARS TO BE
 ADDITIONAL LOAD ON "PA"? HOW, ARE THESE
 LOADS DIFFERENT OF THAT ON "DP"?
 PLEASE SHOW COMPLETE LOAD CALCULATIONS
 PER ABOVE AND 220.3,220.10,220.11,220.13
 ETC. AND 215.3, 230.42 ETC
  
 6) NOTE: OK.
  
 7) NOTE:NO, PLEASE SEE CONTROLS FOR ALL SEPARATE
 SPACES DO NOT SEEM TO BE INDICATED.(BATHRM) PLEASE SEE
 "S" ARE BEING NOTED IN RESPONSE LTR AND SHOWN AS OC ,
 HOWEVER IF THESE DEVICES ARE LOCATED BEHIND WALL WHICH
 SEPARATES STORAGE/BACK AREA FROM STORE SALES ARES, HOW
 WOULD THESE OCSENSOR TYPE SWITCHES BE EFFECTIVE.
 PLEASE INDICATE THE NORMAL SCHEDULING TIME OF DAY.
 PLEASE CLARIFY WHERE THE MAX TIMES PERMITTED ON THE
 DEVICES AS CHOSEN IS LOCATED ON PLANS? (OC TYPE 30MINS)
 (TIMER TYPE 4HRS MAX).
 PLEASE SEE MISSING THE PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.2.ABC.1, TABLES, 415.2.C.1, 415.2.B.1
 PLEASE SHOW A BREAK DOWN ON MAX LIGHTING POWER
 DENSITIES.
  
 ** PREVIOUS REVIEW NOTES**
 PLEASE SEE FBC 2004 CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2, AND .1.3.
 PLEASE SEE SPACE IS IN A BUILDING
 GREATER THAN 5000 SQ FT AND CONTROLS FOR
 LIGHTING WILL BE REQUIRED (SHOWN),
 HOWEVER PLEASE SEE .1.2, AND .1.3 AS
 CONTROLS FOR SEPARATE SPACES WITH FLR TO
 CEILING PARTITIONS ARE REQUIRED. PLEASE
 SEE PERMITTED TYPE OF DEVICES AS "TIMER"
 TYPE OVER RIDES ARE ONLY PERMITTED TO
 OVER RIDE NORMAL SCHEDULING A MAX OF
 4HRS. PLEASE SEE ANY OCCUPANCY SENSOR(S)
 TYPE DEVICES SHALL ONLY PERMIT A MAX OF
 30 MINS. PLEASE SHOW LOCATION OF THESE
 OVER RIDES DEVICES AND PLEASE SEE THESE
 ARE REQUIRED AT THE POINT OF ENTRANCE
 INTO SPACE SO THE OCCUPANT CAN VISUALLY
 SEE LTS BEING CONTROLLED. PLEASE SEE
 EXCEPTION FOR OCC SENSORS.
 PLEASE SEE BATH R, STOCK RM ETC,,,
 IT IS NOTED BY THIS OFFICE THAT A TIME
 CLOCK IS BEING PROVIDED , HOWEVER
 PLEASE SEE ABOVE FOR OTHER REQUIREMENTS.
  
 8) NOTE:OK, HOWEVER SEE NOTE ABOVE WITH RESPECT TO
 THE SIZE AND OCP FOR UNIT. THESE MAY INDEED CHANGE.
  
 PLEASE SEE NOTES SHOW #8 FOR
 FEED TO TRANSFORMER, HOWEVER A 60A BRKR
 IS SHOWN. PLEASE SEE 310.16, 240.4,
 110.14, AS THE MAX OCP FOR THE #8' IS
 50A'S. PLEASE SEE 310.16 75 DEGREE
 COLUMN AS THE #8'S ARE RATED AT 50A'S.
 PLEASE ADJUST ONCE ALL CALCULATIONS ARE
 DONE.
  
 *** NEW NOTE **
 9) NOTE: PLEASE SEE RISER MENTIONS A NEW 150A
 DISCONNECTAT LANDLORDS METER CENTER, IF PART OF THIS
 PERMIT, PLEASE COMPLETE RISER SHOWING THIS. IF NOT
 SEPARATE PERMIT AND PLANS WILL BE REQUIRED FOR THIS
 INSTALLATION.
  
 10) NOTE: PLEASE BE SURE NEW "E" SHEETS ONLY CONTAIN
 THE RAISED SEAL PER FAC 61G15-23.001 FOR THE NEW
 WORDING "LICENSE" . THE OLDER SEALS WITH THE WORDING OF
 "CERTIFICATE ARE NO LONGER VALID. RULED PAST ON 2/04
 AND EXTENDED TO 12/31/05.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-07-24 Cont ID  
Sent By dpalmer Date 2006-07-24 Time 20:57 Rev Time 0.00
Received By dpalmer Date 2006-07-24 Time 19:58 Sent To PC
Notes
2006-07-24 00:00:00******* UNSAT ********
  
 ** PLEASE KNOW, ALL PLANS ARE REQUIRED
 TO HAVE THE STAMPED FROM CITY PLACE ON
 ALL SHEETS. PLEASE CONTACT CITY PLACE AT 561-820-0074
 PLEASE DO NOT SUBMIT WITHOUT STAMPS, AS
 PLANS MAY BE REJECTED ON THAT ALONE.
  
  
 ** PLEASE KNOW PLANS ARE STILL ONLY
 BEING SUBMITTED FOR "PLAN REVIEW" AND
 NOT FOR PERMIT.
  
 ** PLEASE SEE THE FOLLOWING COMMENTS ARE
 BASED ON PLANS SUBMITTED FOR THIS REVIEW
 ONLY AND PLANS DATED 7/6/06.
  
 1) NOTE: PLEASE SEE TITLE SHEET IS
 INDICATING A 2004 NATIONAL ELECTRICAL
 CODE, HOWEVER PLEASE KNOW, THERE IS NO
 2004 NEC AND PLEASE KNOW AS PER CHAPTER
 27 OF THE 2004 FBC, THE 2002 NEC IS
 CURRENTLY IN EFFECT. PLEASE REVISE AND
 ADJUST.
  
 2) NOTE: PLEASE SEE DESIGNATION BEHIND
 RECEPT CIRCUITING ON E 2.0 PLANS SHOW
 "E" AND "F" WHICH COULD NOT BE LOCATED
 ON SYMBOL LIST/
 PLEASE CLARIFY.
 106.1.2 FBC ADMIN SECT.
  
 3) NOTE: PLEASE SEE COLOR CODING FOR
 277/480V SHALL BE BROWN, PURPLE, YELLOW.
 IT IS UNCLEAR WHERE BLACK AND YELLOW
 STRIP COMES FROM?
 PLEASE KNOW, AS PER CITY AND PALM BEACH
 COUNTY LOCAL AMENDMENTSTHE ABOVE COLOR
 CODING HAS BEEN IN EFFECT FOR 25 PLUS
 YRS. PLEASE KNOW AS OF THE 2004 FBC
 LOCAL TECHNICAL AMENDMENTS DO NOT EXIST,
 HOWEVER COLOR CODING FOR CITY OF WEST
 PALM BEACH AND PALM BEACH COUNTY SHALL
 REMAIN THE SAME AS ALL CURRENT
 ELECTRICAL SYSTEMS IN BUILDINGS ARE
 CODED PER ABOVE ANDTHE NEC DOES NOT
 PROVIDE COLOR CODING FOR 277/480A.
 90.4
  
 4) NOTE: PLEASE PROVIDE LOAD
 CALCULATIONS INDICATING LOADS FOR TRACK
 LIGHTING PER 220.12B. PLEASE SHOW.
  
 5) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125%. 215.3,230.42 ETC.
 PLEASE SEE LOADSHOWN ON TRANSFORMER
 PLACES LOAD AT 44.97KVA. PLEASE SEE
 ABOVE NOTES, AS CONTINUOUS LOADS WILL
 PLACE THIS LOAD OVER RATING OF SAID
 45KVA UNIT.
 PLEASE CLARIFY WHAT APPEARS TO BE
 ADDTIONAL LOAD ON "PA"? HOW, ARE THESE
 LOADS DIFFERENT OF THAT ON "DP"?
 PLEASE SHOW COMPLETE LOAD CALCULATIONS
 PER ABOVE AND 220.3,220.10,220.11,220.13
 ETC. AND 215.3, 230.42 ETC
  
 6) NOTE: PLEASE SEE GROUNDING NOTE FOR
 TRANSFORMER MENTIONS TO GROUND UNIT TO
 EITHER BUILDING STEEL "OR" COLD WATER.
 PLEASE SEE 250.50, 250.66 ,
 250.20,250.30 AS BOTH WILL BE REQUIRED.
 PLEASE NOTE, THIS SHALL BE ATTACHED AND
 PART OF THE BUILDINGS GE SYSTEM.
  
 7) NOTE: PLEASE SEE FBC 2004 CHAPTER 13,
 13-415.1.ABC.1.1, .1.2, AND .1.3.
 PLEASE SEE SPACE IS IN A BUIDLIGN
 GREATER THAN 5000 SQ FT AND CONTROLS FOR
 LIGHTING WILL BE REQUIRED (SHOWN),
 HOWEVER PLEASE SEE .1.2, AND .1.3 AS
 CONTROLS FOR SEPARATE SPACES WITH FLR TO
 CEILING PARTITIONS ARE REQUIRED. PLEASE
 SEE PERMITTED TYPE OF DEVICES AS "TIMER"
 TYPE OVER RIDES ARE ONLY PERMITTED TO
 OVER RIDE NORMAL SCHEDULING A MAX OF
 4HRS. PLEASE SEE ANY OCCUPANCY SENSOR(S)
 TYPE DEVICES SHALL ONLY PERMIT A MAX OF
 30 MINS. PLEASE SHOW LOCATION OF THESE
 OVER RIDES DEVICES AND PLEASE SEE THESE
 ARE REQUIRED AT THE POINT OF ENTRANCE
 INTO SPACE SO THE OCCUPANT CAN VISUALLY
 SEE LTS BEING CONTROLLED. PLEASE SEE
 EXCEPTION FOR OCC SENSORS.
 PLEASE SEE BATH R, STOCK RM ETC,,,
 IT IS NOTED BY THIS OFFICE THAT A TIME
 CLOCK IS BEING PROIVIDED , HOWEVER
 PLEASE SEE ABOVE FOR OTHER REQUIREMENTS.
  
 8) NOTE: PLEASE SEE NOTES SHOW #8 FOR
 FEED TO TRANSFORMER, HOWEVER A 60A BRKR
 IS SHOWN. PLEASE SEE 310.16, 240.4,
 110.14, AS THE MEX OCP FOR THE #8' IS
 50A'S. PLEASE SEE 310.16 75 DEGREE
 COLUMN AS THE #8'S ARE RATED AT 50A'S.
 PLEASE ADJUST ONCE ALL CALCULATIONS ARE
 DONE.
  
  
 ** IMPORTANT**
  
 PLEASE SURE WHEN RESUBMITTING PLANS TO
 COMPLETELY REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE SET OF
 THE OLD/VOIDED SHEETS FOR REFERENCE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-21 Cont ID  
Sent By btrobaug Date 2006-06-21 Time 17:04 Rev Time 1.00
Received By btrobaug Date 2006-06-21 Time 16:57 Sent To  
Notes
2006-06-21 00:00:00 
 NONCOMPLIANT
  
  
 1} PLEASE SEE THE EMERGENCY LIGHTS MUST
 BE ON THE SAME CIRCUITS RTHE LIGHTING
 IN THE AREA PER 700.12(E), 2002 NEC.
  
 "THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES."
  
 THE EXCEPTION DOES NOT APPLY, THERE IS
 ONLY ONE CIRCUIT IN THE STORAGE ROOM.
  
 2} THE NOTE REGARDING THE 2005 CODE,
 "REVIEW COMMENTS", SHOULD BE CHANGED TO
 READ 2002 NEC, THE CURRENT NEC FOR THE
 STATE OF FLORIDA.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-17 Cont ID  
Sent By btrobaug Date 2006-05-17 Time 16:57 Rev Time 0.50
Received By btrobaug Date 2006-05-17 Time 16:19 Sent To  
Notes
2006-05-17 00:00:00 
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEER SEAL IS NOT CURRENT
 61G15-23.001 SEALS ACCEPTABLE TO THE
 BOARD.
 (1) PURSUANT TO SECTION 471.025, F.S.,
 THE BOARD HEREBY ESTABLISHES AS
 INDICATED BELOW THE FORMS OF EMBOSSING
 IMPRESSION SEALS
 WHICH ARE ACCEPTABLE TO THE BOARD. SAID
 SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES
 IN DIAMETER. ALL ENGINEERS MUST BE
 UTILIZING A SEAL
 AS ILLUSTRATED IN THIS RULE NO LATER
 THAN JANUARY 1, 2006.
  
 2} PLEASE SEE THE EMERGENCY LIGHTS MUST
 BE ON THE SAME CIRCUITAS RTHE LIGHTING
 IN THE AREA PER 700.12(EE), 2002 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-11-22 Cont ID  
Sent By mwennerg Date 2006-11-22 Time 14:37 Rev Time 0.00
Received By mwennerg Date 2006-11-22 Time 14:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-28 Cont ID  
Sent By nmccray Date 2006-06-28 Time 10:52 Rev Time 0.00
Received By nmccray Date 2006-06-28 Time 10:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-05-25 Cont ID  
Sent By mwennerg Date 2006-05-25 Time 13:59 Rev Time 0.00
Received By mwennerg Date 2006-05-25 Time 13:59 Sent To  
Notes
2006-05-25 00:00:00PLAN REVIEW ONLY
 NOT FOR PERMITTING
  
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-07 Cont ID  
Sent By adarroug Date 2007-02-07 Time 16:19 Rev Time 0.00
Received By adarroug Date 2007-02-07 Time 16:19 Sent To  
Notes
2007-02-18 16:22:53TO COMM BAORD #29
2007-02-07 16:19:48WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-30 Cont ID  
Sent By adarroug Date 2006-11-30 Time 11:07 Rev Time 0.00
Received By adarroug Date 2006-11-30 Time 11:06 Sent To  
Notes
2006-12-10 08:33:54TO COMM BAORD #64
2006-11-30 11:07:57WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 09:23 Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 09:23 Sent To  
Notes
2006-10-26 13:15:13TO "COMM" BD#29
2006-10-25 09:25:54WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 12:12 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 12:12 Sent To E
Notes
2006-07-22 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 11:11 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 11:11 Sent To  
Notes
2006-06-21 00:00:00TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-01 Time 11:07 Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 14:40 Sent To  
Notes
2006-05-15 00:00:00TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2007-02-20 Cont ID  
Sent By tgordon Date 2007-02-20 Time 16:44 Rev Time 0.20
Received By tgordon Date 2007-02-20 Time 16:44 Sent To  
Notes
2007-02-20 16:45:43NO MECHANICAL WORK TO BE DONE, MECH. PERMIT # 06100828
 HAS BEEN VOIDED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-12-12 Time 14:07 Rev Time 0.30
Received By tgordon Date 2006-12-12 Time 14:07 Sent To  
Notes
2006-12-12 14:14:08*** DENIED ***
 1) PLANS PAGES ME-1.0, ME-2.0, AND ME-3.0 SHOW NO
 MECHANICAL WORK TO BE DONE THAT REQUIRES A MECHANICAL
 PERMIT. PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW OR IF
 NO MECHANICALWORK THAT REQUIRES A PERMIT IS TO BE
 DONE, PLEASE VOID YOUR MECHANICAL PERMIT #06100828.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-31 Cont ID  
Sent By tgordon Date 2006-10-31 Time 09:41 Rev Time 0.30
Received By tgordon Date 2006-10-31 Time 09:41 Sent To  
Notes
2006-10-31 09:46:03*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW.
 MECHANICAL PERMIT # 06100828 WAS APPLIED FOR PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC/ WPB
 AMEND. 106.3.5.1.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-31 Cont ID  
Sent By tgordon Date 2006-05-15 Time 15:19 Rev Time 0.15
Received By tgordon Date 2006-05-15 Time 15:19 Sent To  
Notes
2006-05-15 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.

Review Stop P PLUMBING
Rev No 4 Status N Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 07:39 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 07:39 Sent To  
Notes
2007-03-10 07:40:04NO PLUMBING WORK SHOWN ON PLANS,

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-11-02 Cont ID  
Sent By jleech Date 2006-11-02 Time 07:57 Rev Time 0.00
Received By jleech Date 2006-11-02 Time 07:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-06-23 Cont ID  
Sent By jleech Date 2006-06-23 Time 09:52 Rev Time 0.00
Received By jleech Date 2006-06-23 Time 09:52 Sent To  
Notes
2006-06-23 00:00:00NO PLUMBING WORK SHOWN ON PLANS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-01 Cont ID  
Sent By jleech Date 2006-06-01 Time 09:10 Rev Time 0.00
Received By jleech Date 2006-06-01 Time 09:10 Sent To  
Notes
***NONE***