Plan Review Details - Permit 06050381
Plan Review Stops For Permit 06050381
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-08-22 Cont ID  
Sent By mperson Date 2006-08-22 Time 10:01 Rev Time 0.33
Received By mperson Date 2006-08-22 Time 10:01 Sent To PC
Notes
2006-08-22 00:00:00REVISION: DELETE TANKLESS WATER HEATER
 AND PIPE TO HEATER. CHANGED SIZE OF PIPE
 TO GENERATOR. REFERENCE GEN/RES PERMIT
 #06040588

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-06-12 Cont ID  
Sent By mperson Date 2006-06-12 Time 10:34 Rev Time 0.33
Received By mperson Date 2006-06-12 Time 10:34 Sent To PC
Notes
2006-06-12 00:00:00 
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 9,950 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By mperson Date 2006-05-12 Time 10:01 Rev Time 0.33
Received By mperson Date 2006-05-12 Time 10:01 Sent To PC
Notes
2006-05-12 00:00:00****** DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. GAS PERMIT CAN'T BE ISSUED UNTIL THE
 GEN/RES PERMIT APPLICATION IS APPROVED
 BY ZONING FOR THE GENERATOR LOCATION.
 ZONING FAILED GEN/RES PERMIT APPLICATION
 4/25/06, SEE ATTACHED ZONING PERMIT PLAN
 REVIEW.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 15:19 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 15:19 Sent To G
Notes
2006-08-16 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-27 Cont ID  
Sent By adarroug Date 2006-05-27 Time 13:11 Rev Time 0.00
Received By adarroug Date 2006-05-27 Time 13:11 Sent To G
Notes
2006-05-27 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-12 Cont ID  
Sent By mperson Date 2006-05-12 Time 10:16 Rev Time 0.00
Received By mperson Date 2006-05-11 Time 13:14 Sent To  
Notes
2006-05-11 00:00:00TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved