Plan Review Details - Permit 06050265
Plan Review Stops For Permit 06050265
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-25 Cont ID  
Sent By alange Date 2006-05-25 Time 16:30 Rev Time 2.50
Received By alange Date 2006-05-25 Time 16:21 Sent To  
Notes
2006-05-25 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SIGN OWNER/AGENT ON ENERGY CALCS PER
 2004 FBC.
  
 3.WRONG PRODUCT APPROVAL FOR GARAGE
 DOORS.INCORRECT SIZE.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 5.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 6.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.SHOW DRAINAGE
 ON PLANS.
  
 7.DESIGN CRITERIA SHOULD BE ASCE 7-02.
  
 8.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.CHECK CODE
 SECTIONS USED. STAIR CALCS. SEE A-1
 SHOULD BE FBC 2004 RESIDENTIAL CODE.
  
 9.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS FS 472.025
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-10 Cont ID  
Sent By btrobaug Date 2006-05-10 Time 18:11 Rev Time 1.00
Received By btrobaug Date 2006-05-10 Time 14:07 Sent To Z
Notes
2006-05-10 00:00:00 
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PANEL "C" IS NOT LISTED IN PANEL "A".
 PLEASE ADD PANEL "C" TO THE SCHEDULE IF
 THATS WHERE ITS FED FROM AS THE RISER
 INDICATES.
  
 2} TO COMPLY WITH ARTICLE 250.52(A)(3),
 THE GROUNDING ELECTRODE SYSTEM MUST
 INCLUDE FOOTING STEEL. PLEASE INDICATE
 SAME ON THE RISER.
  
 3} PLEASE SEE CIRCUIT #2/4 OVEN, PANEL
 "A". THE OCP@60 AMPS IS TOO LARGE FOR
 THE #8 WIRE, 310.16.
  
 4} PLEASE SEE 680.70 FOR JACUZZI GFI
 REQUIREMENTS AND INDICATE COMPLIANCE ON
 PANEL SCHEDULE OR AT THE UNITS.
  
 5} THE DINING ROOM RECEPTACLES DO NOT
 SHOW A FEED AND NONE ON THE SCHEDULES.
 SEE 210.52(B)(1), NO OTHER OUTLETS.
  
 6} THE BREAKFAST ROOM IS SHARING A
 CIRCUIT WITH THE FAMILY ROOM. SEE
 210.52(B)(1).
  
 7} THE CABANA BATH IS ON THE SAME
 CIRCUIT WITH THE LAUNDRY, SEE
 210.11(C)(2) AND 210.11(C)(3).
  
 8} CIRCUIT A-17 MUST COMPLY WITH
 210.11(C)(3), AND HAVE NO OTHER OUTLETS.
 THE RECEPTACLE AT AC#2 IS SHOWN ON THAT
 CIRCUIT.
  
 9} THE SMOKE DETECTORS ARE REQUIRED TO
 BE INTERCONNECTED PER R313.1 RESIDENTIAL
 FBC. PLEASE NOTE THEY ARE BEING SHOWN ON
 CIRCUITS C-33 AND B-6. VERIFY THEY CAN
 BE ON TWO CIRCUITS AND STILL
 INTERCONNECT, IF SO PLEASE SUBMIT THAT
 SPEC. ALSO ARC FAULT IS REQUIRED ON ALL
 BEDROOM "OUTLETS" PER 210.12. NOTE THE
 ARTICLE DOES NOT INDICATE THEY MUST BE
 ON A BEDROOM CIRCUIT, A SEPERATE ARC
 FAULT BREAKER WILL MEET THE INTENT.
  
 10} THE FRONT BALCONY RECEPTACLE CANNOT
 BE ON WITH THE BATHROOM RECEPTACLES. SEE
 B-11, SECOND FLOOR. 210.11(C)(3).
  
 11} SEE CIRCUIT B-15, BATH #5, AND
 BALCONY OFF BED ROOM #5, RECEPTACLES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-05-30 Cont ID  
Sent By jleech Date 2006-05-30 Time 08:44 Rev Time 0.00
Received By jleech Date 2006-05-30 Time 08:44 Sent To  
Notes
2006-05-30 00:00:00DENIED;
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-30 Cont ID  
Sent By jleech Date 2006-05-30 Time 08:49 Rev Time 0.00
Received By jleech Date 2006-05-08 Time 10:28 Sent To  
Notes
2006-05-08 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By tgordon Date 2006-05-12 Time 09:09 Rev Time 1.30
Received By tgordon Date 2006-05-12 Time 09:09 Sent To P
Notes
2006-05-12 00:00:00*** DENIED ***
 1)PLEASE SUBMIT A MANUAL J CALCULATION,
 PER 2004 FBC 13-607.1.ABC.1 .
  
 2) RETURN AIR TRANSFER DUCT TO MASTER
 BEDROOM IS TO SMALL, SEE NOTE #8.
  
 3) 2ND FLOOR RETURN AIR TRANSFER DUCTS
 ARE ALL TO SMALL, SEE NOTE #8.
  
 4) PLEASE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR GAS FIRE PLACE.
  
 5) PLUMBING PLANS PAGE P-4 GAS DIST. IS
 SHOWING A GAS DRYER, PLEASE PROVIDE
 COMBUSTION AIR IN LAUNDRY-ROOM FOR GAS
 DRYER, ON MECHANICAL PLANS PER 2004
 FBC/M 701.1 .
  
 6) PLUMBING PLANS PAGE P-4 GAS DIST. IS
 SHOWING A GAS BBQ GRILL PLEASE SHOW ON
 MECHANICAL PLANS AND SUBMIT DETAILED
 MANUFACTURE'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS.
  
 7) PLEASE SHOW ON MECHANICAL PLANS PAGE
 M-3 A/C SCHEDULE, EACH SYSTEM'S SENSIBLE
 BTU'S.
  
 8)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-30 Cont ID  
Sent By jleech Date 2006-05-30 Time 08:33 Rev Time 0.00
Received By jleech Date 2006-05-30 Time 08:33 Sent To  
Notes
2006-05-30 00:00:00DENIED;
 SANITARY ISOMETRIC;
 1.BRANCH DRAIN TO AUTOMATIC CLOTHES
 WASHER TO BE 3" FBC-2004 PLUMBING SEC.
 406.3.
 2.LAUNDRY TUB IS REQUIRED DOWN STREAM OF
 THE BATHROOM GROUP. SEC.909.1
 WATER ISOMETRIC;
 1.WATER HAMMER ARRESTORS ARE REQUIRED
 FOR ICE MACHINE, REF. AND HOT SIDE OF
 KITCHEN SINK. PER 604.9 SHOW ON DRAWING
 .
 2.P&T DISCHARGE PIPE CANNOT BE TRAPED
 AND A AIR GAP FITTING IS REQUIRED PER
 SEC. 504.6.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2006-05-11 Cont ID  
Sent By mmclean Date 2006-05-11 Time 14:34 Rev Time 0.00
Received By mmclean Date 2006-05-11 Time 14:34 Sent To P
Notes
2006-05-11 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE WITH EASEMENT APPROVAL FROM THE
 CITY OF WEST PALM BEACH UTILITY DEPT.
  
 MUST MEET THE VISIBILITY TRIANGLE ON
 GRANADA RD & S OLIVE AVE.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK, MEETING THE REQUIRED SIDE
 SETBACK OF 10FT ON THE CORNER (GRANADA
 RD & S OLIVE AVE).