Plan Review Details - Permit 06050236
Plan Review Stops For Permit 06050236
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-05-08 Cont ID  
Sent By lursu Date 2006-05-08 Time 17:24 Rev Time 0.00
Received By lursu Date 2006-05-08 Time 17:24 Sent To  
Notes
2006-05-08 00:00:00PERMIT ASSIGNED TO EXT #0016 @15151 N
 FLAGLER DR #920
2006-05-05 00:00:00PLEASE ADD EXTENSION FOR SUITE # 920

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-12 Cont ID  
Sent By mjacobs Date 2006-06-10 Time 16:14 Rev Time 0.00
Received By mjacobs Date 2006-06-10 Time 06:06 Sent To  
Notes
2006-06-10 00:00:00PROVISO:
 EACH EGRESS DOOR SHALL BE READILY
 OPENABLE IN THE DIRECTION OF EGRESS
 TRAVEL WITHOUT THE USE OF KEYS SPECIAL
 KNOWLEGE OR EFFORT. SEE DOOR #2 IN
 VESTIBLE AREA.THE EXIT DOOR FACING THE
 ELECTRIAL ROOM, THE DOUBLE DOORS TO THE
 RIGHT AND BOTH SINGLE DOOR IN THE
 CIRRIDOR LEADING TO THE STAIRS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-16 Cont ID  
Sent By mjacobs Date 2006-05-16 Time 11:34 Rev Time 0.00
Received By mjacobs Date 2006-05-16 Time 07:04 Sent To  
Notes
2006-05-16 00:00:001) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
 2) A DETAIL ELEVATION DRAWING SHOWING
 THE CLEAR FLOOR SPACE AND FORWARD
 APPROCH FOR THE SINK IN THE LOUNGE AREA.
 ALSO A DETAIL DRAWING OF EACH NEW WALL.
 FBC. SEC 11-4.24 AND ALL SUB SECTIONS.
  
 3) SHOW THE NEW LIFESAFETY ROUTE FOR
 EGRESS.
  
 4) NOW THAT THIS SPACE IS CLOSED OFF
 FROM THE OTHER SPACE, SHOW THE RESTROOMS
 FOR THE ADJACENT OFFICE SPACE
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-12 Cont ID  
Sent By btrobaug Date 2006-06-12 Time 08:56 Rev Time 0.75
Received By btrobaug Date 2006-06-12 Time 07:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-05-12 Cont ID  
Sent By btrobaug Date 2006-05-12 Time 16:26 Rev Time 0.75
Received By btrobaug Date 2006-05-12 Time 16:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-16 Cont ID  
Sent By mwennerg Date 2006-06-16 Time 11:03 Rev Time 0.00
Received By mwennerg Date 2006-06-16 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-17 Cont ID  
Sent By mwennerg Date 2006-05-17 Time 09:25 Rev Time 0.00
Received By mwennerg Date 2006-05-17 Time 09:25 Sent To  
Notes
2006-05-17 00:00:00***DENIED***
  
 1) A DIRECTIONAL EXIT SIGN IS REQUIRED
 AT THE END OF HALL 'A' TO DIRECT PERSONS
 FROM OFFICES IN THAT AREA.
  
 2) PLEASE SEE BUILDING REVIEW COMMENT
 #3.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION. SHT A-1.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-05 Cont ID  
Sent By adarroug Date 2006-06-05 Time 10:50 Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 10:50 Sent To  
Notes
2006-06-05 00:00:00TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-17 Cont ID  
Sent By adarroug Date 2006-05-17 Time 10:39 Rev Time 0.00
Received By rbrown Date 2006-05-08 Time 08:51 Sent To  
Notes
2006-05-10 00:00:00TO "BOB"#8
2006-05-08 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-05-11 Cont ID  
Sent By tgordon Date 2006-05-11 Time 11:16 Rev Time 0.20
Received By tgordon Date 2006-05-11 Time 11:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-13 Cont ID  
Sent By jleech Date 2006-06-13 Time 06:35 Rev Time 0.00
Received By jleech Date 2006-06-13 Time 06:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-15 Cont ID  
Sent By jleech Date 2006-05-15 Time 13:55 Rev Time 0.00
Received By jleech Date 2006-05-15 Time 13:55 Sent To  
Notes
2006-05-15 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM; MECHANICAL
 VENTS CAN ONLY BE USED ON THE TOP 4
 FLOORS, PER. FBC-2004 PLUMBING SEC.
 917.3.1. IF SUITE IS MORE THAN 4 FLOORS
 FROM TOP VENT MUST BE RUN TO VENT STACK.
 2.BREAK SINK IS REQUIRED TO HAVE A
 FRONTAL APPROACH. MUST COMPLY WITH
 FBC-2004 CHAPTER 11. SEC'S ;
 11-4.24.3 KNEE CLEARANCE 27" HIGH
 30" WIDEAND 19" DEEP.
 11-4.24.4 SINK TO BE MAX. OF 6 1/2"
 DEEP.
 11-4.24.6 RAP EXPOSED PIPES.
 11-4.24.7 FAUCET TO BE LEVER
 OPERATED.
 SHOW A DETAIL ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  