Plan Review Details - Permit 06050213
Plan Review Stops For Permit 06050213
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-21 Cont ID  
Sent By jgomez Date 2007-05-21 Time 11:20 Rev Time 0.00
Received By jgomez Date 2007-05-21 Time 11:20 Sent To  
Notes
2007-05-21 11:20:57FOUNDATION REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-17 Cont ID  
Sent By alange Date 2006-11-17 Time 09:24 Rev Time 0.00
Received By alange Date 2006-11-17 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-26 Cont ID  
Sent By alange Date 2006-09-26 Time 09:02 Rev Time 1.50
Received By alange Date 2006-09-26 Time 09:02 Sent To  
Notes
2006-09-26 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $73,382.ADDITIONAL PERMIT FEES ARE
 DUE.
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-09 Cont ID  
Sent By alange Date 2006-06-09 Time 08:20 Rev Time 2.00
Received By alange Date 2006-06-09 Time 08:20 Sent To  
Notes
2006-06-09 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $73,382.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 4.PRODUCT APPROVALS REQUIRED FOR ALL
 EXTERIOR DOORS, WINDOWS, IMPACT
 PROTECTION, ROOFING, STRAPS AND TIE
 DOWNS AND LINTELS IN USED.
  
 5.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 7.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 8.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 9.ARCHITECTS SEAL AND SIGNATURE NOT ON
 ALL PAGES.
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 11.R403.1.4 MINIMUM DEPTH.
 ALL EXTERIOR FOOTINGS SHALL BE PLACED AT
 LEAST 12 INCHES BELOW THE UNDISTURBED
 GROUND SURFACE.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-12-21 Cont ID  
Sent By btrobaug Date 2006-12-21 Time 10:27 Rev Time 0.50
Received By btrobaug Date 2006-12-20 Time 18:13 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-11-16 Cont ID  
Sent By btrobaug Date 2006-11-16 Time 07:15 Rev Time 0.50
Received By btrobaug Date 2006-11-15 Time 17:24 Sent To M
Notes
2006-11-16 07:15:36 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEERING FIRM SHALL INDICATE
 THE CERTIFICATE OF AUTHORIZATIONNUMBER
 ALONG WITH OTHER INFORMATION REQUIRED BY 61G15-23.002
 FLORIDA ADMINISTRATIVE
 CODE
  
 2} THE BATH CIRCUIT REQUIRED BY 210.11(C)(3) DOES NOT
 APPEAR ON THE PANEL SCHEDULE. PLEASE INCLUDE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-11 Cont ID  
Sent By btrobaug Date 2006-09-11 Time 09:58 Rev Time 1.00
Received By btrobaug Date 2006-09-11 Time 07:25 Sent To M
Notes
2006-09-11 00:00:00 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEERING FIRM SHALL INDICATE
 THE CERTIFICATE OF AUTHORIZATIONNUMBER
 ALONG WITH OTHER INFORMATION REQUIRED BY 61G15-23.002
 FLORIDA ADMINISTRATIVE
 CODE.
  
 2} SHEET SP-1 INDICATES THE EXISTING A/C
 UNIT TO REMAIN AND ADDING A/C-2. THERE
 IS ONLY ONE SYSTEM ON THE ELECTRICAL
 PLAN, PLEASE CLARIFY, CORRECT THE PANEL
 SCHEDULE AND LOAD CALCS IF NECESSARY.
  
 3} THE DRYER CIRCUIT INDICATES A #12
 CONDUCTOR ON THE 25 AMP BREAKER. THE
 CONDUCTOR MUST BE #10 TO COMPLY WITH
 240.4(D).
  
 4} RESEPTACLES MUST BE ADDED IN THE
 DINING AND MASTER BED ROOMS PER 210.52.
  
 5} PLEASE PROVIDE A PANEL SCHEDULE SO
 THAT BRANCH/FEEDER CIRCUIT CONDUCTOR AND
 OVER CURRENT PROTECTION COMPLIANCE MAY
 BE REVIEWED.
 NOTE: A LOAD CALCULATION AND PANEL
 SCHEDULE ARE REQUIRED PER 106.3.5.4, FBC
 AS AMENDED.
  
 6} TWO COMPLETE SETS OF DOCUMENTS ARE
 REQUIRED TO BE SUBMITTED FOR REVIEW PER
 106.1 FBC, AS AMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-26 Cont ID  
Sent By btrobaug Date 2006-05-26 Time 12:52 Rev Time 0.50
Received By btrobaug Date 2006-05-26 Time 12:11 Sent To P
Notes
2006-05-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A PANEL SCHEDULE SO
 THAT BRANCH/FEEDER CIRCUIT CONDUCTOR AND
 OVER CURRENT PROTECTION COMPLIANCE MAY
 BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2007-01-25 Cont ID  
Sent By mperson Date 2007-01-25 Time 14:05 Rev Time 0.33
Received By mperson Date 2007-01-25 Time 14:05 Sent To Z
Notes
2007-01-25 14:16:49NOTE: SEPERATE GAS PERMIT REQUIRED

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2006-12-27 Cont ID  
Sent By mperson Date 2006-12-27 Time 09:48 Rev Time 0.45
Received By mperson Date 2006-12-27 Time 09:48 Sent To M
Notes
2006-12-27 09:54:11DENIED 4TH TIME
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED ON THE
 RESUBMITTED DRAWINGS TO MEET CODE COMPLIANCE:
  
 1. PLEASE REFERENCE PLUMBING COMMENTS NUMBERS 5 AND 7
 FOR THE RESUBMITTAL.
  
 2. SHEETS P-1 AND E-1 INDICATE AN ELECTRIC DRYER AND
 SHEET P-2 INDICATES A GAS DRYER, THIS IS CONFUSING,
 PLEASE CORRELATE THE DRAWINGS ON THE RESUBMITTAL.
 PLEASE NOTE IF THERE IS TO BE A GAS DRYER IT ALSO NEEDS
 TO BE ADDED TO THE GAS RISER DIAGRAM ON SHEET P-1.
  
 3. SHEET P-1 GAS RISER DIAGRAM STATES IN CLOUDED AREA
 "APPROXIMATE DISTANCE OF 25' FROM METER TO NEW SERVICE
 ENTRANCE" AND THERE APPEARS TO BE A NATURAL GAS METER
 INDICATED ON THE RISER DIAGRAM, THIS IS CONFUSING,
 PLEASE INDICATE ON THE RESUBMITTED GAS RISER DIAGRAM
 ONLY ONE NATURAL GAS METER AND DELETE ALL OTHERS.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2006-11-27 Cont ID  
Sent By mperson Date 2006-11-27 Time 13:19 Rev Time 0.33
Received By mperson Date 2006-11-27 Time 13:19 Sent To B
Notes
2006-11-27 14:29:13UNSAT 3RD TIME
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING
 LENGTHS INDICATED.
  
 2. PLEASE NOTE THAT THE INDICATED MATERIAL ON SHEET P-1
 IS SCH. 40 BLK STEEL PIPE, WITH A TOTAL DEVELOPED
 LENGTH OF OVER 30' WHEN ALL CUT SECTIONS OF PIPE ARE
 ACCOUNTED FOR AND A TOTAL BTU LOAD OF 96,000 NOT
 121,000 AS THE DRAWING INDICATES. PER FBC-2004 FUEL
 GAS, TABLE 402.4 (2)GAS SYSTEM IS SIZED WRONG, PLEASE
 REFERENCE THE CORRECTED GAS RISER AND TOTAL BTU LOAD IN
 RED FOR THE RESUBMITTAL.
  
 3. PER FBC-2004 FUEL GAS SECTION 404.11 PIPING
 UNDERGROUND BENEATH BILDING. PLEASE PROVIDE A DETAIL OF
 THIS INSTALLATION.
 NOTE: AS AN ALTERNATIVE IT IS SUGGESTED TO PIPE GAS
 OVERHEAD INSTEAD OF UNDERGROUND.
  
 4. PLEASE INDICATE ON THE RESUBMITTAL COMPLIANCE WITH
 FBC-2004 FUEL GAS, SECTIONS 404.8 AND 404.8.1
 PROTECTION AGAINST CORROSION.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-09-23 Cont ID  
Sent By jleech Date 2006-09-23 Time 13:45 Rev Time 0.00
Received By jleech Date 2006-09-23 Time 13:44 Sent To P
Notes
2006-09-23 00:00:00GAS REVIEW DENIED;
 1.TYPE OF PIPING MATERIAL NOT ON PLAN.
 IS GAS PIPE MOUNTED ON WALL, RUN IN
 ATTIC OR UNDER GROUND?
 2.GAS ISOMETRIC SHOWS 2 APPLIANCES, W/H
 AND STOVE, FLOOR PLAN SHOWS DRIER IS GAS
 ALSO. PLEASE CLARIFY.
 3.GAS PIPE TO BE SLEEVED IF RUN THRU
 WALL SHOW ON PLANS.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-05 Cont ID  
Sent By jleech Date 2006-06-05 Time 14:23 Rev Time 0.00
Received By jleech Date 2006-06-05 Time 14:23 Sent To M
Notes
2006-06-05 00:00:001. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-03-11 Cont ID  
Sent By adarroug Date 2008-03-11 Time 10:24 Rev Time 0.00
Received By adarroug Date 2008-03-11 Time 10:24 Sent To M
Notes
2008-03-11 10:24:53TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-02-08 Cont ID  
Sent By adarroug Date 2008-02-08 Time 16:44 Rev Time 0.00
Received By adarroug Date 2008-02-08 Time 16:44 Sent To M
Notes
2008-02-08 16:44:18TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 12:51 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 12:51 Sent To Z
Notes
2007-01-20 12:51:31TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 14:01 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 14:01 Sent To E
Notes
2006-11-08 14:01:49TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-26 Cont ID  
Sent By adarroug Date 2006-10-26 Time 14:07 Rev Time 0.00
Received By adarroug Date 2006-10-26 Time 14:07 Sent To Z
Notes
2006-10-26 14:07:40TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 09:44 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 09:44 Sent To E
Notes
2006-09-05 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-26 Cont ID  
Sent By adarroug Date 2006-08-26 Time 15:18 Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 15:18 Sent To Z
Notes
2006-08-26 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 15:47 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 15:47 Sent To E
Notes
2006-05-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-09 Cont ID  
Sent By alange Date 2006-06-09 Time 08:20 Rev Time 0.00
Received By alange Date 2006-05-05 Time 13:20 Sent To  
Notes
2006-05-05 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-03-11 Cont ID  
Sent By tgordon Date 2008-03-11 Time 11:16 Rev Time 0.35
Received By tgordon Date 2008-03-11 Time 11:16 Sent To  
Notes
2008-03-11 11:17:03REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-02-11 Cont ID  
Sent By tgordon Date 2008-02-11 Time 10:29 Rev Time 0.40
Received By tgordon Date 2008-02-11 Time 10:29 Sent To  
Notes
2008-02-11 10:59:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO MECHANICAL PLAN **
 *** DENIED ***
 1) PLEASE SUBMIT A NEW LETTER FROM THE ENGINEER WITH
 THE JOB ADDRESS AND PERMIT NUMBER 06050213 ON IT.
  
 2) PROVIDE COMBUSTION AIR OR MAKE UP AIR FOR THE GAS
 WATER HEATER IN THE LAUNDRY ROOM, SEE 2004 FBC/R
 G2407.1 AND G2407.4.
  
 3) PROVIDE FOR RETURN AIR IN THE NEW MASTER SUITE, SEE
 2004 FBC/R M1602.4.
  
 4) SHOW THE CFM'S AT ALL NEW SUPPLY AIR GRILLS ON
 MECHANICAL PLAN, SEE 2004 WPB AMEND. 106.3.5.4 (10).
  
 5) SHOW WERE THE CLOTHES DRYER VENT WILL TERMINATE AT
 ON THE MECHANICAL PLAN, SEE 2004 FBC/R M303.4.2.
  
 6) SHOW ANY NEW BATHROOM EXHAUST FANS BEING INSTALLED,
 ON THE MECHANICALPLAN, SEE 2004 FBC/R R303.3.
  
 7) SHOW THE HEATER KW IN THE A/C EQUIPMENT SCHEDULE,
 SEE 2004 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-01-24 Cont ID  
Sent By tgordon Date 2007-01-24 Time 12:10 Rev Time 0.30
Received By tgordon Date 2007-01-24 Time 12:09 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-12-27 Cont ID  
Sent By tgordon Date 2006-12-27 Time 14:35 Rev Time 0.45
Received By tgordon Date 2006-12-27 Time 14:35 Sent To  
Notes
2006-12-27 14:46:41*** DENIED ***
 1) MANUAL N CAL'S ARE SHOWING ON PAGE 6, 1870 SQ. FT.
 AREA. PLANS ARE SHOWING 1534 SQ. FT. AREA, PLEASE
 CORRECT MANUAL N CAL'S..
  
 2) 12" RETURN AIR TRANSFER GRILL TO MASTER BEDROOM
 SUITE NEEDS TO BE 16".
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-11-16 Cont ID  
Sent By tgordon Date 2006-11-16 Time 09:00 Rev Time 0.45
Received By tgordon Date 2006-11-16 Time 09:00 Sent To P
Notes
2006-11-16 09:07:04*** DENIED ***
 1) AS NOTED IN LAST TWO REVIEWS 6-5-06 NOTE #2 AND
 9-12-06 NOTE #1 PLEASE CORRECT ENERGY CALCULATIONS,
 ENERGY CALCULATIONS SHOW 1960 SQ. FT. UNDER AIR, PLANS
 ARE SHOWING ONLY 1534 SQ. FT. UNDER AIR.
  
 2) AS NOTED IN LAST REVIEW 9-12-06 NOTE #5, SEE PAGE
 SP-1, D-1, A-1, S-2 ARE SHOWING EXISTING CU-1 CONDENSER
 UNIT TO REMAIN, WERE PAGE E-1 SHOWS EXIST. CU-1 TO BE
 REPLACED, PLEASE CORRECT.
  
 3) THEIR ARE NO MANUAL J CALCULATIONS WITH THE PLANS AT
 THIS TIME. PLEASE SUBMITMANUAL J CALCULATIONS, PER
 2004 FBC 13-607.1.ABC.1 .
  
 4) SEE PLANS PAGE M-4 MISSING ENGINEER'S PRINTED NAME
 MUST APPEAR IN THE TITLE BLOCK, ALSO THE ENGINEERING
 BUSINESS'S CERTIFICATE OF AUTHORIZATION NUMBER, PER FAC
 61G15-23.002 .
  
 5)SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 TIMES THE FEE. THIS IS ONLY A NOTICE AT THIS TIME.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-09-12 Cont ID  
Sent By tgordon Date 2006-09-12 Time 08:16 Rev Time 0.45
Received By tgordon Date 2006-09-12 Time 08:16 Sent To P
Notes
2006-09-12 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 6-5-06 #2.
 PLEASE MAKE CORRECTIONS TO ENERGY
 CALCULATIONS, SEE CONDITIONED FLOOR
 AREA, HOT WATER SYSTEM, AND HVAC
 CREDITS. SAME ENERGY CAL'S. WERE
 RESUBMITTED.
  
 2) AS NOTED IN LAST REVIEW 6-5-06 #6.
 ALL RETURN AIR TRANSFER DUCTS ARE TO
 SMALL. RETURN AIR TRANSFER DUCTS NEED TO
 BE 1 1/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCTS
 ENTERING THE ROOM. THE MASTER SUITE MUST
 INCLUDE THE BATHROOM AND CLOSET. PER
 2004 FBC/R M1602.4 .
  
 3) CLOTHES DRYER VENTS CAN NOT HAVE
 SCREENS IN THEM, PER 2004 FBC/R M1501.1,
 PLEASE CORRECT.
  
 4) THE CLOTHES DRYER VENT AND THE GAS
 WATER HEATER VENT CAN NOT DISCHARGE TO
 THE COVERED PORCH, PER 2004 FBC/M 501.2,
 PLEASE CORRECT.
  
 5) SEE PAGE SP-1, D-1, A-1, S-2 ARE
 SHOWING EXISTING CU-1 CONDENSER UNIT TO
 REMAIN, WERE PAGE E-1 SHOWS EXIST. CU-1
 TO BE REPLACED, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-05 Cont ID  
Sent By tgordon Date 2006-06-05 Time 16:38 Rev Time 1.15
Received By tgordon Date 2006-06-05 Time 16:38 Sent To B
Notes
2006-06-05 00:00:00*** DENIED ***
 1) ENGINEER'S PRINTED NAME MUST APPEAR
 IN THE TITLE BLOCK, ALSO THE ENGINEERING BUSINESS'S
 CERTIFICATE OF AUTHORIZATION
 NUMBER, PER FAC 61G15-23.002 .
  
 2) PLEASE MAKE CORRECTIONS TO ENERGY
 CALCULATIONS, SEE CONDITIONED FLOOR
 AREA, HOT WATER SYSTEM, AND HVAC
 CREDITS.
  
 3) PROVIED COMBUSTION AIR FOR GAS WATER
 HEATER AND GAS CLOTHES DRYER, PER 2004
 FBC/R M1701.1 .
  
 4) PLEASE SUBMIT A MANUAL 'D'
 CALCULATION (RESIDENTIAL DUCT DESIGN),
 PER 2004 FBC/R M1601.1 .
  
 5) RETURN AIR GRILL 20" X 20" WITH A
 FILTER IS TO SMALL FOR A 4 TON SYSTEM,
 PLEASE CORRECT.
  
 6) ALL THE RETURN AIR TRANSFER GRILLS
 ARE TO SMALL, SEE NOTE #7.
  
 7) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-01-25 Cont ID  
Sent By mperson Date 2007-01-25 Time 13:35 Rev Time 0.33
Received By mperson Date 2007-01-25 Time 13:35 Sent To G
Notes
2007-01-25 13:43:04****************PROVISO****************
 PER FBC-2004 PLUMBING, SECTION 708.9 . ACCESS SHALL
 BE
 PROVIDED TO ALL CLEANOUTS. CLEANOUT FOR WASHING MACHINE
 TO BE FOUR FEET ABOVE FINNISH FLOOR

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-12-27 Cont ID  
Sent By mperson Date 2006-12-27 Time 08:13 Rev Time 1.50
Received By mperson Date 2006-12-27 Time 08:13 Sent To G
Notes
2006-12-27 09:45:51DENIED 4TH TIME
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE, SEE
 ATTACHED NOTICE FS 553.80(2)(B) REGUARDING FOUR (4)
 TIMES THE FEE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION
 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.
 NOTE: THE SUBMITTED SANITATY RISER DIAGRAM ON SHEET P-1
 STILL DOES NOT INDICATE ALL TRAP SIZES. PLEASE
 REFERENCE THE CORRECTED SANITARY RISER DIAGRAM IN RED
 ON SHEET P-1 FOR THE RESUBMITTAL.
  
 2. THE WASHING MACHINE DRAIN INDICATED ON SHEET P-1
 SANITARY RISER DIAGRAM IS STILL INDICATED WRONG PER
 FBC-2004 PLUMBING, SECTION 406.3 WASTE CONNECTIONS,
 SECTION 802.4 STAND PIPES, SECTION 708.7 CLEANOUT
 MINIMUM SIZE AND SECTION 708.9 CLEANOUT ACCESS, FOR
 WASHING MACHINE CLEANOUT TO BE INDICATED AT FOUR FEET
 ABOVE FINNISH FLOOR (4' AFF). PLEASE REFERENCE THE
 CORRECTED SANITARY RISER DIAGRAM IN RED ON SHEET P-1
 FOR THE RESUBMITTAL.
  
 3. THE DISHWASHER DRAIN ON SHEET P-1 SANITARY RISER
 DIAGRAM IS STILL INDICATED WRONG PER FBC-2004 PLUMBING,
 SECTION 802.1.6. PLEASE REFERENCE THE CORRECTED
 SANITARY RISER DIAGRAM IN RED ON SHEET P-1 FOR THE
 RESUBMITTAL.
  
 THE FOLLOWING ARE NEW ITEMS THAT NEED TO BE CORRECTED
 TO MEET CODE COMPLIANCE:
  
 4. PLEASE INDICATE ON THE RESUBMITTED DRAWINGS ON
 SHEET P-1 THAT THE WATER-HAMMER ARRESTORS TO BE
 INSTALLED PER FBC-2004 PLUMBING SECTION 604.9.
  
 5. A} SHEET P-2, A TITLE BLOCK IS REQUIRED WITH THE
 FOLLOWING INFORMATION:
 FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 NOTE: ITEMS #1 ADDRESS IS DIFFERENT, #2 AND#6 ARE
 MISSING FROM TITLE BLOCK.
 B} REVISED SHEET P-1 RESUBMITTAL IS INTIALED INSTEAD
 OF BEING SIGNED, PLEASE CORRECT THIS ON THE NEXT
 RESUBMITTAL.
  
 6. SHEET P-2 WATER HEATER DETAIL A VACUUM RELIEF VALVE
 IS REQUIRED ON A BOTTOM FED WATER HEATER PER FBC-2004,
 SECTION 504.2. THE HEAT RECOVERY RETURN SHOULD READ
 FUTURE AND IT SHOULD TIE INTO THE C.W. SUPPLY. PLEASE
 REFERENCE THE CORRECTED DETAIL IN RED AND PLEASE
 CORRECT THE WATER HEATER DETAIL TO REFLECT THIS ON THE
 RESUBMITTAL.
  
 7. PER FBC-2004 CHAPTER 1, SECTION 106.1 MINIMUM OF
 TWO COMPLETE SETS OF DRAWINGS ARE REQUIRED, ONLY ONE
 REVISED SHEET P-1 WAS IN THE RESUBMITTAL PACKAGE.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-11-27 Cont ID  
Sent By mperson Date 2006-11-27 Time 11:41 Rev Time 0.33
Received By mperson Date 2006-11-27 Time 11:41 Sent To G
Notes
2006-11-27 13:17:23UNSAT 3RD TIME
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS. PLEASE SIZE THESANITARY PLUMBING
 RISER ON SHEET P-1 PER FBC-2004 PLUMBING, TABLE 709.1.
  
 2. THE WASHING MACHINE DRAIN INDICATED ON SHEET P-1
 SANITARY PLUMBING RISER IS INDICATED WRONG PER THE
 FOLLOWING FBC-2004 PLUMBING SECTIONS.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. PLEASE INDICATE PIPE SIZE ON THE
 RESUBMITTAL.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
  
 3. THE DISHWASHER DRAIN ON SHEET P-1 SANITARY PLUMBING
 RISER IS INDICATED WRONG PER FBC-2004 PLUMBING, SECTION
 802.1.6. THE DISHWASHER SHALL DISCHARGE INTO A
 WYE-BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK
 OR THE DISHWASHER CONNECTION OF A FOOD WASTE GRINDER.
 PLEASE REFERENCE THE CORRECTED DRAWING ON SHEET P-1 FOR
 THE RESUBMITTAL.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-23 Cont ID  
Sent By jleech Date 2006-09-23 Time 14:03 Rev Time 0.00
Received By jleech Date 2006-09-23 Time 14:03 Sent To B
Notes
2006-09-23 00:00:00DENIED;
 1. TWO SETS OF PLANS ARE REQUIRED.
 2. RISER DIAGRAM; SHOWER NOT VENTED AS
 DRAWN, LAVATORY VENT TO BE BETWEEN W/C
 AND SHOWER. SEE P-1 MARKED IN RED.
 PLEASE MAKE CORRECTIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-05 Cont ID  
Sent By jleech Date 2006-06-05 Time 14:01 Rev Time 0.00
Received By jleech Date 2006-06-05 Time 14:01 Sent To M
Notes
2006-06-05 00:00:00DENIED;
 SANITARY RISER DIAGRAM;
 AUTOMATIC CLOTHES WASHER IS REQUIRED
 DISCHARGE INDIRECTLY INTO A STANDPIPE A
 MINIMUM OF 18" NOT INTO A FLOOR DRAIN,
 SEE FBC-2004 PLUMBING SEC.802.4.
 2.W/M AND KITCHEN SINK SHALL NOT DRAIN
 INTO THE WET VENT OF A BATHROOM GROUP.
 SEC. 909.1.
 3.BRANCH DRAIN FOR W/M SHALL BE 3", SEC.
 406.3
 WATER RISER DIAGRAM;
 1.WATER HAMMER ARRESTORS ARE REQUIRED
 PER SEC. 604.9
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2006-11-06 Cont ID  
Sent By mmclean Date 2006-11-06 Time 11:19 Rev Time 0.00
Received By mmclean Date 2006-11-06 Time 11:19 Sent To I
Notes
2006-11-06 11:20:02PROVISO: THE PROPOSED ADDITION MUST SIT BEYOND THE 25FT
 FRONT SETBACK.ALSO, MUST HAVE INTERIOR ACCESS
 THROUGH-OUT THE STRUCTURE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-09-02 Cont ID  
Sent By mmclean Date 2006-09-02 Time 09:05 Rev Time 0.00
Received By mmclean Date 2006-09-02 Time 09:05 Sent To I
Notes
2006-09-02 00:00:00DENIED,
 1. ONLY ONE SET OF PLANS WERE SUBMITTED.
 2.NEED TO SUBMIT ANOTHER SET PLANS FOR
 STAMPING, ONE COPY IS FOR OFFICE FILE
 AND THE OTHER IS FOR THE CONTRACTOR.
  
 PROVISO: THE PROPOSED ADDITION AND
 EXSITING GARAGE MUST MEET THE 25FT FRONT
 SETBACK AS REQUIRED BY ZONING & LAND
 DEVELOPMENT REGULATIONS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-22 Cont ID  
Sent By mmclean Date 2006-05-22 Time 11:42 Rev Time 0.00
Received By mmclean Date 2006-05-22 Time 11:42 Sent To I
Notes
2006-05-22 00:00:00DENIED,
 1. THE PROPOSED BATH MUST SIT BEYOND THE
 25FT FRONT SETBACK.
 2. THE EXISTING STRUCTURE ONLY SITS
 24'-103/3" AND DOES NOT MEET THE CURRENT
 REQUIREMENT FOR THE FRONT SETBACK WHICH
 IS 25FT, SO ANY PORPOSED ADDITION MUST
 MEET THAT REQUIRED SETBACK.
 3. MUST PROVIDE A COPY OF CURRENT
 SURVEY.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720