Plan Review Details - Permit 06050208
Plan Review Stops For Permit 06050208
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-01 Cont ID  
Sent By jwitmer Date 2006-09-01 Time 11:25 Rev Time 2.22
Received By jwitmer Date 2006-09-01 Time 11:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-30 Cont ID  
Sent By jwitmer Date 2006-05-30 Time 13:24 Rev Time 0.55
Received By jwitmer Date 2006-05-30 Time 13:24 Sent To  
Notes
2006-05-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06050208
 ADD: 4826 N HAVERHILL RD
 CONT: KREG ELECTRIC
 TEL: (561)786-1642
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)OVIDE PLANS ENOUGH TO VERIFY LOCATION
 OF GENERATOR VERSES BUILDING OPENINGS
 WINDOWS, DOORS OR SOFFIT TYPE VENTS,
 ETC.
  
 MECHANICAL CODE
 804.3.4 HORIZONTAL TERMINATIONS.
 HORIZONTAL TERMINATIONS SHALL COMPLY
 WITH THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO
 WALKWAYS, THE TERMINATION OF MECHANICAL
 DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3
 FEET (914 MM) ABOVE ANY FORCED AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 3.THE VENT SYSTEM SHALL TERMINATE
 AT LEAST 4 FEET (1219 MM) BELOW, 4 FEET
 (1219 MM) HORIZONTALLY FROM OR 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR
 GRAVITY AIR INLET INTO THE BUILDING.
 4.THE VENT TERMINATION POINT SHALL
 NOT BE LOCATED CLOSER THAN 3 FEET (914
 MM) TO AN INTERIOR CORNER FORMED BY TWO
 WALLS PERPENDICULAR TO EACH OTHER.
 5.THE VENT TERMINATION SHALL NOT BE
 MOUNTED DIRECTLY ABOVE OR WITHIN 3 FEET
 (914 MM) HORIZONTALLY FROM AN OIL TANK
 VENT OR GAS METER.
 6.THE BOTTOM OF THE VENT
 TERMINATION SHALL BE LOCATED AT LEAST 12
 INCHES (305 MM) ABOVE FINISHED GRADE.
  
 804.3.5 VERTICAL TERMINATIONS.
 VERTICAL TERMINATIONS SHALL COMPLY WITH
 THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO
 WALKWAYS, THE TERMINATION OF MECHANICAL
 DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3
 FEET (914 MM) ABOVE ANY FORCED AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 3.WHERE THE VENT TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF
 STRUCTURE, THE TERMINATION POINT SHALL
 BE LOCATED AT LEAST 3 FEET (914 MM) FROM
 SUCH STRUCTURE.
 4.THE VENT SHALL TERMINATE AT LEAST
 4 FEET (1219 MM) BELOW, 4 FEET (1219 MM)
 HORIZONTALLY FROM, OR 1 FOOT (305 MM)
 ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET FOR THE BUILDING.
 5.A VENT CAP SHALL BE INSTALLED TO
 PREVENT RAIN FROM ENTERING THE VENT
 SYSTEM.
 6.THE VENT TERMINATION SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM)
 HORIZONTALLY FROM ANY PORTION OF THE
 ROOF STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE.
  
 THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED
 OUTDOORS AT A POINT WHERE IT WILL NOT
 CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE
 EXHAUSTED INTO AN ATTIC OR CRAWL SPACE
  
 401.5 OPENING LOCATION.
 OUTDOOR AIR EXHAUST AND INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET
 (3048 MM) FROM LOT LINES OR BUILDINGS ON
 THE SAME LOT. WHERE OPENINGS FRONT ON A
 STREET OR PUBLIC WAY, THE DISTANCE SHALL
 BE MEASURED TO THE CENTERLINE OF THE
 STREET OR PUBLIC WAY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-16 Cont ID  
Sent By dpalmer Date 2006-08-16 Time 15:25 Rev Time 0.00
Received By dpalmer Date 2006-08-16 Time 15:25 Sent To  
Notes
2006-08-16 00:00:00NEW PLANS BROUGHT IN, NEW ELECTRICAL,
 NEW BUIDLING. REMOVED OLD SHEETS AND
 INSERTED NEW SHEETS

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-10 Cont ID  
Sent By dpalmer Date 2006-08-10 Time 18:18 Rev Time 0.00
Received By dpalmer Date 2006-08-10 Time 14:39 Sent To  
Notes
2006-08-10 00:00:00********* UNSAT 2ND REVIEW *****
  
 ** PLEASE SEE SOME NOTE FROM THE
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED. PLEASE SEE COMMENT BELOW ARE
 TAKEN DIRECTLY FROM THE PREVIOUS REVIEW.
 PLEASE KNOW SOME INFORMATION(SPECS) ARE
 ONLY NOW BEING REVIEWED FOR THE FIRST
 TIME.
  
 ** PLEASE KNOW PERMIT APPLICATION WAS
 ONCE AGAIN SUBMITTED WITH THE ADDRESS OF
 "4826" N. HAVERHILL WHICH IS THE ADDRESS
 FOR "COTTAGE #10". PLEASE SEE PLANS NOW
 INDICATE "4884" N. HAVERHILL WHICH IS
 THE ADDRESS FOR WHAT WAS/IS GOING TO BE
 THE ADMIN BLDG.
 **PLEASE SEE THE ADDRESS FOR THIS
 PROJECT IS LOCATED AT THE SOCIAL
 BUILDING WHICH IS "4888" N HAVERHILL RD.
  
 THIS REVIEWER HASPERSONALLY CHANGED
 OUR SYSTEM, MOVED PERMITS TO THE "4884"
 AND HAS CHANGED THE PERMIT APPLICATION
 TO READ 4888.
 PLEASE SEE PLANS/TITLE BLOCKS ARE
 SHOWING 4884, WHICH WAS GOING TO BE
 CHANGED BY HAND HOWEVER PLANS ARE COMING
 BACK FOR CORRECTIONS, PLEASE REVISE AT
 THAT TIME.
  
 1) NOTE: NO, PLEASE SEE THE SAME SHEET
 WAS SUBMITTED BACK FOR SLAB DETAIL, IN
 FACT A "COLORED PHOTO-COPY" WAS MADE OF
 THE SAME SHEETS WHICH THIS REVIEWER
 HIGHLIGHTED AND REDLINED "COPY" . PLEASE
 KNOW THIS IS 2ND TIME THIS NOTE IS
 STATED THAT ALL PLANS, DETAILS ETC DONE
 BY AN ENGINEER SHALL CONTAIN AN ORIGINAL
 SIGNATURE, DATE AND SEAL.
 PLEASE KNOW THAT A "RAISED SEAL" OVER A
 DOCUMENT WHICH IS A PHOTO-COPY OF THE
 ENGINEER'S SIGNATURE IS NOT ACCEPTABLE.
 IF THERE ARE ANY QUESTIONS ON THIS
 PLEASE CONTACT MR. PAUL MARTIN EXECUTIVE
 DIRECTOR FOR THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEER'S AND MR. JERRY
 ONGLEY INVESTIGATOR TO THE BOARD. THEY
 HAVE BEEN CONTACTED ON THIS MATTER AND
 PENDING BUILDING OFFICIAL'S RULING,
 PLANS WHICH WERE RETAINED ON THE
 PREVIOUS REVIEW AND PLANS NOW BEING
 RETAINED ON THIS REVIEW MAY BE FORWARDED
 TO THE STATE FBPE'S FOR REVIEW.
 PLEASE SEE FAC 61G15-23.002, AND FS
 471.025. PLEASE STILL MISSING LICENSE
 NUMBER WHICH WAS NOT AS THE SAME
 SHEET(S) WERE SUBMITTED BACK FOR REVIEW.
 IF THERE ARE ANY QUESTIONS ON THIS
 PLEASE ALSO DO NOT HESITATE IN
 CONTACTING THIS REVIEWER (# BELOW ) OR
 THEDIRECTOR/BUILDING OFFICIALMR.
 NEIL MELICK @ 561-805-6654
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE BE SURE ALL SHEETS
 CONTAIN AN ORIGINAL SIGNATURE. PLEASE
 SEE SLAB DETAIL SHEET CONTAINS A RAISED
 SEALED OVER A PHOTO-COPIED SIGNATURE FOR
 THE ENGINEER OF RECORD.
 PLEASE KNOW, ONE COPY IS BEING RETAINED
 FOR FILE.
 FS 471.025,FAC 61G15-23.002
  
 2) NOTE: NO, THIS WAS ADJUSTED BY THE
 OFFICE BASED ON THE MARSHALL'S /SWIFT
 GUIDE WHICH IS ADOPTED BY THE FBC AND
 FEES OF $488.80 ARE NOW DUE BEFORE
 PERMIT CAN BE ISSUED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE FOR SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND
 MATERIALS, EVEN IF ANY EQUIPMENT IS
 OWNER SUPPLIED. PLEASE SEE VALUE AT
 30,000 IS WAY LOW FOR SCOPE.
 108.3 FBC
  
 3) NOTE: OK, SPEC ARE NOW SUBMITTED.
 THIS IS THE FIRST TIME THIS OFFICE HAS
 REVIEWED SPECS.
 ** PLEASE SEE SPECS ARE SHOWING A 3-POLE
 ATS WHICH DOES NOT CORRELATE WITH THE
 PLANS. PLEASE SEE COMMENT BELOW WITH
 RESPECT TO THE "SEPARATELY DERIVED
 SYSTEM".
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE SPECS FOR
 GENERATOR AND ATS. SPECS FOR GEN WERE
 SUBMITTED HOWEVER COULD NOT LOCATE THE
 LISTING FROM A NRTL.
 PLEASE ALSO SEE NO SPECS FOR THE ATS
 WERE SUBMITTED.
  
 4) NOTE:NO, PLEASE SEE THE GENERATOR
 ON PLANS ARE NOW SHOWING A 4-POLE ATS
 AND CONDUCTORS FROM THE GEN TO THE
 BUILDING IS INDICATING A SD SYSTEM,
 HOWEVER PLEASE INCLUDE A NEW GROUNDING
 ELECTRODE SYSTEM AT GENERATOR AS
 REQUIRED PER 250.50,250.20.
 THIS IS ONE ITEM THAT SHOULD REALLY BE
 DISCUSSED AND COORDINATED WITH OWNER'S,
 CONTRACTOR AND DESIGN TEAM ON WHICH
 SYSTEM IS GOING TO BE INSTALLED AS SPECS
 SHEETS FOR EQUIPMENT ORDERED FROM
 MANUFACTURE DOES NOT CORRELATE.
 IF THERE ARE QUESTIONS ON THIS AND THIS
 OFFICE CAN BE OF ASSISTANCE, PLEASE DO
 NOT HESITATE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE CONDUCTORS SHOWN
 FROM GENERATOR TO THE ATS TEND TO LEND
 GENERATOR BEING A SEPARATELY DERIVED
 SYSTEM, YET THE ATS IS SHOWN AS 3-POLE?
 PLEASE CLARIFY AND SHOW GROUNDING PER
 250.30.
 IF NOT A SDS, THEN PLEASE INCLUDE THE
 EQUIPMENT GROUNDING CONDUCTOR.
 250.110,250.122 ETC
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 ** NEW NOTE **
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS. THIS IS ONLY
 A NOTICE GIVEN AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-02 Cont ID  
Sent By dpalmer Date 2006-06-02 Time 11:10 Rev Time 0.00
Received By dpalmer Date 2006-06-02 Time 09:06 Sent To  
Notes
2006-06-02 00:00:00************* UNSAT ***************
  
 1) NOTE: PLEASE BE SURE ALL SHEET
 CONTAIN AN ORIGINAL SIGNATURE. PLEASE
 SEE SLAB DETAIL SHEET CONTAINS A RAISED
 SEALED OVER A PHOTO-COPIED SIGNATURE FOR
 THE ENGINEER OF RECORD.
 PLEASE KNOW, ONE COPY IS BEING RETAINED
 FOR FILE.
 FS 471.025,FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE VALUE FOR SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND
 MATERIALS, EVEN IF ANY EQUIPMENT IS
 OWNER SUPPLIED. PLEASE SEE VALUE AT
 30,000 IS WAY LOW FOR SCOPE.
 108.3 FBC
  
 3) NOTE: PLEASE SUBMIT THE SPECS FOR
 GENERATOR AND ATS. SPECS FOR GEN WERE
 SUBMITTED HOWEVER COULD NOT LOCATE THE
 LISITNG FROM A NRTL.
 PLEASE ALSO SEE NO SPECS FOR THE ATS
 WERE SUBMITTED.
  
 4) NOTE: PLEASE SEE CONDUCTORS SHOWN
 FROM GENERATOR TO THE ATS TEND TO LEND
 GENERATOR BEING A SEPARATELY DERIVED
 SYSTEM, YET THE ATS IS SHOWN AS 3-POLE?
 PLEASE CLARIFY AND SHOW GROUNDING PER
 250.30.
 IF NOT A SDS, THEN PLEASE INCLUDE THE
 EQUIPMENT GROUNDING CONDUCTOR.
 250.110,250.122 ETC
  
 5) NOTE: PLEASE SEE A DISCONNECTING
 MEANS FOR FEEDERS COMING FROM THE
 GENERATOR IS REQUIRED AND IS TO BE
 GROUPED WITH THE SERVICE MEANS OF
 DISCONNECT PER 225.31-225.39.
  
 6) NOTE: PLEASE PROVIDE A SITE OVERVIEW
 SHOWING THE LOCATIONS OF ALL EQUIPMENT,
 DISC'S AND GEN.
 215.3
  
 7) NOTE: PLEASE BE SURE AIC RATINGS ARE
 INDICATED FOR THE ATS AND ANY NEW
 DISCONNECTS.
 110.9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-31 Cont ID  
Sent By mwennerg Date 2006-08-31 Time 12:47 Rev Time 0.00
Received By mwennerg Date 2006-08-31 Time 12:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By mcarsill Date 2006-06-19 Time 11:16 Rev Time 0.00
Received By mcarsill Date 2006-06-19 Time 11:06 Sent To  
Notes
2006-06-19 00:00:001. PLANS THAT WERE SUBMITTED WERE TWO
 SHEETS OF E5-4.01. THESE SHEETS DO NOT
 INDICATE WHERE THE DIESEL GENERATOR WILL
 BE INSTALLED WITH RESPECT TO BUILDINGS,
 DOORS, WINDOWS, ETC.
  
 2. THE BASE TANK MEETS WHICH RECOGNIZED
 CRITERIA TO CONTAIN DIESEL FUEL. IS IT
 DESIGNED TO SUPPORT THE WEIGHT OF THE
 GENERATOR.
  
 3. WHAT IS THE PROPOSED GENERATOR GOING
 TO SUPPLY. EMERGENCY EQUIPMENT OR
 CONVENIENCE EQUIPMENT.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-24 Cont ID  
Sent By pschmitz Date 2006-06-24 Time 09:34 Rev Time 0.00
Received By pschmitz Date 2006-06-24 Time 09:33 Sent To  
Notes
2006-06-24 00:00:00NOT REQUIRED.
 DIESEL FUEL REVIEW BY MECHANICAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 15:42 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 15:42 Sent To  
Notes
2006-08-09 00:00:00TO "COMM" BD#1
2006-07-31 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-19 Cont ID  
Sent By adarroug Date 2006-07-19 Time 14:14 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 14:38 Sent To  
Notes
2006-05-24 00:00:00TO "COMM" BD#27
2006-05-06 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-23 Cont ID  
Sent By tgordon Date 2006-08-23 Time 13:55 Rev Time 0.20
Received By tgordon Date 2006-08-23 Time 13:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-15 Cont ID  
Sent By tgordon Date 2006-08-15 Time 14:12 Rev Time 0.20
Received By tgordon Date 2006-08-15 Time 14:12 Sent To  
Notes
2006-08-15 00:00:00*** DENIED ***
 MECHANICAL REVIEW IS OK, PLEASE CORRECT
 ELECTRICAL REVIEW NOTES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By tgordon Date 2006-06-27 Time 12:07 Rev Time 0.30
Received By tgordon Date 2006-06-27 Time 12:07 Sent To  
Notes
2006-06-27 00:00:00*** DENIED ***
 1) PLEASE PROVIDE A SITE PLAN SHOWING
 THE PROPOSED LOCATION OF THE GENERATOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-08-25 Cont ID  
Sent By mmclean Date 2006-08-25 Time 16:21 Rev Time 0.00
Received By mmclean Date 2006-08-25 Time 16:21 Sent To  
Notes
2006-08-25 00:00:00NOTE: THEY NEED TO INSTALL FENCE AND
 LANDSCAPING THAT IS PART OF PERMIT
 NUMBER 06081882 PRIOR TO C.O OF
 GENERATOR

Review Stop Z ZONING
Rev No 2 Status F Date 2006-08-14 Cont ID  
Sent By lmartine Date 2006-08-14 Time 10:25 Rev Time 0.00
Received By lmartine Date 2006-08-14 Time 10:25 Sent To  
Notes
2006-08-14 00:00:00A PERMIT FOR THE SCREEN WALL AND
 LANDSCAPE IS REQUIRED TO BE SUBMITTED
 PRIOR TO THE ISSUANCE OF THE GENERATOR
 PERMIT.
  
 THE WALL AND THE LANDSCAPE WILL BE
 REQUIRED TO BE INSTALLED PRIOR TO THE
 C.O. OF THE GENERATOR.
  
 CONTACT ERIC SCHNEIDER @ (561)822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By eschneid Date 2006-07-19 Time 10:45 Rev Time 0.00
Received By eschneid Date 2006-07-19 Time 10:45 Sent To  
Notes
2006-07-19 00:00:001) PROVIDE SITE AND LANDSCAPE PLANS
 SHOWING THE LOCATION OF THE GENERATOR
 AND THE REQUIRED SCREENING.
  
 2) THE PLANS SHALL MATCH THE PLANS
 APPROVED BY THE PLANNING AND ZONING
 DEPARTMENT ON DECEMBER 12, 2005.
  
 3) LANDSCAPE AND SCREEN WALL ARE
 REQUIRED TO BE INSTALLED WITH THE
 GENERATOR AND INCLUDED WITH THIS PERMIT.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.