Plan Review Details - Permit 06050195
Plan Review Stops For Permit 06050195
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-01-14 Cont ID  
Sent By mjacobs Date 2008-01-14 Time 10:26 Rev Time 0.00
Received By mjacobs Date 2008-01-14 Time 10:14 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2007-12-28 Cont ID  
Sent By mjacobs Date 2007-12-28 Time 07:45 Rev Time 0.00
Received By mjacobs Date 2007-12-28 Time 07:15 Sent To PC
Notes
2007-12-28 07:45:45BUILDING PLAN REVIEW
 PERMIT: 06050195
 ADD: 5505 S. DIXIE HWY
 CONT: PACE CONST.
 TEL: (561)827-7223
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)THE DRAWINGS SHALL INDICATE ALL EXISTING PARKING
 SPACES WITH THE REQUIRED STRIPING LINES ALONG WITH THE
 PROPOSEDACCESSIBLE PARKING SPACE. PLEASE SEE THE
 ZONING NOTES AND REFERENCE DRAWING IN THE PACKAGE. THE
 PLANS NEED TO SHOW THE EXISTING PARKING LOT AND THE
 PROPOSED.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 COMFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS,ORDINANCES, RULES AND REGULATIONS AS DETERMINED BY
 THE BUILDING OFFICIAL. FBC 106.1.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-10-18 Cont ID  
Sent By mjacobs Date 2007-10-18 Time 10:26 Rev Time 0.00
Received By mjacobs Date 2007-10-18 Time 09:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-06-13 Cont ID  
Sent By mjacobs Date 2007-06-13 Time 09:27 Rev Time 0.00
Received By mjacobs Date 2007-06-11 Time 14:44 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-05-04 Cont ID  
Sent By mjacobs Date 2007-05-04 Time 05:32 Rev Time 0.00
Received By mjacobs Date 2007-05-03 Time 10:52 Sent To  
Notes
2007-05-04 13:32:27BUILDING PLAN REVIEW
 PERMIT: 06050195
 ADD: 5505 S.DIXIE HWY.
 CONT: PACE CON
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 5TH
 ACTION: DENIED
  
 1)1003.3.3 HORIZONTAL PROJECTIONS.
 ELEMENTS CANNOT PROJECT OVER A WALKING SURFACE MORE
 THAN 4 INCHES (102 MM) WHEN THEY ARE LOCATED BETWEEN 27
 AND 80 INCHES (686 AND 2032 MM) ABOVE THE FLOOR.
 HANDRAILS CAN PROJECT UP TO 4? INCHES (114 MM) FROM THE
 WALL. THE DRINKNIG FOUNTAIN CONNOT PROJECT INTO THE
 HALLWAY MORE THAN 4". SEE PLUMBING COMMENTS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-03-01 Cont ID  
Sent By mjacobs Date 2007-03-01 Time 11:56 Rev Time 0.00
Received By mjacobs Date 2007-02-28 Time 16:50 Sent To  
Notes
2007-02-28 18:44:41BUILDING PLAN REVIEW
 PERMIT:06050195
 ADD:5505S. DIXIE HWY
 CONT: PACE CON
 TEL: (561)827-7233
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW4TH
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)ON PAGE #1 THE NOTE WHICH REFERES TO CH. 34 SHALL
 BE REMOVED OR STRIKE OUT BEACAUSE THATSECTION IS FROM
 THE 2001 FBC. ALL PLANS SUBMITTED AFTER OCT. 1ST 2005
 SHALL REFERENCE THE 2004 FBC.
  
 4)THE ARCHITECT'S SEAL SHALL BE LEGIBLE ON EACH
 SHEET. THE SEAL IS NOT CLEAR ON SOME SHEETS. THE SEAL
 SHALL BE CLEAR AND LEGIBLE ON ALL SHEETS. SEE F.S.
 481.221THE SIGNATURE, DATE, AND SEAL SHALL BE
 EVIDENCE OF THE AUTHENTICITY OF THAT TO WHICH THEY ARE
 AFFIXED, THEREFORE THE SEAL AND SIGNATURE MUST BE
 CLEAR, AND ORIGINAL ON EACH SHEET.
  
 5)PROVIDE THE MANUFACTURE SPECIFICATIONS FOR THE
 INSTALLATION OF THE NEW DENSE FOAM MOLDING INDICATING
 HOW IT WILL BE ATTATCHED TO THE BUILDING.
  
 6)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER. THE ARCHITECT
 SHALL SIGNED AND SEAL EACH DOCUMENT WHICH SHALL BE KEPT
 FOR PUBLIC RECORD.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-01-05 Cont ID  
Sent By mjacobs Date 2007-01-05 Time 15:59 Rev Time 0.00
Received By mjacobs Date 2007-01-03 Time 17:35 Sent To PC
Notes
2007-01-05 10:25:21BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
  
 1 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2)WHAT TOILET IS USED BY 'STO 1' AND 'STO 2'.
 INDICATE WHICH BATHROOM WILL BE USED BY THESE SPACES.
  
 3)ON PAGE #1THE NOTE WHICH REFEERS TO CH. 34 SHALL
 EITHER BE REMOVED OR STRIKE OUT BECAUSE THE SECTIONS IT
 REFERENCES ARE IN THE 2001 FBC.
  
 4)THE ARCHITECT'S SEAL SHALL BE LEGIBLE ON EACH
 SHEET. THE SEAL IS NOT CLEAR ON SOME SHEETS. SEE 61G-16
 FAC.
  
 5)FBC.106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL COMFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).A WALL LEGEND IS REQUIRED TO SHOW WHICH
 WALLS WILL BE DEMO AND THE NEW TYPES OF WALLS. SHOW THE
 THIS INFORMATION SHALL BE CLEARLY INDICATED ON THE
 DRAWINGS.
  
 6)SHOW IN DETAIL HOW THE NEW FACIA WILL BE ATTATCHED
 TO THE BUILDING.
  
 7)708.3 FIRE -RESISTANCE RATING.
 THE FIRE -RESISTANCE RATING OF THE WALLS SHALL BE AT
 LEAST 1 HOUR FOR INDIVIDUAL TENANT SPACES. (SEE
 FBC.708.1 AND 708.4)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-08 Cont ID  
Sent By alange Date 2006-09-08 Time 08:40 Rev Time 0.00
Received By alange Date 2006-09-08 Time 08:40 Sent To  
Notes
2006-09-08 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-18 Cont ID  
Sent By alange Date 2006-05-18 Time 09:33 Rev Time 2.00
Received By alange Date 2006-05-18 Time 09:33 Sent To  
Notes
2006-05-18 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 3.PRODUCT APPROVALS REQUIRED FOR
 EXTERIOR DOORS AND WINDOWS AND STORE
 FRONTS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 5.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 6.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 7.MINIMUM PLAN RVIEW CRITERIAL FOR
 BUILDINGS.WPB AMMENDMENTS TO THE 2004
 FBC.SHOW CONSTRUCTION TYPE AND
 OCCUPANCY TYPE.
  
 8.NOTE: PLANS SHOW BLDG. ON FEDERAL
 HWY..SHOULD BE S DIXIE HWY.
  
 9.CLEARLY SHOW EXISTING AREAS AND NEW
 AREAS INCLUDING ALL WALLS.
  
 10.SUBMIT SPECIFICATIONS FOR SPRAY
 BOOTH AND VENTILATION SYSTEM.
  
 11.SHOW BATHROOM ELEVATIONS SO
 COMPLIANCE CAN BE CHECKED FOR
 ACCESSABILITY PER FBC CHAPTER 11.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-10-23 Cont ID  
Sent By btrobaug Date 2007-10-23 Time 14:25 Rev Time 0.00
Received By btrobaug Date 2007-10-23 Time 14:12 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-06-12 Cont ID  
Sent By btrobaug Date 2007-06-12 Time 13:11 Rev Time 0.50
Received By btrobaug Date 2007-06-12 Time 13:01 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-04-26 Cont ID  
Sent By btrobaug Date 2007-04-26 Time 08:33 Rev Time 0.00
Received By btrobaug Date 2007-04-26 Time 07:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-26 Cont ID  
Sent By btrobaug Date 2007-02-26 Time 17:34 Rev Time 0.75
Received By btrobaug Date 2007-02-26 Time 16:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-12-20 Cont ID  
Sent By btrobaug Date 2006-12-20 Time 17:38 Rev Time 1.00
Received By btrobaug Date 2006-12-20 Time 16:39 Sent To  
Notes
2006-12-20 17:38:22 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PREVIOUS COMMENTS NOT CORRECTLY ADDRESSED, PRIOR NUMBER
 USED.
  
 2} SEE ARTICLE 440-22 AND VERIFY THE OCP
 FOR THE ACU MEETS THESE PERAMETERS. ALL
 PANELS. SEE HOUSE PANEL. 60 AMP, 2 POLE, WITH #10
 CONDUCTORS.
  
 3} THERE IS NO PARKING LOT LIGHTING
 BRANCH CIRCUIT LISTED, OR TIME CLOCK, IN
 THE HOUSE PANEL. PLEASE VERIFY AND
 INDICATE HOW LIT.
  
 4} THE CIRCUITING FOR THE EMERGENCY WALL
 LIGHTS MUST BE CIRCUITED WITH THE MAIN
 LIGHTING IN THE AREA, SEE 700.12(5)(E). THERE IS A NOTE
 REFERENCING COMPLIANCE,. BUT THE CIRCUIT NUMBERS ON THE
 PLAN ARE NOT CORRECT. SEE SHEET 3.
  
 5} PLEASE SUBMIT THE CORRECT ENERGY
 CALCULATION FORM AND INDICATE COMPLIANCE
 13-414 AND 415 ON THE PLANS. SHOW
 OCCUPANCY SENSORS, TIMERS, ETC.
  
 NEW COMMENTS, THIS REVIEW.
  
 6} ELECTRICAL NOTES #4 & 7 REFERENCED ARTICLES ARE NOT
 IN THE 2004 FBC. PLEASE CLARIFY.
  
 7} THE ARCHITECTS SEAL IS NOT DISCERNIBLE. SEE 61G1-16
 FAC. PLEASE RESEAL ALL SHEETS.
  
 THE FIRST 4 COMMENTS WERE ON THE
 PREVIOUS REVIEW. PLEASE PROVIDE WRITTEN RESPONSE
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-07 Cont ID  
Sent By btrobaug Date 2006-09-07 Time 13:22 Rev Time 1.00
Received By btrobaug Date 2006-09-07 Time 12:00 Sent To  
Notes
2006-09-07 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST COMPLY WITH THE MINIMUM REQUIREMENT
 OF 2/0 CU PER 250.66.
  
 2} SEE ARTICLE 440-22 AND VERIFY THE OCP
 FOR THE ACU MEETS THESE PERAMETERS. ALL
 PANELS.
  
 3} THERE IS NO PARKING LOT LIGHTING
 BRANCH CIRCUIT LISTED, OR TIME CLOCK, IN
 THE HOUSE PANEL. PLEASE VERIFY AND
 INDICATE HOW LIT.
  
 4} THE CIRCUITING FOR THE EMERGENCY WALL
 LIGHTS MUST BE CIRCUITED WITH THE MAIN
 LIGHTING IN THE AREA, SEE 700.12(5)(E).
  
 5} PLEASE SUBMIT THE CORRECT ENERGY
 CALCULATION FORM AND INDICATE COMPLIANCE
 13-414 AND 415 ON THE PLANS. SHOW
 OCCUPANCY SENSORS, TIMERS, ETC.
  
 6} THE HOUSE PANEL DOES NOT HAVE
 CONTINUOUS LOADS IN THE CALCULATION PER 210.20(A).
  
 7} THE ELECTRIC NOTE #1 REGARDING GFI('S
 IS INCORRECT @ 4'. SEE 210.8(A)(7).
  
 8} ALL REFERENCES TO THE S.F.B.C., NOTES
 4 AND 7, ARE OBSOLETE AND REFERENCES TO
 THAT CODE SHOULD BE REMOVED.
  
 9} ELECTRICAL NOTE #8REGARDING 110.16
 IS NOT TAKEN FROM THE 2002 NEC, AND DOES
 NOT PERTAIN TO DISCONNECTSWITCHES.
 THE FIRST 5 COMMENTS WERE ON THE
 PREVIOUS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-10 Cont ID  
Sent By btrobaug Date 2006-05-10 Time 13:52 Rev Time 1.00
Received By btrobaug Date 2006-05-10 Time 07:43 Sent To  
Notes
2006-05-10 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST COMPLY WITH THE MINIMUM REQUIREMENT
 OF 2/0CU PER 250.66.
  
 2} THE DISCONNECT ON THE RISER SAYS 475
 AMP, THE LOAD CALCULATION SAYS 450 AMP
 SERVICE. PLEASE CORRELATE.
  
 3} PLEASE INDICATE THE TYPE OF CONDUIT
 SPECIFIED FOR THE RISER AND SEE
 APPROPRIATE CHART IN CHAPTER #8 FOR
 CONDUIT FILL. #750 MCM THW IN A 2 1/2"
 CONDUIT IS NOT IN THE CHARTS.
  
 4} INDICATE THE AMPERAGE RATING OF THE
 PANEL FEEDER DISCONNECTS IN THE METER
 CENTER, AND WHICH PANEL THEY FEED.
  
 5} SEE ARTICLE 440-22 AND VERIFY THE OCP
 FOR THE ACU MEETS THESE PERAMETERS. ALL
 PANELS.
  
 6} THERE IS NO PARKING LOT LIGHTING
 BRANCH CIRCUIT LISTED, OR TIME CLOCK, IN
 THE HOUSE PANEL. PLEASE VERIFY AND
 INDICATE HOW LIT.
  
 7} INDICATE MEANS OF EGRESS ILLUMINATION
 TO DIXIE HIGHWAY.( PLEASE SEE SHEET 1
 REFERENCES "FEDERAL" HIGHWAY"). SEE
 7.8.1.1 NFPA-101.
  
 8} THE CIRCUITING FOR THE EMERGENCY WALL
 LIGHTS MUST BE CIRCUITED WITH THE MAIN
 LIGHTING IN THE AREA, SEE 700.12(5)(E).
  
 8} PLEASE SUBMIT THE CORRECT ENERGY
 CALCULATION FORM AND INDICATE COMPLIANCE
 13-414 AND 415 ON THE PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2007-10-23 Cont ID  
Sent By mwennerg Date 2007-10-23 Time 10:06 Rev Time 0.00
Received By mwennerg Date 2007-10-23 Time 10:06 Sent To  
Notes
2007-10-23 10:06:55REVISION DATED 9/20/07

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2007-06-13 Cont ID  
Sent By mawillia Date 2007-06-13 Time 16:20 Rev Time 0.00
Received By mawillia Date 2007-06-13 Time 16:12 Sent To B1
Notes
2007-06-13 16:14:51*****APPROVED*****
  
 ALL OTHER REVIEWERS HAVE BEEN SATISFIED;PLAN SHEETS #
 2 AND # 7 WHICH WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 15:12 Rev Time 0.00
Received By mjacobs Date 2007-05-07 Time 15:03 Sent To FIRE
Notes
2007-05-07 15:09:31*****PROVISO*****
  
 PLAN SHEETS # 2 AND # 7 WHICH WERE STAMPED, INITIALED,
 AND DATED ON 02/27/07;HOWEVER, TO ELIMINATE
 REDUNDANCY, THE RESUBMITTED SHEETS WILL BE STAMPED WHEN
 ALL OTHER PLAN REVIEWS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-02-27 Cont ID  
Sent By mawillia Date 2007-02-27 Time 11:40 Rev Time 0.00
Received By mawillia Date 2007-02-27 Time 11:40 Sent To  
Notes
2007-02-27 11:42:04*****APPROVED*****
  
 PLAN SHEETS # 2 AND # 7 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-12-26 Cont ID  
Sent By mawillia Date 2006-12-26 Time 10:02 Rev Time 0.00
Received By mawillia Date 2006-12-26 Time 10:02 Sent To  
Notes
2006-12-26 10:08:03*****APPROVED*****
  
  
 TO BE STAMPED AND SIGNEDWHEN ALL PLAN REVIEWS HAVE
 BEEN SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-09-13 Cont ID  
Sent By mwennerg Date 2006-09-13 Time 11:33 Rev Time 0.00
Received By mwennerg Date 2006-09-13 Time 11:33 Sent To  
Notes
2006-09-13 00:00:00***DENIED***
  
 SOME REVISIONS TO PLANS ARE NOTED
 HOWEVER SOME COMMENTS FROM PREVIOUS
 REVIEW NEED TO BE ACKNOWLEDGED.
  
 1) PLEASE DEFINE OCCUPANCY TYPE IN
 ACCORDANCE WITH FBC AND NFPA 101,
 CHAPTER 6 FOR ALL SPACES SHOWN ON PLANS.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION. PLEASE ADD TO PLANS.
  
 3) OK- REMOVED FROM PLANS.
  
 4) OK- REMOVED FROM PLANS.
  
 5) OK
  
 6) STROBES APPEAR TO HAVE BEEN REMOVED
 FROM INDIVIDUAL SPACES, BUT STILL ARE
 SHOWING IN CORRIDOR. AGAIN, PLEASE
 ADVISE WHAT STROBES ARE CONNECTED TO. IS
 THERE AN EXISTING FIRE ALARM SYSTEM?
  
 7) OK
  
 8) PLEASE ILLUSTRATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-16 Cont ID  
Sent By mwennerg Date 2006-05-16 Time 13:57 Rev Time 0.00
Received By mwennerg Date 2006-05-16 Time 13:57 Sent To  
Notes
2006-05-16 00:00:00******DENIED******
  
 1) PLEASE DEFINE OCCUPANCY TYPE IN
 ACCORDANCE WITH FBC AND NFPA 101,
 CHAPTER 6 FOR ALL SPACES SHOWN ON PLANS.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 3) IF PAINT SPRAY BOOTH ISN'T EXISTING,
 PLEASE NOTE THAT SEPARATE SHOP DRAWINGS
 AND PERMIT ARE REQUIRED. AT THE TIME OF
 PERMITTING, PLEASE INCLUDE MANUFACTURER
 SPEC SHEETS.
  
 4) PAINT SPRAY BOOTH TO BE INSTALLED IN
 COMPLIANCE WITH NFPA 33.
  
 5) 2A-10B,C RATED FIRE EXTINGUISHERS
 SHALL BE MOUNTED BASED ON THE HAZARD,
 AND SHALL NOT EXCEED 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 6) PLANS SHOW STROBES THROUGHOUT. WHAT
 ARE THE STROBES CONNECTED TO?
  
 7) ILLUMINATED EXIT SIGNS ARE REQUIRED
 THAT WOULD LEAD PERSONS FROM SPACES 1-4
 INTO THE COMMON CORRIDOR.
  
 8) PLEASE ILLUSTARTE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 17:11 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 17:11 Sent To B
Notes
2008-01-11 17:11:39TO MYRON JACOBS

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 14:26 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 14:26 Sent To Z
Notes
2007-12-19 14:26:38TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 15:31 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 15:31 Sent To  
Notes
2007-10-15 10:44:50TO "COMM" BD#5
2007-09-24 15:31:53WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-05-17 Cont ID  
Sent By adarroug Date 2007-05-17 Time 08:58 Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 08:58 Sent To  
Notes
2007-06-05 14:13:48TO "COMM" BD#21
2007-05-17 08:58:17WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 18:25 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 18:18 Sent To  
Notes
2007-04-12 16:02:48TO COMM BOARD # 36
2007-03-30 18:25:35WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 11:49 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 11:49 Sent To  
Notes
2007-02-14 11:53:27TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-17 Cont ID  
Sent By dpalmer Date 2006-12-17 Time 12:33 Rev Time 0.00
Received By dpalmer Date 2006-12-17 Time 12:33 Sent To  
Notes
2006-12-17 12:34:07ROUTED TO BOB BOARD SPACE #15

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 13:38 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 13:38 Sent To  
Notes
2006-12-01 13:38:33WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-08-15 Time 11:53 Rev Time 0.00
Received By adarroug Date 2006-08-15 Time 11:53 Sent To  
Notes
2006-09-05 00:00:00TO "BOB"#16
2006-08-15 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-18 Cont ID  
Sent By alange Date 2006-05-18 Time 10:47 Rev Time 0.00
Received By alange Date 2006-05-05 Time 14:05 Sent To  
Notes
2006-05-08 00:00:00TO "BOB"#18
2006-05-05 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-04-03 Cont ID  
Sent By tgordon Date 2007-04-03 Time 11:51 Rev Time 0.20
Received By tgordon Date 2007-04-03 Time 11:51 Sent To  
Notes
2007-04-03 11:52:54NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-05-08 Cont ID  
Sent By tgordon Date 2006-05-08 Time 16:47 Rev Time 0.15
Received By tgordon Date 2006-05-08 Time 16:47 Sent To  
Notes
2006-05-08 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 7 Status P Date 2007-06-12 Cont ID  
Sent By jleech Date 2007-06-12 Time 07:25 Rev Time 0.00
Received By jleech Date 2007-06-12 Time 07:24 Sent To  
Notes
2007-06-12 07:29:36PROVISO;
  
 NO DEAD ENDS PERMITED IN THE SANITARY DRAINAGE SYSTEM.
 PLUMBING DEMO TO BE DONE BY A LICENSED PLUMBING
 CONTRACTOR. PERMIT AND INSPECTION REQUIRED. SEE
 FBC-2004 PLUMBING SECTION 704.5.

Review Stop P PLUMBING
Rev No 6 Status F Date 2007-06-11 Cont ID  
Sent By jleech Date 2007-06-11 Time 09:22 Rev Time 0.00
Received By jleech Date 2007-06-11 Time 09:22 Sent To  
Notes
2007-06-11 09:46:21DENIED;
 1. DRINKING FOUNTAIN NOT SHOWN ON SANITARY RISER
 DIAGRAM OR ON PAGE # 6, FLAT PLUMBING DRAWING.
 2. DRINKING FOUNTAIN MUST BE RECESSED. ( SHOW ON
 DRAWING NOT 8 X 11 PAGE).
 3. CHANGE NOTES ON PAGE 10 " DEMO PLAN" ,FOR BATHROOM
 FIXTURESTO BE REMOVED, TO READ "NO DEAD ENDS PERMITED
 IN THE PLUMBING SYSTEM. REMOVE ALL PIPES BACK TO THE
 BUILDING DRAIN AND HARD CAP". FBC-2004 PLUMBING SECTION
 704.5.
 4. ADD NOTE TO DEMO PAGE 10"PLUMBING DEMO TO BE DONE
 BY A LICENSED PLUMBING CONTRACTOR, PERMIT AND
 INSPECTIONS REQUIRED".
 5.ADD NOTE TO PAGE # 2, " IF SPACES 5 AND 6 DO NOT HAVE
 ACCESS TO HALL WAY A DRINKING FOUNTAIN SHALL BE
 INSTALLED PER FBC-2004 PLUMBING TABLE 403.1".
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 5 Status F Date 2007-04-13 Cont ID  
Sent By jleech Date 2007-04-13 Time 13:13 Rev Time 0.00
Received By jleech Date 2007-04-13 Time 13:13 Sent To  
Notes
2007-04-13 14:22:09DENIED;
 I AM SENDING A COPY OF MY LAST 4 PLUMBING PLAN REVIEWS
 THE THIS 5TH PLUMBING PLAN REVIEW, TO SHOW THE SAME
 COMMENTS HAVE NOT BEEN ADDRESSED. I HAVE ALSO MARKED
 ONE SET OF PLANS IN RED AND YELLOW HIGHLIGHTER FOR YOUR
 REVIEW.
 1. PER OUR PHONE CONVERSATION ABOUT DRINKING FOUNTAINS,
 I AGREED THAT ONE DRINKING FOUNTAIN COULD BE INSTALLED
 IF ALL BAYS HAD ACCESS. BAY 5 AND 6 DO NOT HAVE ACCESS
 TO THE HALL WAY. DRINKING FOUNTAIN WOULD BE REQUIRED IN
 THOSE 2 BAYS. ON PAGE 2 YOU SHOW A BOTTLE WATER
 DISPENSOR AND ON PAGE 8A DIAGRAM OF A BOTTLE WATER
 COOLER IS SHOWN. A DRINKING FOUNTAIN IS REQUIRED AND
 CANNOT BE SUBSTITUTED WITH BOTTLE WATER. SEE FBC-2004
 PLUMBING SECTION 410.1. THE DRINKING FOUNTAINS MUST
 MEET HANDICAP REQUIREMENTS IN CHAPER 11 OF THE BUILDING
 CODE SECTIONS 11-4.1.3(10) AND SECTIONS 11-4.15.1 THRU
 11-4.15. 5. SHOW CUP HOLDER FOR PEOPLE FOR PEOPLE WITH
 BAD BACKS. IF A DRINKING FOUNTAIN IS IN A HALE WAY IT
 MUST BE RECESSED SO IT WILL NOT BE AN OBSTRUCTION THAT
 BE BE BUMPED INTO. SEE FIGURE 27(D), A COPY IS GLUED
 ONTO PAGE 8 ALSO.
 2. WATER CLOSET IN BAY 7 IS STILL NOT VENTED. THE
 BRANCH DRAINFROM THE W/C GOES TO THE BUILDING DRAIN
 WITHOUT A VENT. THERE ARE TOO MANY FIXTURE UNITS ON THE
 BUILDING DRAIN TO WET VENT W/C #7. SEE TABLE 909.3 WET
 VENT SIZING.
 3. BUILDING DRAIN SIZE IS NOT CORRECT. SEE
 TABLE710.1(1) THREE INCH. PIPE AT 1/4" PITCH CAN CARRYA
 MAXUMUM OF 42 FU'S PLANS SHOW A TOTAL OF 64FU'S. PIPE
 SIZE MUST INCRESS TO 4" AFTER BATHROON # 4.
 4. WATER RISER DIAGRAM PAGE 6.1. EXTEND 1" WATER PIPE
 TO BATHROOM 3.
 PLEASE READ THE IMPORTANT NOTICE THAT IS
 ATTACHED TO MY PLUMBING PLAN REVIEWS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-03-03 Cont ID  
Sent By jleech Date 2007-03-03 Time 09:15 Rev Time 0.00
Received By jleech Date 2007-03-03 Time 09:15 Sent To  
Notes
2007-03-03 09:47:09DENIED;
 FOURTH PLUMBING REVIEW. COMMENTS FROM REVIEW # 3 WERE
 NOT ADDRESSED. SHOW DATE OF REVISION ON PLANS AND CLOUD
 CHANGES FOR CLARITY.
 1. DRINKING FOUNTAINS ARE REQUIRED IN EACH UNIT. SEE
 FBC-2004 PLUMBING TABLE 403.1(6M). AND SECTION 410.1.
 2. SANITARY RISER DIAGRAM;
 A) TOILET IN BAY 7 IS NOT VENTED. ( ONE SET OF
 PLANS MARKED IN RED)
 B) TABLE 710.1(1) ONLY 42 FIXTURES PERMITED ON 3"
 AT 1/4" PER FT PITCH.
 3. WATER PIPE SIZING NOT CORRECT. SEE TABLE 603.1 ( SEE
 ONE SET OF PLANS MARKED IN RED)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-01-08 Cont ID  
Sent By jleech Date 2007-01-08 Time 08:34 Rev Time 0.00
Received By jleech Date 2007-01-08 Time 08:34 Sent To  
Notes
2007-01-08 09:09:34DENIED;
 1.DRINKING FOUNTAINS REQUIRED FBC-2004 PLUMBING CODE
 TABLE 403.1 (6M).
 2.SANITARY RISER DIAGRAM;
 (A)W/C IN BAY 7 IS NOT VENTED.
 (B)PIPE SIZE NOT CORRECT SEE TABLE710.1.
 3. WATER PIPE SIZING TO SMALL, SEE APPENDIX E OF THE
 PLUMBING CODE,
 TABLE E103.3(2) LOAD VALUES
 TABLE E103.3(3) ESTIMATING DEMAND
 FIGURE E103.3(3).
 NOTE; FLUID VALOCITIES IN EXCESS OF 5 TO 8 FT/SEC
 ARE NOT RECOMMENDED. VALOCITY OF SERVICE PIPE WOULD BE
 OVER 10 FT/SEC.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-09 Cont ID  
Sent By jleech Date 2006-09-09 Time 13:41 Rev Time 0.00
Received By jleech Date 2006-09-09 Time 13:40 Sent To  
Notes
2006-09-09 00:00:00DENIED;
 1.(SECOND REQUEST) TYPE OF OCCUPANCY NOT
 SHOWN. SEE FBC-2004 EXISTING BUILDING
 CODE SECTION 810.1. IF CHANGE OF
 OCCPANCY THEN DRINKING FOUNTAINS ARE
 REQUIRED. BOTTLE WATER CAN NOT BE USED
 AS A SUBSTITUTE SEE PLUMBING CODE
 SECTION 410.1.
 2.(SECOND REQUEST) WATER AND SANITARY
 RISER DIAGRAMS ARE REQUIRED. SEE CHAPTER
 1 WPB AMENDMENTS, SECTION
 106.3.5.1.3(13).
 3.(SECOND REQUEST) BACLFLOW PROTECTION
 REQUIRED ON WATER SERVICE. SHOW ON PLAN
 OR ADD NOTE TO PLAN.
 4.(SECOND REQUEST) SHOW MINIMUM SLOPE
 ON HORIZONTAL 3" DRAIN PIPE WITH 40 FU"S
 IS 1/4" PER FOOT. NOT SHOWN ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-15 Cont ID  
Sent By jleech Date 2006-05-15 Time 09:45 Rev Time 0.00
Received By jleech Date 2006-05-15 Time 09:45 Sent To  
Notes
2006-05-15 00:00:00DENIED;
 1.OCCUPANCY TYPE NOT SHOWN ON PLANS.
 PLANS MUST COMPLY WITH FBC-2004 PLUMBING
 TABLE 403.1. DRINKING FOUNTAINS IN EACH
 SPACE ARE REQUIRED. IS AN EYE WASH
 REQUIRED AT SPRAY BOTH?
 2.WATER AND SANITARY RISER DIAGRAMS ARE
 REQUIRED. CHAPTER 1 WPB AMENDMENTS SEC.
 106.3.5.1.3(13).
 3.SHOW DETAIL OF HANDICAP BATHROOMS ON
 PLANSINCLUDE ALL REQUIRED MEASUREMENTS
 TO MEET FBC CHAPTER 11 SECS. 11-4.16 AND
 11-4.19.
 4.BACKFLOW PROTECTION REQUIRED ON WATER
 SERVICES.
 5. BUILDING DRAIN TO BE SIZEDUSING
 TABLE 710.1. SHOW MIN. SLOPE PER FOOT ON
 PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-14 Cont ID  
Sent By choops Date 2008-01-14 Time 10:02 Rev Time 0.00
Received By choops Date 2008-01-14 Time 10:02 Sent To B
Notes
2008-01-14 10:03:35***APPROVED - REVISION - ADDING HANDICAP PARKING***
  
  
  
 SEMT TO "B" - MJ

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-21 Cont ID  
Sent By choops Date 2007-12-21 Time 13:36 Rev Time 0.00
Received By choops Date 2007-12-21 Time 13:36 Sent To B
Notes
2007-12-21 13:47:46***FAILED - REVISION - ADDING HANDICAP PARKING***
  
  
 1)BACKING AISLE IS REQUIRED TO BE A MINIMUM OF 24'
 FROM THE REAR OF THE H/C SPACE TO THE BACK EDGE OF THE
 ALLEY.INDICATE COMPLIANCE WITH REQUIRED AISLE WIDTH.
  
 2)STRIPING SHALL BE IN COMPLIANCE WITH TYPICAL
 DETAIL (SEE ATTACHED).
  
 3)PURSUANT TO SECTION 94-443(C)(3)(A):TERMINAL
 ISLANDS.EACH ROW OF PARKING SPACES SHALL BE
 TERMINATED BY LANDSCAPED ISLANDS OF NOT LESS THAN FIVE
 FEET IN WIDTH AND NOT LESS THAN THE LENGTH OF THE
 ADJACENT PARKING STALL. THE LANDSCAPED ISLAND SHALL
 HAVE A MINIMUM RADIUS OF 2 1/2 FEET AT ITS END SO AS TO
 ALLOW CAR MANEUVERING. THE LANDSCAPED ISLAND SHALL
 CONTAIN AT LEAST ONE SHADE OR FLOWERING TREE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status N Date 2007-04-09 Cont ID  
Sent By jbabcock Date 2007-04-09 Time 10:11 Rev Time 0.00
Received By jbabcock Date 2007-04-09 Time 10:11 Sent To I
Notes
2007-04-09 10:12:121. SIGNAGE SHOWN ON SHEET 7, NORTH ELEVATION WILL
 REQUIRE A SEPERATE PERMIT.


Account Summary | Usage Policy | Privacy Policy