Plan Review Details - Permit 06050177
Plan Review Stops For Permit 06050177
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-12 Cont ID  
Sent By alange Date 2006-06-12 Time 11:42 Rev Time 0.50
Received By alange Date 2006-06-12 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-08 Cont ID  
Sent By jleahy Date 2006-09-07 Time 06:26 Rev Time 0.45
Received By jleahy Date 2006-09-07 Time 06:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-25 Cont ID  
Sent By jleahy Date 2006-07-25 Time 14:16 Rev Time 0.39
Received By jleahy Date 2006-07-25 Time 14:16 Sent To B
Notes
2006-07-25 00:00:00SPECS FOR TRANSFER SWITCH IS NOT WHAT IS
 SHOWN ON DRAWINGS.
  
 DRAWINGS SHOW TRANSFER SWITCH PANEL
 COMBO
  
 JAKE LEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-05 Cont ID  
Sent By btrobaug Date 2006-06-05 Time 14:22 Rev Time 0.50
Received By btrobaug Date 2006-06-05 Time 13:53 Sent To P
Notes
2006-06-05 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN MUST PRINT AND SIGN THEIR NAME TO
 SAME PER 106.3.4.2. FBC AS AMENDED. THIS
 ARTICLE ALSO IS AN EXTRACTION FROM THE
 EXEMPTION IN CHAPTER 471 OF THE FLORIDA
 STATUTES , 471.003, ALLOWING YOU TO DRAW
 YOUR OWN PLANS .
  
 IF USING 220.35 FOR CALCULATION THERE IS
 NO 80%. PLEASE USE CODE ARTICLES WHEN
 CALCULATING LOADS. 220 PART II,
 220.31(B)- AHU AT 100%. ONLY THE
 CIRCUITS IN THE GENERATOR PANEL NEED BE
 CALCULATED.
  
 PLEASE LOCATE ALL SERVICE EQUIPMENT ON
 THE PLAN, METER ENCLOSURE,
 DISCONNECTS,ATS, GENERATOR AND PANELS,
 SO THAT COMPLIANCE WITH ARTICLES 225 AND
 230 CAN BE REVIEWED. ASITE PLAN WILL
 SUFFICE.
  
 SUBMIT MANUFACTURERS SPEC'S FOR THE ATS,
 MUST BE SERVICE RATED OR HAVE A
 DISCONNECTING MEANS FROM THE GENERATOR.
 ARTICLE 225.31-225.38.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-05 Cont ID  
Sent By mperson Date 2006-06-05 Time 16:23 Rev Time 0.15
Received By mperson Date 2006-06-05 Time 16:23 Sent To M
Notes
2006-06-05 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 16:44 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 16:44 Sent To E
Notes
2006-08-18 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-21 Cont ID  
Sent By adarroug Date 2006-07-21 Time 08:36 Rev Time 0.00
Received By adarroug Date 2006-07-21 Time 08:36 Sent To E
Notes
2006-07-21 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 16:06 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 16:06 Sent To E
Notes
2006-05-22 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-12 Cont ID  
Sent By alange Date 2006-06-12 Time 11:42 Rev Time 0.00
Received By alange Date 2006-05-06 Time 13:57 Sent To  
Notes
2006-05-06 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-05 Cont ID  
Sent By mperson Date 2006-06-05 Time 16:23 Rev Time 0.00
Received By mperson Date 2006-06-05 Time 16:23 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-05-22 Cont ID  
Sent By mmclean Date 2006-05-22 Time 11:14 Rev Time 0.00
Received By mmclean Date 2006-05-22 Time 11:14 Sent To I
Notes
2006-05-22 00:00:00GENERATOR SITS BEYOND THE 25FT FRONT
 SETBACK.