| 2006-05-18 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED |
| | ON THE DRAWING AND TO THE PLUMBING NOTES |
| | FOR PLUMBING PLAN REVIEW: |
| | |
| | 1.PER CHAPTER 1, SECTION 106, PLEASE |
| | SUBMIT A DRAWING INDICATING EXISTING |
| | FLOOR PLAN LAY-OUT OF ROOMS AND A |
| | SEPERATE DRAWING INDICATING THE NEW |
| | PROPOSED FLOOR PLAN LAY-OUT. |
| | 2. 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE |
| | BUILDING OFFICIAL. NOTE THE SANITARY |
| | ISOMETRIC RISER DIAGRAM ON SHEET E-1 |
| | DOES NOT REFLECT THE FLOOR PLAN. |
| | (A) SHOWER IS NOT INDICATED ON SANI- |
| | TARY RISER DIAGRAM. |
| | 3. THE SINK INDICATED ON THE SANITARY |
| | PLUMBING RISER DIAGRAM IS NOT VENTED PER |
| | SECTION 901.2.1. PLEASE CORRECT FOR |
| | RESUBMITTAL. |
| | 4. PLUMBING NOTES #12 AND #14 ON SHEET |
| | E-1 ARE INCORRECT. #12 SHOULD READ, |
| | SOIL, WASTE & VENTING TO BE PVC DWV NOT |
| | DVW, PLEASE CORRECT FOR RESUBMITTAL. #14 |
| | SHOULD READ WATER HAMMER ARRESTORS NOT |
| | AIR HANDLER ARRESTERS PLEASE CORRECT FOR |
| | RESUBMITTAL |
| | |
| | END OF COMMENTS: |
| | |