Plan Review Details - Permit 06050125
Plan Review Stops For Permit 06050125
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-24 Cont ID  
Sent By alange Date 2006-10-24 Time 08:51 Rev Time 0.00
Received By alange Date 2006-10-24 Time 08:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-17 Cont ID  
Sent By alange Date 2006-10-17 Time 14:00 Rev Time 0.00
Received By alange Date 2006-10-17 Time 14:00 Sent To  
Notes
2006-10-17 14:02:27DENIED
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NEW COMMENT:713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-26 Cont ID  
Sent By alange Date 2006-07-26 Time 14:43 Rev Time 0.33
Received By alange Date 2006-07-26 Time 14:43 Sent To  
Notes
2006-07-26 00:00:00DENIED
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-09 Cont ID  
Sent By alange Date 2006-06-09 Time 08:10 Rev Time 1.50
Received By alange Date 2006-06-09 Time 08:10 Sent To  
Notes
2006-06-09 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-12 Cont ID  
Sent By btrobaug Date 2006-10-12 Time 13:43 Rev Time 0.50
Received By btrobaug Date 2006-10-12 Time 13:28 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 12:54 Rev Time 0.00
Received By dpalmer Date 2006-07-23 Time 11:54 Sent To M
Notes
2006-07-23 00:00:00******** UNSAT *************
  
 ** PLEASE SEE PLANS WERE REVISED AND
 THIS REVIEW IS BASED ON PLANS DATED JULY
 06 FROM ARCHITECT.
  
 ** IMPORTANT***
  
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 TAKEN OUT FOR CORRECTIONS. PLEASE
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE COPY OF
 THE OLD/VOIDED SHEETS FOR REFERENCE.
  
 1) NOTE: PLEASE SHOW IDENIFY AND SHOW
 LOCATIONS OF ALL PANELS ON PLANS. PLEASE
 SEE PLANS NOW INDICATE THE MAIN EXST
 150A LOCATED IN THE REAR OF BUIDLING,
 HOWEVER PLANS ALSO SHOW A PANEL IN
 GARAGE HOWEVER THIS IS NOT LABELED.
 LOCATED THE EXISTING 60A PANEL NOW SHOWN
 ON PLANS IN HALL. PLEASE CLAIFY PANEL IN
 GARAGE WHICH WAS REDLINED ON PLANS.
 110.26,240.24, ETC
  
 2) NOTE: PLEASE CORRLELATE ALL
 ELECTRICAL LOADS ON PLANS WITH PANEL
 SCHEDULES AND LOAD CALCULATIONS. PLEASE
 SEE GDO ON PLANS, BUT NOT ON CALCS OR
 PANEL SCHEDULES.
 PLEASE SEE A LAUNDRY CIRCUIT IS SHOWN ON
 LOADS CALCS, HOWEVER THIS IS NOT CLEAR
 AS ONLY A WASHER CIRCUIT IS SHOWN ON
 PANEL SCHEDULE. PLEASE SEE PLANS SHOWS
 ONE WASHER AND ONE LAUNDRY. PLEASE KNOW,
 WASHER/ LAUNDRY CIRCUIT(S) ARE A MIN OF
 1500VA FOR EACH PROVIDED.
 PLEASE CORRELATE AND ADJUST AS NEEDED.
 PLEASE CORRELATE LABELING OF PANEL(S)
 AND CALCS.210.11C2,220.16
 PLEASE SEE LOAD SHOWN FOR AHU IS 10KW
 AND PANEL SCHEDULE DOES NOT MEET THIS
 FOR OCP ETC.
 220, 106.1.2 FBC.
  
 3) NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU. PLEASE SEE CALCULATIONS SHOWS
 10KW, YET THE CONDUCTOR SIZES AND OCP ON
 PANEL SCHEDULE SHOWS #10 AND 30A OCP.
 PLEASE ADJUST.
  
 4) NOTE: PLEASE SEE 210.11C1,220.16 FOR
 THE MIN VA TO BE FIGURED FOR EACH SM
 APPL AND DINING RM AND AREAS OF THE LIKE
 CIRCUITS. ( DINING 1500VA MIN).
  
 5) NOTE: PLEASE SEE IT SEEM THE EXISTING
 WATER HEATER CIRCUIT SPACES ARE BEING
 REPLACED WITH THE NEW CIRCUITS FOR SMALL
 APPL'S HOWEVER PLEASE SEE #10 AWG, 30 A
 OCP AND 2-POLE BRKRS ARE STILL BEING
 SHOWN. PLEASE SEE MAX OCP ON SMALL APPL
 IS 20A'S.
 PLEASE ADJUST. 240.4,310.16,
  
 6) NOTE: PLEASE SEE LOADS SHOWN ON MAIN
 PANEL IS SHOWING 85 DEMAND AMPS, YET THE
 DE-RATED AMPERAGE IS 133A'S, HOW IS THIS
 POSSIBLE??
 PLEASE SHOW LOAD CALCULATIONS FOR SUB
 PANEL AND ADJUST LOADS FOR MAIN PANEL.
 PLEASE ALSO LABEL PANELS. ( A, B OR ?
 ETC).
 220.31,408.4,
  
 7) NOTE: PLEASE SEE 210.12BAND LIST
 THE REQUIRED ARC FAULT PROTECTION FOR
 NEW CIRCUITS AS REQUIRED.
 (BEDRMS).
 PLEASE ALSO SEE NEXT COMMENTS FOR SD'S.
  
 8) NOTE: PLEASE SEE 2004 FBC RESIDENTIAL
 CODE R313. PLEASE SHOW A LAYOUT FOR THE
 EXSITING DWELLING SHOWING COMPLIANCE FOR
 ALL SD'S MEEITNG THE CURRENT NFPA-72
 11.5.1.1, 11.8.3. SHOW SD'S IF EXISTING
 MEETING CURRENT CODES, OR PLEASE SHOW
 ALL NEW WHICH WILL BE REQUIRED TO BE
 INSTALLED.
 PLEASE KNOW, THESE SHALL BE WIRED
 INLINE, 120V W/ BATTERY BACK UP AND
 SHALL BE ON A ARC FAULT PROTECTED
 CIRCUIT.210.12B
  
 9) NOTE: PLEASE CLARIFY THE SIZE OF THE
 EXISTING GROUNDING ELECTRODE CONDUCTOR??
 THIS IS OK, HOWEVER SEEMS TO BE VERY
 LARGE FOR THE 150A SERVICE SHOWN.
 PLEASE ALSO SEE AS THE GEC IS REQUIRED
 TO BE CONTINUOUS AND THE NEW FOOTER
 STEEL IS REQUIRED TO BE PART OF THE
 EXISTING GROUNDING ELECTRODE SYSTEM, IF
 SHOWN AS 1/0, THEN 1/0 WILL BE REQUIRED.
 PLEASE SEE TABLES IN 250.66 FOR MIN SIZE
 AND REQUIRED NEW FOOTER PER 250.50.
  
 10) NOTE: PLEASE SEE PLANS SHALL REFLECT
 THE CURRENT CODES AS ADOPTED BY THE
 STATE FOR PROJECT. PLEASE SEE THE
 FOLLOWING CODES AT A MIN DHOULD BE NOTED
 ON PLANS.
 2002 NFPA-70 (NEC) AND NFPA-72 2002.
  
 11) NOTE: NOTED BY PREVIOUS REVIEWER,
 PLEASE BE SURE PERMIT APPLICATION IS
 REVISED TO INCLUDE INTERIOR REMODEL
 ALONG WITH ADDITION OF THE GARAGE
 ALREADY MENTIONED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By btrobaug Date 2006-05-31 Time 16:15 Rev Time 1.00
Received By btrobaug Date 2006-05-31 Time 15:10 Sent To P
Notes
2006-05-31 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} THERE ARE NO RATINGS ON ANY OF THE
 PROPOSED SERVICE EQUIPMENT. INDICATE
 VOLTAGE , AMPERE AND MAIN BREAKER
 RATINGS.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 3} PROVIDE PANEL SCHEDULES FOR ALL
 PANELS. 215.5.
  
 4} PROVIDE A TOTAL LOAD CALCULATION PER
 220 PART II, OR OPTIONAL PER 220.III.
 INDICATE WHICH ARTICLE IS BEING USED.
 THE CALCULATION GIVEN IS ONLY PARTIAL.
  
 5} THE DESCRIPTION ON THE APPLICATION
 DOES NOT MENTION THE INTERIOR WORK,
 INCLUDING AN ELECTRICAL SERVICE CHANGE
 AND BRANCH CIRCUIT WIRING. PLEASE
 INDICATE THE SCOPE OF WORK ON THE
 APPLICATION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected].
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-20 Cont ID  
Sent By adarroug Date 2006-10-20 Time 15:10 Rev Time 0.00
Received By adarroug Date 2006-10-20 Time 15:08 Sent To B
Notes
2006-10-20 15:08:42TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-29 Cont ID  
Sent By adarroug Date 2006-09-29 Time 11:34 Rev Time 0.00
Received By adarroug Date 2006-09-29 Time 11:34 Sent To E
Notes
2006-09-29 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 10:53 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 10:53 Sent To E
Notes
2006-07-18 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-13 Cont ID  
Sent By adarroug Date 2006-07-13 Time 08:14 Rev Time 0.00
Received By adarroug Date 2006-07-13 Time 08:14 Sent To Z
Notes
2006-07-13 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 12:49 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 12:49 Sent To E
Notes
2006-05-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-09 Cont ID  
Sent By alange Date 2006-06-09 Time 08:11 Rev Time 0.00
Received By alange Date 2006-05-04 Time 16:36 Sent To  
Notes
2006-05-04 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-07-24 Cont ID  
Sent By tgordon Date 2006-07-24 Time 14:49 Rev Time 0.20
Received By tgordon Date 2006-07-24 Time 14:49 Sent To P
Notes
2006-07-24 00:00:00VENT OPENINGS TO SUPPLY COMBUSTION AIR
 FOR GAS APPLIANCES HAVE BEEN PROVIED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-05 Cont ID  
Sent By tgordon Date 2006-06-05 Time 15:25 Rev Time 0.30
Received By tgordon Date 2006-06-05 Time 15:25 Sent To B
Notes
2006-06-05 00:00:00*** DENIED ***
 1) PROVIED COMBUSTION AIR FOR GAS
 CLOTHES DRIER, IF DIRECT VENT PROVIED
 DETAILED MANUFACTURE'S SPECIFICATION'S
 AND INSTALLATION INSTRUCTIONS. PER 2004
 FBC/R M1701.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-25 Cont ID  
Sent By jleech Date 2006-07-25 Time 09:23 Rev Time 0.00
Received By jleech Date 2006-07-25 Time 09:23 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-05 Cont ID  
Sent By jleech Date 2006-06-05 Time 12:06 Rev Time 0.00
Received By jleech Date 2006-06-05 Time 12:06 Sent To M
Notes
2006-06-05 00:00:00DENIED;
 1.DELETE WATER HEATER DETAIL HEATER IS
 GAS NOT ELECTRIC. GAS HEATER TO BE 18"
 AFF TO GAS BURNERS.
 2.P & T RELIEF VALVE REQUIRES AN AIR GAP
 FITTING IF RUN TO OUTSIDE FBC-2004
 PLUMBING SEC. 504.6.1.
 3.CLEANOUT REQUIRED ON W/M STACK AT 48"
 AFF.
 4.WATER HEATER CLOSET OUTSIDE AIR
 REQUIRED AT THE TOP OF THE W/H ROOM
 ALSO, SEE MECHANICAL CODE SEC. 702 AND
 703.2.
 5.CLOTHES DRYER IS IN A CONFINED SPACE,
 SEE SEC. 702.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-17 Cont ID  
Sent By mmclean Date 2006-07-17 Time 16:29 Rev Time 0.00
Received By mmclean Date 2006-07-17 Time 16:29 Sent To I
Notes
2006-07-17 00:00:00NOTE: THE PROPOSED ADDITION/GARAGE MUST
 MEET THE MINIMUM SETBACK OF 25FT WITHIN
 THE FRONT SETBACK OF PROPERTY. THE
 SUBMITTED SITEPLANS SHOWS THE FRONT
 SETBACK AT 25FT.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-19 Cont ID  
Sent By mmclean Date 2006-05-19 Time 14:24 Rev Time 0.00
Received By mmclean Date 2006-05-19 Time 14:24 Sent To I
Notes
2006-05-19 00:00:00DENIED,
 1. THE PROPOSED ADDITION ON BOTH
 SITEPLAN & SURVEY DOES MATCH SETBACKS.
 NOTE: SURVEY SHOWS 18.6 AND SITEPLAN
 25.1. (SURVEY IS A LEGAL DOCUMENT,
 PLEASE CORRECT).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720