| 2006-07-23 00:00:00 | ******** UNSAT ************* |
| | |
| | ** PLEASE SEE PLANS WERE REVISED AND |
| | THIS REVIEW IS BASED ON PLANS DATED JULY |
| | 06 FROM ARCHITECT. |
| | |
| | ** IMPORTANT*** |
| | |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | TAKEN OUT FOR CORRECTIONS. PLEASE |
| | COMPLETELY REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. PLEASE ONLY SUBMIT ONE COPY OF |
| | THE OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | 1) NOTE: PLEASE SHOW IDENIFY AND SHOW |
| | LOCATIONS OF ALL PANELS ON PLANS. PLEASE |
| | SEE PLANS NOW INDICATE THE MAIN EXST |
| | 150A LOCATED IN THE REAR OF BUIDLING, |
| | HOWEVER PLANS ALSO SHOW A PANEL IN |
| | GARAGE HOWEVER THIS IS NOT LABELED. |
| | LOCATED THE EXISTING 60A PANEL NOW SHOWN |
| | ON PLANS IN HALL. PLEASE CLAIFY PANEL IN |
| | GARAGE WHICH WAS REDLINED ON PLANS. |
| | 110.26,240.24, ETC |
| | |
| | 2) NOTE: PLEASE CORRLELATE ALL |
| | ELECTRICAL LOADS ON PLANS WITH PANEL |
| | SCHEDULES AND LOAD CALCULATIONS. PLEASE |
| | SEE GDO ON PLANS, BUT NOT ON CALCS OR |
| | PANEL SCHEDULES. |
| | PLEASE SEE A LAUNDRY CIRCUIT IS SHOWN ON |
| | LOADS CALCS, HOWEVER THIS IS NOT CLEAR |
| | AS ONLY A WASHER CIRCUIT IS SHOWN ON |
| | PANEL SCHEDULE. PLEASE SEE PLANS SHOWS |
| | ONE WASHER AND ONE LAUNDRY. PLEASE KNOW, |
| | WASHER/ LAUNDRY CIRCUIT(S) ARE A MIN OF |
| | 1500VA FOR EACH PROVIDED. |
| | PLEASE CORRELATE AND ADJUST AS NEEDED. |
| | PLEASE CORRELATE LABELING OF PANEL(S) |
| | AND CALCS.210.11C2,220.16 |
| | PLEASE SEE LOAD SHOWN FOR AHU IS 10KW |
| | AND PANEL SCHEDULE DOES NOT MEET THIS |
| | FOR OCP ETC. |
| | 220, 106.1.2 FBC. |
| | |
| | 3) NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU. PLEASE SEE CALCULATIONS SHOWS |
| | 10KW, YET THE CONDUCTOR SIZES AND OCP ON |
| | PANEL SCHEDULE SHOWS #10 AND 30A OCP. |
| | PLEASE ADJUST. |
| | |
| | 4) NOTE: PLEASE SEE 210.11C1,220.16 FOR |
| | THE MIN VA TO BE FIGURED FOR EACH SM |
| | APPL AND DINING RM AND AREAS OF THE LIKE |
| | CIRCUITS. ( DINING 1500VA MIN). |
| | |
| | 5) NOTE: PLEASE SEE IT SEEM THE EXISTING |
| | WATER HEATER CIRCUIT SPACES ARE BEING |
| | REPLACED WITH THE NEW CIRCUITS FOR SMALL |
| | APPL'S HOWEVER PLEASE SEE #10 AWG, 30 A |
| | OCP AND 2-POLE BRKRS ARE STILL BEING |
| | SHOWN. PLEASE SEE MAX OCP ON SMALL APPL |
| | IS 20A'S. |
| | PLEASE ADJUST. 240.4,310.16, |
| | |
| | 6) NOTE: PLEASE SEE LOADS SHOWN ON MAIN |
| | PANEL IS SHOWING 85 DEMAND AMPS, YET THE |
| | DE-RATED AMPERAGE IS 133A'S, HOW IS THIS |
| | POSSIBLE?? |
| | PLEASE SHOW LOAD CALCULATIONS FOR SUB |
| | PANEL AND ADJUST LOADS FOR MAIN PANEL. |
| | PLEASE ALSO LABEL PANELS. ( A, B OR ? |
| | ETC). |
| | 220.31,408.4, |
| | |
| | 7) NOTE: PLEASE SEE 210.12BAND LIST |
| | THE REQUIRED ARC FAULT PROTECTION FOR |
| | NEW CIRCUITS AS REQUIRED. |
| | (BEDRMS). |
| | PLEASE ALSO SEE NEXT COMMENTS FOR SD'S. |
| | |
| | 8) NOTE: PLEASE SEE 2004 FBC RESIDENTIAL |
| | CODE R313. PLEASE SHOW A LAYOUT FOR THE |
| | EXSITING DWELLING SHOWING COMPLIANCE FOR |
| | ALL SD'S MEEITNG THE CURRENT NFPA-72 |
| | 11.5.1.1, 11.8.3. SHOW SD'S IF EXISTING |
| | MEETING CURRENT CODES, OR PLEASE SHOW |
| | ALL NEW WHICH WILL BE REQUIRED TO BE |
| | INSTALLED. |
| | PLEASE KNOW, THESE SHALL BE WIRED |
| | INLINE, 120V W/ BATTERY BACK UP AND |
| | SHALL BE ON A ARC FAULT PROTECTED |
| | CIRCUIT.210.12B |
| | |
| | 9) NOTE: PLEASE CLARIFY THE SIZE OF THE |
| | EXISTING GROUNDING ELECTRODE CONDUCTOR?? |
| | THIS IS OK, HOWEVER SEEMS TO BE VERY |
| | LARGE FOR THE 150A SERVICE SHOWN. |
| | PLEASE ALSO SEE AS THE GEC IS REQUIRED |
| | TO BE CONTINUOUS AND THE NEW FOOTER |
| | STEEL IS REQUIRED TO BE PART OF THE |
| | EXISTING GROUNDING ELECTRODE SYSTEM, IF |
| | SHOWN AS 1/0, THEN 1/0 WILL BE REQUIRED. |
| | PLEASE SEE TABLES IN 250.66 FOR MIN SIZE |
| | AND REQUIRED NEW FOOTER PER 250.50. |
| | |
| | 10) NOTE: PLEASE SEE PLANS SHALL REFLECT |
| | THE CURRENT CODES AS ADOPTED BY THE |
| | STATE FOR PROJECT. PLEASE SEE THE |
| | FOLLOWING CODES AT A MIN DHOULD BE NOTED |
| | ON PLANS. |
| | 2002 NFPA-70 (NEC) AND NFPA-72 2002. |
| | |
| | 11) NOTE: NOTED BY PREVIOUS REVIEWER, |
| | PLEASE BE SURE PERMIT APPLICATION IS |
| | REVISED TO INCLUDE INTERIOR REMODEL |
| | ALONG WITH ADDITION OF THE GARAGE |
| | ALREADY MENTIONED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |