Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-12 Cont ID  
Sent By rmcdouga Date 2006-07-11 Time 16:10 Rev Time 0.00
Received By rmcdouga Date 2006-07-11 Time 16:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-19 Cont ID  
Sent By rmcdouga Date 2006-06-19 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2006-06-19 Time 16:32 Sent To  
Notes
2006-06-19 00:00:00DENIED
  
 1) THE NOA SUBMITTED FOR THE CERTAINTEED
 MODIFIED BITUMEN ROOFING SYSTEM REQUIRES
 RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING BE SIGNED AND SEALED BY AN
 ARCHITECT, ENGINEER OR REGISTERED ROOF
 CONSULTANT. SEE COMMENT #2 ON FIRST
 REVIEW. SUBMIT SIGNED AND SEALED RAS 117
 CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-02 Cont ID  
Sent By rmcdouga Date 2006-05-02 Time 14:18 Rev Time 0.00
Received By rmcdouga Date 2006-05-02 Time 14:18 Sent To  
Notes
2006-05-02 00:00:00DENIED
  
 1) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 COVERSHEET WITH FL PRODUCT NUMBER FOR
 ALL PRODUCTS.
  
 2) INDICATE WHICH ONE OF THE APPROVED
 SYSTEMS LISTED IN NOA THE FOR THE
 MODIFIED BITUMEN ROOF SYSTEM WILL BE
 INSTALLED. CIRCLE THE APPROVED ASSEMBLY
 INFORMATION IN THE NOA ON PAGES 31-38
 FOR NON-INSULATED WOOD DECKS. NOTE: NONE
 OF THE SYSTEMS LISTED WILL WORK WITHOUT
 ENHANCED FASTENING, WHICH IS ALLOWED BY
 LIMITATION #7 ON PAGE 40 OF THE NOA.
 HOWEVER, LIMITATION #7 REQUIRES THE RAS
 117 CALCULATIONS FOR INCREASED FASTENERS
 DENSITIES BEPREPARED BY AN ENGINEER,
 ARCHITECT OR REGISTERED ROOFING
 CONSULTANT. THEREFORE, SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE
 ASPHALT SHINGLES. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED IS FOR HIP AND RIDGE
 CAP SHINGLES.
  
 4) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-11 Cont ID  
Sent By adarroug Date 2006-07-11 Time 15:21 Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 15:21 Sent To B
Notes
2006-07-11 00:00:00TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-19 Cont ID  
Sent By rmcdouga Date 2006-06-19 Time 16:33 Rev Time 0.00
Received By rmcdouga Date 2006-06-19 Time 14:55 Sent To  
Notes
2006-06-19 00:00:00TO "RMCDOUGAL" DESK/RESUB