Plan Review Details - Permit 06050052
Plan Review Stops For Permit 06050052
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-06-28 Cont ID  
Sent By mperson Date 2006-06-28 Time 11:54 Rev Time 0.33
Received By mperson Date 2006-06-28 Time 11:53 Sent To PC
Notes
2006-06-28 00:00:00REVISION: CHANGED PIPING FROM CSST TO
 GALVANIZED, DELETED FUTURE BBQ.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 900 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 9,950 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-05-10 Cont ID  
Sent By mperson Date 2006-05-10 Time 13:58 Rev Time 0.50
Received By mperson Date 2006-05-10 Time 13:58 Sent To PC
Notes
2006-05-10 00:00:00 
  
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.5 0R
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 900 CUBIC FEET REQUIRED.
  
 ******PROVISO******
 PER SECTION 404.12 OUTLET CLOSURES. GAS
 OUTLETS THAT DO NOT CONNECT TO
 APPLIANCES SHALL BE CAPPED GAS TIGHT.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 11:16 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 11:16 Sent To P
Notes
2006-06-15 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-10 Cont ID  
Sent By mperson Date 2006-05-10 Time 14:07 Rev Time 0.00
Received By mperson Date 2006-05-02 Time 12:24 Sent To  
Notes
2006-05-02 00:00:00TO "G" BOX