| 2006-05-31 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06041193 |
| | ADD: 410 EVERNIA ST |
| | CONT: MEISNER ELECTRIC |
| | TEL: (561)278-8362 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | 1) GENERATOR SLAB & ANCHOR REQUIREMENT |
| | PLEASE PROVIDE SIZE OF GENERATOR(WXL), |
| | PLUS PROVIDE PLANS WITH THE INFORMATION |
| | DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE |
| | THE DEVICE REQUIRES WITHOUT LOAD |
| | REDUCTION. |
| | SECOND, PROVIDE INFORMATION ON THE |
| | SLAB, THICKNESS, WIDTH AND LENGTH, IF |
| | WIREMESH, FIBER MESH OR IF STEEL REBAR |
| | WILL BEUSED. |
| | THE NEW SLAB AND HOLD DOWN DETAILS: |
| | 104.2.1* ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 2)PROVIDE PLANS ENOUGH TO VERIFY |
| | LOCATION OF GENERATOR VERSES BUILDING |
| | OPENINGS WINDOWS, DOORS OR SOFFIT TYPE |
| | VENTS, ETC. |
| | |
| | MECHANICAL CODE |
| | 804.3.4 HORIZONTAL TERMINATIONS. |
| | HORIZONTAL TERMINATIONS SHALL COMPLY |
| | WITH THE FOLLOWING REQUIREMENTS: |
| | 1.WHERE LOCATED ADJACENT TO |
| | WALKWAYS, THE TERMINATION OF MECHANICAL |
| | DRAFT SYSTEMS SHALL BE NOT LESS THAN 7 |
| | FEET (2134 MM) ABOVE THE LEVEL OF THE |
| | WALKWAY. |
| | 2.VENTS SHALL TERMINATE AT LEAST 3 |
| | FEET (914 MM) ABOVE ANY FORCED AIR INLET |
| | LOCATED WITHIN 10 FEET (3048 MM). |
| | 3.THE VENT SYSTEM SHALL TERMINATE |
| | AT LEAST 4 FEET (1219 MM) BELOW, 4 FEET |
| | (1219 MM) HORIZONTALLY FROM OR 1 FOOT |
| | (305 MM) ABOVE ANY DOOR, WINDOW OR |
| | GRAVITY AIR INLET INTO THE BUILDING. |
| | 4.THE VENT TERMINATION POINT SHALL |
| | NOT BE LOCATED CLOSER THAN 3 FEET (914 |
| | MM) TO AN INTERIOR CORNER FORMED BY TWO |
| | WALLS PERPENDICULAR TO EACH OTHER. |
| | 5.THE VENT TERMINATION SHALL NOT BE |
| | MOUNTED DIRECTLY ABOVE OR WITHIN 3 FEET |
| | (914 MM) HORIZONTALLY FROM AN OIL TANK |
| | VENT OR GAS METER. |
| | 6.THE BOTTOM OF THE VENT |
| | TERMINATION SHALL BE LOCATED AT LEAST 12 |
| | INCHES (305 MM) ABOVE FINISHED GRADE. |
| | |
| | 804.3.5 VERTICAL TERMINATIONS. |
| | VERTICAL TERMINATIONS SHALL COMPLY WITH |
| | THE FOLLOWING REQUIREMENTS: |
| | 1.WHERE LOCATED ADJACENT TO |
| | WALKWAYS, THE TERMINATION OF MECHANICAL |
| | DRAFT SYSTEMS SHALL BE NOT LESS THAN 7 |
| | FEET (2134 MM) ABOVE THE LEVEL OF THE |
| | WALKWAY. |
| | 2.VENTS SHALL TERMINATE AT LEAST 3 |
| | FEET (914 MM) ABOVE ANY FORCED AIR INLET |
| | LOCATED WITHIN 10 FEET (3048 MM). |
| | 3.WHERE THE VENT TERMINATION IS |
| | LOCATED BELOW AN ADJACENT ROOF |
| | STRUCTURE, THE TERMINATION POINT SHALL |
| | BE LOCATED AT LEAST 3 FEET (914 MM) FROM |
| | SUCH STRUCTURE. |
| | 4.THE VENT SHALL TERMINATE AT LEAST |
| | 4 FEET (1219 MM) BELOW, 4 FEET (1219 MM) |
| | HORIZONTALLY FROM, OR 1 FOOT (305 MM) |
| | ABOVE ANY DOOR, WINDOW OR GRAVITY AIR |
| | INLET FOR THE BUILDING. |
| | 5.A VENT CAP SHALL BE INSTALLED TO |
| | PREVENT RAIN FROM ENTERING THE VENT |
| | SYSTEM. |
| | 6.THE VENT TERMINATION SHALL BE |
| | LOCATED AT LEAST 3 FEET (914 MM) |
| | HORIZONTALLY FROM ANY PORTION OF THE |
| | ROOF STRUCTURE. |
| | |
| | 501.2 OUTDOOR DISCHARGE. |
| | |
| | THE AIR REMOVED BY EVERY MECHANICAL |
| | EXHAUST SYSTEM SHALL BE DISCHARGED |
| | OUTDOORS AT A POINT WHERE IT WILL NOT |
| | CAUSE A NUISANCE AND FROM WHICH IT |
| | CANNOT AGAIN BE READILY DRAWN IN BY A |
| | VENTILATING SYSTEM. AIR SHALL NOT BE |
| | EXHAUSTED INTO AN ATTIC OR CRAWL SPACE |
| | |
| | 401.5 OPENING LOCATION. |
| | OUTDOOR AIR EXHAUST AND INTAKE OPENINGS |
| | SHALL BE LOCATED A MINIMUM OF 10 FEET |
| | (3048 MM) FROM LOT LINES OR BUILDINGS ON |
| | THE SAME LOT. WHERE OPENINGS FRONT ON A |
| | STREET OR PUBLIC WAY, THE DISTANCE SHALL |
| | BE MEASURED TO THE CENTERLINE OF THE |
| | STREET OR PUBLIC WAY. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |