Plan Review Details - Permit 06041182
Plan Review Stops For Permit 06041182
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-08-01 Cont ID  
Sent By shill Date 2006-06-19 Time 15:04 Rev Time 0.00
Received By shill Date 2006-06-19 Time 15:04 Sent To  
Notes
2006-06-19 00:00:00SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)PROVIDE A FLOOR PLAN SHOWING WINDOW
 SIZES AND LOCATIONS.SHOW ZONE 5 ON THE
 PLAN.
  
 THE PRODUCT APPROVAL HAS A PRODUCT WITH
 A DP LIMIT OF -46.1.A ZONE 5, 20SF
 WOULD HAVE A DESIGN PRESSURE OF -46.2.
 CONTRACTOR INDICATED THAT THE PRODUCT TO
 BE USED WILL BE THE PRODUCT WITH +-70
 LIMITATION.PLEASE CIRCLE THIS ON THE
 PRODUCT APPROVAL.+-70 IS COMPLIANT FOR
 ALL OPENINGS REGARDLESS OF ZONE.
  
 2.)INDICATE THAT THE WINDOWS ARE TO BE
 INSTALLED IN THE SAME LOCATIONS, SAME
 SIZES OR SHOW THE PROPOSED ALTERATIONS
 ON THE PLAN.
  
 NOT ADDRESSED.
  
 3.)PROVIDE THE BUILDING HEIGHT AND
 DESIGN PRESSURE INFORMATION FBC1609.
  
 HEIGHT WAS PROVIDED.SEE #1 ABOVE.
 SOME OPENINGS ARE NOT COMPLIANT FOR ZONE
 5 FOR THIS BUILDING HEIGHT, FBC TABLE
 1609B AND D.SAME COMMENT APPLIES; IF
 PRODUCT WITH +-70 IS USED, THIS IS
 COMPLIANT FOR ALL OPENINGS.CIRCLE ON
 THE PRODUCT APPROVAL.
  
 4.)THE NOTICE OF COMMENCEMENT PROVIDED
 DOES NOT HAVE THE OWNER INFORMATION.
 FS713.13.
  
 5.)VALUATION APPEARS LOW.PROVIDE A
 REASONABLE VALUE OF WORK OR AN ESTIMATE
 WILL BE DONE FOR YOU USING MARSHALL &
 SWIFT. - NOTE - ADJUSTED VALUE PER
 CONTRACTOR
  
 NEW COMMENTS -
  
 6.)THE NEW PLAN SUBMITTED SHOWS
 MULLIONS.PLEASE PROVIDE PRODUCT
 APPROVALS.IF THE MULLION PRODUCT
 APPROVALS SHOW NONCOMPLIANT OPTIONS
 BASED ON WIND PRESSURES FBC TABLE
 1609.6B AND D, CIRCLE WHICH PRODUCT YOU
 WILL USE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-04 Cont ID  
Sent By shill Date 2007-09-04 Time 08:12 Rev Time 0.00
Received By shill Date 2007-09-04 Time 08:12 Sent To  
Notes
2007-09-04 08:13:04REV OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-01 Cont ID  
Sent By shill Date 2006-08-01 Time 15:46 Rev Time 0.00
Received By shill Date 2006-08-01 Time 15:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-24 Cont ID  
Sent By shill Date 2006-05-24 Time 18:23 Rev Time 0.00
Received By shill Date 2006-05-24 Time 18:23 Sent To  
Notes
2006-05-24 00:00:00SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE A FLOOR PLAN SHOWING WINDOW
 SIZES AND LOCATIONS.SHOW ZONE 5 ON THE
 PLAN.
  
 2.)INDICATE THAT THE WINDOWS ARE TO BE
 INSTALLED IN THE SAME LOCATIONS, SAME
 SIZES OR SHOW THE PROPOSED ALTERATIONS
 ON THE PLAN.
  
 3.)PROVIDE THE BUILDING HEIGHT AND
 DESIGN PRESSURE INFORMATION FBC1609.
  
 4.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 5.)THE VALUE APPEARS VERY LOW; $300
 PER OPENING, INSTALLED, FOR IMPACT GLASS
 ON A MULTISTORY BUILDING.PROVIDE A
 MORE REASONABLE VALUE OR AN ESTIMATE
 WILL BE DONE FOR YOU USING MARSHALL &
 SWIFT.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 16:36 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 16:36 Sent To B
Notes
2007-08-29 16:39:36TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-11 Cont ID  
Sent By adarroug Date 2007-06-11 Time 13:46 Rev Time 0.00
Received By adarroug Date 2007-06-11 Time 13:46 Sent To B
Notes
2007-06-11 13:46:50TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 15:12 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 15:12 Sent To B
Notes
2006-07-14 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 11:35 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 11:35 Sent To  
Notes
2006-06-08 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-24 Cont ID  
Sent By shill Date 2006-05-24 Time 18:25 Rev Time 0.00
Received By shill Date 2006-04-29 Time 15:32 Sent To  
Notes
2006-04-29 00:00:00TO "MISC' BOX#1