Plan Review Details - Permit 06041179
Plan Review Stops For Permit 06041179
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-09-04 Cont ID  
Sent By shill Date 2007-09-04 Time 08:08 Rev Time 0.00
Received By shill Date 2007-09-04 Time 08:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-08-31 Cont ID  
Sent By shill Date 2006-08-31 Time 16:19 Rev Time 0.00
Received By shill Date 2006-08-31 Time 16:19 Sent To  
Notes
2006-08-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)ENGINEERING LETTERS ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS, TWO
 ORIGINALS REQUIRED.THE LETTER
 SUBMITTED VIA FAX FOR PRELIMINARY WAS
 ONE PAGE WITH NO SIGNATURE OR SEAL.WAS
 THE LETTER COMPLETE?
  
 2.)THE LETTER IS TO REFER TO THE
 SPECIFIC PRODUCT BEING INSTALLED.IT IS
 NOT CLEAR FROM THE LETTER WHICH PRODUCT
 WAS REVIEWED.
  
 3.)ENGINEERING IS TO INCLUDE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002.
  
 4.)THE FLOOR PLAN NOTE REGARDING THE
 MULLION IS NOT LEGIBLE.ALSO, IT POINTS
 A GENERAL DIRECTION BUT IS NOT CLEAR AS
 TO WHERE THE MULLIONS ARE LOCATED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-08-24 Cont ID  
Sent By shill Date 2006-08-24 Time 14:21 Rev Time 0.00
Received By shill Date 2006-08-24 Time 14:21 Sent To  
Notes
2006-08-31 00:00:00COMMENTS REGARDING THE ENGINEERING
 LETTER:
  
 1.)ENGINEERING LETTERS ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS, TWO
 ORIGINALS REQUIRED.THE LETTER
 SUBMITTED VIA FAX FOR PRELIMINARY WAS
 ONE PAGE WITH NO SIGNATURE OR SEAL.WAS
 THE LETTER COMPLETE?
  
 2.)THE LETTER IS TO REFER TO THE
 SPECIFIC PRODUCT BEING INSTALLED.IT IS
 NOT CLEAR FROM THE LETTER WHICH PRODUCT
 WAS REVIEWED.
  
 3.)ENGINEERING IS TO INCLUDE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002.
  
  
2006-08-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE WINDOW PRODUCT APPROVALS
 SUBMITTED APPEAR CODE COMPLIANT.
 HOWEVER, THE FLOOR PLAN SUBMITTED
 PREVIOUSLY SHOWS 3 MULLIONS.ONE IS A
 90 DEGREE MULLION.IS THIS CORRECT?IF
 IT IS, SUBMIT A MULLION PRODUCT APPROVAL
 FOR THIS APPLICATION.IF NOT, REVISE
 THE FLOOR PLAN TO CORRECTLY REFLECT THE
 SCOPE OF WORK.MAKE ALL NOTES ON THE
 FLOOR PLAN LEGIBLE; THE MULLION NOTE IS
 VERY SMALL AND IT IS DIFFICULT TO READ
 THE WINDOW SIZES.
  
 2.)THE MULLION PRODUCT APPROVAL
 APPEARS TO BE LIMITED TO SIMONTON
 STORMBREAKER WINDOWS.SUBMIT A MULLION
 PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-01 Cont ID  
Sent By shill Date 2006-08-01 Time 15:45 Rev Time 0.00
Received By shill Date 2006-08-01 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-19 Cont ID  
Sent By shill Date 2006-06-19 Time 12:10 Rev Time 0.00
Received By shill Date 2006-06-19 Time 12:10 Sent To  
Notes
2006-06-19 00:00:00SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)PROVIDE A FLOOR PLAN SHOWING WINDOW
 SIZES AND LOCATIONS.SHOW ZONE 5 ON THE
 PLAN.
  
 THE PRODUCT APPROVAL HAS A PRODUCT WITH
 A DP LIMIT OF -46.1.A ZONE 5, 20SF
 WOULD HAVE A DESIGN PRESSURE OF -46.2.
 CONTRACTOR INDICATED THAT THE PRODUCT TO
 BE USED WILL BE THE PRODUCT WITH +-70
 LIMITATION.PLEASE CIRCLE THIS ON THE
 PRODUCT APPROVAL.+-70 IS COMPLIANT FOR
 ALL OPENINGS REGARDLESS OF ZONE.
  
 2.)INDICATE THAT THE WINDOWS ARE TO BE
 INSTALLED IN THE SAME LOCATIONS, SAME
 SIZES OR SHOW THE PROPOSED ALTERATIONS
 ON THE PLAN.
  
 NOT ADDRESSED.
  
 3.)PROVIDE THE BUILDING HEIGHT AND
 DESIGN PRESSURE INFORMATION FBC1609.
  
 HEIGHT WAS PROVIDED.SEE #1 ABOVE.
 SOME OPENINGS ARE NOT COMPLIANT FOR ZONE
 5 FOR THIS BUILDING HEIGHT, FBC TABLE
 1609B AND D.SAME COMMENT APPLIES; IF
 PRODUCT WITH +-70 IS USED, THIS IS
 COMPLIANT FOR ALL OPENINGS.CIRCLE ON
 THE PRODUCT APPROVAL.
  
 4.)THE NOTICE OF COMMENCEMENT PROVIDED
 DOES NOT HAVE THE OWNER INFORMATION.
 FS713.13.
  
 5.)VALUATION APPEARS LOW.PROVIDE A
 REASONABLE VALUE OF WORK OR AN ESTIMATE
 WILL BE DONE FOR YOU USING MARSHALL &
 SWIFT. - NOTE - ADJUSTED VALUE PER
 CONTRACTOR
  
 NEW COMMENTS -
  
 6.)THE NEW PLAN SUBMITTED SHOWS
 MULLIONS.PLEASE PROVIDE PRODUCT
 APPROVALS.IF THE MULLION PRODUCT
 APPROVALS SHOW NONCOMPLIANT OPTIONS
 BASED ON WIND PRESSURES FBC TABLE
 1609.6B AND D, CIRCLE WHICH PRODUCT YOU
 WILL USE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-25 Cont ID  
Sent By shill Date 2006-05-25 Time 07:39 Rev Time 0.00
Received By shill Date 2006-05-25 Time 07:39 Sent To  
Notes
2006-05-25 00:00:00SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE A FLOOR PLAN SHOWING WINDOW
 SIZES AND LOCATIONS.SHOW ZONE 5 ON THE
 PLAN.
  
 2.)INDICATE THAT THE WINDOWS ARE TO BE
 INSTALLED IN THE SAME LOCATIONS, SAME
 SIZES OR SHOW THE PROPOSED ALTERATIONS
 ON THE PLAN.
  
 3.)PROVIDE THE BUILDING HEIGHT AND
 DESIGN PRESSURE INFORMATION FBC1609.
  
 4.)THE NOTICE OF COMMENCEMENT PROVIDED
 DOES NOT HAVE THE OWNER INFORMATION.
 FS713.13.
  
 5.)VALUATION APPEARS LOW.PROVIDE A
 REASONABLE VALUE OF WORK OR AN ESTIMATE
 WILL BE DONE FOR YOU USING MARSHALL &
 SWIFT.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 16:31 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 16:31 Sent To B
Notes
2007-08-29 16:32:52TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-11 Cont ID  
Sent By adarroug Date 2007-06-11 Time 14:03 Rev Time 0.00
Received By adarroug Date 2007-06-11 Time 14:03 Sent To B
Notes
2007-06-11 14:03:51TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-31 Cont ID  
Sent By adarroug Date 2006-08-31 Time 10:35 Rev Time 0.00
Received By adarroug Date 2006-08-31 Time 10:35 Sent To B
Notes
2006-08-31 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-08-15 Time 14:00 Rev Time 0.00
Received By adarroug Date 2006-08-15 Time 14:00 Sent To B
Notes
2006-08-15 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 15:11 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 15:11 Sent To B
Notes
2006-07-14 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 15:19 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 15:19 Sent To B
Notes
2006-06-08 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING