| 2006-06-19 00:00:00 | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.)PROVIDE A FLOOR PLAN SHOWING WINDOW |
| | SIZES AND LOCATIONS.SHOW ZONE 5 ON THE |
| | PLAN. |
| | |
| | THE PRODUCT APPROVAL HAS A PRODUCT WITH |
| | A DP LIMIT OF -46.1.A ZONE 5, 20SF |
| | WOULD HAVE A DESIGN PRESSURE OF -46.2. |
| | CONTRACTOR INDICATED THAT THE PRODUCT TO |
| | BE USED WILL BE THE PRODUCT WITH +-70 |
| | LIMITATION.PLEASE CIRCLE THIS ON THE |
| | PRODUCT APPROVAL.+-70 IS COMPLIANT FOR |
| | ALL OPENINGS REGARDLESS OF ZONE. |
| | |
| | 2.)INDICATE THAT THE WINDOWS ARE TO BE |
| | INSTALLED IN THE SAME LOCATIONS, SAME |
| | SIZES OR SHOW THE PROPOSED ALTERATIONS |
| | ON THE PLAN. |
| | |
| | NOT ADDRESSED. |
| | |
| | 3.)PROVIDE THE BUILDING HEIGHT AND |
| | DESIGN PRESSURE INFORMATION FBC1609. |
| | |
| | HEIGHT WAS PROVIDED.SEE #1 ABOVE. |
| | SOME OPENINGS ARE NOT COMPLIANT FOR ZONE |
| | 5 FOR THIS BUILDING HEIGHT, FBC TABLE |
| | 1609B AND D.SAME COMMENT APPLIES; IF |
| | PRODUCT WITH +-70 IS USED, THIS IS |
| | COMPLIANT FOR ALL OPENINGS.CIRCLE ON |
| | THE PRODUCT APPROVAL. |
| | |
| | 4.)THE NOTICE OF COMMENCEMENT PROVIDED |
| | DOES NOT HAVE THE OWNER INFORMATION. |
| | FS713.13. |
| | |
| | 5.)VALUATION APPEARS LOW.PROVIDE A |
| | REASONABLE VALUE OF WORK OR AN ESTIMATE |
| | WILL BE DONE FOR YOU USING MARSHALL & |
| | SWIFT. - NOTE - ADJUSTED VALUE PER |
| | CONTRACTOR |
| | |
| | NEW COMMENTS - |
| | |
| | 6.)THE NEW PLAN SUBMITTED SHOWS |
| | MULLIONS.PLEASE PROVIDE PRODUCT |
| | APPROVALS.IF THE MULLION PRODUCT |
| | APPROVALS SHOW NONCOMPLIANT OPTIONS |
| | BASED ON WIND PRESSURES FBC TABLE |
| | 1609.6B AND D, CIRCLE WHICH PRODUCT YOU |
| | WILL USE. |