Plan Review Details - Permit 06041140
Plan Review Stops For Permit 06041140
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-11 Cont ID  
Sent By shill Date 2006-09-11 Time 13:24 Rev Time 0.00
Received By shill Date 2006-09-11 Time 13:24 Sent To  
Notes
2006-09-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS LIST, NUMBERING
 REMAINING THE SAME FOR CONSISTENCY
  
 1.)THE FIRST LIST REQUESTED THAT YOU
 SHOW COMPLIANCE WITH FBC TABLE 601, TWO
 BUILDINGS ON THE SAME LOT.YOUR
 RESPONSE LETTER STATES THAT THIS IS ONE
 STRUCTURE, BUT THE ELEVATION 1-S2 SHOWS
 TWO STRUCTURES, NOT STRUCTURALLY
 CONNECTED.PLEASE ADDRESS.
  
 2.)COMMENT FROM FIRST LIST - PROVIDE
 INFORMATION IN REGARDS TO THE EXISTING
 BUILDING AND THE PROPOSED BUILDING;
 DECLARE THE BUILDING AREA, MINIMUM
 BUILDING TYPE FBC6, FIRE SPRINKLER
 INFORMATION, OCCUPANCY FBC3, AND ANY
 OTHER INFORMATION REQUIRED TO DETERMINE
 CODE COMPLIANCE FOR THE PROPOSED WORK.
  
 2ND REVIEW - S1/F1 WAS DECLARED FOR
 OCCUPANCY.ARE PORTIONS OF THE BUILDING
 DIFFERENT OCCUPANCIES?STATE SQUARE
 FOOT AREA FOR EACH. PROVIDE MORE
 INFORMATION IN REGARDS TO THE USE OF THE
 EXISTING BUILDING AND THE ADDITION.
  
 BUILDING TYPE WAS DECLARED AS IA.SEE
 FBC TABLE 601.PROVIDE CALCULATED FIRE
 RESISTANCE OR ASSEMBLY LISTING TO SHOW
 THAT BOTH THE EXISTING BUILDING HAS THE
 FIRE RESISTANCE AS REQUIRED AND THAT THE
 PROPOSED ADDITION ALSO HAS FIRE
 RESISTANCE AS REQUIRED BY THIS TABLE.
 IT DOES NOT APPEAR THE THE COLUMNS HAVE
 A 3 HOUR FIRE RESISTANCE, ROOF DOES NOT
 APPEAR TO BE 1 1/2 HOUR.
  
 COMPLIANCE WITH FBC TABLE 503, ALLOWABLE
 HEIGHT AND BUILDING AREAS, CANNOT BE
 DETERMINED UNTIL CORRECT OCCUPANCY
 CLASSIFICATION, BUILDING TYPE, AND ISSUE
 OF SEPARATE BUILDINGS HAS BEEN
 ADDRESSED.
  
 3.)SHOW HOW EGRESS AND ACCESSIBILITY
 IN THE EXISTING BUILDING AREA AFFECTED
 BY THIS IMPROVEMENT.
  
 4.-5.)ADDRESSED.
  
 6.)FLORIDA STATE PRODUCT APPROVAL WAS
 SUBMITTED.PLEASE HAVE THIS REVIEWED BY
 THE DESIGNER OF RECORD, FBC*106.3.3.
  
 7.)ADDRESSED.
  
 NEW COMMENTS:
  
 8.)PROVIDE INFORMATION IN REGARDS TO
 MATERIALS TO BE STORED.
  
 9.)ADDITIONS ARE TO COMPLY WITH FBC EB
 CHAPTER 9.SEE FBC901.2, FBC902.2.
  
 10.)ACCESSIBILITY REQUIREMENTS ARE NOT
 CLEAR AS YOU HAVE DECLARED F1 AND S1.
 SEE FBC905.1, FBC CHAPTER 11.
  
 11.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE IS REQUIRED TO BE
 CHARGED IF THE COMMENTS ARE NOT PROPERLY
 ADDRESSED A THIRD TIME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By shill Date 2006-05-24 Time 14:35 Rev Time 0.00
Received By SHILL Date 2006-05-24 Time 11:19 Sent To  
Notes
2006-05-24 00:00:00SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)SHOW COMPLIANCE WITH FBC TABLE 601,
 TWO BUILDINGS ON THE SAME LOT.PROVIDE
 AN ELEVATION OF THE EXISTING BUILDING
 (THE SIDE THAT FACES THE PROPOSED
 STRUCTURE ONLY).
  
 2.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING AND THE PROPOSED
 BUILDING; DECLARE THE BUILDING AREA,
 MINIMUM BUILDING TYPE FBC6, FIRE
 SPRINKLER INFORMATION, OCCUPANCY FBC3,
 AND ANY OTHER INFORMATION REQUIRED TO
 DETERMINE CODE COMPLIANCE FOR THE
 PROPOSED WORK.
  
 3.)SHOW HOW EGRESS AND ACCESSIBILITY
 IN THE EXISTING BUILDING AREA AFFECTED
 BY THIS IMPROVEMENT.
  
 4.)DOES CMRF STAND FOR COMMERCIAL
 MATERIALS RECYCLING FACILITY?PLEASE
 STATE ON THE PLAN TO ASSIST IN
 DETERMINING CODE COMPLIANCE.
  
 5.)DECLARE THE FLOOD ZONE DESIGNATION
 FOR THIS PARCEL.IF THIS IS IN A
 SPECIAL HAZARD FLOOD ZONE WITH A BASE
 FLOOD ELEVATION, SEE CITY OF WEST PALM
 BEACH MUNICIPAL CODE, SEC 94-546.
 FINISHED FLOOR IS TO BE 6IN ABOVE THE
 BFE.
  
 6.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FOR THE ROOF PANELS,
 FAC9B72, WWW.FLORIDABUILDING.ORG
  
 7.)VALUAATION APPEARS LOW.PROVIDE A
 MORE REASONABLE VALUE OR AN ESTIMATE
 WILL BE DONE FOR YOU.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-09-26 Cont ID  
Sent By btrobaug Date 2006-09-26 Time 17:47 Rev Time 0.50
Received By btrobaug Date 2006-09-26 Time 17:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-05-23 Cont ID  
Sent By btrobaug Date 2006-05-23 Time 07:06 Rev Time 0.33
Received By btrobaug Date 2006-05-23 Time 06:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-10-23 Cont ID  
Sent By mwennerg Date 2006-10-23 Time 15:37 Rev Time 0.00
Received By mwennerg Date 2006-10-23 Time 15:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By nmccray Date 2006-06-15 Time 14:50 Rev Time 0.00
Received By nmccray Date 2006-06-15 Time 14:28 Sent To  
Notes
2006-06-15 00:00:00******DENIED***********************
  
 1) IS THIS BUILDING PROTECTED BY AN
 AUTOMATIC FIRE SPRINKLER SYSTEM?
  
 2) WILL THIS CANOPY BE FIRE SPRINKLER
 PROTECTED
  
 3) WILL THERE BE VEHICLES PARKED
 UNDERNEATH THIS CANOPY?
  
 4) WILL THERE BE ANY COMBUSTIBLES OR
 FLAMMABLE LIQUIDS STORED AND HANDLED
 UNDERNEATH THIS CANOPY?
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-25 Cont ID  
Sent By adarroug Date 2006-08-25 Time 15:32 Rev Time 0.00
Received By adarroug Date 2006-08-25 Time 15:32 Sent To  
Notes
2006-08-28 00:00:00TO "COMM" BD#49
2006-08-25 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-19 Cont ID  
Sent By adarroug Date 2006-07-19 Time 14:19 Rev Time 0.00
Received By adarroug Date 2006-04-28 Time 11:01 Sent To  
Notes
2006-05-19 00:00:00TO "COMM" BD#5
2006-04-28 00:00:00WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-05 Cont ID  
Sent By eschneid Date 2006-09-05 Time 11:20 Rev Time 0.00
Received By eschneid Date 2006-09-05 Time 11:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-19 Cont ID  
Sent By eschneid Date 2006-07-19 Time 11:58 Rev Time 0.00
Received By eschneid Date 2006-07-19 Time 11:58 Sent To  
Notes
***NONE***