| 2006-05-09 00:00:00 | *** DENIED *** |
| | 1) AS REQUESTED IN LAST REVIEW 5-2-06 |
| | NOTE #1 ENERGY CAL'S. NEED TO BE SIGNED |
| | BY OWNER/AGENT. |
| | |
| | 2) AS REQUESTED IN LAST REVIEW NOTE #2 |
| | PLEASE SUBMIT 2 COPYS OF ALL PAPER WORK |
| | (NEED 2 COPYS OF PLANS). |
| | |
| | 3) MASTER BEDROOM IS LISTED IN THE |
| | MANUAL J CAL'S. BUT NO PLANS HAVE BEEN |
| | SUBMITTED SHOWING THE MASTER BEDROOM, |
| | PLEASE SUBMIT. |
| | |
| | 4) PLEASE SHOW CFM'S AT A/C GRILLS FOR |
| | OFFICE AND LIVING ROOM. |
| | |
| | 5) PLEASE SHOW SIZE OF RIGID DUCT IN |
| | LIVING ROOM AND HALL-WAY. |
| | |
| | 6) PLEASE SHOW SEER OF A/C SYSTEM ON |
| | PLANS. |
| | |
| | 7) RETURN AIR TRANSFER GRILLS IN BEDROOM |
| | 1 AND 2 ARE TO SMALL, SEE NOTE #8 (B). |
| | |
| | 8)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |