Plan Review Details - Permit 06041137
Plan Review Stops For Permit 06041137
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-18 Cont ID  
Sent By adarroug Date 2006-05-18 Time 15:25 Rev Time 0.00
Received By adarroug Date 2006-05-18 Time 15:25 Sent To M
Notes
2006-05-18 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-08 Cont ID  
Sent By adarroug Date 2006-05-08 Time 15:15 Rev Time 0.00
Received By adarroug Date 2006-05-08 Time 15:15 Sent To M
Notes
2006-05-08 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-02 Cont ID  
Sent By tgordon Date 2006-05-02 Time 09:45 Rev Time 0.00
Received By tgordon Date 2006-04-28 Time 11:37 Sent To  
Notes
2006-04-28 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-06-19 Cont ID  
Sent By tgordon Date 2006-06-19 Time 11:23 Rev Time 0.30
Received By tgordon Date 2006-06-19 Time 11:23 Sent To  
Notes
2006-06-19 00:00:00REVISION TO MECH. PLANS AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-05-19 Cont ID  
Sent By tgordon Date 2006-05-19 Time 10:26 Rev Time 0.30
Received By tgordon Date 2006-05-19 Time 10:26 Sent To  
Notes
2006-05-19 00:00:00*** PROVISO ***
 1)THE DWELLING WILL BE REQUIRED TO HAVE
 SMOKE ALARMS INSTALLED IF NOT ALREADY
 PRESENT, PER 2004 FBC/R 313.1.1, AND SEE
 2004 FEBC 303.1 LEVEL ONE ALTERATION
 INCLUDE REPLACEMENT OF EQUIPMENT.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-05-09 Cont ID  
Sent By tgordon Date 2006-05-09 Time 08:57 Rev Time 0.45
Received By tgordon Date 2006-05-09 Time 08:56 Sent To  
Notes
2006-05-09 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 5-2-06
 NOTE #1 ENERGY CAL'S. NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 2) AS REQUESTED IN LAST REVIEW NOTE #2
 PLEASE SUBMIT 2 COPYS OF ALL PAPER WORK
 (NEED 2 COPYS OF PLANS).
  
 3) MASTER BEDROOM IS LISTED IN THE
 MANUAL J CAL'S. BUT NO PLANS HAVE BEEN
 SUBMITTED SHOWING THE MASTER BEDROOM,
 PLEASE SUBMIT.
  
 4) PLEASE SHOW CFM'S AT A/C GRILLS FOR
 OFFICE AND LIVING ROOM.
  
 5) PLEASE SHOW SIZE OF RIGID DUCT IN
 LIVING ROOM AND HALL-WAY.
  
 6) PLEASE SHOW SEER OF A/C SYSTEM ON
 PLANS.
  
 7) RETURN AIR TRANSFER GRILLS IN BEDROOM
 1 AND 2 ARE TO SMALL, SEE NOTE #8 (B).
  
 8)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-02 Cont ID  
Sent By tgordon Date 2006-05-02 Time 09:11 Rev Time 0.30
Received By tgordon Date 2006-05-02 Time 09:11 Sent To  
Notes
2006-05-02 00:00:00**** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY PREPARER AND OWNER/AGENT.
  
 2) PLEASE SUBMIT TWO COPYS OF ALL PAPER
 WORK.
  
 3) MANUAL J CALCULATIONS ARE CALLING FOR
 A 5 TON A/C SYSTEM, PLEASE RE-CALCULATE
 THE MANUAL J CAL'S..
  
 4) BY PASSIVE RETURN DO YOU MEAN RETHRN
 AIR TRANSFER GRILLS OR RETURN AIR
 TRANSFER DUCTS (IF DUCTS SHOW SIZE OF
 DUCT ALSO), PLEASE CORRECT.
  
 5) PLEASE PROVIDE RETURN AIR FOR BEDROOM
 #3.
  
 6)NEED TO FILE A NOTICE OF COMMENCEMENT,
 PER F. S. 713.13 .
  
 7) CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.