Plan Review Details - Permit 06041126
Plan Review Stops For Permit 06041126
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-25 Cont ID  
Sent By alange Date 2006-05-25 Time 11:25 Rev Time 2.00
Received By alange Date 2006-05-25 Time 11:04 Sent To Z
Notes
2006-05-25 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $27,025.00.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS FOR FLAT ROOF USED
 SHALL HAVE THE ASSEMBLY USED SELECTED.
 STORM PANELS NEED ALL STATE PRODUCT
 APPROVAL PAGES. NOT JUST PAGE ONE.
 DOOR PRODUCT APPROVAL IS FOR INSWING
 DOOR YET PLANS SPEC A OUT SWING DOOR.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 8.PROTECTION AGAINST DECAY R319.1
 2. ALL WOOD FRAMING MEMBERS THAT REST
 ON CONCRETE OR MASONRY EXTERIOR
 FOUNDATION WALLS AND ARE LESS THAN 8
 INCHES FROM THE EXPOSED GROUND.
 5.WOOD SIDING, SHEATHING AND WALL
 FRAMING ON THE EXTERIOR OF A BUILDING
 HAVING A CLEARANCE OF LESS THAN 6 INCHES
 FROM THE GROUND.
  
 9. R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6
 FEET SHALL HAVE NOT LESS THAN A ONE-HOUR
 FIRE-RESISTIVE RATING WITH EXPOSURE FROM
 BOTH SIDES. PROJECTIONS SHALL NOT EXTEND
 TO A POINT CLOSER THAN 4 FEET FROM AN
 ADJACENT PROJECTION OR WALL.
  
 10.ONLY ONE WINDOW IN BEDROOM MEETS
 THE EMERGENCY ESCAPE AND RESCUE SIZE
 REQUIREMENTS. THIS WINDOW IS NOT
 PERMITTED TO HAVE AN AIRCONDITIONER IN
 IT.R310.1 AND R310.4
  
 11. SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS.FS 472.025
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-01 Cont ID  
Sent By btrobaug Date 2006-05-01 Time 13:16 Rev Time 0.75
Received By btrobaug Date 2006-05-01 Time 12:25 Sent To Z
Notes
2006-05-01 00:00:00 
 DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE FEEDER TO SUB PANEL "B" ON
 PANEL "A" SCHEDULE.
  
 2} INDICATE FEEDER "B" SIZE ON THE
 RISER. 215.5.
  
 3} THE SUB PANEL CIRCUITS #21, 23, 25,
 AND 22 HAVE OVERCURRENT PROTECTION TOO
 HIGH FOR THE WIRE SIZE. SEE 310.16.
  
 4} ELECTRICAL NOTE #7 REFERENCES THE
 1996 CODE, REMOVE IT OR CORRECT IT.
  
 5} A RECEPTACLE NEEDS TO BE ADDED TO THE
  
 BEDROOM PER 210.52(A)(1).
  
 6} THE BATH CIRCUIT MUST COMPLY WITH
 210.11(C)(3).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-31 Cont ID  
Sent By mmclean Date 2006-05-31 Time 12:00 Rev Time 0.00
Received By mmclean Date 2006-04-28 Time 15:57 Sent To  
Notes
2006-04-28 00:00:00TO "E" BOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By mperson Date 2006-05-08 Time 09:33 Rev Time 1.25
Received By mperson Date 2006-05-08 Time 09:33 Sent To B
Notes
2006-05-08 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A PLUMBING PERMIT:
  
 1. PER SECTION 708.3.4, CLEANOUTS SHALL
 BE LOCATED AT THE BASE OF EACH WASTE OR
 SOIL STACK. PLEASE SEE CORRECTED
 PLUMBING SHEET 2/2FOR RESUBMITTAL
 REFERENCE.
 2. PER SECTION 708.3.5, THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER.
 PLEASE SEE CORRECTED PLUMBING SHEET 2/2
 FOR RESUBMITTAL REFERENCE.
 3. PER SECTION 501.4 WATER HEATER
 LOCATION. WATER HEATERS SHALL BE LOCATED
 AND CONNECTED SO AS TO PROVIDE ACCESS
 FOR OBSERVATION, MAINTENANCE, SERVICING,
 AND REPLACEMENT. PLEASE PROVIDE A DETAIL
 OF WATER HEATER SIZE AND HOW THE ABOVE
 GOING TO HAPPEN INSIDE A CABINET WITH A
 SINK.
 4. PER SECTION 504.7 REQUIRED PAN. WHERE
 WATER HEATERS ARE INSTALLED ABOVE THE
 GROUND FLOOR SPACE A PAN SHALL BE
 INSTALLED FOR WATER HEATER. PLEASE
 INDICATE THIS ON PRINT. PER SECTION
 504.7.1 PAN DRAIN SIZE SHALL BE MINIMUM
 3/4" AND PER SECTION 504.7.2 SHALL
 TERMINATE NOT LESS THAN 6" AND NOT MORE
 THAN 24" ABOVE THE ADJACENT GROUND OF
 THE EXTERIOR OF BUILDING. PLEASE
 INDICATE THIS ON PRINT. PER SECTION
 504.6.1 INDICATE THE DISCHAREGE OF THE
 WATER HEATER RELIEF VALVE EITHER INTO
 THE HEATER PAN OR OUTSIDE OF THE
 BUILDING.
 5. ON SHEET 2/2 PLEASE NOTE THE 2" PVC
 UNDER SINK VENT CHANGED TO 2" PVC AIR
 ADMINTANCE VALVE PER SECTION 917. PLEASE
 SEE CORRECTED PLUMBING SHEET 2/2 FOR
 REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By mmclean Date 2006-05-31 Time 11:54 Rev Time 0.00
Received By mmclean Date 2006-05-31 Time 11:53 Sent To  
Notes
2006-05-31 00:00:00DENIED,
 1. CANNOT HAVE A GUEST HOUSE(STRUCTURE).
 2. ZONED SF7, WHICH ONLY ALLOWS 1 SINGLE
 FAMILY DWELLING.
 3. ACCESSORY STRUCTURE (CANNOT BE USED
 FOR LIVING SPACE) MUST MEET THE SIDE
 SETBACK AND MUST BE 6FT FROM THE MAIN
 STRUCTURE.
 3. SEE SEC 94-71, ARTICLE 111 OF THE
 ZONING CODE FOR ACCESSORY STRUCTURE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720