Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-04-26 Cont ID  
Sent By mwennerg Date 2006-04-26 Time 13:24 Rev Time 0.00
Received By mwennerg Date 2006-04-26 Time 13:24 Sent To  
Notes
2006-04-26 00:00:00******APPROVED******
  
 1) IF NOT PRESENT, A SMOKE DETECTOR IS
 REQUIRED IN THE FIRE COMMAND ROOM.
  
 2) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE. CERTIFICATE
 SHALL BE AVAILABLE PRIOR TO OR AT THE
 TIME OF BUILDING FIRE ALARM FINAL.
  
 3) SEPARATE SHOP DRAWINGS AND PERMIT
 WILL BE REQUIRED FOR FIRE ALARM DEVICE
 INSTALLATION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722