Plan Review Details - Permit 06041060
Plan Review Stops For Permit 06041060
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-24 Cont ID  
Sent By jwitmer Date 2006-08-24 Time 08:51 Rev Time 0.77
Received By jwitmer Date 2006-08-24 Time 08:51 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-16 Cont ID  
Sent By jwitmer Date 2006-05-16 Time 13:11 Rev Time 2.22
Received By jwitmer Date 2006-05-16 Time 13:11 Sent To  
Notes
2006-05-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06041060
 ADD: 1541 BELVEDERE RD
 CONT: PINNACLE CONTRACTORS
 TEL: (954)815-2542
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) THE PERMIT APPLICANT IS A STATE
 "CBC"CONTRACTOR AND LIMITED TO THE SCOPE
 OF WORK OF THAT LICENSE. THE SCOPE OF
 WORK APPLIED FOR, REMOVAL AND
 REPLACEMENT OF UNDERGROND STORAGE TANKS,
 FUEL LINES AND DISPENSERS WOULD BE
 WORKING OUT OF YOUR SCOPE OF
 LICENSE.MUST BE STRUCK.
 FL S S 489.105 (P) "POLLUTANT STORAGE
 SYSTEMS CONTRACTOR" MEANS A CONTRACTOR
 WHOSE SERVICES ARE LIMITED TO, AND WHO
 HAS THE EXPERIENCE, KNOWLEDGE, AND SKILL
 TO INSTALL, MAINTAIN, REPAIR, ALTER,
 EXTEND, OR DESIGN, WHEN NOT PROHIBITED
 BY LAW, AND USE MATERIALS AND ITEMS USED
 IN THE INSTALLATION, MAINTENANCE,
 EXTENSION, AND ALTERATION OF, POLLUTANT
 STORAGE TANKS. ANY PERSON INSTALLING A
 POLLUTANT STORAGE TANK SHALL PERFORM
 SUCH INSTALLATION IN ACCORDANCE WITH THE
 STANDARDS ADOPTED PURSUANT TO S.
 376.303.
  
 3) ENGINEER CURT KEYSER IS MISSING
 61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
 SEE SHELL/ MOTIVA ENGINEERING SHEETS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-11 Cont ID  
Sent By dpalmer Date 2006-08-11 Time 07:08 Rev Time 0.00
Received By dpalmer Date 2006-08-10 Time 21:17 Sent To  
Notes
2006-08-11 00:00:00ELEC OK, STAMPED.
2006-08-10 00:00:00IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-17 Cont ID  
Sent By dpalmer Date 2006-05-17 Time 20:23 Rev Time 0.00
Received By dpalmer Date 2006-05-17 Time 20:06 Sent To  
Notes
2006-05-17 00:00:00********* UNSAT ***********
  
 1) NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER AS REQUIRED UNDER FS 471.023.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS, ALL TITLE BLOCKS WHETHER OR NOT
 COMMENTS ARE MADE BYOTHER REIVEWER(S)>
  
 2) NOTE:PLEASE ALSO SEE THE REFERENCED
 FLORIDA ADMINISTRATIVE CODE AS ALL PLANS
 SIGNED , DATED AND SEALED BY SAID
 ENGINEER , SHALL CONTAIN TILE BOCKS WITH
 ALL INFORMATION AS REQUIRED.
  
 3) NOTE: PLEASE SEE THAT PLANS REFERENCE
 THE CURRENT CODES RELEVANT TO THIS
 PROJECT. PLEASE KNOW, PLANS MENTIONS THE
 "LATEST EDITION" OF THE NEC, HOWEVER
 PLEASE KNOW THE STATE OF FLORIDA IS
 STILL UNDER THE 2002 EDITION. PLEASE
 ADJUST ACCORDINGLY.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-09-08 Cont ID  
Sent By rchokshi Date 2006-09-08 Time 14:30 Rev Time 0.00
Received By rchokshi Date 2006-09-08 Time 14:30 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2006-08-08 Cont ID  
Sent By rchokshi Date 2006-08-08 Time 14:26 Rev Time 0.00
Received By rchokshi Date 2006-08-08 Time 14:10 Sent To  
Notes
2006-08-08 00:00:00NEED THE FOLLOWING:
  
 1. UTILITY REVIEW FROM 45TH STREET FROM
 MANNY G.,ENG. SERVICES
 2. DETAILS OF POLLUTION PREVENTION
 PLANS, BEFORE,DURING,AFTER CONST., FENCE
 DETAIL AROUND SITE
 3. STORM/DRAINAGE
 CAL.,PERVIOUS,IMPERVIOUS,AREA
 CAL.,RUNOFF WATER CAL.,GEOTECHNICAL ENG
 REPORT, SFWMD PERMIT.
 4. NOTES ON DRAWINGS THAT
 SIDEWALK,DRIVEWAY,PARKINGS,WILL MEET
 CITY OF WPB STANDARDS, ADA, STATE,
 FEDERAL STANDARDS.
 5. LOWEST FLOOR ELEVATION SHOULD BE
 ATLEAST 12" HIGHER THAN CURB ELE., FLOOD
 HISTORY TO AVOID FLOOD.
 6.YOU MAY NEED FDEP PERMIT, POSSIBLY
 HEALTH DEPT PERMIT FOR STAGE II
 RECOVERY.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-07-14 Cont ID  
Sent By rchokshi Date 2006-07-14 Time 14:01 Rev Time 0.00
Received By rchokshi Date 2006-07-14 Time 13:47 Sent To  
Notes
2006-07-14 00:00:00PLEASE ADD NOTES ON YOUR DRAWING SHEET 1
 AND OTHER SHEETS (ADA SITE PLAN) THAT
 CONTRACTOR SHALL DO WORK PER "TYPICAL
 PAVER STONE DRIVEWAY APPROACH DETAILS"
 OF CITY OF WEST PALM BEACH, PUBLIC
 UTILITY DEPARTMENT. TYPICAL PAVER STONE
 DRIVEWAY APPROACH DETAILS SHEET ENCLOSED
 FOR YOUR USE.
  
 PLEASE CALL FOR ANY QUESTIONS
 RASIK CHOKSHI 805-6723
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-22 Cont ID  
Sent By mawillia Date 2006-08-22 Time 10:36 Rev Time 0.00
Received By mawillia Date 2006-08-22 Time 10:36 Sent To B
Notes
2006-08-22 00:00:00**APPROVED**
  
  
  
  
  
 FIRE PLAN REVIEW NOTES/CONCERNS OF
 06/16/2006 HAVE BEEN ADDRESSED
 AND(OR)NOTED BY CONTRACTOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By mcarsill Date 2006-06-16 Time 11:48 Rev Time 0.00
Received By mcarsill Date 2006-06-16 Time 11:35 Sent To  
Notes
2006-06-16 00:00:001. SUITABLE ACCESS TO BE MAINTAINED WHEN
 WORK IS BEING ACCOMPLISHED FOR EMERGENCY
 SERVICES DELIVERY PURPOSES.
  
 2. THE REMOVAL OF THE UNDERGROUND
 STORAGE TANKS (UST'S) SHALL COMFORM WITH
 ALL APPLICABLE REGULATIONS AND NFPA 30.
  
 3. ALL OF THE FIRE SAFETY NOTES
 DISPLAYED ON G-1 SHALL BE FOLLOWED. ALL
 APPROPRIATE WARNING SIGNS WILL BE
 REQUIRED TO BE INSTALLED. (8-10)
  
 4. GASOLINE DISPENSERS HOSES SHALL NOT
 EXCCED THE REQUIRED LENGHTS AND BE
 EQUIPPED WITH THE APPROPRIATE BREAK-AWAY
 DEVICES.
  
 5. PLEASE ENSURE THAT RELOCATED
 EMERGENCY STOP DEVICE FOR THE FUEL AREAS
 IS PROPERLY IDENTIFIED.
  
 6. ALL ELECTRICAL WORK SHALL COMPLY WITH
 NFPA 70, THE NATIONAL ELECTRICAL CODE.
  
 7. APPROPRIATE FIRE EXTINGUISHING
 EQUIPMENT SHALL BE PRESENT AT FUEL
 DISPENSING LOCATIONS. COULD NOT LOCATE
 THIS INFORMATION ON THE DRAWINGS. PLEASE
 ADVISE.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 13:39 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 13:39 Sent To ENG
Notes
2006-09-06 00:00:00TO "ENG" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 14:28 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 14:28 Sent To  
Notes
2006-08-05 00:00:00TO COMM BOARD #44

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 16:44 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 16:44 Sent To  
Notes
2006-07-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-18 Time   Rev Time 0.00
Received By adarroug Date 2006-04-27 Time 12:32 Sent To  
Notes
2006-05-11 00:00:00TO "COMM" BD#47
2006-04-27 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-22 Cont ID  
Sent By tgordon Date 2006-08-15 Time 11:02 Rev Time 1.30
Received By tgordon Date 2006-08-22 Time 16:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By tgordon Date 2006-06-27 Time 14:13 Rev Time 0.30
Received By tgordon Date 2006-06-27 Time 14:13 Sent To  
Notes
2006-06-27 00:00:00*** DENIED ***
 1) SEE BUILDING REVIEW NOTES #2, AND 3
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-08-21 Cont ID  
Sent By kstevens Date 2006-08-21 Time 13:00 Rev Time 0.00
Received By kstevens Date 2006-08-21 Time 13:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-20 Cont ID  
Sent By kstevens Date 2006-06-20 Time 10:42 Rev Time 0.00
Received By kstevens Date 2006-06-20 Time 10:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-14 Cont ID  
Sent By kdfreema Date 2006-08-14 Time 14:31 Rev Time 0.00
Received By kdfreema Date 2006-08-14 Time 14:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-18 Cont ID  
Sent By kdfreema Date 2006-07-18 Time 16:03 Rev Time 0.00
Received By kdfreema Date 2006-07-18 Time   Sent To  
Notes
2006-07-18 00:00:00PLACED BACK IN SLOT #47