Plan Review Details - Permit 06040989
Plan Review Stops For Permit 06040989
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-09-07 Cont ID  
Sent By alange Date 2006-09-07 Time 10:23 Rev Time 0.00
Received By alange Date 2006-09-07 Time 10:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-25 Cont ID  
Sent By alange Date 2006-08-25 Time 09:01 Rev Time 1.00
Received By alange Date 2006-08-25 Time 09:01 Sent To  
Notes
2006-08-25 00:00:00DENIED
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4. SUBMIT TWO COMPLETE SETS OF
 MIAMI-DADE PRODUCT APPROVALS USED WITH
 THE APPROPRIATE STATE PRODUCT APPROVAL.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By alange Date 2006-07-10 Time 13:07 Rev Time 1.50
Received By alange Date 2006-07-10 Time 11:27 Sent To  
Notes
2006-07-10 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SIGN OWNER/AGENT ON ENERGY CALCS
 PER 2004 FBC.
  
 4.PRODUCT APPROVALS REQUIRED FOR
 LINTELS, SIDE LITES/FIXED GLASS AND
 GLASS BLOCK.
  
 NOTE: PRODUCT APPRROVALS SUBMITTED ARE
 NOT COMPLETE.SUBMIT NOA'S WITH THE
 APPROPRIATE STATE PRODUCT APPROVALS
 ATTACHED.
  
 5.QUALITY ASSURANCE REQUIRED WITH ALL
 STATE PRODUCT APPROVALS, (MIAMI-DADE)
 FOR EXAMPLE.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SEE ELECTRICAL REVIEW DONE FOR
 BUILDING.
 SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 9.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS. FS 472.025
  
 NOTE:AN ELEVATION CERTIFICATE IS
 REQUIRED PRIOR TO GETTING A CERTIFICATE
 OF COMPLETION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-24 Cont ID  
Sent By alange Date 2006-05-24 Time 09:40 Rev Time 1.50
Received By alange Date 2006-05-24 Time 09:40 Sent To  
Notes
2006-05-24 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 4.PRODUCT APPROVALS REQUIRED FOR
 LINTELS, SIDE LITES/FIXED GLASS AND
 GLASS BLOCK.
  
 5.QUALITY ASSURANCE REQUIRED WITH ALL
 STATE PRODUCT APPROVALS, (MIAMI-DADE)
 FOR EXAMPLE.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 9.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS. FS 472.025
  
 10.ENGINEERS SEALS SHALL READ
 "LICENSED" NOT CERTIFICATE 61 G1-16.001
  
 11.ASCE 7-98 IS THE INCORRECT
 STANDARD.
  
 12.PROPERTY IS IN AN AREA OF
 QUESTIONABLE SOILS.SUBMIT A SOILS
 REPORT INCLUDING FOOTING
 RECOMMENDATIONS.
  
 NOTE:AN ELEVATION CERTIFICATE IS
 REQUIRED PRIOR TO GETTING A CERTIFICATE
 OF COMPLETION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-11-20 Cont ID  
Sent By btrobaug Date 2007-11-20 Time 16:01 Rev Time 0.00
Received By btrobaug Date 2007-11-20 Time 15:49 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-08-13 Cont ID  
Sent By btrobaug Date 2007-08-13 Time 09:46 Rev Time 0.00
Received By btrobaug Date 2007-08-13 Time 07:03 Sent To PC
Notes
2007-08-13 09:46:36 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1}A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED AT THE
 SEPARATE STRUCTURE (CABANA)PER 250.32, SIZED PER
 250.66 AND TIED TO FOOTER STEEL PER 250.53(A)(3). THE
 PERMIT SET OF PLANS HAD THIS SHOWN CORRECTLY, BUT HAS
 BEEN DELETED FROM THE REVISED PLAN SUBMITTED.
  
 2} THE PANEL AT THE CABANA IS REQUIRED TO HAVE A
 DISCONNECTING MEANS PER 225.31, LOCATED PER 225.32. THE
 CABANA PANEL NOW IS LISTED AS A "MAIN LUG" PANEL, NOT
 IN COMPLIANCE, UNLESS ANOTHER DISCONNECTING MEANS IS
 INSTALLED AS PER THE ABOVE LISTED ARTICLES. THE
 DISCONNECT MUST BE LOCATED ON THE PLAN AND ON THE RISER
 DIAGRAM.
  
 3} THERE IS NO OVERCURRENT PROTECTION FOR THE POOL
 PANEL FEEDER SHOWN IN THE METER/MAIN PANEL. INDICATE
 THE SIZE OF THE OCP PER 310.16 OR 310.15(B)(6).
  
 4} THE 10 K AHU LISTED ON THE PANEL SCHEDULE IS SHOWN
 ON A 50 AMP CIRCUIT BREAKER, AND DOES NOT COMPLY WITH
 THE REQUIREMENT FOR THE BRANCH CIRCUIT RATING OF 125%,
 424.3(B). THIS WAS A REDLINED ITEM ON THE PERMIT SET,
 NOW MUST BE CORRECTED AS THIS REVISION IS INTENDED AS
 THE LAST FOR RECORD RETENTION.
  
 5} GIVEN THE LOCATION OF THE AHU IN THE ATTIC,ALSO
 SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).
  
 6} THE LOAD CALCULATION FORMAT HAS BEEN CHANGED FROM
 THE ORIGINAL PERMITTED SET. PROVIDE LOAD CALCULATIONS
 PER ARTICLE 220 PART II, STANDARD OR PART III OPTIONAL,
 INDICATE METHOD USED.
  
 7} THE POOL EQUIPMENT LOAD HAS BEEN MOVED FROM THE
 CABANA PANEL TO THE HOUSE PANEL. THIS IS CONTRARY TO
 THE RISER WHICH NOW SHOWS A POOL PANEL. PLEASE PROVIDE
 A PANEL SCHEDULE FOR THE POOL PANEL SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED.
  
 8} THE 200 AMP EXISTING HOUSE PANEL HAS NOW BEEN LISTED
 AS A MAIN LUG PANEL ON THE RISER. THAT PANEL IS LISTED
 AS A 200 AMP MAIN BREAKER PANEL ON THE PERMIT SET OF
 DRAWINGS. IF THAT PANEL WAS CHANGED IT WAS DONE OUTSIDE
 OF THE SCOPE OF THIS PERMIT. PLANS AND ANOTHER
 APPLICATION OR REVISION INDICATING THE INCREASED VALUE
 FOR LABOR AND MATERIAL, MUST BE SUBMITTED. 105.14 FBC
 AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-24 Cont ID  
Sent By btrobaug Date 2006-08-24 Time 11:09 Rev Time 0.75
Received By btrobaug Date 2006-08-21 Time 17:33 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-25 Cont ID  
Sent By dpalmer Date 2006-06-25 Time 12:23 Rev Time 0.00
Received By dpalmer Date 2006-06-25 Time 11:48 Sent To P
Notes
2006-06-25 00:00:00*********** UNSAT 2ND REVIEW **********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO CHANGES
 AND ITEMS REVIEWED ON PLANS.
  
  
 1) NOTE: PLEASE SEE RISER SHOWS NEW 150A
 FEED TO CABANA NOW BEING FED DIRECTLY
 FROM THE EXISTING METER. PLEASE SEE
 MAINS ARE NOT GROUPED AS REQUIRED. PLANS
 SHOWS A MAIN AT THE CABANA AND A MCB
 PANEL???
 PLEASE KNOW, THE MCB IS REQUIRD AT
 CABANA, HOWEVER THE 150A MAIN DISCONNECT
 IS REQUIRED TO BE GROUPED WITH THE
 EXISTING MCB 200A PANEL.
 230.72.
 PLEASE SEE THE 150A DISCONNECT IS SHOWN
 AS WP ON RISER AND PLANS INDICATE AN
 ADDITIONAL DISCONNECT IN THE LAUNDRY RM
 WITH THE MCB PANEL.
  
 2) NOTE: PLEASE INDICATE THE SIZE OF THE
 NEW METER CAN AS THE EXISTING 200A METER
 CAN NO LONGER BE USED.
 215.5
  
 3) NOTE: PLEASE KNOW, BSAED ON THE
 INCREASE IN SERVICE SIZE AND THE
 INCREASED SEC'S, THE EXISTING GROUNDING
 ELECTRODE CONDUCTOR SHALL BE INCREASED
 PER 310.15B6,250.66 (#2 MIN).
  
 4) NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM REQUIRED AT DETACHED
 BUILDING/CABANA. 250.32. NEW FOOTER
 STEEL, CWP ETC.
 250.50
  
 5) NOTE: PLEASE SEE RISER SHOWS
 "EQUIPMENT GROUNDING CONDUCTOR(S)" FROM
 THE METER TO THE FIRST MEANS OF
 DISCONNECT(S). PLEASE SEE 250.6,250.24B,
 AS THE EUP GRNDS ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISC.
  
 6) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT.
 110.9,215.5
  
 7) NOTE: PLEASE SEE A DISCONNECTING
 MEANS FOR THE LTS IN OUTSIDE LOGGIA
 AREA. THE POWER FOR THESE LTS BEING
 SHOWN ON A 3-WAY FROM MAIN HOUSE SHALL
 ORIGINATE FROM CABANA PANEL.
 225.31,225.34
  
 8) NOTE: PLEASE SEE MISSING DISCONNECT
 FOR CU #1, 440.11
  
 9) NOTE: PLEASE SEE MISSING REQUIRED GFI
 RECEPT FOR CU. 210.63,210.8
  
 10) NOTE: PLEASE SEE MIN OCP FOR 10KW
 AHU SHALL BE SIZED AT A MIN OF 125%.
 424.3B
 PLEASE SEE THE EXISTING IN MAIN HOUSE
 SHALL BE VERIFIED AND CORRECTED IF NOT
 60A MIN.
 NFPA-73
  
 11) NOTE: PLEASE SEE LOAD CALCULATIONS
 INDICATES THE CU LOADS AS FIGURED IN,
 WHEN THIS SHOULD DICTATE THE AHU/HEAT
 LOADS.
 PLEASE CORRECT.220.31B, 220.21, ETC
  
 12) NOTE: PLEASE SEE THE "STUDIO" RM
 SHALL CONTAIN A SMOKE DETECTOR INSIDE
 AND OUTSIDE THIS ROOM. THIS IS
 CONSIDERED ADN ADAPTABLE SLEEPING RM.
 NFPA-72 11.5.1.1
  
 13) NOTE: PLEASE SEE 210.12B AND NOTE
 THE ARC FAULT PROTECTION WILL ALSO BE
 REQUIRED FOR THE "STUDIO RM", AS THIS IS
 ALSO CONSIDERED AN ADAPTABLE SLEEPING
 RM.
  
 14) NOTE: PLEASE SEE THE MIN LOAD/KW TO
 BE FIGAURED FOR DRYERS SHALL BE 5KW PER
 220.18. PLEASE ADJUST CABANA PANEL, MAIN
 HOUSE AND LOAD CALCS.
 215.5
  
 15) NOTE: PLEASE SEE PLANS INDICATE A
 "ON-DEMAND" WATER HEATER AT CABANA, YET
 THE LOAD INDICATED IS SHOWN AS 4.5KW ON
 PANEL SCHEDULE. PLEASE VERIFY SIZE OF
 UNIT BEING INSTALLED AND SUBMIT
 MANUFACTURE SPEC/CUT SHEETS FOR UNIT
 BEING INSTALLED. PLEASE KNOW THIS UNIT
 SHALL BE LISTED BY A NRTL.
 215.5
 FBC 106.1.2 ADMIN SECT.
  
 16) NOTE: PLEASE SEE FS 471.025, NO HAND
 DRAWN CHANGES MAY BE DONE ON PLANS WHICH
 ARE ALREADY SIGNED,DATED AND SEALED BY
 THE ENGINEER OF RECORD.
 (RISER, 100A TO 150A.)
  
 17) NOTE: PLEASE SEE BUIDLING REVIEW
 COMMENTS TO FOLLOW AS THE SUBMITTED
 "TRUSS" PACKAGE CONTAINS A "RUBBER
 STAMP"AND MANY OTHER SHEETS ARE SEALED
 "PHOTO-COPIES" OF THE "RUBBER STAMPED
 SIGNATURE" IN LEIU OF THE REQUIRED
 ORIGINAL SIGNATURE AND DATE FROM THE
 ENGINEER. FS 471.025
 PLEASE ALSO SEE SEAL IS NO LONGER
 ACCELTABLE PER FAC 61G15-23.001. THE
 WORDING IN SAID SEAL SHALL CONTAIN THE
 WORDING OF "LICENSE" AS "CERTIFICATE"
 CAN NOT BE USED.
 THIS RULE WAS PASSED IN FEB 04 AND THE
 EXTENSION GIVEN TO ENGINEERS WAS ONLY TO
 DEC 31ST, 2005.
  
 **THIS IS REQUIRED**
  
 18) NOTE: PLEASE SEE FS553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS. THIS IS ONLY
 A NOTE AT THIS TIME.
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 OR COMMENTS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-16 Cont ID  
Sent By btrobaug Date 2006-05-16 Time 09:28 Rev Time 1.00
Received By btrobaug Date 2006-05-16 Time 06:34 Sent To P
Notes
2006-05-16 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SHEET E-1.1 SHOWS A NEW 350 AMP
 SERVICE. SHEET E-1.2 RISER HAS A 200 AMP
 SERVICE, PLEASE CORRELATE. SEE 225.31
 FOR REQUIREMENTS FOR THE DISCONNECT AT
 THE CABANA, AND 250.32 FOR GROUNDING
 REQUIREMENTS OF SAME.
  
 2} THE #6 FEEDERS TO THE INTENDED 100
 AMP CABANA PANEL ARE TOO SMALL AND MUST
 COMPLY WITH THE MINIMUM SIZE IN TABLE
 310.15(B)(6).
  
 3} THE PANEL LOCATION IN THE CABANA IS
 IN VIOLATION OF 110.26. THE WASHER IS IN
 THE CLEAR WORK SPACE.
  
 4} THE BATHROOM MUST COMPLY WITH
 210.52(D), 3' SPACING, AND 210.11(C)(3),
 DEDICATED CIRCUIT.
  
 5} IF THE SMALL APPLIANCE CIRCUIT IS
 INDICATING THERE IS A KITCHEN IN THE
 CABANA, THEN IT MUST HAVE TWO, PER
 210.11(C)(1), AND ENTERED INTO THE
 CALCULATIONS.
  
 6} THE GENERAL LIGHTING CIRCUITS IN THE
 CABANA PANEL SCHEDULE LIST # 14
 CONDUCTORS ON A 20 AMPERE BREAKER IN
 VIOLATION OF 310.16.
  
 7} THE RISER INDICATES THAT THE CABANA
 PANEL IS BEING FED FROM THE HOUSE PANEL,
 BUT IT IS NOT LISTED IN THE HOUSE PANEL
 SCHEDULE.
  
 8} PLEASE USE THE LARGER LOAD WHEN
 COMPUTING THE HEAT-A/C LOADS, THEPER
 220.21. ALSO SEE 220.30 OR 220.31(B),
 INDICATE WHICH ARTICLE IS USED FOR THE
 CALCULATIONS.
  
 9} SEE ARTICLE 210.8(A)(7) FOR GFI
 REQUIREMENTS AT WET BAR/SINK.
  
 10} THE ENGINEER OF RECORD SEALED THE
 PLANS WITH ASEAL THAT IS NO LONGER
 VALID. SEE 61G15-23.002 FAC.
  
 PLEASE PROVIDE WRITTEN RESPONSES TO ALL
 COMMENTS TO EXPEDITE PLAN REVIEW OF THE
 RESUB.
  
 IF THERE ARE QUESTIONS , PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 10:50 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 10:50 Sent To E
Notes
2007-11-15 10:50:40TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 09:05 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 09:05 Sent To E
Notes
2007-08-03 09:05:55TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-31 Cont ID  
Sent By alange Date 2006-08-31 Time 12:04 Rev Time 0.00
Received By alange Date 2006-08-31 Time 12:04 Sent To B
Notes
2006-08-31 00:00:00PLANS TO ALANGE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-21 Cont ID  
Sent By adarroug Date 2006-08-21 Time 16:36 Rev Time 0.00
Received By adarroug Date 2006-08-21 Time 16:36 Sent To E
Notes
2006-08-21 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 08:55 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 08:55 Sent To Z
Notes
2006-08-14 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 10:33 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 10:33 Sent To E
Notes
2006-06-22 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 16:03 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 16:03 Sent To E
Notes
2006-05-11 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-24 Cont ID  
Sent By alange Date 2006-05-24 Time 09:40 Rev Time 0.00
Received By alange Date 2006-04-25 Time 13:52 Sent To  
Notes
2006-04-25 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-05-18 Cont ID  
Sent By tgordon Date 2006-05-18 Time 12:57 Rev Time 0.20
Received By tgordon Date 2006-05-18 Time 12:57 Sent To B
Notes
2006-05-18 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-08 Cont ID  
Sent By jleech Date 2006-07-08 Time 10:08 Rev Time 0.00
Received By jleech Date 2006-07-08 Time 10:08 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-18 Cont ID  
Sent By mperson Date 2006-05-18 Time 08:49 Rev Time 1.33
Received By mperson Date 2006-05-18 Time 08:49 Sent To M
Notes
2006-05-18 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW FOR A PERMIT:
  
 1. INDICATE ON SHEET A-1 AND SHEET A-2
 THE OUTSIDE SHOWER DRAIN PIPE, DRAIN
 PIPE SIZE AND WHERE IT IS DRAINING TO.
 2. ON SHEET A-6 PLUMBING RISER DIAGRAM
 THERE INDICATES A FUTURE OUTDOOR SINK.
 PLEASE INDICATE ON SHEET A-2 THE
 LOCATION OF THE FUTURE OUTDOOR SINK.
 3. ON SHEET A-6 PLUMBING RISER DIAGRAM
 THE FOLLOWING IS REQUIRED FOR THE FUTURE
 OUTDOOR SINK.
 (A) 704.4 FUTURE FIXTURES. DRAINAGE
 PIPING FOR FUTURE FIXTURES SHALL
 TERMINATE WITH AN APPROVED CAP OR PLUG.
 (B) 905.6 VENT FOR FUTURE FIXTURES.
 WHERE THE DRAINAGE PIPING HAS BEEN
 ROUGHED-IN FOR FUTURE FIXTURES, A
 ROUGH-IN CONNECTION FOR A VENT SHALL BE
 INSTALLED. THE VENT SIZE SHALL BE NOT
 LESS THAN ONE-HALF THE DIAMETER OF THE
 ROUGH-IN DRAIN TO BE SERVED. THE VENT
 ROUGH-IN SHALL CONNECT TO THE VENT
 SYSTEM, OR SHALL BE VENTED BY OTHER
 MEANS AS PROVIDED FOR IN THIS CHAPTER.
 THE CONNECTION SHALL BE IDENTIFIED TO
 INDICATE THAT IT IS A VENT.
 4. ON SHEET A-6 PLUMBING RISER DIAGRAM
 THE BRANCH DRAIN AND THE DRAINAGE STACK
 ARE SIZED INCORRECTLY FOR THE WASHING
 MACHINE, THE FOLLOWING IS REQUIRED FOR
 THE SIZING OF THE WASHING MACHINE.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE
 INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING (NOTE: THE INDICATION OF THE
 STAND PIPE ON CORRECTED PLBG. RISER
 DIAGRAM)
 5. PLEASE NOTE THE CORRECTED CLEANOUT
 LOCATIONS ON A-6 PLBG. RISER DIAGRAM AND
 THE FOLLOWING CODE REQUIREMENTS FOR
 CLEANOUTS
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.(NOTE THE
 LOCATION OF THE WASHING MACHINE
 CLEANOUT)
 6. PLEASE NOTE THE FOLLOWING WILL BE
 REQUIRED FOR THE GAS DRYER AND GAS WATER
 HEATER.
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL INSPECTION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-19 Cont ID  
Sent By mmclean Date 2006-08-19 Time 09:33 Rev Time 0.00
Received By mmclean Date 2006-08-19 Time 09:33 Sent To I
Notes
2006-08-19 00:00:00NOTE: THE PROPOSED CABANA CANNOT EXCEED
 THE MAXIMUM FLOOR AREA OF 1000 SQUARE
 FEET AND CANNOT BE USED FOR LIVING
 SPACE.
  
 NOTE: THE PROPOSED WALL/GATE/FENCE MUST
 HAVE A SEPARATE PERMIT WITH CITY OF WEST
 PALM BEACH UTILITY ESEMENT APPROVAL.
  
 NOTE:
 THE PROPOSED A/C SHL NOT BE CLOSER THAN
 11FT FROM REAR PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-05-11 Cont ID  
Sent By mmclean Date 2006-05-11 Time 09:53 Rev Time 0.00
Received By mmclean Date 2006-05-11 Time 09:52 Sent To I
Notes
2006-05-11 00:00:00NOTE: THE PROPOSED CABANA CANNOT BE USED
 AS A LIVING SPACE. SF7