Plan Review Details - Permit 06040969
Plan Review Stops For Permit 06040969
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-11-25 Cont ID  
Sent By rnuquist Date 2006-11-25 Time 10:11 Rev Time 0.00
Received By rnuquist Date 2006-11-25 Time 10:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-17 Cont ID  
Sent By rnuquist Date 2006-10-17 Time 21:31 Rev Time 0.00
Received By rnuquist Date 2006-10-17 Time 21:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-16 Cont ID  
Sent By rnuquist Date 2006-08-16 Time 18:57 Rev Time 0.00
Received By rnuquist Date 2006-08-16 Time 18:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-05-31 Cont ID  
Sent By rnuquist Date 2006-05-31 Time 20:51 Rev Time 0.00
Received By rnuquist Date 2006-05-31 Time 20:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-11-13 Cont ID  
Sent By btrobaug Date 2006-11-13 Time 07:57 Rev Time 0.33
Received By btrobaug Date 2006-11-13 Time 07:49 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-13 Cont ID  
Sent By btrobaug Date 2006-10-13 Time 07:50 Rev Time 0.25
Received By btrobaug Date 2006-10-13 Time 07:45 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-08 Cont ID  
Sent By btrobaug Date 2006-08-08 Time 08:24 Rev Time 0.33
Received By btrobaug Date 2006-08-08 Time 07:55 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-03 Cont ID  
Sent By btrobaug Date 2006-05-03 Time 07:59 Rev Time 0.33
Received By btrobaug Date 2006-05-03 Time 07:53 Sent To P
Notes
2006-05-03 00:00:00 
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC AS BEING FED FROM
 "SERVICE", FEEDER AND CONDUIT SIZE AND
 TYPE, PANEL RATING AND OCP, PANEL
 SCHEDULE AND COMPUTED LOAD, ETC. IF AN
 ELECTRIC HEATER IS TO BE INSTALLED
 PLEASE SUBMIT CALCULATIONS FOR THE MAIN
 SERVICE.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-05-03 Cont ID  
Sent By mperson Date 2006-05-03 Time 14:15 Rev Time 0.00
Received By mperson Date 2006-05-03 Time 14:15 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-11-12 Cont ID  
Sent By adarroug Date 2006-11-12 Time 12:59 Rev Time 0.00
Received By adarroug Date 2006-11-12 Time 12:59 Sent To E
Notes
2006-11-12 12:59:39TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 09:02 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 09:02 Sent To Z
Notes
2006-11-07 09:03:29TO "Z" BOX/RESUB--NEW SHEETS SUBMITTED FOR ALL TRADES

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 10:03 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 10:03 Sent To E
Notes
2006-10-10 10:03:38TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-04 Cont ID  
Sent By adarroug Date 2006-10-04 Time 11:46 Rev Time 0.00
Received By adarroug Date 2006-10-04 Time 11:46 Sent To Z
Notes
2006-10-04 00:00:00TO "Z" BOX/RESUB--NEW SHEETS FOR "B" AND
 "E"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 08:30 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 08:30 Sent To E
Notes
2006-08-03 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-28 Cont ID  
Sent By adarroug Date 2006-07-28 Time 14:17 Rev Time 0.00
Received By adarroug Date 2006-07-28 Time 14:17 Sent To Z
Notes
2006-07-28 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 09:45 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 09:45 Sent To E
Notes
2006-05-02 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-02 Cont ID  
Sent By jgomez Date 2006-06-02 Time 13:46 Rev Time 0.00
Received By jgomez Date 2006-04-26 Time 10:11 Sent To  
Notes
2006-04-26 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-11-14 Cont ID  
Sent By mperson Date 2006-11-14 Time 13:24 Rev Time 0.33
Received By mperson Date 2006-11-14 Time 13:24 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-10-13 Cont ID  
Sent By mperson Date 2006-10-13 Time 16:26 Rev Time 0.33
Received By mperson Date 2006-10-13 Time 16:26 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-10 Cont ID  
Sent By mperson Date 2006-08-10 Time 08:18 Rev Time 0.45
Received By mperson Date 2006-08-10 Time 08:18 Sent To B
Notes
2006-08-10 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 SEC. 424.2 OR
 FBRC-2004 SEC.4101 SWIMMING POOLS.
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR PLUMBING PLAN REVIEW:
  
 1. THE SHEETS SUBMITTED NEED THE
 FOLLOWING PER FLORIDA ADMINISTRATIVE
 CODE AND STATE STATUTE.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 2. PLEASE SUBMIT POOL SPECIFICATIONS
 WITH PRINT. PLEASE REFERENCE THE
 ATTACHED EXAMPLE OF POOL SPECIFICATIONS
 FOR RESUBMITTAL.
 3. PER FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1", 1-1/2" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
 PLEASE REFERENCE THE ATTACHED EXAMPLE OF
 A VENT TABLE FOR REFERENCE FOR
 RESUBMITTAL.
 4. FBC-2004 SEC. 424.2.7.2, OR FBCR-2004
 SEC. R4101.7.2 PUMPS AND EQUIPMENT SHALL
 BE MOUNTED ON A SUBSTANTIAL BASE IN A
 MANNER THAT WILL ELIMINATE STRAIN ON
 PIPING.SLAB SHALL BE A NOMINAL 4"
 THICK. (DETAIL REQUIRED PLEASE ADD TO
 PRINT)
 5. FBC-2004 SEC. 424.2.9, OR FBCR-2004
 SEC. R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
 6. FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (ADD TO NOTES)
 7. FBC-2004 SEC. 424.2.13.2, OR
 FBCR-2004 SEC.R4101.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING.(ADD TO
 NOTES)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-03 Cont ID  
Sent By mperson Date 2006-05-03 Time 11:51 Rev Time 1.00
Received By mperson Date 2006-05-03 Time 11:51 Sent To G
Notes
2006-05-03 00:00:00******DENIED******
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1) FBC-2004 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 3) FBC-2004424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 4) FBC-2004424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)
 5) FBC-2004424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (NEED MANUFACTURE CUT SHEET
 OF VACUUM OR PRESSURE CLEANING FITTING
 OR MAKE AND MODEL NUMBER ADDED TO PRINT)
 6) FBC-2004 424.2.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (INDICATE SLAB
 THICKNESS ONDETAIL)
 7) FBC-2004 SEC. 424.2.9 WATER SUPPLY,
 LOCAL ORD. #2853-95, BACKFLOW REQUIRED
 ON WATER SERVICE. (ADD TO NOTES)
 8) FBC-2004 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 9) FBC-2004 SEC. 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC-2004 PLMG. SEC. 605.21,
 PURPLE PRIMER REQUIRED ON PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 10) ON SHEET 2 "POOL DATA EQUIPMENT"
 INDICATES "QTY RETURNS:4", BUT ON SHEET
 1 THERE APPEARS TO BE ONLY 3 RETURNS.
 PLEASE CORRELATE.
  
 NOTE: ON SHEET 2 PIPING SCHEMATIC THERE
 INDICATES AN "OPTIONAL HEATER" IF THERE
 IS A HEATER THE FOLLOWING SHALL APPLY,
 IF THERE ISN'T A HEATER PLEASE REMOVE
 OPTIONAL HEATER FROM PRINT:
 11) FBC-2004 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 CUT SHEETS REQUIRED)
 12) FBC-2004 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN HEATER WHEN PUMP IS SHUT OFF.
 (MANUFACTURE CUT SHEETS REQUIRED)
 13) FBC-2004 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER. (ADD
 TO NOTES)
 14) FBC-2004 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPERATE PLANS
 AND PERMIT REQUIRED. (ADD TO NOTES)
 15) ADD HEATER TO "POOL DATA EQUIPMENT"
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2006-11-10 Cont ID  
Sent By mmclean Date 2006-11-10 Time 09:21 Rev Time 0.00
Received By mmclean Date 2006-11-10 Time 09:20 Sent To I
Notes
2006-11-11 09:22:04PROVISO: THE PROPOSED POOL EQUIPMENT SHALL NOT BE
 CLOSER THAN 1FT FROM SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 3 Status F Date 2006-10-06 Cont ID  
Sent By lfranco Date 2006-10-06 Time 16:09 Rev Time 0.00
Received By lfranco Date 2006-10-05 Time 19:58 Sent To I
Notes
2006-10-06 00:00:0010/06/06 ***FAILED***
  
 1) PLEASE RESPOND TO ALL COMMENTS IN
 WRITING.
  
 2) THE SITE PLAN AND THE SURVEY NEED TO
 MATCH, I.E.:
 A) WHERE WAS THE EXISTING CANVAS
 RELOCATED?
 B) POOL AND POOL DECK REAR SETBACKS ARE
 NOT SHOWN ON THE SURVEY OR THE PLAN.
 C) POOL EQUIPMENT IS NOT SHOWN ON THE
 SURVEY.
 D) WOOD DECK IS NOT SHOWN ON THE SITE
 PLAN.
 E) ASPHALT DRIVE IS NOT SHOWN ON THE
 SITE PLAN.
 F) A/C IS NOT SHOWN ON THE SITE PLAN.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA
 DAVILA, PLANNER, 822-1427.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-08-02 Cont ID  
Sent By mmclean Date 2006-08-02 Time 11:14 Rev Time 0.00
Received By MMCLEAN Date 2006-08-02 Time 19:58 Sent To I
Notes
2006-08-02 00:00:00DENIED,
 1. THE SITPLAN SUBMITTED DOES NOT
 PROVIDE ALL INFORMATION THAT IS NEEDED
 TO COMPLETE THE VERIFICATION OF THE
 PROPOSED WORK.
 2. THE SITEPLAN DOES NOT PROVIDE THE
 ADDRESS OF THE PROPERTY AND DEPICT WHAT
 IS ON THE SURVEY (WHICH IS A LEGAL
 DOCUMENT), SETBACKS OF THE STRUCTURE
 FROM PROPERTY LINE AND DRIVEWAY ETC.
 3. THE SURVEY MAYBE USED FOR THE
 PROPOSED WORK, BUT NEED TO SHOW THE DECK
 WITH SETBACKS, POOL WITH SETBACKS (FROM
 WATER'S EDGE TO PROPERTY LINE), THE
 LOCATION OF THE POOL EQUIPMENT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-30 Cont ID  
Sent By mmclean Date 2006-04-30 Time 17:54 Rev Time 0.00
Received By mmclean Date 2006-04-30 Time 17:54 Sent To I
Notes
2006-04-30 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE PROPOSED POOL/DECK
 WITH SETBACKS.
 2. NO SURVEY SUBMITTED.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720