Plan Review Details - Permit 06040960
Plan Review Stops For Permit 06040960
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-23 Cont ID  
Sent By amorse Date 2006-05-23 Time 14:54 Rev Time 2.00
Received By amorse Date 2006-05-23 Time 14:54 Sent To Z
Notes
2006-05-23 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. PERMIT FEES
 WILL BE ADJUSTED ACCORDINGLY
  
 3) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 4) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
  
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
 NOTE: REQUIRED FOR WINDOWS, DOORS,
 ROOFING, SHUTTERS WHERE OPENINGS ARE NOT
 IMPACT RATED AND WOOD CONNECTOR/STRAPS
  
 5) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 7) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 8) SUBMIT A SIGNED AND SEALED COPY OF
 SURVEY PER 106.3.4 FBC* THAT IS LESS
 THAN 1 YR OLD ALSO PROVIDE A SITE PLAN
 WITH THE DRAWINGS PER 106.3.5 FBC*
  
 9) SUBMIT A SOIL REPORT PER R401.4 WHERE
 SOILS ARE DEEMED TO BE QUESTIONABLE
  
 10) CORRECT TABLE REFERENCES ON PAGE 1,
 ALSO COMPONANT AND CLADDING PRESSURE
 SCHEDULE HAS 2 END ZONES
  
 11) SEE SIMPSON STRAP SCHEDULE ON PAGE 4
  
 OUTLOOKER HANGER IS SPEC'D AS LUS310
 THAT HANGER IS FOR 3X10 PLEASE CLARIFY
  
 12) SHOW/STATE VENTILATION METHOD FOR
 ROOF SYSTEM ON 1/5 PAGE 5
  
 13) CONFIRM DEPTH OF TRUSS AND OUTLOOKER
 MATCH UP FOR HANGER AND WALL ATTACHMENT
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By btrobaug Date 2006-05-08 Time 14:50 Rev Time 0.50
Received By btrobaug Date 2006-05-08 Time 11:55 Sent To P
Notes
2006-05-08 00:00:00 
  
 FAILED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE DISCONNECTING MEANS PER
 230.70. THE PANEL IS NOTED AS BEING A
 MLO. ALSO SEE 230.71.
  
 2} LOCATE THE NEW 200 AMP PANEL ON THE
 PLAN.
  
 3} PLEASE PROVIDE A PANEL SCHEDULE
 INDICATING BRANCH CIRCUIT WIRE SIZE AND
 OVERCURRENT PROTECTION SO THAT
 COMPLIANCE CAN BE REVIEWED.
  
 4} RECEPTACLES MUST BE ADDED TO BOTH
 BEDROOMS FOR SPACING REQUIREMENTS PER
 210.52(A)(1).
  
 5} PLEASE SEE THE ENGINEERS SEAL NEEDS
 UPDATED TO COMPLY WITH 61G15-23.002.FAC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 13:39 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 13:39 Sent To E
Notes
2007-05-08 13:39:28TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-25 Cont ID  
Sent By mmclean Date 2006-05-25 Time 10:09 Rev Time 0.00
Received By mmclean Date 2006-04-25 Time 14:06 Sent To  
Notes
2006-04-25 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-11 Cont ID  
Sent By tgordon Date 2006-05-11 Time 09:53 Rev Time 0.20
Received By tgordon Date 2006-05-11 Time 09:53 Sent To B
Notes
2006-05-11 00:00:00*** DENIED ***
 1)NO MECHANICAL PLANS WERE SUBMITTED FOR
 REVIEW. PLEASE SUBMIT MECHANICAL PLANS
 FOR REVIEW, OR YOU MAY WISH TO VOID YOUR
 MECHANICAL PERMIT NUMBER 06040967 SO
 YOUR BUILDING PLANS MAY BY-PASS A
 MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-11 Cont ID  
Sent By jleech Date 2006-05-11 Time 07:22 Rev Time 0.00
Received By jleech Date 2006-05-11 Time 07:22 Sent To M
Notes
2006-05-11 00:00:00DENIED;
 SANITARY RISER DIAGRAM; BATHROOM GROUPS
 CONTAIN LAV., SHR. OR TUB AND A TOILET.
 NOT A SINK. PLEASE SHOW BATHROOMS ON
 RISER DIAGRAM. SIZE ALL PIPE SECTIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2006-05-25 Cont ID  
Sent By mmclean Date 2006-05-25 Time 10:08 Rev Time 0.00
Received By mmclean Date 2006-05-25 Time 10:02 Sent To  
Notes
2006-05-25 00:00:00DENIED,
 1. MUST PROVIDE TWO CURRENT COPY OF
 SURVEY SHOWING THE LOCATION OF THE
 PROPOSED WORK WITH SETBACK OF THE
 STRUCTURE FROM PROPERTY LINE
 (FRONT/SIDE/REAR?)
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720