| 2006-05-23 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SETS OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561) 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 2) THE STATE OF FLORIDA REQUIRES |
| | COLLECTION OF A RADON SURCHARGE ON ALL |
| | NEW CONSTRUCTION COMPUTED ON UNDER ROOF |
| | FLOOR SPACE PER 10D-91 FAC. PERMIT FEES |
| | WILL BE ADJUSTED ACCORDINGLY |
| | |
| | 3) THE CLAIMED VALUATION ON THE PERMIT |
| | APPLICATION IS LOW. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| | COST EXCLUDING LAND VALUE. OUR VALUATION |
| | REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| | AND MEANS COST ANALYSIS SERVICES PER |
| | 108.3 FBC* |
| | |
| | 4) THE PERMIT APPLICATION SHALL INCLUDE |
| | TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| | |
| | IS RELEVANT PER 9B-72. THESE SHOULD |
| | INCLUDE THE FLORIDA STATE APPROVAL COVER |
| | PAGES, AND THE PRODUCT NOA THAT LISTS |
| | THE SYSTEM COMPONENTS/ FASTENER LIST |
| | PAGES, THE PAGES WITH THE CHOSEN |
| | ASSEMBLY/ SYSTEM TO BE USED AND THE |
| | GENERAL LIMITATIONS PAGE. ALL CAN BE |
| | FOUND ON WWW.FLORIDABUILDING.ORG |
| | NOTE: REQUIRED FOR WINDOWS, DOORS, |
| | ROOFING, SHUTTERS WHERE OPENINGS ARE NOT |
| | IMPACT RATED AND WOOD CONNECTOR/STRAPS |
| | |
| | 5) THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 6) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT |
| | APPLICATION OR BEFORE INSTALLATION |
| | |
| | 7) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND |
| | DATED BY PREPARER AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL |
| | |
| | 8) SUBMIT A SIGNED AND SEALED COPY OF |
| | SURVEY PER 106.3.4 FBC* THAT IS LESS |
| | THAN 1 YR OLD ALSO PROVIDE A SITE PLAN |
| | WITH THE DRAWINGS PER 106.3.5 FBC* |
| | |
| | 9) SUBMIT A SOIL REPORT PER R401.4 WHERE |
| | SOILS ARE DEEMED TO BE QUESTIONABLE |
| | |
| | 10) CORRECT TABLE REFERENCES ON PAGE 1, |
| | ALSO COMPONANT AND CLADDING PRESSURE |
| | SCHEDULE HAS 2 END ZONES |
| | |
| | 11) SEE SIMPSON STRAP SCHEDULE ON PAGE 4 |
| | |
| | OUTLOOKER HANGER IS SPEC'D AS LUS310 |
| | THAT HANGER IS FOR 3X10 PLEASE CLARIFY |
| | |
| | 12) SHOW/STATE VENTILATION METHOD FOR |
| | ROOF SYSTEM ON 1/5 PAGE 5 |
| | |
| | 13) CONFIRM DEPTH OF TRUSS AND OUTLOOKER |
| | MATCH UP FOR HANGER AND WALL ATTACHMENT |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |