Plan Review Details - Permit 06040957
Plan Review Stops For Permit 06040957
Review Stop B BUILDING (STRUCTURAL)
Rev No 72 Status P Date 2008-07-25 Cont ID  
Sent By jwitmer Date 2008-07-25 Time 15:25 Rev Time 0.77
Received By jwitmer Date 2008-07-25 Time 15:25 Sent To  
Notes
2008-07-25 15:26:15ENERGY CALCS REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 71 Status F Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 12:15 Rev Time 0.77
Received By jwitmer Date 2008-06-03 Time 12:15 Sent To PC
Notes
2008-06-03 12:17:59 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
 SUBMITTAL: ENERGY CALCS: NOTE SHEET 97 HEADING DOORS
 INDICATES ON THE FIRST FLOOR THE DOORS ARE STEEL DOORS
 WITH HONEY COMB FILLED CORES THEY ARE ACTUALLY GLAZED
 OPENINGS. PLEASE CORRET.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 70 Status P Date 2008-05-16 Cont ID  
Sent By rbrown Date 2008-05-16 Time 20:04 Rev Time 0.00
Received By rbrown Date 2008-05-16 Time 20:04 Sent To  
Notes
2008-05-16 20:06:13LOCAL PRODUCT APPROVAL FOR FOUR METCOE SKYLIGHT,
 INC.ALUMINUM EXTRUSION SKYLIGHTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 69 Status P Date 2008-05-16 Cont ID  
Sent By rbrown Date 2008-05-16 Time 15:22 Rev Time 0.00
Received By rbrown Date 2008-05-16 Time 15:22 Sent To  
Notes
2008-05-16 15:24:36ENGINEERING REPORT FOR SLAB TO CURTAIN WALL FIRESTOP
 DETAIL.OK PER FBC 713.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 68 Status P Date 2008-05-12 Cont ID  
Sent By jwitmer Date 2008-05-12 Time 13:35 Rev Time 0.77
Received By jwitmer Date 2008-05-12 Time 13:35 Sent To PC
Notes
2008-05-12 13:37:05 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION:
 SUBMITTAL: SHEET A0.21 REVISION# 43
 REVISION:

Review Stop B BUILDING (STRUCTURAL)
Rev No 67 Status F Date 2008-05-08 Cont ID  
Sent By jwitmer Date 2008-05-08 Time 13:55 Rev Time 0.00
Received By jwitmer Date 2008-05-08 Time 13:55 Sent To PC
Notes
2008-05-08 14:03:15 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
 SUBMITTAL: # 03450-020 IS FOR A PRECAST MONUMENT SIGN,
 REQUIRES ITS OWN PERMIT, FEES AND REVIEWS.
 CITY CODE OF ORDANCES: ARTICLE V.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 66 Status F Date 2008-05-05 Cont ID  
Sent By jwitmer Date 2008-05-05 Time 13:16 Rev Time 3.33
Received By jwitmer Date 2008-05-05 Time 13:16 Sent To PC
Notes
2008-05-05 16:06:46 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
 SUBMITTAL: 20000-0010 FIRESTOP ENGINEERING JUDGMENT-
 ENGINEERING JUDGMENTS ARE UASULLY PROVIDED WHEN THERE
 IS NO ASSEMBLY THAT MATCHES WITH THE TYPE OF
 CONFIGURATION THAT IS TO PROPOSED TO BE BUILT. IN EACH
 OF THE CASES THE UL SYSTEM NO. CW-D-2040 AND CW-D-2042
 IN BOTH CASES THE MULLION COVER OF THE CURTAIN WALL
 INSULATION SYSTEM IS NOT BEING APPLIED. THE MULLION
 COVERS ARE TOABUT THE FORMING MATERIAL (ITEM 3A)
 ABOVE AND BELOW THE FLOOR.
 713.4 EXTERIOR CURTAIN WALL/FLOOR INTERSECTION.
 WHERE FIRE- RESISTANCE-RATED FLOOR OR FLOOR/CEILING
 ASSEMBLIES ARE REQUIRED, VOIDS CREATED AT THE
 INTERSECTION OF THE EXTERIOR CURTAIN WALL ASSEMBLIES
 AND SUCH FLOOR ASSEMBLIES SHALL BE SEALED WITH AN
 APPROVED MATERIAL OR SYSTEM TO PREVENT THE INTERIOR
 VERTICAL SPREAD OF FIRE. SUCH MATERIAL OR SYSTEMS SHALL
 BE SECURELY INSTALLED AND CAPABLE OF PREVENTING THE
 PASSAGE OF FLAME AND HOT GASES SUFFICIENT TO IGNITE
 COTTON WASTE WHERE SUBJECTED TO ASTM E 119
 TIME-TEMPERATURE FIRE CONDITIONS UNDER A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF WATER
 (2.49 PA) FOR THE TIME PERIOD AT LEAST EQUAL TO THE
 FIRE-RESISTANCE RATING OF THE FLOOR ASSEMBLY. HEIGHT
 AND FIRE-RESISTANCE REQUIREMENTS FOR CURTAIN WALL
 SPANDRELS SHALL COMPLY WITH SECTION 704.9 .
  
 CW-D-2005 WE SEE NO NEED FOR THE ENGINEERING JUDGEMENT
 AND WILL STAMP THIS SUBMITTAL
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 65 Status P Date 2008-05-05 Cont ID  
Sent By jwitmer Date 2008-05-05 Time 07:37 Rev Time 1.22
Received By jwitmer Date 2008-05-05 Time 07:37 Sent To  
Notes
2008-05-05 07:56:18 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
  
 REVISION:
  
 RFI 0474 PLATFORM OVER CONDENSER WATER PIPES
 RFI 0473- ACCESS TO SCF-2 THROUGH EXISTING SCREENWALL
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 64 Status P Date 2008-04-30 Cont ID  
Sent By jwitmer Date 2008-04-30 Time 15:00 Rev Time 0.77
Received By jwitmer Date 2008-04-30 Time 15:00 Sent To PC
Notes
2008-04-30 15:02:20 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: REVIEWED
 SUBMITTAL: 7552-010
 ROOF EDGW DETAIL

Review Stop B BUILDING (STRUCTURAL)
Rev No 63 Status P Date 2008-04-30 Cont ID  
Sent By jwitmer Date 2008-04-30 Time 13:14 Rev Time 0.77
Received By jwitmer Date 2008-04-30 Time 13:14 Sent To PC
Notes
2008-04-30 13:19:16 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: REVIEWED
 SUBMITTAL: RFI 0495 SHAFT WALL @ SPF-1 & SPF-2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 62 Status P Date 2008-04-30 Cont ID  
Sent By jwitmer Date 2008-04-30 Time 16:31 Rev Time 0.55
Received By jwitmer Date 2008-04-30 Time 12:35 Sent To PC
Notes
2008-04-30 16:34:00 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2REVIEW
 ACTION: REVIEWED
 SUBMITTAL: \
 07415-006 CORNICE END PANEL CALCULATIONS
 07415-007 NORTH CANOPY BEAM WRAP CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 61 Status P Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 16:45 Rev Time 0.88
Received By jwitmer Date 2008-04-21 Time 16:45 Sent To  
Notes
2008-04-21 16:47:09 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
  
 SUBMITTAL: 05510-003 STAIR SHOP DRAWING AND
 CALCULATIONS
 REVISION:

Review Stop B BUILDING (STRUCTURAL)
Rev No 60 Status P Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 16:31 Rev Time 0.66
Received By jwitmer Date 2008-04-21 Time 16:31 Sent To  
Notes
2008-04-21 16:32:28 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL: 08960-001 R3 & SHOP DRAWINGGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 59 Status F Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 16:20 Rev Time 0.88
Received By jwitmer Date 2008-04-21 Time 16:19 Sent To  
Notes
2008-04-21 16:22:48 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION:
 SUBMITTAL: 08600-006 SKYLIGHT PRODUCT EVALUATION
 REPORT
 FOR THE LOCAL PRODUCT APPROVAL THE CIY FORM MUST BE
 FILLED OUT COMPLETELY, ALSO INCLUDEDIS A CHECKLIST
 FOR LOCAL APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 58 Status F Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 15:44 Rev Time 0.55
Received By jwitmer Date 2008-04-21 Time 15:44 Sent To  
Notes
2008-04-21 15:46:36 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW DENIED
 ACTION:
 SUBMITTAL: SPF-2 & SCF-1
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL-
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING
 THE PLANS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 57 Status F Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 15:40 Rev Time 0.55
Received By jwitmer Date 2008-04-21 Time 15:40 Sent To B
Notes
2008-04-21 15:41:51 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW DENIED
 ACTION:
 SUBMITTAL: RFI 047-R3
 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED &
 SEALED BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER
 THE: NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER
 OR, THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 56 Status F Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 15:02 Rev Time 0.55
Received By jwitmer Date 2008-04-21 Time 15:02 Sent To  
Notes
2008-04-21 15:29:24CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED/ DENIED
  
 SUBMITTAL NO.7552-010
 ROOF LEDGE DETAIL INDICATES A REVISION TO DETAIL
 2/A5.62 THIS WILL REQUIRE A REVISION FEE
  
 2) IF A REVISION THE ARCHITECT WILL REQUIRE:
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL-
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING
 THE PLANS
  
 3) ENGINEERING SHEETS:
 61G15-23.002(2)FL. ADMIN. CODE. A COVER SHEET OR
 INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED
 AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF
 THE PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 55 Status P Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 14:53 Rev Time 0.55
Received By jwitmer Date 2008-04-21 Time 14:53 Sent To  
Notes
2008-04-21 14:57:52 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION:
 SUBMITTAL: NO. 10210-009
 REVIEWEDALUFAB SOUTH CANOPY SHOP DRAWINGSBLDG
 PROVISO, TABLE 601 FIRE RATINGS MAINTAINED

Review Stop B BUILDING (STRUCTURAL)
Rev No 54 Status F Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 14:14 Rev Time 0.77
Received By jwitmer Date 2008-04-21 Time 14:13 Sent To  
Notes
2008-04-21 14:22:52BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW- REVISION
 ACTION: DENIED
  
 REVISION: RFI NO 0473 REVISON
 1) PLEASE PAY FOR REVISION
 2) ENGINNER MISSING TITLE BLOCK:
 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
 MISSING THEIR COA IN THE TITLE BLOCK.
 3) WHAT APPEARS AS A PARTIAL ROOF PLAN THAT HAS BEEN
 COPIED, HAND DRAWN CHANGESNO TITLE BLOCK AND NO SEAL
 NOR SIGNATURE.
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL-
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING
 THE
 PLANS
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 53 Status F Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 14:08 Rev Time 0.00
Received By jwitmer Date 2008-04-21 Time 14:11 Sent To  
Notes
2008-04-21 14:11:09 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW- REVISION
 ACTION: DENIED
  
 REVISION: RFI NO 0471 REVISON
 1) PLEASE PAY FOR REVISION
 2) ENGINNER MISSING TITLE BLOCK:
 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 52 Status F Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 13:55 Rev Time 0.55
Received By jwitmer Date 2008-04-21 Time 13:55 Sent To  
Notes
2008-04-21 14:00:13 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
 SUBMITTAL:
 NO 07415-006 STRUCTURAL CALCS EXTERIOR COMPOSITE-
 PANELS CORNICE END PANELS
 NO 07415-007 STRUCTURAL CALCS EXTERIOR COMP PANELS-
 PORTE COCHERE BEAM WRAP PANELS
  
  
 61G15-23.002(2)FL. ADMIN. CODE. A COVER SHEET OR
 INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED
 AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF
 THE PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 51 Status P Date 2008-04-07 Cont ID  
Sent By shill Date 2008-04-07 Time 12:15 Rev Time 0.00
Received By shill Date 2008-04-07 Time 12:15 Sent To  
Notes
2008-04-07 12:16:53REVISION 36 DATED 1/6, A1.02, 1.03, 1.04, 1.05
 (ADDRESSED BUILDING REVIEW #39 COMMENTS)

Review Stop B BUILDING (STRUCTURAL)
Rev No 50 Status P Date 2008-03-25 Cont ID  
Sent By shill Date 2008-03-25 Time 07:36 Rev Time 0.00
Received By shill Date 2008-03-25 Time 07:36 Sent To  
Notes
2008-03-25 07:45:08REVISION 37 OK (REV 33 SUPERSEDED 28; REVISION 33
 ZONING COMMENTS ONLY PER ARCHITECT)
 L1, L2,L2.1, L2.2
 A0.21, 0.21A, A1.01, A1.09, A2.07, A3.01, A10.09

Review Stop B BUILDING (STRUCTURAL)
Rev No 49 Status F Date 2008-03-21 Cont ID  
Sent By shill Date 2008-03-21 Time 13:34 Rev Time 0.00
Received By shill Date 2008-03-21 Time 13:34 Sent To  
Notes
2008-03-21 13:37:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.THE PLANS STATE TO MOUNT EXHAUST "AS HIGH AS
 POSSIBLE".PLEASE PROVIDE AN ELEVATION AS COMPLIANCE
 WITH FBC11-4.4.2, OVERHEAD HAZARDS, IS NOT CLEAR.SEE
 ALSO FBC FIGURE 11-8; IT IS NOT CLEAR IF THIS
 OBSTRUCTION WILL BE OVER 80INCHES (FIGURE 11-8(A) OR IF
 THE BOTTOM WILL BE LESS THAN 27INCHES (FIGURE 11-8(A)
 AND (B)).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 48 Status N Date 2008-03-25 Cont ID  
Sent By rregueir Date 2008-03-25 Time 10:32 Rev Time 0.00
Received By shill Date 2008-02-29 Time 10:37 Sent To  
Notes
2008-03-25 10:22:36MECH REVIEW FROM 3/10/08 ACCIDENTALLY ENTERED UNDER
 THIS REVIEW.
 RJR

Review Stop B BUILDING (STRUCTURAL)
Rev No 47 Status P Date 2008-02-29 Cont ID  
Sent By jwitmer Date 2008-02-29 Time 08:46 Rev Time 2.22
Received By jwitmer Date 2008-02-29 Time 08:46 Sent To  
Notes
2008-02-29 10:39:17 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION:
 SUBMITTAL:
 8912-013R1 CURTAIN WALL SHOP DRAWINGS
 8912-014R1 CURTAIN WALL CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 46 Status P Date 2008-02-27 Cont ID  
Sent By jwitmer Date 2008-02-27 Time 10:32 Rev Time 2.22
Received By jwitmer Date 2008-02-27 Time 10:32 Sent To PC
Notes
2008-02-27 10:59:24 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL:
 #0350-019 ARCHITECTURAL PRECAST CONCRETE DETAILS R-32 &
 R-33
 10210-005 ALUFAB SOUTH CANOPY SHOP DRAWING &
 CALCULATIONS
 10210-007 ALUFAB LOUVER SHOP DRAWINGS & CALCULATIONS
 08960-008 PORTE COCHERE BREAK METAL SHOP DRAWINGS
 08960-009 PORTE COCHERE BREAK METAL CALCS
 08960-002-R2 SLOPED GLAZING SYSTEM NOA
 08960-006 SLOPED GLAZING CALCS ENGINEERED

Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status P Date 2008-02-13 Cont ID  
Sent By jwitmer Date 2008-02-13 Time 07:24 Rev Time 8.88
Received By jwitmer Date 2008-02-13 Time 07:24 Sent To PC
Notes
2008-02-13 07:49:41 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: REVIEWED
  
 REVISION: # 33
  
 A0.23 REV# 33
 A0.24 REV# 33
 A0.31 REV# 33
 A1.01-FAILED ZONING COMMENTS
 A1.02 REV# 33, A1.03 REV# 33, A1.04 REV# 33, A1.05 REV#
 33, A1.06 REV# 33 , A1.07 REV# 33, A1.08 REV# 33, A1.09
 REV# 33 & A1.15 REV# 33
 A2.01A REV# 33, A2.06 REV# 33, A2.07 REV# 33, A2.16
 REV# 33 & A2.17.
 A3.02 REV# 20, A3.03 REV# 3
 A4.01, A4.02 A4.03 REV# 33
 A5.44, A5.62 & A5.81 REV# 33
 A6.06 REV# 33
 A8.01, A8.11, A8.11A, A8.12, A8.61 & A8.71 REV# 33
 A10.01, A10.02, A10.03, A10.04, A10.05, A10.06 A10.07
 A10.08 & A10.09

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status F Date 2008-02-13 Cont ID  
Sent By jwitmer Date 2008-02-13 Time 07:21 Rev Time 0.99
Received By jwitmer Date 2008-02-13 Time 07:21 Sent To  
Notes
2008-02-13 07:23:49 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 REVISION:# 33
  
 SHEETS , A0.21 & A3.01 BOTH WERE DENIED BY ZONING
 REVIEWER.
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status F Date 2008-01-31 Cont ID  
Sent By jwitmer Date 2008-01-31 Time 12:08 Rev Time 0.77
Received By jwitmer Date 2008-01-31 Time 12:08 Sent To PC
Notes
2008-01-31 12:14:14BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SHOP DRAWINGS & CALCSREVIEW
 ACTION: DENIED
  
 SUBMITTALS: 08800-007
 08411-009
 08800-006
 08411-008
  
 SHEET -101 INDICATES THE STRUCTURAL DESIGN (B) 2001
 FLORIDA BUILDING CODE (HVHZ REQUIREMENTS)
 PLEASE CORRECT THE STATEMENTS TO READ TO THE 2004
 FLORIDA BUILDING CODE. NOT LOCATED IN THE HIGH WIND
 VELOCITY ZONE.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status F Date 2008-01-31 Cont ID  
Sent By jwitmer Date 2008-01-31 Time 10:07 Rev Time 0.55
Received By jwitmer Date 2008-01-31 Time 10:07 Sent To PC
Notes
2008-01-31 10:17:28BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SHOP DRAWINGS & CALCSREVIEW
 ACTION: DENIED
  
 SUBMITTAL: LETTER
  
 THIS LETTER HAS NOT BEEN REVIEWED BY THE DESIGN
 PROFESSIONALS IN CHARGE OF THIS PROJECT. PLEASE HAVE
 THE DESIGN TEAM REVIEW SUCH LETTERAS THEY WOULD SHOP
 DRAWINGS.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 T

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status F Date 2008-01-31 Cont ID  
Sent By jwitmer Date 2008-01-31 Time 10:04 Rev Time 0.55
Received By jwitmer Date 2008-01-31 Time 10:04 Sent To PC
Notes
2008-01-31 10:05:53BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SHOP DRAWINGS & CALCSREVIEW
 ACTION: DENIED
  
 REVISION: REVISED CURTAIN WALL HEAD CONNECTION 14 TH
 FL
  
 1)FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE
 FOR SUPERVISING AND REVIEWING ALL PROJECT DATA,
 REPORTS, SHOP DRAWINGS ETC...
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3) 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED &
 SEALED BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER
 THE: NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER
 OR, THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status F Date 2008-01-31 Cont ID  
Sent By jwitmer Date 2008-01-31 Time 09:31 Rev Time 0.33
Received By jwitmer Date 2008-01-31 Time 09:31 Sent To  
Notes
2008-01-31 09:54:32 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SHOP DRAWINGS & CALCSREVIEW
 ACTION: DENIED
  
 REVISION: REVISED CURTAIN WALL CONNECTIONS
  
 1)FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE
 FOR SUPERVISING AND REVIEWING ALL PROJECT DATA,
 REPORTS, SHOP DRAWINGS ETC...
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3) 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED &
 SEALED BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER
 THE: NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER
 OR, THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 4) 61G15-23.002(2)FL. ADMIN. CODE. A COVER SHEET OR
 INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED
 AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF
 THE PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status P Date 2008-01-24 Cont ID  
Sent By jwitmer Date 2008-01-24 Time 08:21 Rev Time 0.55
Received By jwitmer Date 2008-01-24 Time 08:21 Sent To PC
Notes
2008-01-24 08:22:38 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL: 03450-018 ARCH PRECAST CONCRETE AS BUILT
 SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status P Date 2008-01-24 Cont ID  
Sent By jwitmer Date 2008-01-24 Time 07:58 Rev Time 0.44
Received By jwitmer Date 2008-01-24 Time 07:58 Sent To  
Notes
2008-01-24 08:16:03 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL: 11010-003 SWINGSTAGE SHOP DRAWING

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2008-01-24 Cont ID  
Sent By jwitmer Date 2008-01-24 Time 07:53 Rev Time 0.37
Received By jwitmer Date 2008-01-24 Time 07:52 Sent To PC
Notes
2008-01-24 07:55:38 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL: 07552-007-R1 ROOF EDGE CORNICE DETAIL W/
 BACKING
 07552-008 PARAPET WALL SECTION 6TH FL
 COPING CAP AND BACKING

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status P Date 2008-01-24 Cont ID  
Sent By jwitmer Date 2008-01-24 Time 07:46 Rev Time 0.44
Received By jwitmer Date 2008-01-24 Time 07:45 Sent To  
Notes
2008-01-24 07:48:54 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL: 11010-004 WINDOW WASHER EQUIPMENT
 CALCULATIONS
 11010-003 WINDOW WASHING EQUIPMENT
 SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status P Date 2008-01-24 Cont ID  
Sent By jwitmer Date 2008-01-24 Time 07:42 Rev Time 0.39
Received By jwitmer Date 2008-01-24 Time 07:42 Sent To  
Notes
2008-01-24 07:44:56 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL: 07415-004-R1 CLADDING SYSTEM SHOP DRAWINGS
 07415-005-R1 CLADDING SYSTEM
 CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2007-12-28 Cont ID  
Sent By jwitmer Date 2007-12-28 Time 09:10 Rev Time 9.90
Received By jwitmer Date 2007-12-28 Time 09:10 Sent To PC
Notes
2007-12-28 09:50:48 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL:
 #09111-018 LIGHT GAUGE FRAMING PAGES 1-40
 #09111-019 LIGHT GAUGE FRAMINGPAGES 1-37
 #08334-002R1 OVERHEAD ROLL-UP DOOR NOA & SHOP DRAWINGS
 DOOR NO. 102B SOUTH DOOR
 DOOR NO. 102B NORTH DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status N Date 2007-12-21 Cont ID  
Sent By jwitmer Date 2007-12-21 Time 15:44 Rev Time 0.33
Received By jwitmer Date 2007-12-21 Time 15:44 Sent To  
Notes
2007-12-21 15:45:29 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION:
 SUBMITTAL: 02430-001R-4 WATER FEATURE- (N)

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status P Date 2007-11-20 Cont ID  
Sent By jwitmer Date 2007-11-20 Time 13:13 Rev Time 2.33
Received By jwitmer Date 2007-11-20 Time 13:13 Sent To PC
Notes
2007-11-20 14:24:52CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION:REVIEWED
  
 SUBMITTAL NO: 08411-006
 #08912-010
 #09111-016 LIGHT GAUGE METAL STUD FRAMING REV # 3
 #10200-007 REVISION# 15 LOUVER ONLY TO BE REVIEWED BY
 MECH FOR DAMPER
 #09111-017 LIGHT GAUGE METAL EAST RAMP ENTRY REV # 4

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2007-11-07 Cont ID  
Sent By jwitmer Date 2007-11-07 Time 07:12 Rev Time 6.00
Received By jwitmer Date 2007-11-07 Time 07:12 Sent To PC
Notes
2007-11-07 07:20:46 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: REVIEWED ARCHITECTURAL REVISION# 19 & 22,
 STRUCTURAL REVISION # 15.

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2007-10-30 Cont ID  
Sent By jwitmer Date 2007-10-30 Time 09:03 Rev Time 0.55
Received By jwitmer Date 2007-10-30 Time 09:03 Sent To B
Notes
2007-10-30 09:04:19SUBMITTAL:
 10200-006 LOUVER SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2007-10-23 Cont ID  
Sent By jwitmer Date 2007-10-23 Time 10:19 Rev Time 2.66
Received By jwitmer Date 2007-10-23 Time 10:19 Sent To  
Notes
2007-10-23 10:43:45SUBMITTALS:
 09111-014 DRIVE THROUGH SOFFIT CLADDING LETTER
 03450-016 LETTER RESPONCE TO ONM&J INSPECTION REPORT
 SIGNED & SEALED ENGINEERED CALCULATIONS & MODIFICATIONS
 IN RESPONSE TO ONM& J OUTSTANDING ITEM LIST
 09111-013INFILL FRAMING @ COLUMN LINE B-9 ELEVATOR
 VESTIBULE SOFFIT FRAMING

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2007-10-12 Cont ID  
Sent By jwitmer Date 2007-10-12 Time 11:31 Rev Time 1.22
Received By jwitmer Date 2007-10-12 Time 11:31 Sent To  
Notes
2007-10-12 11:51:10 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL:
 NO. 09111-001 LIGHT GAUGE METAL STUD FRAMING
 NO. 09111-010 LIGHT GAUGE METAL STUD FRAMING
 NO. 09111-011 GARAGE PARARET LIGHT GAUGE METAL STUD
 FRAMING
 NO. 09111-012 SOFFIT METAL STUD FRAMING
 NO. 08600-001 SKYLIGHT SHOP DRAWINGS
 NO. 08600-003 SKYLIGHT CALCULATIONS
 N0. 03450-004 PRECAST STRUCTURAL DESIGN CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status F Date 2007-09-28 Cont ID  
Sent By jwitmer Date 2007-09-28 Time 13:35 Rev Time 1.33
Received By jwitmer Date 2007-09-28 Time 13:35 Sent To PC
Notes
2007-09-28 13:52:40 
 BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
 SUBMITTAL:
 REVISION:
  
 #05511-003 CALCULATIONS & SHOP DRAWINGS PREFABRICATED
 STEEL STAIRS BOTH THE CALCS AND STAIR SHOP DRAWINGS
 REQUIRE ORIGINAL SIGNATURE NOT RUBBER STAMP SIGNTURES.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.FL STATE STAT:
 61G15-23.002 ENGINEERS
 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER .
  
 61G15-23.002
 SEAL, SIGNATURE AND DATE SHALL BE AFFIXED.
  
 ACOVER OR INDEX SHEET FOR ENGINEERING SPECIFICATIONS
 MAY BE USED AND THAT SHEET MUST BE SIGNED, SEALED AND
 DATED BY THOSE PROFESSIONAL ENGINEERS IN RESPONSIBLE
 CHARGE OF THE SPECIFICATIONS MAY BE USED AND THE
 PREPERATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX SO THAT THE USER WILL BE AWARE OF EACH
 PORTION OF THESPECIFICATIONS FOR WHICH EACH
 PROFESSIONAL ENGINEER IS RESPONSIBLE.
  
  
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status F Date 2007-09-25 Cont ID  
Sent By jwitmer Date 2007-09-25 Time 16:06 Rev Time 0.77
Received By jwitmer Date 2007-09-25 Time 16:06 Sent To PC
Notes
2007-09-25 16:27:00BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0359
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 SUBMITTAL NO:
 11010-002 TRACTEL WINDOW WASHING CALCS
 11010-001 R3 TRACTEL WINDOW WASHING SHOP DRAWINGS
  
 TRACTEL WINDOW WASHING CALCS THERE IS NO TITLE BLOCK
 PROVIDING REQUIRED INFORMATION ON THE ENGINEER:)
 61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL
 INCLUDE EITHER THE NAME, ADDRESS AND LICENSE NUMBER OF
 THE OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS( IF DOING BUSINESS AS A DBA)
 THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S.
 AND 471.023 F.S.).
  
 SHOP DRAWINGS ALSO ARE MISSING A TITLE BLOCK WITH THE
 ENGINEERS INFORMATION, 61G15-23.002(2)
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status F Date 2007-09-25 Cont ID  
Sent By jwitmer Date 2007-09-25 Time 15:02 Rev Time 0.55
Received By jwitmer Date 2007-09-25 Time 15:02 Sent To PC
Notes
2007-09-25 15:28:36BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: BALFOUR BEATTY
 TEL: (561)718-0935
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
 CONTRACTOR SUBMITTED THREE SETS OFPRECAST STRUCTURAL
 DESIHN CALCULATIONS 2 ARE SIGNED AND SEALED THE THIRD
 SET IS A COPY. THREE SETS OF ORIGINAL SIGNED AND SEALED
 CALCS ARE REQUIRED. PLANS, SPECIFICATIONS, REPORTS
 OR OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL
 AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2007-09-25 Cont ID  
Sent By jwitmer Date 2007-09-25 Time 14:24 Rev Time 3.33
Received By jwitmer Date 2007-09-25 Time 14:23 Sent To  
Notes
2007-09-25 15:02:32SUBMITTALS;
 STRUCTURAL STEEL SHOP DRAWINGS (E1-E25)
 SUBMITTAL# 03450-015 PRECAST SHOP DRAWINGS EXTERIOR
 WALL PANELS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2007-09-24 Cont ID  
Sent By jwitmer Date 2007-09-24 Time 09:35 Rev Time 3.33
Received By jwitmer Date 2007-09-24 Time 09:35 Sent To  
Notes
2007-09-24 09:48:31SUBMITTALNO. 05500-002-MISC METAL
 SUBMITTAL NO. 08800-004 HARMON HI-5000 NOA04-0217.08
 LARGE MISSILE
 HARMON HI-5000
 NOA04-0217.09 SMALL MISSILE
 SUBMITTAL NO. 08800-005 CALCS FOR HARMON SYSTEM PUNCHED
 WINDOWS SHEETS 1-50
 SUBMITTAL NO 08912-007 HARMON HI-7000 LMI NOA
 04-0217.11
 SUBMITTAL NO 07552-005 ROOF PRODUCT APPROVALS AND
 CALCULATIONS ON TARGET ENGINEERING ROOF PERMIT#
 06040961
 SUBMITTAL NO 08912-007,008 HARMON STOREFRONT SHOP
 DRAWINGS SF1,SF2,SF3,SF4,SF4A,SF5,SF6&SF7.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status F Date 2007-09-17 Cont ID  
Sent By jwitmer Date 2007-09-17 Time 10:27 Rev Time 0.77
Received By jwitmer Date 2007-09-17 Time 10:27 Sent To  
Notes
2007-09-17 10:36:29BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: BALFOUR BEATTY CONSTRUCTION
 TEL: (561)653-8139
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ROOFREVIEW SUBMITTALFILE# 07552-005
 ACTION: DENIED
  
 1) SUBMITTAL WAS BROUGHT IN BY THE CGC AND UNDER THE
 BUILDING PERMIT, WORKING OUT OF THE SCOPE FOR THE
 BUILDING PERMIT AND FLORIDA LICENSING LAWS
 489. SUBMITTALS ARE TO BE BROUGHT IN UNDER THE ROOFING
 PERMIT AND ROOFING CONTRACTOR.
  
 2) MISSING FLORIDA COVERSHEET FOR NOA 06-0417.10&
 06-0626.05.PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2007-09-17 Cont ID  
Sent By jwitmer Date 2007-09-17 Time 09:07 Rev Time 0.77
Received By jwitmer Date 2007-09-17 Time 09:05 Sent To  
Notes
2007-09-17 09:09:19LIGHT GAUGE METAL STUD FRAMING. SHOP DRAWINGS, CALCS
 FOR EXTERIOR LIGHT GAUGE FRAMING FILE # 09111-004
  
 SUBMITTAL# 07811-001 SPRAYED FIREPROOFING MATERIAL-
 MONOCOTE
 SUBMITTAL# 07811-002- SPRAYED FIREPROOFING SHOP
 DRAWINGS
 SUBMITTAL# 07811-003 EDGE CONSTRUCTION FIRE PROOFING
 BETWEEN FLOORS
 SUBMITTAL# 20000-0009 UL SYSTEM SLAB EDGE AT CURTAIN
 WALL
 SUBMITTAL# 09111-005 LIGHT GAUGE METAL STUD FRAMING
 SUBMITTAL# 05722-003 BARRIER CABLE RAILING SHOP
 DRAWINGS & CALCS
 SUBMITTAL# 05722-004 BARRIER CABLE RAILING SHOP
 DRAWINGS AND CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2007-09-17 Cont ID  
Sent By jwitmer Date 2007-09-17 Time 08:57 Rev Time 0.33
Received By jwitmer Date 2007-09-17 Time 08:57 Sent To  
Notes
2007-09-17 08:59:46WIND LOAD LETTER 500 YEAR SPEED DIVIDED BY THE SQUARE
 ROOT OF 1.5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status F Date 2007-08-27 Cont ID  
Sent By jwitmer Date 2007-08-27 Time 10:20 Rev Time 3.00
Received By jwitmer Date 2007-08-26 Time 13:01 Sent To  
Notes
2007-08-26 13:28:50BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: BALFOUR BEATTY CONSTRTION
 TEL: (561)718-0935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SHOP DRAWINGREVIEW : DIXIE METAL PRODUCTS
 ACTION: DENIED
  
 SUBMITTAL:
  
 1)SHEET14-1 & 15-2 BOTH INDICATE THE HANDRAIL HAVE
 A CLEARANCE OF 2 1/4", PLEASE CORRECT.
 2004 FBC BUILDING11-4.9.4(3) THE CLEAR SPACE BETWEEN
 HANDRAILS AND WALL SHALLBE 1 1/2".
  
 2) SHEET 15-E1 SECTION A INDICATES 3/8" PICKETS BUT THE
 4 1/2" BETWEEN DOES NOT INDICATE IF THIS IS THE SPACE
 BETWEEN OR CENTER TO CENTER.
 1012.3 OPENING LIMITATIONS. OPEN GUARDS SHALL HAVE
 BALUSTERS OR ORNAMENTAL PATTERNS SUCH THAT A
 4-INCH-DIAMETER (102 MM) SPHERE CANNOT PASS THROUGH ANY
 OPENING UP TO A HEIGHT OF 34 INCHES (864 MM). FROM A
 HEIGHT OF 34 INCHES (864 MM) TO 42 INCHES (1067 MM)
 ABOVE THE ADJACENT WALKING SURFACES, A SPHERE 8 INCHES
 (203 MM) IN DIAMETER SHALL NOT PASS.
 EXCEPTIONS:
 1.THE TRIANGULAR OPENINGS FORMED BY THE RISER,
 TREAD AND BOTTOM RAIL AT THE OPEN SIDE OF A STAIRWAY
 SHALL BE OF A MAXIMUM SIZE SUCH THAT A SPHERE OF 6
 INCHES (152 MM) IN DIAMETER CANNOT PASS THROUGH THE
 OPENING.
  
 3) SHEET 15-E1 SECTION C PICKETS DO NOT PROVIDE ANY
 INFORMATION NOTR DOES THETRIANGLE FORMED BY THE RISE,
 RUN OF STEP AND BOTTOM RAILING MEMBER.
 SEE 1012.3 ABOVE FOR OPENING LIMITATION.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2007-08-26 Cont ID  
Sent By jwitmer Date 2007-08-26 Time 12:33 Rev Time 3.00
Received By jwitmer Date 2007-08-26 Time 09:30 Sent To  
Notes
2007-08-26 12:34:36ARCHITECTURAL REV# 14 & 15OK
 STRUCTURAL REV# 5OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2007-08-22 Cont ID  
Sent By jwitmer Date 2007-08-22 Time 07:09 Rev Time 1.55
Received By jwitmer Date 2007-08-22 Time 07:09 Sent To B
Notes
2007-08-22 07:11:11HARMON CURTAINWALL NOA 04-0217.08 & 04-0217.11

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2007-08-20 Cont ID  
Sent By jwitmer Date 2007-08-20 Time 13:08 Rev Time 0.00
Received By jwitmer Date 2007-08-22 Time 07:09 Sent To PC
Notes
2007-08-20 13:08:27BUILDING PROVISO# 2 OK ALCAN ALUCOBOND PLUS WITH
 ENHANCED FASTENING SYSTEM

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2007-05-10 Cont ID  
Sent By jwitmer Date 2007-05-10 Time 10:17 Rev Time 3.33
Received By jwitmer Date 2007-05-10 Time 10:17 Sent To  
Notes
2007-05-10 14:08:50BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX CONSTRUCTION
 TEL: (561)629-4174
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.REMOVE ALL
 VOID SHEETS FROM ALL PLANS AND PLACE ONE SET
 OF THEM LOOSELY ON TOP OF THE COLLATED PLANS
 TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)SHEET A0.21INDICATES A PLANTER THAT PASSES OVER THE
 PROPERTY LINE.
 3202.2.2 ARCHITECTURAL FEATURES.
 COLUMNS OR PILASTERS, INCLUDING BASES AND MOLDINGS
 SHALL NOT PROJECT MORE THAN 12 INCHES (305 MM). BELT
 COURSES, LINTELS, SILLS, ARCHITRAVES, PEDIMENTS AND
 SIMILAR ARCHITECTURAL FEATURES SHALL NOT PROJECT MORE
 THAN 4 INCHES (102 MM).
  
 3) SHEET A1.06 THE 6TH FLOOR IS INDICATED AS A SINGLE
 FLOOR TENANT THE DOUBLE DOORS ON BOTH THE NORTH AND
 SOUTH SIDE SWING AGAINST THE EGRESS FOR OCCUPANT LOADS
 OF 50 OR MORE. 1008.1.2 DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT
 LOAD OF 50 OR MORE PERSONS
  
 4) SHEET A3.01 REVISION # 10 AT THE 66'-0" LEVEL
 INDICATES A CHANGE IN THE TRIM, THIS SHEET INDICATES
 PRECAST CONCRETE CORNICE TYPICALBUT THE SECTION 4
 SHEET A4.11 INDICATES THE TRIM TO BE EFIS TYPE TRIM
 ABOVE AND BELOW THE 40' MARK TO DATE NO EFIS TRIM HAS
 BEEN SUBMITTED THAT MEET THE NON-COMBUSTIBILITY TEST.
 1406.2.2 ARCHITECTURAL TRIM.
 IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION
 THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS
 SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE
 PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL
 COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN
 EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION
 DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.
 THE VARIANCE GRANTED BY THE CONSTRRUCTION BOARD OF
 ADJUSTMENT AND APPEAL WAS THAT YOU ONLY NEEEDED TO MEET
 THE CODE REQUIREMENT OF 703.4.
 703.4 NONCOMBUSTIBILITY TESTS.
  
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2 , 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE ? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 SHALL
 BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 5) THE OTHER ISSUE THAT I SEE IS IN TERMINOLOGY DETAIL
 4 SHEET A4.11 REVISION# 10 IN THE GARAGE CEILING BEING
 STUCCO ON 5/8" DENSGLASS GOLD, IS THIS FINISH TRUELY
 STUCCO OR AN EFIS FINISH? 106.1.2* ADDITIONAL
 INFORMATION REQUIRED.
  
 6) SHEET A4.12 DETAIL# 1 COMPOSITE ALUMINIUM PANEL
 SYSTEM AT ROOF,A BUILDING PROVISO TO DATE HAS NOT BEEN
 SATISFIED:
 PERMIT:06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX
 TEL: (561) 629-4124
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ALUCOBOND REVIEW
 ACTION: DENIED
 3-19-07
 THE ISSUES WITH THE USE OF ALUCOBOND ON THIS PROJECT IS
 WITH THE WIND PRESSURES NOT FIRE RESISTANCY.
 THE FINAL CLADDING REPORT FROM RWDI REFRENCES FIGURE
 8,12,16 & 20 FOR THE DESIGN OF THE EYEBROW.
 IN REVIEWING THESE PRESSURES AGAIN I BELIEVE THERE IS A
 PROBLEM IN NOT MEETING THE STATED PRESSURES LISTED IN
 THE
 TEST REPORTMIAMI-DADE 00-0802.05. THE FLORIDA COVER
 SHEET BREAKS THE DESIGN PRESSURES OUT BY IF ALUCOBOND
 IS ATTACHED TO A STRUCTURE AND IF THE ALUCOBOND IS
 ATTACHED DIRECTLY TO A PLYWOOD BACKING. SEE THE
 ATTACHED DETAIL TAKEN FROM THE APPROVED PLANS WHERE
 THERE IS NO SOLID BACKING BEHIND THE ALUCOBOND PANEL
 WHICH IS TESTED TO 36PSF NOT NEARLY THE PRESSURES FOUND
 SHEET# 8 OF A RANGE FROM 70 TO 165.
  
 THE SECOND ISSUE WITH THIS SYSTEM WILLSTILL REQUIRE
 ADDITIONAL FASTENERS TO ACHIEVE THE PRESSURES FOUND AT
 THE ROOF TOP LEVELS, THE ENGINEER OF RECORD WILL NEED
 TO SUBMIT THIS INFORMATION
 NOTE ONE SET OF PRODUCT APPROVAL AND RWDI COVERSHEET
 ARE BEING RETAINED.
 PLEASE CONTACT THIS OFFICE IF THERE IS FURTHER
 ASSISTANCE REQUIRED.
  
 7) SHEET A4.14 DETAIL # 3 THE MINIMUM VERTICAL CLEAR
 DISTANCE FOR VAN ACCESSIBLE PARKING IS NOT 96" BUT 98"
 11-4.6.5.
  
 8)SHEET A4.14 DETAILREVISION# 10 INCLUDES A
 SKYLIGHT PLEASE PROVIDE PRODUCT APPROVALS FOR SKYLIGHT
 AND ADDITIONAL INFORMATION ON THE CURBING AND
 ATTACHMENT TO CURB .
  
 9)SHEET A4.21 DETAIL # 1 IS A DETAIL OF THE FRAMING
 FOR THE MCM PANELS REFERS TO STRUCTURAL SHEET S1.17
 DETAIL 1 DOES NOT PROVIDE THE HORIZONTAL FRAMING MEMBER
 INFORMATION
 AS SHOWN ON THE ARCHITECTURAL PLAN. THE SAME S DETAIL
 SHOWN S5.03 AND NO HORIZONTAL FRAMING MEMBERS ARE
 SHOWN?
  
 10) A2.16 ELEVATOR VESTIBULE 1606INDICATES WALL TYPE 6A
 WHICH IS A 1HR RATED WALL BUT DOOR # A1606 ON THE DOOR
 SCHEDULE A8.11INDICATE A REVISION AND THE DOOR RATING
 WAS REMOVED.
  
 11) THERE ARE MANY SHEETS THAT DO NOT INDICATE ANY
 CHANGES BUT WERE SUBMITTED AS A REVISION, PLEASE
 PROVIDE ADDITIONAL INFORMATION WHY THESE SHEETS WERE
 PROVIDED?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2007-05-08 Cont ID  
Sent By jwitmer Date 2007-05-08 Time 14:21 Rev Time 3.33
Received By jwitmer Date 2007-05-08 Time 13:32 Sent To PC
Notes
2007-05-08 14:22:05BUILDING PLAN REVIEW
 PERMIT:06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX
 TEL: (561) 629-4124
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 EFIS TRIM REVIEW: DENIED
  
 THE CONSTRUCTION BOARD OF ADJUSTMENT AND APPEALS
 GRANTED THE USE OF EFIS TRIM AS IS STATED IN THE 2004
 FBC, SECTION 1406.2.2,THAT THE PETIONER WOULD STILL
 NEED TO PROVIDE A PRODUCT THAT MEETS THE REQUIREMENTS
 OF 703.4 THE NON-COMBUSTIBILITY TEST.
  
 703.4 NONCOMBUSTIBILITY TESTS.
  
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2 , 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 SHALL
 BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 THE BOARD REFRENCED ASTM E-84 AS THE STANDARD, THIS
 STANDARD IS TO BE USED WITH COMPOSITE TYPE MATERIALS,
 THAAT IS PUT TOGETHER, OR FORMED FROM DISTINCT PARTS. I
 DO NOT BELIEVE THE EFIS TRIM SYSTEM CAN MEET THIS
 CRITERIA, IT WOULD APPEAR THAT THE NON-COMBUSTIBILITY
 TEST FOR ELEMENTARY MATERIALS ASTM E-136 WOULD BE THE
 TEST REQUIRED FOR THE EFIS TYPE TRIM SYSTEM.
  
 IN THE E-136 REPORT RESULTS (8)
 8.1) REPORT THE MATERIAL AS PASSING THE TEST IF AT
 LEAST THREE OF THE FOUR TEST SPECIMENS MEET THE
 FOLLOWING CONDITIONS:
 8.1.1) THE RECORDED TEMPERATURE OF THE SURFACE AND
 INTERIOR THERMOCOUPLES DO NOT AT ANY TIME DURING THE
 TEST RISE MORE THAN 54 DEGREES ABOVE THE STABILIZED
 TEMPERATURE MEASURED AT T2 PRIOR TO THE TEST. 8.1.2)
 THERE IS NO FLAMING FROM THE SPECIMEN AFTER THE FIRST
 30 SECONDS, AND
 8.1.3) WHEN THE WEIGHT LOSS OF THE SPECIMENDURING THE
 TESTING EXCEEDS 50%, THE RECORDED TEMPERATURE OF THE
 SURFACE AND INTERIOR THERMOCOUPLES DO NOT AT ANY TIME
 DURING THE TEST RISE ABOVE THE FURNACE AIR TEMPERATURE
 AT THE BEGINNING OF THE TEST, AND THERE IS NO FLAMING
 OF THE SPECIMEN.
  
 THE REPORT SUBMITTED IS A TEST FOR FLAMMABILITY, NOT OF
 COMBUSTIBILITY, THE OTHER ISSUE WITH THIS REPORT IS
 THERE IS NO REFERENCE TO EITHERTHE ASTM E-136 OR ASTM
 E-84.
 IN THE TEST RESULTS THE REPORT STATES THERE WAS MOLTEN
 EXPANDED POLYATRRENE DROPLETS FALLING FROM THE TEST
 SPECIMEN. THIS WOULD BE PUTTING THE FIRE FIGHTERS AT
 GREAT RISK!
 THIS IS WHY THE TEST HAS TO INDICATE
 NON-COMBUSTIBILITY!
  
 THE OTHER ISSUE WILL BE TO HAVE THIS PRODUCT PASS THE
 REVIEW THE PLANS WILL ALSO HAVE TO REFLECT THE PRODUCT
 THAT IS BEING PROPOSED, A REVISION. IF THE REVISION IS
 TO INCLUDE THE MOLDING BEING ADHERRED TO THE WALL OR IF
 THE MOLDING IS TO BE PINNED, THEN AGAIN THE DESIGN
 PROFESSIONALS WILL INDICATE THE TYPE OF FASTENING
 SYSTEM TO BE USED. THE BACK UP DATA WILL BE NEEDED FOR
 REVIEW AS WELL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 PLAN REVIEW II - BUILDING
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2007-04-10 Cont ID  
Sent By jwitmer Date 2007-04-10 Time 14:47 Rev Time 4.44
Received By jwitmer Date 2007-04-10 Time 14:47 Sent To FIRE
Notes
2007-05-08 14:18:50BUILDING PLAN REVIEW
 PERMIT:06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX
 TEL: (561) 629-4124
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 EFIS TRIM REVIEW: DENIED
  
 THE CONSTRUCTION BOARD OF ADJUSTMENT AND APPEALS
 GRANTED THE USE OF EFIS TRIM AS IS STATED IN THE 2004
 FBC, SECTION 1406.2.2,THAT THE PETIONER WOULD STILL
 NEED TO PROVIDE A PRODUCT THAT MEETS THE REQUIREMENTS
 OF 703.4 THE NON-COMBUSTIBILITY TEST.
  
 703.4 NONCOMBUSTIBILITY TESTS.
  
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2 , 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 SHALL
 BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 THE BOARD REFRENCED ASTM E-84 AS THE STANDARD, THIS
 STANDARD IS TO BE USED WITH COMPOSITE TYPE MATERIALS,
 THAAT IS PUT TOGETHER, OR FORMED FROM DISTINCT PARTS. I
 DO NOT BELIEVE THE EFIS TRIM SYSTEM CAN MEET THIS
 CRITERIA, IT WOULD APPEAR THAT THE NON-COMBUSTIBILITY
 TEST FOR ELEMENTARY MATERIALS ASTM E-136 WOULD BE THE
 TEST REQUIRED FOR THE EFIS TYPE TRIM SYSTEM.
  
 IN THE E-136 REPORT RESULTS (8)
 8.1) REPORT THE MATERIAL AS PASSING THE TEST IF AT
 LEAST THREE OF THE FOUR TEST SPECIMENS MEET THE
 FOLLOWING CONDITIONS:
 8.1.1) THE RECORDED TEMPERATURE OF THE SURFACE AND
 INTERIOR THERMOCOUPLES DO NOT AT ANY TIME DURING THE
 TEST RISE MORE THAN 54 DEGREES ABOVE THE STABILIZED
 TEMPERATURE MEASURED AT T2 PRIOR TO THE TEST. 8.1.2)
 THERE IS NO FLAMING FROM THE SPECIMEN AFTER THE FIRST
 30 SECONDS, AND
 8.1.3) WHEN THE WEIGHT LOSS OF THE SPECIMENDURING THE
 TESTING EXCEEDS 50%, THE RECORDED TEMPERATURE OF THE
 SURFACE AND INTERIOR THERMOCOUPLES DO NOT AT ANY TIME
 DURING THE TEST RISE ABOVE THE FURNACE AIR TEMPERATURE
 AT THE BEGINNING OF THE TEST, AND THERE IS NO FLAMING
 OF THE SPECIMEN.
  
 THE REPORT SUBMITTED IS A TEST FOR FLAMMABILITY, NOT OF
 COMBUSTIBILITY, THE OTHER ISSUE WITH THIS REPORT IS
 THERE IS NO REFERENCE TO EITHERTHE ASTM E-136 OR ASTM
 E-84.
 IN THE TEST RESULTS THE REPORT STATES THERE WAS MOLTEN
 EXPANDED POLYATRRENE DROPLETS FALLING FROM THE TEST
 SPECIMEN. THIS WOULD BE PUTTING THE FIRE FIGHTERS AT
 GREAT RISK!
 THIS IS WHY THE TEST HAS TO INDICATE
 NON-COMBUSTIBILITY!
  
 THE OTHER ISSUE WILL BE TO HAVE THIS PRODUCT PASS THE
 REVIEW THE PLANS WILL ALSO HAVE TO REFLECT THE PRODUCT
 THAT IS BEING PROPOSED, A REVISION. IF THE REVISION IS
 TO INCLUDE THE MOLDING BEING ADHERRED TO THE WALL OR IF
 THE MOLDING IS TO BE PINNED, THEN AGAIN THE DESIGN
 PROFESSIONALS WILL INDICATE THE TYPE OF FASTENING
 SYSTEM TO BE USED. THE BACK UP DATA WILL BE NEEDED FOR
 REVIEW AS WELL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 PLAN REVIEW II - BUILDING
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-04-10 14:50:31NO REVIEW TOOK PLACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2007-03-19 Cont ID  
Sent By jwitmer Date 2007-03-19 Time 12:43 Rev Time 0.55
Received By jwitmer Date 2007-03-19 Time 12:43 Sent To PC
Notes
2007-03-19 12:44:14BUILDING PLAN REVIEW
 PERMIT:06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX
 TEL: (561) 629-4124
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ALUCOBOND REVIEW
 ACTION: DENIED
 3-19-07
 THE ISSUES WITH THE USE OF ALUCOBOND ON THIS PROJECT IS
 WITH THE WIND PRESSURES NOT FIRE RESISTANCY.
 THE FINAL CLADDING REPORT FROM RWDI REFRENCES FIGURE
 8,12,16 & 20 FOR THE DESIGN OF THE EYEBROW.
 IN REVIEWING THESE PRESSURES AGAIN I BELIEVE THERE IS A
 PROBLEM IN NOT MEETING THE STATED PRESSURES LISTED IN
 THE
 TEST REPORTMIAMI-DADE 00-0802.05. THE FLORIDA COVER
 SHEET BREAKS THE DESIGN PRESSURES OUT BY IF ALUCOBOND
 IS ATTACHED TO A STRUCTURE AND IF THE ALUCOBOND IS
 ATTACHED DIRECTLY TO A PLYWOOD BACKING. SEE THE
 ATTACHED DETAIL TAKEN FROM THE APPROVED PLANS WHERE
 THERE IS NO SOLID BACKING BEHIND THE ALUCOBOND PANEL
 WHICH IS TESTED TO 36PSF NOT NEARLY THE PRESSURES FOUND
 SHEET# 8 OF A RANGE FROM 70 TO 165.
  
 THE SECOND ISSUE WITH THIS SYSTEM WILLSTILL REQUIRE
 ADDITIONAL FASTENERS TO ACHIEVE THE PRESSURES FOUND AT
 THE ROOF TOP LEVELS, THE ENGINEER OF RECORD WILL NEED
 TO SUBMIT THIS INFORMATION
 NOTE ONE SET OF PRODUCT APPROVAL AND RWDI COVERSHEET
 ARE BEING RETAINED.
 PLEASE CONTACT THIS OFFICE IF THERE IS FURTHER
 ASSISTANCE REQUIRED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2007-03-08 Cont ID  
Sent By jwitmer Date 2007-03-08 Time 15:10 Rev Time 0.77
Received By jwitmer Date 2007-03-08 Time 15:10 Sent To PC
Notes
2007-03-08 15:15:01BUILDING PLAN REVIEW
 PERMIT:06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX
 TEL: (561) 629-4124
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ALUCOBOND REVIEW
 ACTION: DENIED
  
 THE ISSUES WITH THE USE OF ALUCOBOND ON THIS PROJECT IS
 WITH THE WIND PRESSURES NOT FIRE RESISTANCY.
 THE FINAL CLADDING REPORT FROM RWDI REFRENCES FIGURE
 8,12,16 & 20 FOR THE DESIGN OF THE EYEBROW.
 IN REVIEWING THESE PRESSURES AGAIN I BELIEVE THERE IS A
 PROBLEM IN NOT MEETING THE STATED PRESSURES LISTED IN
 THE
 TEST REPORTMIAMI-DADE 00-0802.05. THE FLORIDA COVER
 SHEET BREAKS THE DESIGN PRESSURES OUT BY IF ALUCOBOND
 IS ATTACHED TO A STRUCTURE AND IF THE ALUCOBOND IS
 ATTACHED DIRECTLY TO A PLYWOOD BACKING. SEE THE
 ATTACHED DETAIL TAKEN FROM THE APPROVED PLANS WHERE
 THERE IS NO SOLID BACKING BEHIND THE ALUCOBOND PANEL
 WHICH IS TESTED TO 36PSF NOT NEARLY THE PRESSURES FOUND
 SHEET# 8 OF A RANGE FROM 70 TO 165.
  
 THE SECOND ISSUE WITH THIS SYSTEM WILLSTILL REQUIRE
 ADDITIONAL FASTENERS TO ACHIEVE THE PRESSURES FOUND AT
 THE ROOF TOP LEVELS, THE ENGINEER OF RECORD WILL NEED
 TO SUBMIT THIS INFORMATION
 NOTE ONE SET OF PRODUCT APPROVAL AND RWDI COVERSHEET
 ARE BEING RETAINED.
 PLEASE CONTACT THIS OFFICE IF THERE IS FURTHER
 ASSISTANCE REQUIRED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2007-03-08 Cont ID  
Sent By jwitmer Date 2007-03-08 Time 15:08 Rev Time 0.55
Received By jwitmer Date 2007-03-08 Time 15:08 Sent To PC
Notes
2007-03-08 15:09:51REVISIONS:
 A0.20
 A1.02
 A1.03
 A1.04
 A1.05

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-03-01 Cont ID  
Sent By jwitmer Date 2007-03-01 Time 11:40 Rev Time 2.22
Received By jwitmer Date 2007-03-01 Time 11:39 Sent To PC
Notes
2007-03-01 11:45:45BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX
 TEL: (561)629-4174
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2005 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW:
 1) REPORT FROM GEOTECHNICALENGINEER CERTIFYING
 AUGER-CAST PILE
  
 2) AS BUILT SURVEY OF AUGER-CAST PILE
  
 3) BUILDING PROVISO # 3, COMPLIED.
  
 4)BUILDING PROVISO# 4, COMPLIED.
  
 THE BUILDING PROVISO # 2, FROM THE ISSUE DATE *********
 (OVER 60 DAYS)********IS STILL MISSING CONTRACTOR
 SUPPLIED STATE APPROVED
 PRODUCT APPROVALS FOR ALOBOND PLUS THAT WILL MEET THE
 REQUIRED WIND RATING. TO BE REVIEWED
 AND APPROVED BY THE DESIGN PROFESSIONAL BEFORE
 SUBMITANCE TO THE CITY FOR
 REVIEW. REVIEWED FOR FIRE RESISTANCE UNDER FL 2661-R1/
 2001
 NO REPORTS HAVE BEEN SUBMITTED FOR WIND.
  
 1609.1.1 DETERMINATION OF WIND LOADS.
 WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION 6 OF ASCE
 7.EXCEPTION# 2 WIND TUNNEL TEST, THE MCM PANELS MAY
 NEED
 ENHANCED FASTENING FOR THE LOCATION ON THE BUILDING.
 THIS ISTO BE COMPLETED BY THE ENGINEER OF RECORD.
  
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2007-01-19 Cont ID  
Sent By jwitmer Date 2007-01-19 Time 11:37 Rev Time 0.77
Received By jwitmer Date 2007-01-19 Time 11:37 Sent To B
Notes
2007-01-19 11:43:00BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX
 TEL: (561) 718-0935
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTALREVIEW
 ACTION: DENIED
  
 1) THIS IS A THRESHOLD BUILDING REQUIRING (3) SETS OF
 PLANS, REPORTS, AND OR SUBMITTALS.
 REPORTS SUBMITTED BY AN "ENGINEER " REQUIRE ORIGINALS
 NOT COPIES. PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE
 AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND
 AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS,
 FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR
 ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED
 AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-12-07 Cont ID  
Sent By jwitmer Date 2006-12-07 Time 10:32 Rev Time 3.33
Received By jwitmer Date 2006-12-07 Time 10:32 Sent To  
Notes
2006-12-07 10:53:23BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD.
 CONT: CENTEX
 TEL: (561)653-8307
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING REVISIONREVIEW
 ACTION: PROVISO
  
 1) THE ARCHITECTURAL PLANS SUBMITTED APPEAR TO BE CODE
 COMPLIANT. THE BUILDING PROVISO FROM THE ISSUE DATE IS
 STILL
 MISSING CONTRACTOR SUPPLIED STATE APPROVED PRODUCT
 APPROVALS FOR ALOBOND PLUS THAT WILL MEET THE REQUIRED
 FIRE
 RATING AND WIND RATING. TO BE REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL BEFORE SUBMITANCE TO THE CITY
 FOR
 REVIEW.
  
 1407.10 TYPE I, II, III AND IV CONSTRUCTION.
 WHERE INSTALLED ON BUILDINGS OF TYPE I, II, III AND IV
 CONSTRUCTION, MCM SYSTEMS SHALL COMPLY WITH SECTIONS
 1407.10.1 THROUGH 1407.10.4 , OR 1407.11 .
  
 1407.10.1 SURFACE-BURNING CHARACTERISTICS.
 MCM SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25
 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 WHEN
 TESTED AS AN ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED
 FOR USE IN ACCORDANCE WITH ASTM E 84.
  
 1609.1.1 DETERMINATION OF WIND LOADS.
 WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION 6 OF ASCE
 7.EXCEPTION# 2 WIND TUNNEL TEST, THE MCM PANELS MAY
 NEED
 ENHANCED FASTENING FOR THE LOCATION ON THE BUILDING.
 THIS ISTO BE COMPLETED BY THE ENGINEER OF RECORD.
  
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-12-04 Cont ID  
Sent By jwitmer Date 2006-12-04 Time 11:41 Rev Time 1.10
Received By jwitmer Date 2006-12-04 Time 11:41 Sent To PC
Notes
2006-12-04 12:07:193'-0"X 7'-0"DOOR 04-0604.02

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-11-15 Cont ID  
Sent By jwitmer Date 2006-11-15 Time 13:27 Rev Time 0.55
Received By jwitmer Date 2006-11-15 Time 13:27 Sent To PC
Notes
2006-11-15 13:44:25BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD.
 CONT: CENTEX CONST
 TEL: (561)629-4174
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO # 4:REVIEW
 ACTION: DENIED
  
 1 )W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-31 Cont ID  
Sent By jwitmer Date 2006-10-31 Time 15:10 Rev Time 2.22
Received By jwitmer Date 2006-10-31 Time 15:10 Sent To PC
Notes
2006-10-31 15:15:12 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 06040957
 ADDRESS: 525 OKEECHOBEE BLVD.
 CONT: CENTEX CONSTRUCTION
 TELL # (954)214-9415
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET
 OF PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 BUILDING PROVISO:
 1)A SEPERATE PERMIT WILL BE REQUIRED FOR THE NORTH
 ELEVATOR TOWER, A ISSUED PERMIT & PLANS TO BE REQUIRED
 WITHIN 60DAYS.
  
 2) PLANS ARE TO BE REVISED TO INDICATE A PRODUCT OTHER
 THAN MCM PANELS,
 A 60 DAY PERIOD WILL BE PROVIDED FOR THE CONTRACTOR AND
 DESIGN TEAM
 TO REVIEW THE NEW PRODUCT FOR CODE COMPLIANCE FOR FIRE
 AND WIND.
 12-04-06 CITY HAS FL APPROVAL FOR FIRE RESISTANCE FL
 2661-R1 ALUCOBOND PLUS.
  
 3) PLANS ALSO INDIICATE THE USE OF ALUMINUM EXTRUSIONS,
 SHOP DRAWING
 WILL BE REQUIRED INDICATING THE SIZE, AND CONDITIONS
 FOR ANCHORING OF PANELS.
 SHOP DRAWINGS FOR ALUMINIUM EXTRUSIONS REVIEWED 3-01-07
 JW
  
  
 4) PRODUCT APPROVALS A 60 DAY PERIOD OF TIME WILL BE
 PROVIDED FOR THE
 CONTRACTOR & DESIGN TEAM TO SUBMIT PRODUCT APPROVALS
 FOR HOLLOW METAL DOORS
 THAT WILL MEET THE LARGE MISSLE IMPACT IF REQUIRED, AND
 WIND.
 12-04-06 COMPLIED MIAMI-DADE 04-0604.02
  
 5) 12-04-06 CITY IS IN RECEIPT OF SIGNED & SEALED WIND
 REPORT. THE WIND STUDY REPORT SUBMITTED IS NOT SIGNED
 NOR SEALED.
 IF THE 3 SETS OF WIND REPORTS
 SIGNED AND SEALED ARE NOT SUBMITTED FOR PUBLIC RECORD
 WITH
 IN A WEEK THE WIND CALCULATIONS WILL NEED TO BE
 ADDRESSED UNDER ASCE 7-02. BUILDING PLAN REVIEW JIM
 WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-27 Cont ID  
Sent By jwitmer Date 2006-10-27 Time 10:48 Rev Time 7.77
Received By jwitmer Date 2006-10-27 Time 10:48 Sent To  
Notes
2006-10-27 12:46:07BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX CONSTRUCTION
 TEL: (954)214-9415
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ---CITY PLACE OFFICE TOWER---
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) SHEET A0.20:
 2A) NORTH ELEVATOR TOWER COMPLIANCE:
 COMMENT# 10A FROM THE PREVIOUS REVIEW,
 ALTHOUGH THE NORTH ELEVATOR TOWER IS IN
 THIS SET OF DOCUMENTS, A SEPERATE PERMIT
 WILL BE REQUIRED.
  
 2B) SHEET A0.20 CODE COMPLIANCE NOTE# 6
 FOR THE NORTH ELEVATOR TOWER INDICATES THAT THE
 EXISTING
 PARKING GARAGE IS NOT FIRE SPRINKLERED, THIS IS
 INCORRECT.
 THE B-BLOCK STORES AND PARKING GARAGE ARE CONSIDERED
 ONE
 BUILDING FOR THE AREA INCREASES TAKEN UNDER THE
 ORIGINAL PERMIT THIS WAS A REQUIREMENT.
  
 3) 3RD REQUEST, COMMENT# FROM THE PREVIOUS
 REVIEW, A4.11 ELV 42'-0",A4.12 SOUTH WALL SECTION,
 EL. 66'-6",A4.13 &
 A4.14 INDICATES THE USE OF EFIS TRIM ON
 THE EXTERIOR OF THE BUILDING.1406.2.2 ARCHITECTURAL
 TRIM. IN BUILDINGS OF TYPE
 I, II, III AND IV CONSTRUCTION THAT DO
 NOT EXCEED THREE STORIES OR 40 FEET (12
 192 MM) IN HEIGHT ABOVE GRADE PLANE,
 EXTERIOR WALL COVERINGS SHALL BE
 PERMITTED TO BE CONSTRUCTED OF WOOD
 WHERE PERMITTED BY SECTION 1405.4 OR
 OTHER EQUIVALENT COMBUSTIBLE MATERIAL.
 COMBUSTIBLE EXTERIOR WALL COVERINGS,
 OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR
 EXTERIOR INSTALLATION, SHALL NOT EXCEED
 10 PERCENT OF AN EXTERIOR WALL SURFACE
 AREA WHERE THE FIRE SEPARATION DISTANCE
 IS 5 FEET (1524 MM) OR LESS.
 ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET
 (12 192 MM) IN HEIGHT ABOVE GRADE PLANE
 SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE
 SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.
  
 4A) COMMENT # 23 FROM THE PREVIOUS REVIEW,
 A4.1.2 PLANS INDICATE USE OF MCM
 ( METAL COMPOSITE MATERIALS) SEE:
 1407.3 ARCHITECTURAL TRIM AND
 EMBELLISHMENTS.
 MCM USED AS ARCHITECTURAL TRIM OR
 EMBELLISHMENTS SHALL COMPLY WITH
 SECTIONS 1407.7 THROUGH 1407.13 .
 1407.10 TYPE I, II, III AND IV
 CONSTRUCTION.
 WHERE INSTALLED ON BUILDINGS OF TYPE I,
 II, III AND IV CONSTRUCTION, MCM SYSTEMS
 SHALL COMPLY WITH SECTIONS 1407.10.1
 THROUGH 1407.10.4 , OR 1407.11 .
  
 WE HAVE RECEIVED A COPY OF THE MIAMI-DADE NOA, WHICH
 INDICATES IN THERE TECHNICAL SHEETS THIS PRODUCT DOES
 HAVE A COMBUSTIBLE PLASTIC CENTER PANEL.THE CODE
 COMMENTARY READS UNDER ARTICLE 1407.3 REFERSYOU BACK
 TO 1406.2.2, COMBUSTIBLE TRIM ON BUILDINGS OVER 40'-0"
 TALL CAN NOT BE USED ABOVE 40'-0".
  
 1407.10.1 INDICATES WHAT TYPE OF MCM PANELS ARE ALLOWED
 ON A TYPEI BUILDING.
 1407.11.1 WHAT TYPE MCM PANELS ARE ALLOWED TO THE
 HEIGHT OF 40'-0".
 1407.11.2 WHAT IS ALLOWABLE TO A HEIGHT OF 50'-0".
  
 4B) DETAIL 25/ A5.47 INDICATES THE USE OF ALUMIMUM
 EXTRUSIONS, THIS WILL
 BE ALLOWABLE AS SHOWN, NOT HAVING A PLASTIC CENTER
 PANEL. BUILDING PROVISO:
 SHOP DRAWINGS WILL BE REQUIRED INDICATING SIZE AND
 CONDITIONS FOR ANCHORING PANELS.
  
 5 COMMENT#24 FROM THEPREVIOUS REVIEW, THIRD REQUEST,
 TO DELETE THE PHRASE "SYNTHETIC TYPE DIRECTAPPLIED
 FINISH SYSTEM OVER GLASS MAT GYPUM SHEATHING."A4.14
 DETAILS INDICATE A COVERED DROP OFF AREA WITH THE USE
 OF THE WORDAGE ABOVE,
 THIS HAS BEEN CHANGED BUT THE FINISH SYSTEM IS NOT
 PROVIDED.
 DETAIL7/ A4.21 DOES
 USE THE PHRASE AS STATED ABOVE, WE CONSIDER THIS AN
 EFIS
 SYSTEM, PROVIDE REPORT WITH APPROVED HORIZONTAL USEAGE.
 RULE 9B-72 FL
 ADDMINISTRATIVE COVE. WHEN USED IN A HORIZONTAL PLANE
 THE PRODUCT HAS TO INDICATE SUCH USAGE.
  
 6)COMMENT 34D) FROM THE PREVIOUS REVIEW,
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG.
 NO REPORT WAS SUBMITTED FOR EXTERIOR
 HOLLOW METAL DOORS, SINGLE NOR PAIRS.
  
 EXTERIOR GLAZED DOORS:YKK DOORS NEITHER THE LARGE
 MISSLE OR SMALL MISSLE REPORTS HAVE
 THE GLASS TYPE NOR MULLIONS HIGHLIGHTED.
  
 CORNELL IRONWORKS: NONE OF THE SUBSYSTEMS
 ARE HIGHLIGHTED INDICATING WHICH SYSTEM WILL
 BE USED FOR THIS PROJECT.
  
 LOUVER : THE REPORT SUBMITTED HAS LOW
 PRESSURESCOMPARED
  
 TO THE WIND TUNNEL TEST.
  
 EFIS REPORT MISSING THIS REPORT TOTALLY.
  
 ROOFING ASSEMBLIES: HIGHLIGHT WHICH SUBSYSTEM YOU WILL
 BE INSTALLING.
 SEE LIMITATION# 7 IF ENHANCED FASTENING WILL BE
 REQUIRED. IF REQUIRED
 USE RAS 117 FOR CALCULATIONS. PROVIDE CALCULATIONS.
 THE ROOFING REPORTSUBMITTED FL 1075 SIPLAST / I COPAL
 THE HIGHLIGHTED SUBSYSTEM (SBS)FOR CONCRETE DECKS HAS
 LOW PRESSURES AND LIMITATION # 9, NO ENHANCED
 FASTENING.
 ALSO THE SUBSYSTEM FOR STEEL DECKS ALSO HAS LOW
 PRESSURE AND LIMITATION #9, NO ENHANCED FASTENING
 ALLOWED.
  
 7) THE WIND STUDY REPORTCOMPLETED BY RWDI IS NOT A
 FINAL REPORT ONLY A DRAFT.
 THE CITY WILL NEED 3 FINAL REPORTS SIGNED AND SEALED.
  
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8) NOTE ALSO A COMMENT FROM FIRE DEALING WITH AREAS OF
 THE BUILDING THAT ARE NOT FIRE SPRINKLERED,
 IF THE BUILDING IS NOT EQUIPPED THROUGHOUT WITH A
 AUTOMATIC FIRE SPRINKLER IN ACCORDANCE WITH 903.3.1.1
 THEN
 THE REQUIREMENTS 704.9, FIGURE 709.4.1 FOR SPANDREL
 GIRDERS . SUCH OPENINGS SHALL BE SEPERATED VERTICALLY
 AT 3 FT BY SPANDREL GIRDERS, EXTERIOR WALLS OR OTHER
 ASSEMBLIES THAT HAVE A FIRE RESISTANCE RATING OF AT
 LEAST 1 HR.
 WEST PALMBEACH
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-31 Cont ID  
Sent By jwitmer Date 2006-07-31 Time 09:33 Rev Time 12.22
Received By jwitmer Date 2006-07-31 Time 09:32 Sent To  
Notes
2006-07-31 00:00:00#

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-02 Cont ID  
Sent By jwitmer Date 2006-06-02 Time 11:41 Rev Time 32.00
Received By jwitmer Date 2006-06-02 Time 11:41 Sent To  
Notes
2006-06-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX CONSTRUCTION
 TEL: (954)214-9415
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ---CITY PLACE OFFICE TOWER---
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) LANDSCAPE PLANS ARE MISSING THE
 SIGNATURE, DATE AND RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3)LANDSCAPE ARCHITECT DSBOCA IS MISSING:
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 4) ROBERT J. MCNAMARA PE SEAL INDICATES
 THE WORD "CERTIFICATE" SEE:
 RULE 61G155-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARENCE
 OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 5) ROBERT J. MCNAMARA PE SIGNATURE IS A
 COPY OR STAMP.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
  
 6) COMMENT# 5 OF FOUNDATION PERMIT,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) COMMENT# 7 FROM FOUNDATION PERMIT,
 WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
  
 8) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S,
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 9) DISCREPANCY BETWEEN THE SKETCH OF
 SURVEY AND THE TAX MAPS AS FAR AS THE
 PROPERTY LINE. TAX MAPS INDICATE LOT 2
 ACTUALLY WRAPPING AROUND THE WEST SIDE
 OF THE "B BLOCK PARKING GARAGE" AND A
 3'-0" SEPERATION BETWEEN THE EXISTING
 PARKING GARAGE AND LOT# 2 JUST TO THE
 SOUTH OF PARKING GARAGE. SUBMIT NOT A
 SCKETH BUT AN ACTUAL SURVEY OF THE
 PROPERTY LINE.
  
 10A) DEPENDING ON THE LOCATION OF THE
 NORTH PROPERTY LINE (SURVEY) TWO PERMIT APPLICATIONS,
 PERMITS AND ASSOCIATED
 FEES, MAY BE NECESSARY. IT APPEARS THAT
 THE ELEVATOR WHICH IS AN ADDITION TO THE
 FIVE STORY PARKING GARAGE AND THE
 GENERATOR JUST TO THE WEST OF THE
 PARKING GARAGE ARE LOCATED ON ANOTHER
 PROPERTY.
  
 10B) ADDITIONAL INFORMATION REQUIRED, IT
 APPEARS THERE ARE (3) GENERATORS, ONE
 LOCATED IN THE NEW 16 STORY OFFICE TOWER
 ROOM# 126 AND THE (2) GENERATOR LOCATED
 WEST OF THE NEW PARKING GARAGE ELEVATOR,
 WHAT IS THESE GENERATORS TO POWER?
  
 11) PROVIDE RATIONALE FOR PARKING GARAGE
 LEVELS 2-5 TO USE ELEVATOR 7 & 8 TO THE
 FIRST FLOOR AND TRANSFER TO ELEVATORS
 1-6 TO GAIN ACCESS TO THE OFFICE TOWER
 SECTION OF BUILDING?
  
 12A) A1.02-A1.05 DISABLED PARKING SPACES 11-4.6.2(1)
 ALL SPACES MUST BE
 LOCATED ON AN ACCESSIBLE ROUTE NO LESS
 THAN 44 INCHES (1118 MM)WIDE SO THAT
 USERS WILL NOT BE COMPELLED TO WALK OR
 WHEEL BEHIND PARKED VEHICLES.
  
 12B) THERE ARE (2) ISSUES ABOVE THE
 FIRST IS A 44" CONTINIOUS ACCESSIBLE
 PATH THE AREA MARKED AS A PATHWAY IN
 FRONT OF THE ELEVATORS IS APPROXIMATELY
 24".
 THE SECOND ISSUE IS THE DISABLED ARE
 COMPLLLED TO WALK OR WHEEL BEHIND PARKED VEHICLES.
  
 13)A1.01 THE EXIT PASSAGE WAY # 122
 DOESN'T TAKE YOU FROM THE EXIT DISCHARGE
 TO THE PUBLIC WAY. A0.22 THE LIFE SAFETY
 PLAN DOESN'T PROVIDE ANY INFORMATION
 ONCE YOU LEAVE THE PROTECTED EXIT.EXIT
 DISCHARGE. THAT PORTION OF A MEANS OF
 EGRESS SYSTEM BETWEEN THE TERMINATION OF
 AN EXIT AND A PUBLIC WAY.
  
 13A) THE MEANS OF EGRESS 44" FOR EXIT
 PASSAGE WAY# 122 STOPS ON EACH SIDE OF
 THE ENTRY FEATURE AREA, SEE CURB LINE.
 NEITHER THE LIFE SAFETY NOR THIS SHEET
 PROVIDES A CONTINIOUS PATH TO THE PUBLIC
 WAY.
  
 13B) A1.01 LOCATED JUST TO THE WEST OF
 THE MAIN ENTRY PLANS INDICATE A
 HANDICAPPED RAMP BUT TOTALLY MISS THE
 REQUIRED PASSENGER LOADING ZONE.
 11-4.1.2(5)(C) IF PASSENGER LOADING
 ZONES ARE PROVIDED, THEN AT LEAST ONE
 PASSENGER LOADING ZONE SHALL COMPLY WITH
 SECTION 11-4.6.6
 .
 11-4.1.2(5)(E) VALET PARKING. VALET
 PARKING FACILITIES SHALL PROVIDE A
 PASSENGER LOADING ZONE COMPLYING WITH
 SECTION 11-4.6.6 LOCATED ON AN
 ACCESSIBLE ROUTE TO THE ENTRANCE OF THE
 FACILITY. SECTION 11-4.1.2 (5)(A),
 SECTION 11-4.1.2 (5)(B), AND SECTION
 11-4.1.2 (5)(D) OF THIS SECTION DO NOT
 APPLY TO VALET PARKING FACILITIES.
  
 11-4.6.6 PASSENGER LOADING ZONES.
 PASSENGER LOADING ZONES SHALL PROVIDE AN
 ACCESS AISLE AT LEAST 60 INCHES (1525
 MM) WIDE AND 20 FEET (6096 MM) LONG
 ADJACENT AND PARALLEL TO THE VEHICLE
 PULL-UP SPACE (SEE FIGURE 11-10 ). IF
 THERE ARE CURBS BETWEEN THE ACCESS AISLE
 AND THE VEHICLE PULL-UP SPACE, THEN A
 CURB RAMP COMPLYING WITH SECTION 11-4.7
 SHALL BE PROVIDED. VEHICLE STANDING
 SPACES AND ACCESS AISLES SHALL BE LEVEL
 WITH SURFACE SLOPES NOT EXCEEDING 1:50
 (2 PERCENT) IN ALL DIRECTIONS.
  
 13C) ALTHOUGH THE EXISTING PARKING
 GARAGE SHOULD BE UNDER A SEPERATE PERMIT
  
 COMMENTS WILL BE ADDRESSED AT THIS TIME
 UNDER THIS PERMIT. ONCE THE PASSENGER
 LOADING ZONE IS PROVIDED AND ACCESS
 AISLE AND CROSS WALK AND CURB CUT
 LEADING TO THE ELEVATOR TOWER NEEDS TO
 BE ADDRESSED, MAKING THIS AN ACCESSIBLE
 ELEMENT.
  
 13D)NOTE: THE CODE SUMMARY OF THE "B"
 BLOCK PARKING GARAGE INDICATES A
 BUILDING TYPE "IB" WHEREAS THE RETAIL
 STORES AND PARKING STRUCTURE ARE
 CONSIDERED ONE STRUCTURE NOT (2)
 INDIVDUAL BUILDINGS, THEY WERE PERMITTED
 THIS WAY FOR PHASING ONLY. AGAIN
 DEPENDING ON THE LOCATION OF THE
 PREOPERTY LINE THERE MAY BE ISSUES WITH
 THE PARKING GARAGE ADDITION OF THE
 ELEVATOR AND TABLE 602!
  
 13E)THE EXIT PASSAGEWAY 122 HAS A 2 HR
 RATING LEADING UPTO DOOR 122A WITH A
 1 1/2 HR FIRE RATING.THE LIFE SAFETY
 PLAN ENDS THE FIRE RATING OF THE
 SURROUNDINGWALLS AND DOOR 120A TO THE
 FIRE PUMP ROOM(SHEET A2.01B) THERE IS NO
 RATING. TRUE YOU HAVE REACHED THE
 EXTERIOR OF THE BUILDING BUT THERE IS
 FIRE DANGER FROM THE FIRE PUMP ROOM AND
 THE WALLS JUST TO THE LEFT AS WELL AS
 THE WALLS TO THE RIGHT WHERE THE FIRE
 PUMP ROOM IS SITUATED. THIS IS SIMILAR
 TO A EXIT COURT ALTHOUGH THERE IS STILL
 A CEILING OVER THE PATH OF TRAVEL.
  
 13F) E1.01A INDICATES OVERHEAD
 CONDUCTORS PASSING DIRECTLY OVER THE
 EXIT PASSAGEWAY 122.1019.1.2
 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH
 AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT
 FOR REQUIRED EXIT DOORS, EQUIPMENT AND
 DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION AND ELECTRICAL
 RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M 2 ). SUCH
 PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 712 . THERE
 SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 13G) IT APPEARS THAT THERE IS (2) SETS
 OF CARD READERS TO GAIN ENTRANCE TO THE
 PARKING GARAGE. THE FIRST AT THE FOOT OF
 THE RAMP AND A SECOND SET INDICATED ON
 A1.02? PROVIDE DETAILS?
  
 14) A2.01A PLANS INDICATE SECURITY
 TURNSTILES, 11-4.13.2 REVOLVING DOORS
 AND TURNSTILES . 11-413.2(1)
 TURNSTILES SHALL NOT BE THE ONLY MEANS
 OF PASSAGE AT AN ACCESSIBLE ENTRANCE OR
 ALONG AN ACCESSIBLE ROUTE. AN ACCESSIBLE
 GATE OR DOOR SHALL BE PROVIDED ADJACENT
 TO THE TURNSTILE OR REVOLVING DOOR AND
 SHALL BE SO DESIGNED AS TO FACILITATE
 THE SAME USE PATTERN.
  
 15) A2.01A WALL DETAIL 8B OR 8C SEE UL
 LISTING U415 MISSING ITEM# 7
 CEMENTITIOUS BACKER UNITSSYSTEM "D" NOM
 1/2 OR 5/8". PROVIDE ADDITIONAL INFO. ON
 SCHEDULE SHEET A).31
  
 16) A2.01 WALL DETRAIL# 1 INDICATES THE
 USE OF A 2 HR RATED BLOCK UL LISTING
 U-905, THE FIVE LISTED BLOCK
 MANUFACTURERS WILL BE THE MANUFACTURERS
 THE BLOCK IS TO BE PURCHASED FROM.
 OTHERWISE PROVIDE THEEQUIVALENT
 THICKNESS FROM THE BLOCK MANUFACTURER
 FROM WHICH THE BLOCK WILL BE PRODUCED,
 SEE TABLE 721.3.2. 721.3.2 CONCRETE
 MASONRY WALLS.
 THE FIRE-RESISTANCE RATING OF WALLS AND
 PARTITIONS CONSTRUCTED OF CONCRETE
 MASONRY UNITS SHALL BE DETERMINED FROM
 TABLE 721.3.2 . THE RATING SHALL BE
 BASED ON THE EQUIVALENT THICKNESS OF THE
 MASONRY AND TYPE OF AGGREGATE USED.
  
 17) A2.01 ALL OF THE NON-RATED DRYWALL
 WALLS INDICATED ON A0.31 HAVE NO HEIGHT LIMITATIONS NOR
 SPACING, SEE T2506.2
 STEEL STUDS NON-LOAD BEARING, ASTM
 C-645.
  
 18A) A2.01B ROOM 115 THE DOOR SWING,
 SWINGS INTO THE CLEAR FLOOR SPACE OF THE
 LAVATORY.11-4.19.3 CLEAR FLOOR SPACE .
 A CLEAR FLOOR SPACE 30 INCHES BY 48
 INCHES (760 MM BY 1219 MM) COMPLYING
 WITH SECTION 11-4.2.4 SHALL BE PROVIDED
 IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL
 ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES
 (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 11-32 ).
  
 18B) PROVIDE CUT SECTION THROUGH SINK
 ROOM 118. 11-4.24.2 SINKS, HEIGHT. SINKS
 SHALL BE MOUNTED WITH THE COUNTER NO
 HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 18C) EMERGENCY GENERATOR ROOM EXHAUST
 BLOWS DIRECTLY ON TO HANDICAPPED RAMPS
 LOCATED JUST EAST OF UNIT, IS THERE AIR DEFLECTION?
  
 18D) RESTROOM 103 IS MISSING THE
 REQUIRED CLEAR FLOOR SPACE 11-4.19.3.
  
 19) A1.06
 19A) PLANS INDICATE THIS PERMIT IS FOR A
 SHELL BUILDING, FLOORS TO BE BUILT OUT
 BY FUTURE TENANTS. LOOKING AT WORCST
 CASE OCCUPANT LOAD FOR THIS FLOOR THERE
 WILL BE PROBLEMS WITH THE CONFERENCE
 ROOM AND IF THE ROOF DECK IS CONSIDERED
 AN ASSEMBLY AREA. IF THE CONFERENCE ROOM
  
 IS FIGURED AT AN OCCUPANT LOAD OF 15SQ
 FT PER OCC= 309 OK FOR DOORS &
 STAIRWAYS.
 THE PROBLEM BEGINS IF THE CONFERENCE
 ROOM IS FIGURED AT A CONCENTRATION OF
 7SQ FT / OCC. OR IF THE ROOF AREA JUST
 WEST OF THE CONFERENCE ROOM WERE TO BE
 CONSIDERED AS PART OF THE ASSEMBLY AREA.
 THEN USING AN OCC LOAD OF 15 SQ FT /OCC
 THE LOAD FOR THE ROOFDECK ALONE IS 472+
 98( CONFERENCE ROOM) 211 (REMAINDER OF
 FLOOR) =781 OCC LOAD. NEITHER THE
 STAIRS NOR DOORWAYS WILL HANDLE THIS
 LOAD AS CONFIGURED.
  
 19B) IF PLANS ARE NOT RECONFIGURED TO
 HANDLE THIS ADDITIONAL OCCUPANT LOAD, A STIPULATION
 WILL BE PUT ON THE
 CERTIFICATE OF OCCUPANCYSTATING THAT
 THE ROOF DECK CAN NOT BE USED AS AN
 ASSEMBLY AREA. 110.2* W. P. B.
 ADMINISTRATIVE CODE, INFORMATION THAT IS
 REQUIRED FOR RECORD KEEPING & FOR
 CERTIFICATE OF OCCUPANCY:
 (F) ANY SPECIAL STIPULATIONS &
 CONDITIONS OF THE BUILDING PERMIT.
  
 19C) IF THE ROOFED AREA IS TO BE FIGURED
  
 AS AN ASSEMBLY AREA, THERE NEEDS TO BE
 ADDTTIONAL DOOR WAYS SINCE AN OCCUPANT
 LOAD GREATER THAN 50.1004.8 OUTDOOR
 AREAS.
 YARDS, PATIOS, COURTS AND SIMILAR
 OUTDOOR AREAS ACCESSIBLE TO AND USABLE
 BY THE BUILDING OCCUPANTS SHALL BE
 PROVIDED WITH MEANS OF EGRESS AS
 REQUIRED BY THIS CHAPTER. THE OCCUPANT
 LOAD OF SUCH OUTDOOR AREAS SHALL BE
 ASSIGNED BY THE BUILDING OFFICIAL IN
 ACCORDANCE WITH THE ANTICIPATED USE.
 WHERE OUTDOOR AREAS ARE TO BE USED BY
 PERSONS IN ADDITION TO THE OCCUPANTS OF
 THE BUILDING, AND THE PATH OF EGRESS
 TRAVEL FROM THE OUTDOOR AREAS PASSES
 THROUGH THE BUILDING, MEANS OF EGRESS
 REQUIREMENTS FOR THE BUILDING SHALL BE
 BASED ON THE SUM OF THE OCCUPANT LOADS
 OF THE BUILDING PLUS THE OUTDOOR AREAS. EXCEPTIONS: 1.
 OUTDOOR AREAS USED EXCLUSIVELY
 FOR SERVICE OF THE BUILDING NEED ONLY
 HAVE ONE MEANS OF EGRESS.
  
 19D) IF THE ROOF AREA IS CONSIDERED A
 ASSEMBLY AREA THE OCCUPANT LOAD FOR THE
 FLOOR WOULD BE APPROX 781 REQUIRING A
 THIRD EXIT. TABLE 1018.1.
  
 19E) A2.06 THIS COMMENT WILL HOLD TRUE
 FOR MORE DOORS THAN JUST THESE
 MENTIONED. S-1/A STAIRDOOR, S-2/A
 STAIRDOOR, 605A MECHANICAL & 606A
 EXECUTIVE VESTIBULE. ALL THESE DOORWAYS
 ARE APPROXIMATELY 21" DEEP. THE WAY THE
 DOORS ARE CONFIGURED A PERSON IN A
 WHEELCHAIR CAN NOT APPROACH THE DOORS
 WITH THE DOOR BEING RECESSED IN THE
 DOORWAY ON THE PULLSIDE. IT IS TRUE
 11-4.13.5 THAT DOOR OPENINGS MAY BE 24"
 DEEP, THE DOORWAY SHOWN AS AN EXAMPLE
 FIGURE 24 IS A CASED OPENING NO DOOR IS
 APPERANT.11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARENCES AT
 DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARENCES
 SHALL BE CLEAR & LEVEL.
  
 20) A1.06- A1.16NOTE SEE ELETRICAL
 COMMENT FOR ELECTRICAL ROOM WITHIN
 TENANT SPACE. UNLESS TENANT OCCUPIES THE
 FULL FLOOR THIS IS A CODE ISSUE.
  
 21) SHEET A4.11 DETAIL# 4, AT VARIOUS
 LEVELS INDICATES EITHER PRECAST UNITS OR
  
 SPANDREL GLASS PANELS AT THE FLOOR
 LEVELS.
 21A) PRECAST PANELS INDICATE VARING
 HEIGHTS FROM THE FLOOR TO THE TOP OF
 PANEL, SOME ARRE 2'-0" OTHERS 2'-6", SEE
 A11.04 DESIGN # CEF 158 P, (G) THE
 CONCRETE WALL PANEL ARE TO BE A MINIMUM
 33" ABOVE THE FLOOR LEVEL.
  
 21B) SPANDREL GLASS PANELS ARE MISSING
 INSULATION AT GAGARGE LEVLE, SEE SHEET
 A11.04 DESIGN# CEJ 116 P NOTE "B" THAT
 THE 33" IS FROM THE FLOOR TOTHE BOTTOM
 OF THE TRANSOM.
  
 22) A4.12 SOUTH WALL SECTION A4.13 &
 A4.14 INDICATES THE USE OF EFIS TRIM ON
 THE EXTERIOR OF THE BUILDING.1406.2.2 ARCHITECTURAL
 TRIM. IN BUILDINGS OF TYPE
 I, II, III AND IV CONSTRUCTION THAT DO
 NOT EXCEED THREE STORIES OR 40 FEET (12
 192 MM) IN HEIGHT ABOVE GRADE PLANE,
 EXTERIOR WALL COVERINGS SHALL BE
 PERMITTED TO BE CONSTRUCTED OF WOOD
 WHERE PERMITTED BY SECTION 1405.4 OR
  
 OTHER EQUIVALENT COMBUSTIBLE MATERIAL.
 COMBUSTIBLE EXTERIOR WALL COVERINGS,
 OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR
 EXTERIOR INSTALLATION, SHALL NOT EXCEED
 10 PERCENT OF AN EXTERIOR WALL SURFACE
 AREA WHERE THE FIRE SEPARATION DISTANCE
 IS 5 FEET (1524 MM) OR LESS.
 ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET
 (12 192 MM) IN HEIGHT ABOVE GRADE PLANE
 SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE
 SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.
  
 23) A4.1.2 PLANS INDICATE USE OF MCM
 ( METAL COMPOSITE MATERIALS) SEE:
 1407.3 ARCHITECTURAL TRIM AND
 EMBELLISHMENTS.
 MCM USED AS ARCHITECTURAL TRIM OR
 EMBELLISHMENTS SHALL COMPLY WITH
 SECTIONS 1407.7 THROUGH 1407.13 .
 1407.10 TYPE I, II, III AND IV
 CONSTRUCTION.
 WHERE INSTALLED ON BUILDINGS OF TYPE I,
 II, III AND IV CONSTRUCTION, MCM SYSTEMS
 SHALL COMPLY WITH SECTIONS 1407.10.1
 THROUGH 1407.10.4 , OR 1407.11 .
  
 24) A4.14 DETAILS INDICATE A COVERED
 DROP OFF AREA WITH THE USE OF EFIS
 SYSTEM, PROVIDE REPORT WITH APPROVED
 HORIZONTAL USEAGE. RULE 9B-72 FL
 ADDMINISTRATIVE COVE.
  
 25) A4.15 FLOOR INSULATION THE 6TH FLOOR
 (LAST FLOOR ABOVE PARKING GARAGE),
 PROVIDE WHAT TYPE OF SPRAY ON FLOOR
 INSULATION WILL BE USED, ALSO WILL THIS
 BE THE SAME FIRE PROOFING MATERIAL
 REQUIRED FOR FLOORS AND BEAMS? IF SO
 DOES THIS MATERIAL HAVE FIRE RATING? 13-405.1.C.1.1.
 FOR FLOORS WITH BEAMS THAT EXTEND BELOW
 THE FLOOR SLAB, THE FLOOR SHALL BE
 INSULATED EITHER ON THE INTERIOR ABOVE
 THE SLAB OR ON THE EXPOSED FLOOR AND ALL
 EXPOSED SURFACES OF THE BEAMS THAT
 EXTEND 24 INCHES (610 MM) AND LESS BELOW
 THE EXPOSED FLOOR.
  
 26) A4.21 DETAIL# 7, INDICATES A
 EXTERIOR SOFFIT DETAIL, NOTE SEE
 STRUCTURAL DRAWINGS FOR UPLIFT
 REQUIREMENTS, STRUCTURAL S0.01 LIGHT
 GAUGE STEEL FRAMING NOTE DOESN'T PROVIDE
  
 ANY REQUIREMENTS NOR SIZE, GAUGE OF
 STEEL, CONFIGURATION SPAN SPACING OR LOADING.2506.2
 STANDARDS.
 GYPSUM BOARD MATERIALS SHALL CONFORM TO
 THE APPROPRIATE STANDARDS LISTED IN
 TABLE 2506.2 AND CHAPTER 35 AND, WHERE
 REQUIRED FOR FIRE PROTECTION, SHALL
 CONFORM TO THE PROVISIONS OF CHAPTER 7 .
  
 27) A4.21 DETAIL# 1 IS A SECTION AT THE
 CORNICE, PLANS INDICATE MORE DETAILS SEE STRUCTURAL
 PLANS, WHERE? ADDITIONAL
 INFORMATION NEEDED.
 106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 28) A5.81:
 28A) DETAIL# 1, CANOPY FROM OFFICE TOWER
 TO THE NEW ELEVATOR TOWER TO COMPLY WITH
 3104.5 & TABLE 602 @ PROPERTY LINE?
  
 28B) PLANS DO NOT INDICATE ON THE OFFICE
 TOWER CANOPY WHAT TYPE OF FENESTRATION
 SHALL BE USED.2405.2 ALLOWABLE GLAZING
 MATERIALS AND LIMITATIONS.
  
 28C) ARCHITECTURAL PLANS DO NOT INDICATE
 ENOUGH DETAILS NOR DOES THE STRUCTURAL
 PLANS. ADDITIONAL INFORMATION REQUIRED.
 106.1.2*ADDITIONAL DATA.
  
 28D) 2405.5 UNIT SKYLIGHTS.
 UNIT SKYLIGHTS SHALL BE TESTED AND
 LABELED AS COMPLYING WITH 101/I.S.2/NAFS
 VOLUNTARY PERFORMANCE SPECIFICATION FOR
 WINDOWS, SKYLIGHTS AND GLASS . THE LABEL
 SHALL STATE THE NAME OF THE
 MANUFACTURER, THE APPROVED LABELING
 AGENCY, THE PRODUCT DESIGNATION AND THE PERFORMANCE
 GRADE RATING AS SPECIFIED IN 101/I.S.2/NAFS. IF THE
 PRODUCT
 MANUFACTURER HAS CHOSEN TO HAVE THE
 PERFORMANCE GRADE OF THE SKYLIGHT RATED
 SEPARATELY FOR POSITIVE AND NEGATIVE
 DESIGN PRESSURE, THEN THE LABEL SHALL
 STATE BOTH PERFORMANCE GRADE RATINGS AS
 SPECIFIED IN 101/I.S.2/NAFS AND THE
 SKYLIGHT SHALL COMPLY WITH SECTION
 2405.5.2 . IF THE SKYLIGHT IS NOT RATED
 SEPARATELY FOR POSITIVE AND NEGATIVE
 PRESSURE, THEN THE PERFORMANCE GRADE
 RATING SHOWN ON THE LABEL SHALL BE THE
 PERFORMANCE GRADE RATING DETERMINED IN
 ACCORDANCE WITH 101/I.S.2/NAFS FOR BOTH
 POSITIVE AND NEGATIVE DESIGN PRESSURE,
 AND THE SKYLIGHT SHALL CONFORM TO
 SECTION 2405.5.1 .
  
 28E) LIGHT- TRANSMITTING PLASTICS: LIGHT-TRANSMITTING
 PLASTIC MATERIALS
 THAT MEET THE OTHER CODE REQUIREMENTS
 FOR WALLS AND ROOFS SHALL BE PERMITTED
 TO BE USED IN ACCORDANCE WITH THE OTHER
 APPLICABLE CHAPTERS OF THE CODE.
  
 2606.2 APPROVAL FOR USE.
 SUFFICIENT TECHNICAL DATA SHALL BE
 SUBMITTED TO SUBSTANTIATE THE PROPOSED
 USE OF ANY LIGHT-TRANSMITTING MATERIAL,
 AS APPROVED BY THE BUILDING OFFICIAL AND
 SUBJECT TO THE REQUIREMENTS OF THIS
 SECTION.
  
 2606.3 IDENTIFICATION.
 EACH UNIT OR PACKAGE OF
 LIGHT-TRANSMITTING PLASTIC SHALL BE
 IDENTIFIED WITH A MARK OR DECAL
 SATISFACTORY TO THE BUILDING OFFICIAL,
 WHICH INCLUDES IDENTIFICATION AS TO THE
 MATERIAL CLASSIFICATION.
  
 2606.4 SPECIFICATIONS.
 LIGHT-TRANSMITTING PLASTICS, INCLUDING THERMOPLASTIC,
 THERMOSETTING OR
 REINFORCED THERMOSETTING PLASTIC
 MATERIAL, SHALL HAVE A SELF-IGNITION
 TEMPERATURE OF 650?F (343?C) OR GREATER
 WHERE TESTED IN ACCORDANCE WITH ASTM D
 1929; A SMOKE-DEVELOPED INDEX NOT
 GREATER THAN 450 WHERE TESTED IN THE
 MANNER INTENDED FOR USE IN ACCORDANCE
 WITH ASTM E 84, OR NOT GREATER THAN 75
 WHERE TESTED IN THE THICKNESS INTENDED
 FOR USE IN ACCORDANCE WITH ASTM D 2843
 AND SHALL CONFORM TO ONE OF THE
 FOLLOWING COMBUSTIBILITY
 CLASSIFICATIONS:
 CLASS CC1: PLASTIC MATERIALS THAT HAVE A
 BURNING EXTENT OF 1 INCH (25 MM) OR LESS
 WHERE TESTED AT A NOMINAL THICKNESS OF
 0.060 INCH (1.5 MM), OR IN THE THICKNESS
 INTENDED FOR USE, IN ACCORDANCE WITH
 ASTM D 635,
 CLASS CC2: PLASTIC MATERIALS THAT HAVE A
 BURNING RATE OF 2.5 INCHES PER MINUTE
 (1.06 MM/S) OR LESS WHERE TESTED AT A
 NOMINAL THICKNESS OF 0.060 INCH (1.5
 MM), OR IN THE THICKNESS INTENDED FOR
 USE, IN ACCORDANCE WITH ASTM D 635.
  
 2606.5 STRUCTURAL REQUIREMENTS.
 LIGHT-TRANSMITTING PLASTIC MATERIALS IN
 THEIR ASSEMBLY SHALL BE OF ADEQUATE
 STRENGTH AND DURABILITY TO WITHSTAND THE
 LOADS INDICATED IN CHAPTER 16 .
 TECHNICAL DATA SHALL BE SUBMITTED TO
 ESTABLISH STRESSES, MAXIMUM UNSUPPORTED
 SPANS AND SUCH OTHER INFORMATION FOR THE
 VARIOUS THICKNESSES AND FORMS USED AS
 DEEMED NECESSARY BY THE BUILDING
 OFFICIAL.
  
 2606.6 FASTENING.
 FASTENING SHALL BE ADEQUATE TO WITHSTAND
 THE LOADS IN CHAPTER 16 . PROPER
 ALLOWANCE SHALL BE MADE FOR EXPANSION
 AND CONTRACTION OF LIGHT-TRANSMITTING
 PLASTIC MATERIALS IN ACCORDANCE WITH
 ACCEPTED DATA ON THE COEFFICIENT OF
 EXPANSION OF THE MATERIAL AND OTHER
 MATERIAL IN CONJUNCTION WITH WHICH IT IS EMPLOYED.
  
 2606.7.4 FIRE SUPPRESSION SYSTEM.
 IN BUILDINGS THAT ARE EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 , PLASTIC LIGHT-DIFFUSING
 SYSTEMS SHALL BE PROTECTED BOTH ABOVE
 AND BELOW UNLESS THE SPRINKLER SYSTEM
 HAS BEEN SPECIFICALLY APPROVED FOR
 INSTALLATION ONLY ABOVE THE
 LIGHT-DIFFUSING SYSTEM. AREAS OF
 LIGHT-DIFFUSING SYSTEMS THAT ARE
 PROTECTED IN ACCORDANCE WITH THIS
 SECTION SHALL NOT BE LIMITED.
  
 28F) THE CANOPY NORTH OF THE THE NEW
 ELEVATOR TOWER IS UNDER A DDIFFERENT
 PCN, SEPERATE PROPERTY REQUIRING A
 SEPERATE PERMIT.ARCHITECTURAL PLANS DO
 NOT INDICATE ENOUGH DETAILS NOR DOES THE STRUCTURAL
 PLANS. ADDITIONAL INFORMATION REQUIRED.106.1.2*
 ADDITIONAL DATA.
  
 28G) LIGHT- TRANSMITTING PLASTICS: LIGHT-TRANSMITTING
 PLASTIC MATERIALS
 THAT MEET THE OTHER CODE REQUIREMENTS
 FOR WALLS AND ROOFS SHALL BE PERMITTED
 TO BE USED IN ACCORDANCE WITH THE OTHER
 APPLICABLE CHAPTERS OF THE CODE.
  
 2606.2 APPROVAL FOR USE.
 SUFFICIENT TECHNICAL DATA SHALL BE
 SUBMITTED TO SUBSTANTIATE THE PROPOSED
 USE OF ANY LIGHT-TRANSMITTING MATERIAL,
 AS APPROVED BY THE BUILDING OFFICIAL AND
 SUBJECT TO THE REQUIREMENTS OF THIS
 SECTION.
  
 2606.3 IDENTIFICATION.
 EACH UNIT OR PACKAGE OF
 LIGHT-TRANSMITTING PLASTIC SHALL BE
 IDENTIFIED WITH A MARK OR DECAL
 SATISFACTORY TO THE BUILDING OFFICIAL,
 WHICH INCLUDES IDENTIFICATION AS TO THE
 MATERIAL CLASSIFICATION.
  
 2606.4 SPECIFICATIONS.
 LIGHT-TRANSMITTING PLASTICS, INCLUDING THERMOPLASTIC,
 THERMOSETTING OR
 REINFORCED THERMOSETTING PLASTIC
 MATERIAL, SHALL HAVE A SELF-IGNITION
 TEMPERATURE OF 650?F (343?C) OR GREATER
 WHERE TESTED IN ACCORDANCE WITH ASTM D
 1929; A SMOKE-DEVELOPED INDEX NOT
 GREATER THAN 450 WHERE TESTED IN THE
 MANNER INTENDED FOR USE IN ACCORDANCE
 WITH ASTM E 84, OR NOT GREATER THAN 75
 WHERE TESTED IN THE THICKNESS INTENDED
 FOR USE IN ACCORDANCE WITH ASTM D 2843
 AND SHALL CONFORM TO ONE OF THE
 FOLLOWING COMBUSTIBILITY
 CLASSIFICATIONS:
 CLASS CC1: PLASTIC MATERIALS THAT HAVE A
 BURNING EXTENT OF 1 INCH (25 MM) OR LESS
 WHERE TESTED AT A NOMINAL THICKNESS OF
 0.060 INCH (1.5 MM), OR IN THE THICKNESS
 INTENDED FOR USE, IN ACCORDANCE WITH
 ASTM D 635,
 CLASS CC2: PLASTIC MATERIALS THAT HAVE A
 BURNING RATE OF 2.5 INCHES PER MINUTE
 (1.06 MM/S) OR LESS WHERE TESTED AT A
 NOMINAL THICKNESS OF 0.060 INCH (1.5
 MM), OR IN THE THICKNESS INTENDED FOR
 USE, IN ACCORDANCE WITH ASTM D 635.
  
 2606.5 STRUCTURAL REQUIREMENTS.
 LIGHT-TRANSMITTING PLASTIC MATERIALS IN
 THEIR ASSEMBLY SHALL BE OF ADEQUATE
 STRENGTH AND DURABILITY TO WITHSTAND THE
 LOADS INDICATED IN CHAPTER 16 .
 TECHNICAL DATA SHALL BE SUBMITTED TO
 ESTABLISH STRESSES, MAXIMUM UNSUPPORTED
 SPANS AND SUCH OTHER INFORMATION FOR THE
 VARIOUS THICKNESSES AND FORMS USED AS
 DEEMED NECESSARY BY THE BUILDING
 OFFICIAL.
  
 2606.6 FASTENING.
 FASTENING SHALL BE ADEQUATE TO WITHSTAND
 THE LOADS IN CHAPTER 16 . PROPER
 ALLOWANCE SHALL BE MADE FOR EXPANSION
 AND CONTRACTION OF LIGHT-TRANSMITTING
 PLASTIC MATERIALS IN ACCORDANCE WITH
 ACCEPTED DATA ON THE COEFFICIENT OF
 EXPANSION OF THE MATERIAL AND OTHER
 MATERIAL IN CONJUNCTION WITH WHICH IT IS EMPLOYED.
  
 2606.7.4 FIRE SUPPRESSION SYSTEM.
 IN BUILDINGS THAT ARE EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 , PLASTIC LIGHT-DIFFUSING
 SYSTEMS SHALL BE PROTECTED BOTH ABOVE
 AND BELOW UNLESS THE SPRINKLER SYSTEM
 HAS BEEN SPECIFICALLY APPROVED FOR
 INSTALLATION ONLY ABOVE THE
 LIGHT-DIFFUSING SYSTEM. AREAS OF
 LIGHT-DIFFUSING SYSTEMS THAT ARE
 PROTECTED IN ACCORDANCE WITH THIS
 SECTION SHALL NOT BE LIMITED.
  
 29)A5.82/ A5.83
 ARCHITECTURAL PLANS DO
 NOT INDICATE ENOUGH DETAILS NOR DOES THE STRUCTURAL
 PLANS. ADDITIONAL INFORMATION REQUIRED.106.1.2*
 ADDITIONAL DATA.
  
 30)A5.92 NEW ELEVATOR TOWER:
 1406.2.2
 ARCHITECTURAL TRIM. IN BUILDINGS OF TYPE
 I, II, III AND IV CONSTRUCTION THAT DO
 NOT EXCEED THREE STORIES OR 40 FEET (12
 192 MM) IN HEIGHT ABOVE GRADE PLANE,
 EXTERIOR WALL COVERINGS SHALL BE
 PERMITTED TO BE CONSTRUCTED OF WOOD
 WHERE PERMITTED BY SECTION 1405.4 OR
 OTHER EQUIVALENT COMBUSTIBLE MATERIAL.
  
 31) A6.06 DETAIL# 2, THE HANDRAIL AT THE
 BOTTOM OF THE STAIRS MISSING HORIZONTAL
 EXTENTION.11-4.9.4(2)IF HANDRAILS
 ARE NOT CONTINUOUS, THEY SHALL EXTEND AT
 LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND AT LEAST 12 INCHES (305 MM)
 PLUS THE WIDTH OF ONE TREAD BEYOND THE
 BOTTOM RISER. AT THE TOP, THE EXTENSION
 SHALL BE PARALLEL WITH THE FLOOR OR
 GROUND SURFACE. AT THE BOTTOM, THE
 HANDRAIL SHALL CONTINUE TO SLOPE FOR A
 DISTANCE OF THE WIDTH OF ONE TREAD FROM
 THE BOTTOM RISER; THE REMAINDER OF THE
 EXTENSION SHALL BE HORIZONTAL [SEE
 FIGURE 11-19 (C) AND FIGURE 11-19 (D)].
 HANDRAIL EXTENSIONS SHALL COMPLY WITH
 SECTION 11-4.4 .
  
 32A) A8.71 DETAIL# 8 INDICATES A TYPICAL
 RESTROOM DETAIL WHEREAS IT DEPICTS A
 BREAKROOM.
  
 32B) SAME DETAIL INDICATES A SINK HEIGTH
 OF 36" IN HEIGTH.
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 32C) DETAIL (1 & 2), PLEASE INDICATE THE
 CLEAR FLOOR SPACE REQUIREDFOR THE
 LAVATORY. 11-4.19.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE 30 INCHES BY 48
 INCHES (760 MM BY 1219 MM) COMPLYING
 WITH SECTION 11-4.2.4 SHALL BE PROVIDED
 IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL
 ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES
 (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 11-32 ).
  
 33) A10.16 /A1.16 PLANS INDICATE OPEN TO
 BELOW, SECTION A5.62 DETAIL 2 INDICATES
 THE ROOF LEDGE BUT NOT THE ACTUAL
 OPENING, TO WHERE?
  
 34) S0.01
 34A) PLANS INDICATE THE DESIGN TO ASCE
 7-02 BUT THE PRESSURES INDICATED DO NOT
 ILLUSTRATE THE PRESSURES FOR WIND ZONES
 1,2 AND 3 FOR THE ROOF ZONES AND ZONES 4
 & 5 FOR THE INTERIOR WALL AND WALL END
 ZONES. 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 34B)FL BLD CODE 1609.1.4: COMPONENTS
 & CLADDING, PROVIDE 2 COPIES(3 IF
 THRESH- OLD OR RESIDENT INSPECTOR) OF
 PRODUCT TESTING REPORTS,MISSING REPORTS
 ARE AS FOLLOWS:
 A) FIXED WINDOWS
 B) STOREFRONT WINDOWS/SPANDREAL
 C) SKYLIGHTS
 D) MULLIONS
 E) EXTERIOR METAL DOORS SINGLE/ PAIRS
 F) EXTERIOR GLAZED DOORS
 G) ROLL UP DOORS
 H) WALL LOUVERS
 I) EFIS EXTERIOR INSULATION FINISH
 SYSTEM/ DENSEGLASS
 J) ROOF ASSEMBLIES
  
 35)1009.5.3 STAIR IDENTIFICATION.
 AN APPROVED SIGN SHALL BE LOCATED AT
 EACH FLOOR LEVEL LANDING IN ALL ENCLOSED
 STAIRWAYS OF BUILDINGS FOUR OR MORE
 STORIES IN HEIGHT. THE SIGN SHALL
 INDICATE THE FLOOR LEVEL AND THE
 AVAILABILITY OF ROOF ACCESS FROM THAT
 STAIRWAY AND AN IDENTIFICATION OF THE
 STAIRWAY. THE SIGN SHALL ALSO STATE THE
 FLOOR LEVEL OF AND DIRECTION TO EXIT
 DISCHARGE. THE SIGN SHALL BE LOCATED
 APPROXIMATELY 5 FEET (1524 MM) ABOVE THE
 FLOOR LANDING IN A POSITION WHICH IS
 READILY VISIBLE WHEN THE DOOR IS IN THE
 OPEN OR CLOSED POSITION. THE FLOOR LEVEL DESIGNATION
 SHALL ALSO BE TACTILE IN
 ACCORDANCE WITH CHAPTER 11 .
  
 36) PROVIDE ADDITIONAL INFORMATION
 INDICATING COMPLIANCE WITH:
 1019.1.8 SMOKEPROOF ENCLOSURES.
 IN BUILDINGS REQUIRED TO COMPLY WITH
 SECTION 403 OR 405, EACH OF THE EXITS OF
 A BUILDING THAT SERVES STORIES WHERE THE
 FLOOR SURFACE IS LOCATED MORE THAN 75
 FEET (22 860 MM) ABOVE THE LOWEST LEVEL
 OF FIRE DEPARTMENT VEHICLE ACCESS OR
 MORE THAN 30 FEET (9144 MM) BELOW THE
 LEVEL OF EXIT DISCHARGE SERVING SUCH
 FLOOR LEVELS SHALL BE A SMOKEPROOF
 ENCLOSURE OR PRESSURIZED STAIRWAY IN
 ACCORDANCE WITH SECTION 909.20 .
  
 1019.1.8.1 ENCLOSURE EXIT.
 A SMOKEPROOF ENCLOSURE OR PRESSURIZED
 STAIRWAY SHALL EXIT INTO A PUBLIC WAY OR
 INTO AN EXIT PASSAGEWAY, YARD OR OPEN
 SPACE HAVING DIRECT ACCESS TO A PUBLIC
 WAY. THE EXIT PASSAGEWAY SHALL BE
 WITHOUT OTHER OPENINGS AND SHALL BE
 SEPARATED FROM THE REMAINDER OF THE
 BUILDING BY 2-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION.
  
 37) PLANS DO NOT PROVIDE INFORMATION AS
 TO ENCLOSED PARKING GARAGES: 406.4.2
 VENTILATION.
 A MECHANICAL VENTILATION SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL .
  
 38) ELEVATORS 7&8:
  
 38A) 3003.6.1 VENTS. HOISTWAYS OF ELEVA-
 TORS SERVING MORE THAN 3 FLOORS SHALL BE
 PROVIDED WITH MEANS OF VENTING SMOKE AND
 HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
  
 38B) 3003.6.2 VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF
 THE HOISTWAY, AND SHALL BE EITHER DIR-
 ECTLY TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 39) NORTH ELEVATOR:
 39A)3003.6.1 VENTS. HOISTWAYS OF
 ELEVA- TORS SERVING MORE THAN 3 FLOORS
 SHALL BEPROVIDED WITH MEANS OF VENTING
 SMOKE AND HOT GASES TO THE OUTER AIR IN
 CASE OF FIRE.
  
 39B) 3003.6.2 VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF
 THE HOISTWAY, AND SHALL BE EITHER DIR-
 ECTLY TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 40)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NOTE: WITH THE RESPONCE COMMENTS FROM
 THIS REVIEW, ADDITONAL COMMENTS MAY
 APPEAR ON THE NEXT REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 23 Status P Date 2008-08-25 Cont ID  
Sent By dpalmer Date 2008-08-25 Time 13:49 Rev Time 0.00
Received By dpalmer Date 2008-08-25 Time 13:49 Sent To  
Notes
2008-08-25 13:49:43** REVISIONS **
  
  
  
  
 1) NOTE:PLANS SUBMITTED WERE NOT PLACED INTO SETS
 WITH OLD SHEETS REMOVED WITH NEW SHEETS INSERTED. THIS
 WAS DONE BY THIS REVIEWER FOR FILE SET ONLY.
 ALL SHEETS IN CONTRACTOR SET(S) ARE NOT IN ORDER. SOME
 SHEETS ARE STAMPED AND SOME ARE NOT DUE TO OTHER
 REVISED SHEETS IN SETS WHICH SUPERCEDE PLAN SHEETS.
  
 FEE BALANCE OF $80 IS DUE FOR PAGES SUBMITTED AFTER THE
 SUBMITTAL DATE OF 8/14/08.
 ALSO OWES FOR REVISED CALCULATIONS.
  
 2) NO GROSS ERRORS IN REVISED ENERGY CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 22 Status F Date 2008-07-16 Cont ID  
Sent By dpalmer Date 2008-07-16 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2008-07-16 Time 12:59 Sent To PC
Notes
2008-07-16 12:59:54** DENIEDREVISIONS **
  
  
 1) NOTE:AS STATED ON PREVIOUS REVIEWS, MEETINGS,
 PHONE CALLS AND E-MAILS. PLEASE BE SURE TO UPDATE
 LIGHTING ON PLANS, UPDATE FIXTURE LEGEND AND BE SURE
 ALL LIGHTING ON PLANS IS PLACED INTO THE ENERGY
 CALCULATIONS AS REQUIRED BY THE FBC CHAPTER 13. 13-400,
 13-101, 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SOME EXAMPLES WILL BE GIVEN BELOW AS A
 BENEFIT.
 THIS IS *NOT* AN EXHAUSTED LIST.
  
 FOR EXAMPLE:
 PLEASE TAKE A LOOK AT THE FIXTURE LEGEND. PLEASE SEE
 PLANS AS THERE ARE NUMEROUS FIXTURES ON PLANS WHICH ARE
 NOT LISTED ON THE FIXTURE LEGEND ON SHEET E3.02. SOME
 OF THESE ARE LG, ED, EE, LB, LC, EA, EB ETC.
 HOW CAN A REVIEW OF ENERGY CALCULATIONS BE VERIFIED
 WHEN THE WATTAGE OF FIXTURES ARE NOT SHOWN?
  
 FOR EXAMPLE:
 PLEASE SEE SHEET E1.00. THERE ARE 250W, 400W FIXTURES.
 THERE ARE NO 400W OR 250W FIXTURES AT ALL IN THE INPUT
 DATA REPORT ON THE SUBMITTED ENERGY CALCULATIONS. THESE
 ARE NOT THE ONLY FIXTURES. PLEASE TAKE A LOOK AT THE
 EXAMPLE ABOVE.
  
 ** HOW CAN CALCULATIONS BE COMPLETE, ACCURATE AND
 VERIFIEDIF THE PLANS ARE NOT COMPLETE OR COORDINATE
 TO DATE?
  
 FOR EXAMPLE:
 IT WAS PREVIOUSLY MENTIONED BY THE MECHANICAL REVIEWER
 AND THIS REVIEW TO ALSO MAKE SURE ALL BUILDING
 COMPONENTS ON PLANS ARE PLACED INTO THE ENERGY
 CALCULATIONS. THERE WILL BE COMMENTS FROM OTHER TRADES
 AS SOME OF THESE ITEMS IN THE IDR ARE SEEN BY THIS
 REVIEWER.
  
 2) NOTE: PLEASE BE SURE ALL PERMITTED TENANT PLANS FOR
 KNOWN LOADS, LIGHTING USE ETC ARE REVISED INTO THE BASE
 BUILDING.
 FOR EXAMPLE:
 CLEVELAND CLINIC AT BOTH LOCATIONS.
 NEC 220, FBC 13-415.2
 FBC 106.1.1, 106.5 FOR CLARITY AND RECORD SETS OF
 PLANS.
  
 3) NOTE: PLEASE BE SURE THE ENGINEER RAISED SEAL IS
 PLACED TO THE FRONT ON SHEETS. THESE DOCUMENTS ARE
 SCANNED AND INFORMATION NEEDS TO FACE FORWARD TO BE
 EASILY READ AS PART OF THE RECORD PLANS. PLEASE SEE
 SHEETS E3.03.1 IN ALL THREE SETS ARE SEAL BACKWARDS.
 THIS IS NOT NECESSARILY A VIOLATION AS THE STATUTE DOES
 NOT SAY IF THE SEAL CAN BE ON THE BACK OF THE PLANS
 HOWEVER BASED ON SCANNING OF PLANS AND DOCUMENTS THESE
 NEED TO BE READ ETC.
 THE INTENT OF THE STATUTE IS THAT THE SEAL IS FACING
 THE FRONT OF PLANS ETC. THIS WAS CONFIRMED WITH THE
 BOARD OF ENGINEERS.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 21 Status F Date 2008-07-16 Cont ID  
Sent By dpalmer Date 2008-07-16 Time 12:57 Rev Time 0.00
Received By dpalmer Date 2008-07-16 Time 12:57 Sent To M
Notes
2008-07-16 12:59:25FAILED ENERGY CALCS, SEE REVIEW UNDER 7/16/08 REV #22

Review Stop E ELECTRICAL
Rev No 20 Status P Date 2008-06-16 Cont ID  
Sent By dpalmer Date 2008-06-16 Time 08:32 Rev Time 0.00
Received By dpalmer Date 2008-06-16 Time 08:38 Sent To  
Notes
2008-06-16 08:38:24UL REPORTS FOR TRANSFER SWITCHES ONLY. OTHER UL REPORTS
 FOR GENERATOR( BI-FUEL), EXHAUST CONTROL PANEL AND
 BREAKER ENCLOSURE UNDER GEN PERMIT 0706.316.

Review Stop E ELECTRICAL
Rev No 19 Status F Date 2008-05-27 Cont ID  
Sent By dpalmer Date 2008-05-27 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2008-05-27 Time 09:06 Sent To PC
Notes
2008-05-27 09:06:30** DENIED REVIEW **
  
 1) NOTE: PLEASE SUPPLY INFORMATION OR PROVIDE THE
 FOLLOWING DETAILS/CORRECTIONS.
  
 A) FINAL REPORT FOR CIRCUIT BREAKER ENCLOSURE: PLEASE
 COORDINATE AIC RATINGS AS LISTED FOR BREAKER AT
 GENERATOR/OUTPUT AND CIRCUIT BREAKER WITH PLANS
 SUBMITTED AND ON FILE. PLEASE ALSO SEE THE ORIGINAL
 GENERATOR SPECS INDICATE A AIC RATING HIGHER THAN WHAT
 IS NOTED IN REPORT.
 PLEASE ALSO OBTAIN AT LEAST ONE COPY WHICH CONTAINS AN
 ORIGINAL SIGNATURE TO BE PLACED IN FILE OF PROJECT AT
 THE CITY. 110.3, 90.7, FBC 106.1.2, 106.5
  
 B) FINAL REPORT FOR EXHAUST FAN CONTROL PANEL.
 PLEASE OBTAIN AT LEAST ONE COPY WHICH CONTAINS AN
 ORIGINAL SIGNATURE TO BE PLACED IN FILE OF PROJECT AT
 THE CITY. 110.3, 90.7, FBC 106.1.2, 106.5
  
 C) FINAL REPORT FORMODIFIED 3000A TRANSFER SWITCH:
 PLEASE PROVIDE CORRECTIONS ON ITEMS IN SECTION 7 OF UL
 REPORT. PLEASE LIST DATES, TIMES, VERIFICATION WHEN AND
 HOW THESE ITEMS WERE ADDRESSED. THE ITEMS WHICH WERE
 ADDRESSED PRIOR TO THE FINAL UL REPORT NEED ONLY TO BE
 VERIFIED IN FIELD AS THESE ARE ITEMS LISTED AS
 *CORRECTED*.
 PLEASE SEE THERE ARE ITEMS SUCH AS WIRING ON SHARP
 EDGES WHICH DOES NOT STATE WHETHER OR NOT THESE
 CORRECTIONS WERE MADE OR VERIFIED.
 PLEASE ALSO OBTAIN AT LEAST ONE COPY WHICH CONTAINS AN
 ORIGINAL SIGNATURE TO BE PLACED IN FILE OF PROJECT AT
 THE CITY. 110.3, 90.7, FBC 106.1.2, 106.5
  
 D) FINAL REPORT FOR MODIFIED 4000A TRANSFER SWITCH:
 PLEASE OBTAIN AT LEAST ONE COPY WHICH CONTAINS AN
 ORIGINAL SIGNATURE TO BE PLACED IN FILE OF PROJECT AT
 THE CITY. 110.3, 90.7, FBC 106.1.2, 106.5
  
 E) FINAL REPORT FOR BI-FUEL ASSEMBLY ADDED TO UL LISTED
 2200 DIESEL GENERATOR.
 PLEASE KNOW THE APPROVAL OF THIS PRODUCT IS NOT BY THIS
 OFFICE. COMPLIANCE WITH LISTING STANDARD, NFPA-70, AND
 NFPA-110 IS THE RESPONSIBILITY OF THE ENGINEER OF
 RECORD, ELECTRICAL CONTRACTOR, GAS CONTRACTOR AND
 GENERAL CONTRACTOR OF PROJECT. THIS OFFICE WILL ONLY
 VERIFY ITEMS AS NOTED IN REPORT ARE IN FACT LISTED AS
 STATED. PLEASE ALSO OBTAIN AT LEAST ONE COPY WHICH
 CONTAINS AN ORIGINAL SIGNATURE TO BE PLACED IN FILE OF
 PROJECT AT THE CITY. 110.3, 90.7, FBC 106.1.2, 106.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 18 Status F Date 2008-05-16 Cont ID  
Sent By dpalmer Date 2008-05-16 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2008-05-16 Time 12:07 Sent To B
Notes
2008-05-16 12:07:50** DENIED**
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT COMPLIANT AT THIS TIME.
 PLEASE SEE THE FOLLOWING ITEMS WHICH NEED TO BE
 ADDRESSED.
  
 A) PLEASE BE SURE TO COMPLETE THE CERTIFICATE SHEETS
 WITH ALL DESIGNER INFORMATION, SIGNED, DATED AND SEALED
 AS REQUIRED UNDER FBC 13-103.1.1.1. THE PERSON LISTED
 AS THE PREPARER IS REQUIRED UNDER FLORIDA STATUTES AND
 FLORIDA BUILDING CODE TO BE A LICENSED ENGINEER. ALL
 INFORMATION IS CURRENTLY *BLANK* FOR THE RESPONSIBLE
 DESIGNER(S).
  
 B) PLEASE KNOW THAT ALL INFORMATION, BUILDING
 COMPONENTS, LIGHTING ETC ON PLANS NEEDS TO BE PLACED ON
 THE INPUT DATA REPORT. ALL INFORMATION ON PLANS NEEDS
 TO COORDINATE WITH THE UNKNOWN AND KNOWN ON THIS
 PROJECT. THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR
 THE REMAINDER OF THIS COMMENT.
 FOR EXAMPLE:
  
 PLEASE SEE THE EXTERIOR LIGHTING ON THE PLANS/PROJECT
 DOES NOT CORRELATE WITH THE IDR. THE IDR SHOWS *ALL*
 OUTSIDE/EXTERIOR LIGHTING AS 32W FIXTURES. HOW IS THIS
 POSSIBLE WHEN THE FIXTURES ON THE PLANS ARE CLEARLY A
 MUCH HIGHER WATTAGE? ONE FIXTURE ALONE AS AN EXAMPLE IS
 FIXTURE *EN*. PLANS CLEARLY INDICATE THIS FIXTURE WITH
 A 150VA/WATT RATING. PLEASE SEE 13-415.2.ABC.1.1, .1.2
 AND .1.3. THE WATTAGE/VA RATING REQUIRED BY CODE TO BE
 USED IS THE RATING OF THE FIXTURE. THIS IS ONLY ONE
 FIXTURE AND THERE ARE SEVERAL OTHERS. PLEASE BE SURE
 THE FIXTURE COUNT OF *ALL* EXTERIOR FIXTURES ARE GONE
 OVER.
 THE LIGHTING FOR THE INTERIOR OF THE IDR ALSO DOES NOT
 COORDINATE. PLEASE TAKE A LOOK AT THE PARKING GARAGE
 FIXTURES AND WATTAGES. THESE DO NOT CORRELATE WITH THE
 NUMBER OF FIXTURES ON PLANS OR THE WATTAGES BASED ON
 THE *LATEST* REVISED PLANS SUBMITTED AND ON FILE WITH
 THIS DEPARTMENT.
 *** IMPORTANT, PLEASE SEE THE LIGHTING FOR ALL TENANTS
 UNDER PERMIT IN THIS BUILDING ALSO NEEDS TO COORDINATE
 WITH THE IDR.
  
 ** THESE ARE ONLY TWO EXAMPLES AND IS NOT AND
 EXHAUSTIVE LIST. THERE ARE MANY OTHERS.
 ** PLEASE SEE SOME FLOORS/ZONES AND THE INFORMATION ON
 THE IDRALSO NEED COORDINATING WITH THE PLANS.
 ** PLEASE ALSO SEE COMMENTS FROM BUILDING REVIEWER AS
 ALL BUILDING COMPONENTS ARE ALSO IN NEED OF
 COORDINATING. AS A *HEADS-UP FOR INFORMATION ONLY AND
 DOES NOT CONSTITUTE AS A BUILDING REVIEW: ONE EXAMPLE
 IS EXTERIOR DOORS.
  
 2) NOTE: PLEASE SEE THAT ALL KNOWN ELECTRICAL LOADS ON
 THE BASE BUILDING FOR TENANT SPACES NEEDS TO BE ON BASE
 BUILDING PLANS AND LOAD CALCULATIONS. THE FOLLOWING ARE
 TWO EXAMPLES ONLY. PLEASE BE SURE TO OBTAINED *ALL
 LATEST* REVISED LOADS ON TENANT SPACES. SOME OF THESE
 HAVE BEEN REVISED AS RECENTLY AS ONE WEEK BEFORE THIS
 REVIEW.
 PLEASE SEE TWO TENANTS ARE JB HANAUER AND NTECH. LOADS
 SUBMITTED AND SHOWN ON BOTH OF THESE TENANTS ARE HIGHER
 THAN THE LOADS SHOWN AND FIGURED INTO THE BASE BUILDING
 CALCULATIONS SUBMITTED.
 PLEASE KNOW THESE ARE TWO EXAMPLES ONLY AND ARE NOT A
 EXHAUSTED LIST.
  
 3) NOTE: PLEASE BE SURE THE METHODS OF CONTROLS ON THE
 IDR ARE COORDINATED WITH PLANS. PLEASE KNOW THERE MANY
 WHICH ARE SHOWN AS *MANUAL ON/OFF* WHEN IN FACT THE
 PLANS CLEARLY INDICATE AUTOMATED SYSTEMS AS REQUIRED BY
 FBC CHAPTER 13.
 FBC 106.1.2 FOR COORDINATION ALONG WITH CHAPTER 13.
  
 4) NOTE: PLEASE SEE A PREVIOUS REVIEW COMMENT FROM JAKE
 LEAHY MENTIONS A NEED TO VERIFY CHAPTER 13 COMPLIANCE
 WITH OUTSIDE LIGHTING.
 PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROLS AND UPDATE.
 EXTERIOR LIGHTING COMPLIANCE WITH NOTE #1 IS ALREADY
 COMMENTED ON.
 1
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 17 Status F Date 2008-02-27 Cont ID  
Sent By jleahy Date 2008-02-27 Time 07:09 Rev Time 4.30
Received By jleahy Date 2008-02-27 Time 06:58 Sent To  
Notes
2008-02-27 07:05:421. PG. E1.01AEF-9 HAS NO BRANCH CIRCUIT NUMBER.
  
 2. PG. E1.06 CLOUD ON DRAWINGS IN HALLWAY SHOWS NO
 CHANGE FROM ORIGINAL PLAN??
  
 3. PG. E3.02 EF-9 NOT SHOWN ON MECHANICAL SCHEDULE.
  
 4. PG. E3.02 P3 SHOWN ON SCHEDULE, NO PANEL SCHEDULE
 SUBMITTED TO REFLECT CHANGE.
  
 5. PG. E3.02 CIF4 SHOWN ON SCHEDULE, NO PANEL SCHEDULE
 SUBMITTED TO REFLECT CHANGE.
  

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2008-03-09 Cont ID  
Sent By jleahy Date 2008-03-09 Time 21:57 Rev Time 3.00
Received By jleahy Date 2008-03-08 Time 21:57 Sent To  
Notes
2008-03-09 21:59:10THIS SET IS REVISION #37JLEAHYNEED TO CHECK TO SEE
 IF CHAPTER 13 OF FBC WILL APPLY TO OUTSIDE LIGHTING
 SUBMITTED IN THIS REVISION.
  
 BASED ON THE ELECTRICAL REVIEW THIS SET IS OK, BUT MAY
 NEED TO BE REVIEWED PER CHAPTER 13 OF THE FBC.
2008-02-16 16:15:062008-02-16 16:15:06
  
 *** ELECTRICAL REVISIONS SUBMITED 2/13/08 HAVE BEEN
 ROUTED TO JAKE LEAHY CHIEF ELECTRICAL INSPECTOR FOR
 REVIEW.

Review Stop E ELECTRICAL
Rev No 15 Status P Date 2007-12-25 Cont ID  
Sent By dpalmer Date 2007-12-25 Time 08:56 Rev Time 0.00
Received By dpalmer Date 2007-12-25 Time 08:56 Sent To PC
Notes
2007-12-25 08:58:22REV'S SUBMITTED OK,
  
 REDLINED SHEETS AS LOW VOLTAGE FOR SECURITY IS TO BE
 UNDER SEPARATE PERMITS. LVIS NIC.
  
 REV #31 SHEETS E101.A,1.02, 1.03, 1.04, 1.05 AND 3.06

Review Stop E ELECTRICAL
Rev No 14 Status N Date 2008-01-03 Cont ID  
Sent By dpalmer Date 2007-12-12 Time 09:29 Rev Time 0.00
Received By dpalmer Date 2007-12-12 Time 09:29 Sent To P
Notes
2007-12-12 09:29:54*** SUBMITTAL FOR WATER FEATURE NOT NEEDED!!!
  

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2007-12-11 Cont ID  
Sent By dpalmer Date 2007-12-11 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2007-12-06 Time 12:44 Sent To PC
Notes
2007-12-11 16:35:13BASE BLDG REV'S.
  
 E1.00, 1.01A, 1.05, 1.06, 3.05, 3.06

Review Stop E ELECTRICAL
Rev No 12 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dpalmer Date 2007-10-27 Time 10:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2007-09-09 Cont ID  
Sent By dpalmer Date 2007-09-09 Time 11:01 Rev Time 0.00
Received By dpalmer Date 2007-09-09 Time 09:38 Sent To PC
Notes
2007-09-09 11:03:142007-09-09 11:03:14
  
 ELECTRICAL REVISIONS REV #19. (MAINLY REV'S FOR EXHAUST
 FANS/DAMPERS MU AIR)
  
 THE PROVISO NOTES FROM PREVIOUS REVIEW STILL REMAIN.

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2007-08-12 Cont ID  
Sent By dpalmer Date 2007-08-12 Time 13:57 Rev Time 0.00
Received By dpalmer Date 2007-08-12 Time 13:57 Sent To PC
Notes
2007-08-12 13:57:35** PROVISO **
  
 CONDITIONS ISSUED FOR PLANS SUBMITTED, PERMIT FOR BASE
 BUILDING AND EQUIPMENT BEING INSTALLED.
  
 PLEASE SEE THE FOLLOWING SHEETS HAVE BEEN REDLINED WITH
 NOTES TO SEE *PROVISO* AS WILL BE ATTACHED TO THE SHEET
 E0.01.
  
 1) NOTE: PLEASE SEE THAT REVISED GENERATOR SPECS/CUT
 SHEETS AND SUBMITTAL LETTER IS TO BE SUBMITTED. THIS
 HAS NOT BEEN SUBMITTED UNDER THE BASE BUILDING PERMIT
 AND WILL BE REQUIRED BEFORE ISSUANCE OF THE
 GENERATOR(S) PERMIT.
 RESPONSE MENTIONS THAT THE CONTRACTOR HAS ASSURED
 DESIGN THESE WERE SUBMITTED, HOWEVER THESE WERE NOT
 LOCATED ON THIS REVISION OR OTHER PREVIOUS REVISIONS AS
 SUBMITTED. THE DOCUMENTS AS SUBMITTED UNDER THE
 GENERATOR PERMIT APPLICATION WERE NOT COMPLETE.
 PLEASE KNOW THAT THE BI-FUEL UNITS WILL BE REQUIRED TO
 BE LISTED AND INDICATE EPA CERTIFICATION AS AGREED IN
 MEETING WITH DESIGN TEAM REPRESENTATIVE MR. DAVE ALLEN
 PE.
 NEC 110.3, 90.7.
 FBC 106.1.2
  
 2) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS FOR
 BASE BUILDING AS THE TENANT BUILD OUTS WERE NOT PART OF
 THE BASE BUILDING AND THE ORIGINAL ASSUMPTIONS MAY NO
 LONGER BE USED ONCE A SPECIFIC DESIGN IS SET-FORTH.
 PLEASE REVISE ACCORDINGLY FBC 13-415.1.A, 13-415.1.B
 AND 13-415.1.C.
 13-103.1.1.1
 **THESE ARE REQUIRED TO BE REVISED, SUBMITTED, STAMPED
 AND ON-SITE FOR INSPECTOR BEFORE APPLYING FOR TCO **
  
  
 3) NOTE: PLEASE BE SURE TO REVISE ALL FLOOR LAYOUTS AND
 LOAD CALCULATIONS WITH THE SPECIFICS TO EACH FLOOR AND
 ALL LOADS FROM BUILD OUTS WITH KNOWN LOADS.
 PLEASE SEE THAT MANY FLOORS WILL BE REVISED DUE TO
 TENANT BUILD OUTS.
 **THESE ARE REQUIRED TO BE REVISED, SUBMITTED, STAMPED
 AND ON-SITE FOR INSPECTOR BEFORE APPLYING FOR TCO **
  
 4) NOTE: REDLINED NOTE ON E0.03, AS THE NOTE STILL
 STATES *ALL* DUCT BANKS ARE TO CONTAIN SAND* THIS IS
 NOT THE CASE AS SOME ARE CONCRETE ENCASED.
 NO CORRECTION IS NEEDED AS THIS WAS ONLY REDLINED AND
 NOTED.
  
  
 ** PLEASE KNOW THAT THE ABOVE NO WAY INDICATES THAT ALL
 OTHER TYPES OF REVISIONS SHOULD, NEED OR ONLY NEED BE
 SUBMITTED BEFORE TCO. THERE MAY BE SEVERAL CHANGES ON
 SITE WHICH WILL STILL BE REQUIRED TO BE SUBMITTED
 DURING THE PROJECT.
  
 **THE CONDITIONS WITH THE CONSTRUCTION BOARD OF APPEALS
 ARE REQUIRED TO BE MET FOR PROJECT FOR ALL AS APPLIED
 BY THE CONTRACTOR/OWNER/DEVELOPER FOR EACH FLOOR OF
 THIS BUILDING.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTIONS SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2007-07-05 Cont ID  
Sent By dpalmer Date 2007-07-05 Time 14:46 Rev Time 0.00
Received By dpalmer Date 2007-07-04 Time 12:36 Sent To I
Notes
2007-07-05 14:47:082007-07-05 14:47:08
 ** UNSAT**
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NEW COMMENTS.
  
 1) NOTE: PLEASE SEE THE NEW LANDSCAPE PLANS SUBMITTED
 IN FACT CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE ON ALL THREE SETS. PLEASE SEE FS 481.221.
 THIS COMMENT HAS BEEN MADE MANY TIMES WITH DIFFERENT
 DESIGNERS ON THIS PROJECT YET PLANS CONTINUE TO COME IN
 WITH THESE SAME VIOLATIONS UNDER FLORIDA STATUTES. **
 PLANS ARE BEING RETAINED AND WILL BE PLACED WITH
 PREVIOUS PLANS RETAINED BY THIS OFFICE FOR THE SAME
 COMMENT.
 ** PLANS MAY BE TURNED OVER TO THE STATES LEGAL COUNSEL
 TO THE BOARD OF ARCHITECTS OR FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS.
 THIS COMMENT SHOULD HAVE TO BE REPEATED.
 PLEASE BE SURE ALL PLANS WHEN SUBMITTED CONTAIN AN
 ORIGINAL, SIGNATURE, DATE AND RAISED SEAL.
  
 2) NOTE: PLEASE SEE NO REVISED ENERGY CALCULATIONS WERE
 SUBMITTED AS PREVIOUSLY REQUESTED DUE TO THE NUMEROUS
 CHANGES TO PLANS AND LIGHTING.
 FBC CHAPTER 13 13-415.1.A,
 13-103.1.1.1
  
 3) NOTE: PLEASE REVISE AND COORDINATE ALL ELECTRICAL
 PLANS FOR EACH FLOOR WITH THATOF THE SHEETS FOR
 BUILD-OUT PERMITS AND PLANS.
 PLEASE SEE THERE ARE TOO MANY ITEMS TO LIST AT THIS
 TIME BASED ON THE MULTIPLE SETS OF PLANS/ REVISIONS AND
 RESUBMITTED PLANS.
 FBC 106.1.2 ADMIN SECTION FOR COORDINATION.
  
 4) NOTE: PLEASE SEE REVISED SUBMITTALS FOR THE
 ATS/GENERATORS ETC WERE NOT SUBMITTED.
 PLEASE SEE THE SUPPORTING SHEET WHICH WAS THE ONLY
 SHEET SUBMITTED CONTAINS THREE STATEMENTS FROM THE
 GENERATOR MANUFACTURE AND ALL THREE STATEMENTS CONTAINS
 THE WORDING *HOWEVER* AND THEN GOES ON TO STATE
 WARRANTY MAY BE AFFECT BY CHANGES ETC TO EQUIPMENT.
 PLEASE PROVIDE THE DOCUMENTATION/LISTING STANDARD FROM
 WHICH THIS GENERATOR IS MANUFACTURED. PLEASE PROVIDE
 LETTERS AND SUPPORTING DOCUMENTATION FROM MANUFACTURES
 WITH RESPECT TO ADDING SPECIFIC AFTERMARKET EQUIPMENT
 AND SUPPORTING DOCUMENTATION FROM LISTING AGENCY WHICH
 ALLOWS THIS.
 THESE ARE LEGALLY REQUIRED AND LIFE SAFETY REQUIRED
 UNITS.
 110.3, 90.7, 700, 701 ETC.
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE UNDERGROUND FEEDERS NOW
 INDICATE *CLEAN FILL* IN LIEU OF THE ALL PREVIOUS PLANS
 WHICH INDICATED THE REQUIRED CONCRETED ENCASEMENT OF
 THE FEEDERS.
 PLEASE SEE 700.9D(1)5. THIS OFFICE DOES NOT HAVE AN
 ISSUE WITH THE FEEDERS UNDER THE BUILDING WHICH ARE
 PROTECTED, HOWEVER THE FEEDERS FROM BUILDING TO
 GENERATOR ARE AND WILL BE REQUIRED TO BE ENCASED IN
 CONCRETE. THIS LOCATION HAS ALREADY HAD CONDUITS DUG UP
 AND DAMAGE FROM ON-SITE CONSTRUCTION. THESE ARE
 CONDUITS WHICH ARE REQUIRED FOR LIFE SAFETY AND ARE
 SHOWN ONLY AT A DEPTH OF 30INCHES.
 PLEASE REVISE PLANS TO INDICATE CONCRETE ENCASEMENT FOR
 ANY OF THESE CONDUITS.
 PLEASE CLARIFY DEPTH OF THE AA-AA BANK WHICH IS BEING
 SHOWN AT 22INCHES. 300.5
  
 6) NOTE: PLEASE SEE THERE ARE SEVERAL SHEETS WHICH
 CONTAIN REVISION WHICH ARE ONLY REVISION 15, YET
 REVISION 10 IS NOT INDICATED ON SHEETS. PLEASE SEE
 REVISION 15 IS LABELED ON NUMEROUS SHEETS AS *BUILDING
 DEPT COMMENTS* WHEN THERE ARE NUMEROUS REVISIONS TO
 PLANS WHICH THIS DEPARTMENT HAD NO COMMENTS AND DID NOT
 ASK FOR THESE CHANGES. PLEASE REVISE ALL TITLE BLOCKS
 AND PLEASE INDICATE THE REVISIONS ON PLANS INCLUDING
 PREVIOUS REVISION IDENTIFICATIONS WHICH ARE NOT ON
 RECORD PLANS.
 FBC 106.1.2, 106.3.5.1.2
 SHEETS: E101A,102, 103,104,105,106 ETC. COORDINATE 115
 ETC.
  
 7) NOTE: PLEASE SEE SITE LIGHTING ON THIS LEGAL
 PROPERTY WHICH STILL DOES NOT INDICATE CIRCUITING.
 PLEASE SEE E1.00 AS ANY EXISTING LIGHTING POLES WHICH
 ARE NOW PART OF THIS SEPARATE LEGAL PROPERTY WILL BE
 REQUIRED TO BE CIRCUITED TO THIS BUILDING.
 FBC 106.1.2, 106.3.5.1.2
 408.4, 310.16.
  
 8) NOTE: PLEASE PROVIDE VD FOR CIRCUITS ON ROOF AND
 15TH FLOOR WHICH ARE BEING SHOWN FED FROM FIRST FLOOR
 LIGHTING PANEL.
 PLEASE CLARIFY CIRCUITS SL41A-16, 14 ETC WHICH FEED THE
 ROOF TOP LIGHTING AND LIGHTING FOR BUILDING
 ILLUMINATION.
 13-413.1. ABC.1.2
 ** SUPPORTS ON THESE VERTICAL RUNS ARE STILL REQUIRED.
 300.19
  
 9) NOTE: PLEASE KNOW AS STATED ON PREVIOUS REVIEW: THE
 REVIEWS OF REVISIONS TO PLANS OTHER THAN THAT OF ITEMS
 PREVIOUSLY NOTED FOR CORRECTION WOULD BE MADE EASIER IF
 INDEED A LETTER OR FORM OF IDENTIFYING CHANGES MADE TO
 PLANS WAS SUBMITTED. EXAMPLE: PLEASE SEE REVISION #10
 TO E0.01, WHICH NOW INCLUDES A DIMMER, YET THIS DEVICE
 IS NOT EASILY REVISED OR LOCATED ON SHEETS SUBMITTED.
 FBC 106.1.2 PLEASE CLARIFY.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-05 07:04:592007-07-05 07:04:59
 REVIEW IN PROGRESS
2007-07-04 12:37:472007-07-04 12:37:47
 1-ROLL OF PLANS REMOVED FROM INCOMING IN ELECTRICAL FOR
 REVIEW. PLANS WILL BE RETURNED TO INCOMING WAITING FOR
 COMM BOARD ONCE ELECTRICAL REVIEW IS COMPLETED.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2007-04-15 Cont ID  
Sent By dpalmer Date 2007-04-15 Time 18:08 Rev Time 0.00
Received By dpalmer Date 2007-04-14 Time 16:02 Sent To  
Notes
2007-04-15 18:08:44** UNSAT **
  
 REVISIONS.
  
 1) NOTE: PLEASE SEE THAT LETTER OF SUBMITTED CHANGE OR
 INFORMATION ON CHANGES MADE WOULD BE HELPFUL IN THE
 REVIEW OF DOCUMENTS FOR CHANGES MADE.
 PLEASE KNOW THAT ALL CHANGES WHICH AFFECT THE BASE
 BUILDING UNDER THE TENANT BUILD OUTS WILL BE REQUIRED
 TO BE REVISED ON BASE BUILDING PLANS.
 THIS IS FOR ALL BUILD OUT AFFECTING BASE PLANS BEFORE
 CO OF MAIN BUILDING.
 PLEASE BE SURE TO COORDINATE WITH ANY ELECTRICAL
 REQUIREMENTS AND CHANGES REQUIRED FOR TENANT FIT UPS.
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPECS/CUT SHEETS
 FOR ALL NEW REVISED ATS AND GENERATOR EQUIPMENT.
 PLEASE KNOW IT HAS COME TO ATTENTION THAT THE ADDITION
 OF THE BI-FUEL DEVICES ON THE GENERATOR UNITS MAY
 INDEED CAUSE ANY LISTINGS TO BE VOIDED AND ALSO VOID
 ANY WARRANTY ON THE UNITS.
 THE WARRANTY IS NOT THE CONCERN OF THIS OFFICE, HOWEVER
 VOIDING ANY LISTINGS OF LEGALLY REQUIRED AND EMERGENCY
 STAND-BY SYSTEMS REQUIRED FOR LIFE SAFETY IS OF
 CONCERN.
 THIS MATTER WILL BE LOOKED INTO FURTHER AND INFORMATION
 FORWARD TO THE LISTING AGENCY AS LISTED ON EQUIPMENT
 SUBMITTED UNDER THE INITIAL BASE BUILDING PERMITTED
 PACKAGE. PLEASE SEE THE SIZE OF THE GENERATOR HAS
 INCREASED HOWEVER THE OCP DEVICES HAVE NOT CHANGED ON
 UNIT?
 PLEASE ALSO SUBMIT THE SPECS FOR THE PARALLELING SWITCH
 GEAR AS REVISED.
 PLEASE CLARIFY.
 110.3, 90.7
  
 3) NOTE: PLEASE CORRELATE RISER AND PARALLELING SWITCH
 GEAR AS THESE NO LONGER MATCH DUE TO CHANGES FOR ATS-1.
 THE ATS- IS NOW SHOWN BEING FED FROM A 3200AMP ON THE
 PS GEAR AND THE RISER HAS NOT CHANGED ALONG WITH THE
 EQUIPMENT?
 PLEASE PROVIDE MORE INFORMATION.
 EQUIPMENT MAY NOT BE FED FROM 3200A OCP WHEN ONLY RATED
 FOR 3000AMPS>
  
 4) NOTE: PLEASESUBMIT A SELECTIVE COORDINATION STUDY
 NOW THAT EQUIPMENT SHOULD ALL BE SELECTED.
 240.12, 700.27, 701.18. NEC
 NFPA-110 6.5.1
 FBC 106.1.2
  
 5) NOTE: PLEASE CLARIFY THE NEW MAINS NOW BEING SHOWN
 FOR THE EMERGENCY SYSTEMS AND LEGALLY REQUIRED SYSTEMS
 WHICH INDICATE GF PROTECTION?
 PLEASE SEE 240.13, 230.95, AND NEC 700.7D
  
 6) NOTE: PLEASE SEE RISER HAS NOW CHANGED TO INDICATE
 THE SWBDB TO BE A 4000AMP RATED MAIN, YET NOTE FOR THIS
 STILL INDICATES THIS AS A 5000AMP SWITCH BOARD?
 PLEASE CORRELATE.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE PLANS HAVE HAD SEVERAL LIGHTING
 FIXTURES REVISED ALONG WITH THE NUMBER AND LOCATIONS OF
 FIXTURES. PLEASE SUBMIT REVISED ENERGY CALCULATIONS FOR
 BUILDING PER 13-415.1.AB.1.1.
  
 8) NOTE: PLEASE SEE THE FIXTURE LEGEND HAS BEEN REVISED
 AND THERE ARE FIXTURES WHICH ARE SHOWN ON PLANS WITH
 DESIGNATIONS WHICH ARE NOT LISTED ON FIXTURE LEGEND.
 (CCE, NL ETC)
 PLEASE SHOW ALL FIXTURES AND COORDINATE WITH LEGEND AND
 REVISED ENERGY CALCULATIONS.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE ELEVATOR MOTORS 1,2 AND 3 WHICH HAS
 NOW INCREASED ALONG WITH THE FEEDING FROM LSPA, YET THE
 OCP FROM LSPA HAS ACTUALLY GONE DOWN??
 PLEASE SEE THE LOAD HAS INCREASED WHICH NO EXCEEDS THE
 RATING OF THE NEW LOWER 200AMP BREAKER?
 PLEASE VERIFY ALL LOADS ON MOTORS PER 430 TABLES AND
 VERIFY THE LOADS ON EACH.
 PLEASE SUBMIT REVISED SCHEDULES FOR THIS.
 PLEASE REVISED ANY LOAD CALCULATIONS.
 FBC 106.1.2
 NEC 240, 430, 220
  
 10) NOTE: PLEASE SEE NEW LIGHTING ON E-100 SEEM TO BE
 LOCATED OUTSIDE PROPERTY LINE OF THE BUILDING. PLEASE
 CLARIFY AND PROVIDE DOCUMENTATION OF ANY CHANGES.
  
 11) NOTE: PLEASE SUPPLY REVISED VOLTAGE DROP
 INFORMATION FOR DECREASED OF CONDUCTORS AND BRANCH
 CIRCUITS ON PLANS FOR SITE LIGHTING WHICH IS NOT
 LOCATED LONGER RUNS THAN PREVIOUS PLANS AND SMALLER
 CONDUCTORS.
 13-413.1.ABC.1
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-15 16:07:07IN PROGRESS
2007-04-14 16:02:49ONE ROLL IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-02-11 Cont ID  
Sent By dpalmer Date 2007-02-11 Time 17:47 Rev Time 0.00
Received By dpalmer Date 2007-02-11 Time 17:30 Sent To  
Notes
2007-02-11 17:48:38REDLINED E1.01, AN OVER RIDE DEVICE IS STILL REQUIRED
 AT THE OTHER ENTRANCE TO THE BANK BY WAY OF TIMER OVER
 RIDE OR OCCUPANCY SENSOR TYPE DEVICE.
 FBC 13-415.1.ABC.1.1, .1.2

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-12-09 Cont ID  
Sent By dpalmer Date 2006-12-09 Time 21:04 Rev Time 0.00
Received By dpalmer Date 2006-12-09 Time 21:04 Sent To  
Notes
2007-01-11 10:00:54PLANS BACK FOR PROCESSING
2006-12-09 21:05:42** UNSAT **
 PLEASE SEE SOME MINOR NOTES FOR THE FOLLOWING SHEETS.
 E-1.01, 3.03, 1.06, AND 3.07.
  
 1) NOTE: PLEASE SEE SHEET 1.01, PLEASE CLARIFY ELEVATOR
 PIT LIGHTING CONTROL, COULD NOT LOCATE SEPARATE SPACE
 CONTROL. PLEASE KNOW THAT AN OCCUPANT TYPE DEVICE WOULD
 NOT BE RECOMMENDED AND PERHAPS A 4HR TIMER?
 PLEASE SEE RETAIL SPACES #1 AND #2 AS LIGHTING CONTROL
 IS BEING SHOWN AT ONE POINT OF ENTRANCE ONLY. PLEASE
 SEE BANK AREA INDICATES CONTROLS AT BOTH POINTS OF
 INGRESS/EGRESS.
 13-415.1.ABC.1.2
  
 2) NOTE: PLEASE SEE E1.06, PLEASE CLARIFY TELEPHONE
 /DATA ROOM LIGHTING FOR FLOORS 8 AND 11?
 13-415.1.ABC.1.2
  
 3) NOTE: PLEASE SEE E3.03; PLEASE SEE WHAT APPEARS TO
 BE A MISPRINT FOR PARALLEL SWITCH GEAR LIGHTING LOADS.
 PLEASE SEE THESE ARE NOTED AT 100%, WHERE LOAD DOES
 APPEAR TO BE FIGURED AT 125%.
 215.3,230.42 ETC
 PLEASE CORRELATE.
 FBC 106.1.2 ADMIN SECTION.
  
 4) NOTE: PLEASE SEE E3.07; PLEASE SEE MISSING LOAD FOR
 "P-2" INDICATE A 600A BREAKER FOR THIS EQUIPMENT, BUT
 LOAD IS BLANK. IT IS NOTICED THE P-1 WAS ADJUSTED TO
 INDICATE 600A OCP FOR THE 200 HP LOAD.
 PLEASE ADJUST/CLARIFY IN RESPONSE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-12-09 Cont ID  
Sent By dpalmer Date 2006-12-09 Time 20:58 Rev Time 0.00
Received By dpalmer Date 2006-12-09 Time 19:58 Sent To  
Notes
2006-12-09 21:03:27**** PLEASE SEE NOTES FOR REVIEW FOR SHEETS E-1.01,
 1.06, 3.03 AND 3.07 DATED TODAYS DATE ALSO WHICH ARE
 BEING ENTERED UNDER THE NEXT REVIEW STOP #6
  
 STAMPED TWO SETS ONLY OF THE OTHER ELECTRICAL SHEETS
 WHICH WERE OK. ZONING HAS THIRD ROLL. PLANS ARE NOT TO
 BE RELASED UNTIL THIRD SET IS STAMPED. THIS SHOULD BE
 VERIFIED UPON PIKCING UPOF PLANS SO THAT JOBSITE
 COPIES CONTAIN STAMPS.
 PLEASE KNOW THIS NOTE IS FOR BUILDING AND PLUMBING ALSO
 AS THEY COULD ONLY STAMP TWO SETS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-31 Cont ID  
Sent By dpalmer Date 2006-10-31 Time 15:52 Rev Time 0.00
Received By dpalmer Date 2006-10-31 Time 15:52 Sent To PC
Notes
2006-11-07 07:25:44MEP'S, IN ELEC FOR STAMPING OF PROVISO.
2006-10-31 16:06:43******* PROVSIO *******
  
 ** PLEASE KNOW A 30 DAY PROVISION FOR THE COMMENTS 1-8
 ARE BEING GIVEN AT THIS TIME.PLEASE MAKE THE
 CORRECTIONS FOR REVIEW. COMPLIANCE MUST BE COMPLETED,
 REVIEWED AND STAMPED FOR THESE ITEMS BEFORE THE 30 DAY
 TIME PERIOD EXPIRES.
 12/1/06
  
 ** PLEASE ALSO KNOW A 90 DAY PROVSION IS BEING GRANTED
 FOR THE GENERATOR AND SUB-BASE FUEL TANK , SEE COMMENT
 #9.
  
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS WHICH
 ARE STILL IN NEED OF ADDRESSING AND NEW CHANGES WHICH
 NEED TO BE MADE AS CERTAIN ITEMS ARE NOT GOING TO TAKE
 PLACE UNDER THIS PERMIT OR PLANS.
  
  
  
 1) NOTE: PLEASE SEE MULTIPLE ENERGY CALCULATIONS WERE
 SUBMITTED FOR BOTH METHOD "A" AND "B", AS PER
 CONVERSATION WITH MR. WORKS, METHOD "B" WILL BE USED
 AND METHOD "A" WILL BE REMOVED.
  
 2) NOTE: PLEASE SEE THERE ARE STILL MANY AREAS/ROOMS ON
 PLANS WHICH ARE MISSING REQUIRED CONTROLS PER FBC 2004
 13-415.1.ABC.1.2.
 ** ALL ROOMS AND AREAS CONTAINING FLOOR TO CEILING
 HEIGHT PARTITIONS SHALL REQUIRE AND OVER-RIDE DEVICE.
 (MAXIMUM TIMES 4HRS FOR TIMER TYPE AND 30MINS FOR
 OCCUPANT SENSING TYPE.)
 PLEASE SEE SYMBOL LEGEND ON E0.01 SHALL INDICATE THESE
 TIMES ON THE DEVICES AS LISTED.
 MAIL ROOM, MACHINE ROOMS, CONFERENCE ROOM (6TH FLR),
 STORAGE ROOMS, ETC.
 ALL LOCATIONS GONE OVER WITH DESIGNER.
  
 3) NOTE: PLEASE SEE NOTE ADDED TO FA SHEETS WHICH
 REQUIRES ALL AREAS TO BE DESIGNED FOR A MINIMUM OF 75
 CANDELA PER FBC 2004 CHAPTER 11-4.28.3(4). THIS WAS NOT
 COMMENTED BY THIS REVIEW ON ANY PREVIOUS REVIEWS AS
 THIS WAS NOT IN THE ELECTRICAL PLAN REVIEW SCOPE AT
 THAT TIME. PLANS INDICATE 75C UNITS, HOWEVER LIGHTING
 LEVELS SHALL BE MAINTAINED IN "ALL" AREAS. PLEASE SEE
 11-4.28.1
  
 4) NOTE: PLEASE SEE ALL ELECTRICAL/ ARCHITECTURAL
 DETAILS, DEVICES, PLANS AND SHEETS WITH REFERENCE TO
 THE ELEVATOR TOWER ON THE "B" BLOCK GARAGE SHALL BE
 REMOVED FROM SETS.
 PLEASE SEE RISER WHICH WILL ALSO REMOVE ALL ELECTRICAL
 WITH REFERENCE TO THIS.
 ALL LOCATIONS GONE OVER WITH DESIGNER.
  
 5) NOTE: PLEASE SEE CIRCUITING FOR FUTURE "B" BLOCK
 ELEVATOR TOWER, VESTIBULE, MACHINE ROOM ETC SHALL MEET
 ALL CIRCUITING AS PREVIOUSLY NOTED ON OTHER REVIEWS.
 PLEASE SEE DEDICATED CIRCUITS REQUIRED FOR RECEPTACLES
 AND LIGHTS ARE REQUIRED PER 620.23 AND 620.24. PLEASE
 SEE RECEPTACLE CIRCUIT BEING NOTED ON PANEL SCHEDULE AS
 BEING AN A/C P-TAC UNIT. PLEASE SEE ELEVATOR CAB LT'S
 BEING SHOWN ON WITH OTHER ELECTRICAL EQUIPMENT. PLEASE
 KNOW A PANEL SCHEDULE WILL BE REQUIRED FOR THESE ITEMS
 ON FUTURE PLANS.
 THIS IS BEING NOTED AT THIS TIME AS THEY ARE SHOWN ON
 THESE DO NOT COMPLY.
 PLEASE SEE SHEET E2.01 SHOULD BE REMOVED ALL TOGETHER
 OR LEFT BLANK FOR ANY OTHER FUTURE USE.
 PLEASE SEE PANEL "P21N" SHOULD ALSO BE REMOVED FROM
 E3.07.
 ALL ITEMS GONE OVER WITH THE DESIGNER.
  
 6) NOTE: PLEASE SEE MISSING PHOTO-METRICS FOR ALL
 EGRESS LOCATIONS AS REQUIRED PER NFPA-101 7.8.1.3,
 7.9.2.2 AS NOTED ON BOTH PREVIOUS REVIEWS.
 PLEASE INDICATE ALL NORMAL AND EMERGENCY FOOT CANDLE
 LEVELS.
 ** PLEASE KNOW, SOME OF THESE WERE DONE AND STAIR
 TOWERS ARE OK.
  
 7) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS FOR
 EACH SERVICE AS SHOWN AND INSTALLED. THIS WOULD BE THE
 5000A SWITCH BOARD"SWBDB" ANDTHE 3000A "SWBDA".
 PLEASE SUBMIT AND INDICATE THE LOADS ON THE PARALLELING
 SWITCH GEAR/EM SIDE.
 PLEASE SHOW AND INDICATE CONTINUOUS LOADS ON THE LOAD
 CALCULATIONS AT 125%. A 1.25 FACTOR WAS ADDED TO
 PANELS.
 PLEASE SHOW AND INDICATE HOW ALL LOADS ARE BEING
 DERIVED AS REQUIRED IN THE NEC.
 PLEASE SEE PREVIOUS NOTES ON BOTH REVIEWS WHICH
 REFLECTED 220.3, 220.10, 220.11, 220.13, 215.3, AND
 230.42 ETC.
  
 8) NOTE: PLEASE KNOW THAT EMERGENCY LIGHTING FIXTURES
 OF SOME TYPE CONTAINING BATTERY BACK UP FOR A MINIMUM
 TIME OF 90MINS WILL BE REQUIRED IN ALL BATHROOMS BEING
 BUILT OUT UNDER THIS PERMIT. NFPA-101 7.8, 7.9
 THIS WAS CONFIRMED WITH DESIGN TEAM, OWNERS AND CHIEF
 FIRE MARSHAL, AND THIS PLANS EXAMINER.
  
 ** GENERATOR PROVISO **
  
 9) NOTE: PLEASE KNOW AT THIS TIME THE GENERATOR AND
 SUB-BASE FUEL TANK IS NOT VALID UNDER THIS BUILDING
 PERMIT UNTIL SUCH TIME APPROVAL FROM DERM IS OBTAINED.
 THIS APPROVAL FROM DERM WILL BE REQUIRED TO BE REVIEWED
 BY THE MECHANICAL PLANS EXAMINER ANDTHE FIRE
 MARSHAL. PLEASE KNOW REVISED ELECTRICAL PLANS SHALL
 ALSO INCLUDE ALL INFORMATION AS REQUIREDFOR THE FIRE
 MARSHAL'S COMPLETE REVIEW OF NFPA-30, NFPA-704,
 NFPA-110,
  
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-20 Cont ID  
Sent By dpalmer Date 2006-10-21 Time 21:27 Rev Time 0.00
Received By dpalmer Date 2006-10-19 Time 20:57 Sent To  
Notes
2006-10-27 16:46:59**** PLEASE KNOW AS OF 10/27/06 THE CONDITION WHICH WAS
 GOING TO BE GRANTED ONLY IF ALL OTHER REVIEWS PASS, IS
 N LONGER AN OPTION. ALL ELECTRICAL CODE COMMENTS WILL
 BE REQUIRED TO BE ADDRESSED AT THIS TIME BEFORE NEXT
 RESUB.
 PLEASE PHONE CALL WAS PLACED TO MR DAVID WORKS AT
 APPROX 15:10ON TODAYS DATE AND INFORMED MR. WORKS OF
 THE STATUS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-10-21 14:08:52***** UNSAT3RD REVIEW ******
  
 10/21/06 14:08:52
  
  
  
 **** PLEASE KNOW PLANS ARE BEING PLACED INTO A FAILED
 STATUS AT THIS TIME. IF ALL OTHER ALL TRADES PASS ALL
 OTHER REVIEWS, A CONDITION KNOWN A "PROVISO" WILL BE
 GIVEN WHICH WILL GRANT ISSUANCE OFPERMIT FOR SAID
 PLANS WITH A CERATINAMOUNT OF TIME TO HAVE
 CORRECTIONS SUBMITTED.
 THIS TIME WILL BE 30 DAYS.
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS WHICH
 ARE STILL IN NEED OF ADDRESSING AND NEW CHANGES WHICH
 NEED TO BE MADE AS CERTAIN ITEMS ARE NOT GOING TO TAKE
 PLACE UNDER THIS PERMIT OR PLANS.
  
 ** SPOKE TO MR. DAVID WORKS VIA PHONE ON FRIDAY OCTOBER
 20TH, 2006
  
 1) NOTE: PLEASE SEE MULTIPLE ENERGY CALCULATIONS WERE
 SUBMITTED FOR BOTH METHOD "A" AND "B", AS PER
 CONVERSATION WITH MR. WORKS, METHOD "B" WILL BE USED
 AND METHOD "A" WILL BE REMOVED.
  
 2) NOTE: PLEASE SEE THERE ARE STILL MANY AREAS/ROOMS ON
 PLANS WHICH ARE MISSING REQUIRED CONTROLS PER FBC 2004
 13-415.1.ABC.1.2.
 ** ALL ROOMS AND AREAS CONTAINING FLOOR TO CEILING
 HEIGHT PARTITIONS SHALL REQUIRE AND OVER-RIDE DEVICE.
 (MAXIMUM TIMES 4HRS FOR TIMER TYPE AND 30MINS FOR
 OCCUPANT SENSING TYPE.)
 PLEASE SEE SYMBOL LEGEND ON E0.01 SHALL INDICATE THESE
 TIMES ON THE DEVICES AS LISTED.
 MAIL ROOM, MACHINE ROOMS, CONFERENCE ROOM (6TH FLR),
 STORAGE ROOMS, ETC.
 ALL LOCATIONS GONE OVER WITH DESIGNER.
  
 3) NOTE: PLEASE SEE NOTE ADDED TO FA SHEETS WHICH
 REQUIRES ALL AREAS TO BE DESIGNED FOR A MINIMUM OF 75
 CANDELA PER FBC 2004 CHAPTER 11-4.28.3(4). THIS WAS NOT
 COMMENTED BY THIS REVIEW ON ANY PREVIOUS REVIEWS AS
 THIS WAS NOT IN THE ELECTRICAL PLAN REVIEW SCOPE AT
 THAT TIME. PLANS INDICATE 75C UNITS, HOWEVER LIGHTING
 LEVELS SHALL BE MAINTAINED IN "ALL" AREAS. PLEASE SEE
 11-4.28.1
  
 4) NOTE: PLEASE SEE ALL ELECTRICAL/ ARCHITECTURAL
 DETAILS, DEVICES, PLANS AND SHEETS WITH REFERENCE TO
 THE ELEVATOR TOWER ON THE "B" BLOCK GARAGE SHALL BE
 REMOVED FROM SETS.
 PLEASE SEE RISER WHICH WILL ALSO REMOVE ALL ELECTRICAL
 WITH REFERENCE TO THIS.
 ALL LOCATIONS GONE OVER WITH DESIGNER.
  
 5) NOTE: PLEASE SEE CIRCUITING FOR FUTURE "B" BLOCK
 ELEVATOR TOWER, VESTIBULE, MACHINE ROOM ETC SHALL MEET
 ALL CIRCUITING AS PREVIOUSLY NOTED ON OTHER REVIEWS.
 PLEASE SEE DEDICATED CIRCUITS REQUIRED FOR RECEPTACLES
 AND LIGHTS ARE REQUIRED PER 620.23 AND 620.24. PLEASE
 SEE RECEPTACLE CIRCUIT BEING NOTED ON PANEL SCHEDULE AS
 BEING AN A/C P-TAC UNIT. PLEASE SEE ELEVATOR CAB LTS
 BEING SHOWN ON WITH OTHER ELECTRICAL EQUIPMENT. PLEASE
 KNOW A PANEL SCHEDULE WILL BE REQUIRED FOR THESE ITEMS
 ON FUTURE PLANS.
 THIS IS BEING NOTED AT THIS TIME AS THEY ARE SHOWN ON
 THESE DO NOT COMPLY.
 PLEASE SEE SHEET E2.01 SHOULD BE REMOVED ALL TOGETHER
 OR LEFT BLANK FOR ANY OTHER FUTURE USE.
 PLEASE SEE PANEL "P21N" SHOULD ALSO BE REMOVED FROM
 E3.07.
 ALL ITEMS GONE OVER WITH THE DESIGNER.
  
 6) NOTE: PLEASE SEE MISSING PHOTO-METRICS FOR ALL
 EGRESS LOCATIONS AS REQUIRED PER NFPA-101 7.8.1.3,
 7.9.2.2 AS NOTED ON BOTH PREVIOUS REVIEWS.
 PLEASE INDICATE ALL NORMAL AND EMERGENCY FOOT CANDLE
 LEVELS.
 ** PLEASE KNOW, SOME OF THESE WERE DONE AND STAIR
 TOWERS ARE OK.
  
 7) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS FOR
 EACH SERVICE AS SHOWN AND INSTALLED. THIS WOULD BE THE
 5000A SWITCH BOARD"SWBDB" ANDTHE 3000A "SWBDA".
 PLEASE SUBMIT AND INDICATE THE LOADS ON THE PARALLELING
 SWITCH GEAR/EM SIDE.
 PLEASE SHOW AND INDICATE CONTINUOUS LOADS ON THE LOAD
 CALCULATIONS AT 125%. A 1.25 FACTOR WAS ADDED TO
 PANELS.
 PLEASE SHOW AND INDICATE HOW ALL LOADS ARE BEING
 DERIVED AS REQUIRED IN THE NEC.
 PLEASE SEE PREVIOUS NOTES ON BOTH REVIEWS WHICH
 REFLECTED 220.3, 220.10, 220.11, 220.13, 215.3, AND
 230.42 ETC.
  
  
  
 ** PLEASE KNOW ALL OF THE ABOVE WERE GONE OVER WITH MR.
 WORKS ITEM BY ITEM, AND PAGE BY PAGE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2006-10-20 21:30:11*** UNSAT****
  
  
 *** PLEASE KNOW A CALLED WAS PLACED TO MR DAVID WORKS
 AND A "MEETING" VIA THE PHONE TOOK PLACED FOR APPROX AN
 HOUR.
  
 ** PLEASE SEE REVIEW WILL BE GOING INTO A FAILED STATUS
 AND REVIEW NOTES WILL BE PLACED INTO THE COMPUTER AND
 PLACED ONLINE ON SATURDAY 10/21 AFTER APPROX 1PM EST.
2006-10-19 20:58:15*** ELECTRICALPLANS IN ELECTRICAL FOR REVIEW,,,,,

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-30 Cont ID  
Sent By dpalmer Date 2006-07-30 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2006-07-16 Time 18:26 Sent To  
Notes
2006-08-02 00:00:00**** NOTE***
  
 A RETURN PHONE CALL WAS PLACED TOMR.
 WORKS AND MR. JOINER AT APPROX 5:45PM TO
 GO OVER COMMENTS OF PLAN REVIEW.
 PHONE CONFERENCE LASTED TILL 7:14PM AND
 SHALL CONTINUE AT THE DESIGN'S TEAM NEXT
 AVAILBLE TIME.
 MOST COMMENTS WERE GONE OVER AND ANY
 FOLLOW UP REVIEW OF COMMENTS WILL TAKE
 PLACE AT A LATER DATE AND TIME.
2006-07-30 00:00:00IN PROGRESS
  
 ******* UNSAT 2ND REVIEW ******
  
 CITY PLACE OFFICE TOWER
 525 OKEECHOBEE BLVD.
  
 ** PLEASE SEE MANY OF THE NOTES FROM THE
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED ALONG WITH NEW COMMENTS.
 PLEASE SEE NOTE BELOW ARE TAKEN DIRECTLY
 FROM PREVIOUS REVIEW WITH FURTHER
 EXPLANATION ADDED IN RESPONSE. PLEASE
 SEE THE NEW NOTES ARE ADDED TO THE
 BOTTOM OF THE FIRST REVIEW.
  
  
  
 **PLEASE KNOW PLANS AND SUBMITTED PAPER
 WORK IS NOT COMPLETE AT THIS TIME FOR A
 COMPLETE AND SUFFICIENT REVIEW. PLEASE
 KNOW THERE MAY BE FURTHER COMMENTS ONCE
 ALL INFORMATION IS SUBMITTED.
  
 1) NOTE: NO, PLEASE SEE ALL VOIDED
 SHEETS WERE ADDED TO ALL THREE SETS. IF
 REPLACING ALL SHEETS IN SETS AND RUNNING
 ALL NEW SETS, PLEASE ONLY SUBMIT "ONE"
 ROLL OF THE "VOIDED" SHEETS SEPARATELY.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW, BEFORE RE-SUBMITTING
 PLANS. PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETED SETS FOR
 REVIEW AND STAMPING. PLEASE KNOW SINCE
 MANY OF THE COMMENTS BELOW AFFECT ALL OF
 THE SHEETS IN THE SETS, ONLY ONE ROLL OF
 OLD SETS SHOULD BE SUBMITTED FOR
 REFERENCE WHEN PLANS ARE BROUGHT BACK.
 THESE SHOULD BE LABELED "OLD/VOIDED".
  
 2) NOTE: NO. PLEASE SEE MISSING
 INFORMATION ON ALL TITLE BLOCKS FOR ALL
 TRADES AND FOR ALL SHEETS. PLEASE KNOW
 THAT "ANY" ARCHITECTURAL FIRM,
 ENGINEERING FIRM, LANDSCAPE FIRMETC
 LISTED ON SAID TITLE BLOCKS ARE REQUIRED
 TO HAVE THEIR CERTIFICATE OF
 AUTHORIZATION NUMBER LISTED ON TITLE
 BLOCKS ALONG WITH ALL OTHER INFORMATION
 AS REQUIRED UNDER THE FLORIDA
 ADMINISTRATIVE CODES AND FLORIDA STATUES
 AS LISTED ON PREVIOUS REVIEW.
 PLEASE SEE THAT THE ENGINEERING FIRM HAS
 NOW ONLY LISTED THE PRINTED PE # FOR THE
 DESIGNER AS THE REQUIRED CA #. PLEASE
 SEE ARCHITECTURAL FIRM ELKUS/MANFREDI
 DOES NOT FIRM NUMBER LISTED.
 PLEASE SEE MISSING LICENSE INFORMATION
 FOR LANDSCAPE PLANS. A NUMBER IS LISTED
 ON LANDSCAPE TITLE BLOCKS BUT IT IS
 UNCLEAR WHAT THIS NUMBER IS AS IT DOES
 NOT COME UP IN THE STATE?S WEBSITE:
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.
 PLEASE ALSO KNOW NUMEROUS SEARCHES UNDER
 DBPR?S SITE FOR OTHER FIRMS HAVE NOT
 DELIVERED ANY OTHER LICENSE INFORMATION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION ON MANY
 OF THE TITLE BLOCKS ON PLANS. PLEASE SEE
 MISSING FIRM LICENSE NUMBERS WHICH ARE
 THE CERTIFICATE OF AUTHORIZATION NUMBERS
 FOR MORE THAN ONE FIRM. PLEASE SEE
 LANDSCAPE AND MEP ENGINEERING FIRMS.
 PLEASE ALSO SEE MANY SHEETS ARE MISSING
 THE PRINTED NAME AND LICENSE NUMBER FOR
 THE PERSON SIGNING AND SEALING SAID
 DOCUMENTS.
 PLEASE SEE MISSING THE PRINTED NAME AND
 PRINTED LICENSE NUMBER FOR ARCHITECT OF
 RECORD ON TITLE BLOCKS FOR STH.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE
 CODE 61G1-16.004 AND 61G15-23.002.
 FLORIDA STATUES 471.023, 481.219
 ** PLEASE KNOW THE ABOVE INFORMATION IS
 REQUIRED FOR ALL TRADES AND FOR ALL
 SHEETS WHETHER OR NOT COMMENTS ARE MADE
 BY OTHER REVIEWERS.
  
 3) NOTE:NO, PLEASE SEE SOME SHEETS IN
 SETS STILL CONTAIN A "RUBBER STAMP" FOR
 THE REQUIRED ORIGINAL SIGNATURE OF
 DESIGN PROFESSIONAL. THIS COMMENT IS FOR
 THE "S" SHEETS AND RESPONSIBLE
 STRUCTURAL ENGINEER.
 PLEASE SEE BUILDING REVIEW NOTES ALSO
 UNDER FOUNDATION PERMIT AS THE "S"
 SHEETS FOR SECOND REVIEW ALL CONTAINED
 THE SAME "RUBBER STAMP".
 ** IMPORTANT** PLEASE SEE NEW NOTE BELOW
 FOR OTHER DESIGNERS OF RECORDS AND
 SIGNATURES NOW ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE OTHER SHEETS WHICH CONTAIN A
 "STAMP" FOR THE REQUIRED "ORIGINAL"
 SIGNATURE BY THE DESIGN PROFESSIONAL.
 PLEASE SEE "S" SHEETS.
 FLORIDA STATUES 471.025
 PLEASE ALSO SEE ANY COMMENTS FROM OTHER
 TRADES WHICH RESPECT TO THE SEAL
 CONTAINING THE WORDING OF "CERTIFICATE"
 WHICH IS NOT LONGER ACCEPTED.
 FAC 61G1-16.001
  
 4) NOTE:NO, PLEASE SEE "A0.12" AS
 PLANS MENTIONS "EMERGENCY AND STAND-BY
 POWER SYSTEMS" PER NFPA-72 2002.
 PLEASE ADJUST AS THE EMERGENCY AND
 STAND-BY SYSTEMS ARE FROM NFPA-110 2002
 AND NFPA-72 2002 IS A SEPARATE CODE
 "NATIONAL FIRE ALARM CODE".
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS SHALL CONTAIN THE
 FOLLOWING MIN CODES REFERENCED AND
 LISTED ON PLANS FOR DESIGN.
 THE ARCHITECTURAL LISTS THE 2004 FBC.
 PLEASE LIST:
 2002 NFPA-70 NATIONAL ELECTRICAL CODE
 2003 NFPA-101 LIFE SAFETY CODE
 2003 NFPA-20 FIRE PUMPS
 2002 NFPA-110 EMERGENCY AND
 STANDBY POWER SYSTEMS.
 NFPA-72 2002
 THESE ARE REQUIRED AT A MIN.
  
 5) NOTE:NO, PLEASE SEE NOT ALL
 MANUFACTURE SPECS/CUT SHEETS WERE
 LOCATED ON BOOKS AND SUBMITTED PACKAGES.
 PLEASE SEE MISSING SPEC FOR THE
 "PARALLELING SWITCH GEAR". IT WAS NOTED
 THAT THE BOOKS CONTAIN AN ELEVATION OF
 THE SWITCH GEAR, HOWEVER NOTHING COULD
 BE LOCATED FROM MANUFACTURE ETC SHOWING
 LISTINGS FROM A NRTL.
 ** WHEN RESUBMITTING SPEC/PRODUCT BOOKS
 PLEASE PROVIDE TAB/LABELS FRO ALL
 ITEMS/EQUIPMENT LOCATED IN SAID BOOK AS
 WINDOWS, DOORS AND OTHERS ARE TABBED.
 PLEASE KNOW, THIS WILL HELP GREATLY IN
 THE REVIEW PROCESS TO FIND ALL ITEMS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR THE FOLLOWING.
 GENERATOR(S), ATS SWITCHES, FIRE PUMP,
 FIRE PUMP CONTROLLER, FUEL TANK,
 PARALLELING SWITCH GEAR AND OTHER
 ASSOCIATE SWITCHGEAR.
 PLEASE KNOW, NONE OF THESE WERE
 SUBMITTED AND UNABLE TO VERIFY MANY
 ITEMS FOR CODE COMPLIANCE AT THIS TIME.
 PLEASE BE SURE ALL EQUIPMENT SHEETS
 /SPECS CONTAIN LISTINGS FROM A NRTL.
  
 6) NOTE: NO, PLEASE KNOW AS OF THE DATE
 OF THIS REVIEW THESE ITEMS ARE NOT PART
 OF THIS LEGAL ADDRESS. PLEASE KNOW THESE
 MUST BE A LEGAL PART OF THIS BUILDING AS
 THESE ARE PART OF THE LIFE SAFETY OF
 SAID BUILDING. PLEASE KNOW THAT THE
 CORRIDOR WORK AND ANY WORK LOCATED ON
 "B-BLOCK" PARKING GARAGE PROPERTY WILL
 MOST LIKELY BE REQUIRED UNDER SEPARATE
 PERMIT. PLEASE SEE THAT ELEVATOR IS
 BEING FED FROM THIS NEW BUILDING AND
 SHALL BE PART OF THIS LEGAL PROPERTY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS SEEM TO INDICATE THE
 2000KW GENERATORS LOCATED ON A SEPARATE
 PROPERTY. PLEASE KNOW, PROPERTY LINES
 MAY CHANGE, SEPARATE PERMIT MAY BE
 REQUIRED ALSO IF INDEED THESE ARE ON
 SEPARATE PROPERTIES. THERE MAY ALSO BE
 THE POSSIBILITY OF EASEMENTS WHICH MAY
 NEED TO BE GRANTED.
 PLEASE ALSO SEE THE ELEVATOR TOWER BEING CONSTRUCTED
 NEXT TO THE PARKING GARAGE
 ALSO SEEM TO BE ON A SEPARATE LEGAL
 PROPERTY BEING FED FROM THE MAIN TOWER.
 PLEASE KNOW THIS MAY NOT BE POSSIBLE
 DEPENDING ON THE OUTCOME OR CHANGES IN
 PROPERTY LINES ETC.
 PLEASE SEE THE PROPOSED WORK IN CORRIDOR
 LOCATED AT THE "B" BLOCK GARAGE
 STRUCTURE WILL BE REQUIRED UNDER A
 SEPARATE PERMIT.
 ** PLEASE ALSO SEE BUILDING REVIEW
 COMMENTS FOR ABOVE AS MANY OF THESE
 ITEMS ARE TO BE PLACED IN BUILDING
 REVIEW AND MAY AFFECT PLANS SUBMITTED.
  
 7) NOTE: OK.
  
 8) NOTE: OK. GATES MUST CONTAIN MANUAL
 OPERATION UNDER POWER FAILURE.
  
 8) NOTE: NO, PLEASE SUBMIT ALL AS
 REQUESTED. PLEASE SEE THAT THE "HAND
 DRAWN" PANEL SCHEDULES SUBMITTED IN
 SUBMITTAL BOOKS IS NOT ACCEPTABLE TO THE
 AHJAS THIS INFORMATION IS PART OF THE
 DESIGN OF THE BUILDING WHICH SHALLBE
 PLACED IN DRAFTSMAN'S LIKE QUALITY IN
 THE COMPLETED SETS OF PLANS SUBMITTED
 WITH ALL RELEVANT TITLE BLOCKS, SIGNED,
 DATED AND SEALED BY THE DESIGN
 PROFESSIONAL OF RECORD.
 PLEASE SEE THAT THESE PANEL SCHEDULES
 CONTAIN ALL ROOM/AREA DESIGNATIONS ,
 CIRCUITS, OCP AND CONDUCTOR SIZES.
 FBC 106.1.3, 106.3.5.1.2, NEC 408.4,
 240.4,310.16, FS 471.025, FAC
 61G15-23.002
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETED PANEL SCHEDULES
 FOR ALL PANELS. THE PANELS ARE INDICATED
 ON E3.03 ARE NOT SUFFICIENT FOR REVIEW
 OF ALL SAID ELECTRICAL BRANCH CIRCUITS
 FOR OVER CURRENT PROTECTION, CONDUCTOR
 SIZES ETC.
 215.5
 MANY ITEMS CAN NOT BE REVIEWED AT THIS
 TIME.
 AN EQUIPMENT SCHEDULE AS SUBMITTED IS
 OK, HOWEVER THESE ITEMS SHOULD BE LISTED
 ON PANEL SCHEDULES TO BE SUBMITTED.
  
 9) NOTE: NO.RESPONSE LETTER FROM
 DESIGN TEAM MENTIONS THIS WAS AND IS
 COMPLETE AS OF FIRST REVIEW HOWEVER
 PLEASE SEE MANY ITEMS ON PLANS WHICH DID
 NOT PREVIOUSLY CONTAIN CIRCUIT #'S ETC,
 NOW DO.HOW PLANS ARE CIRCUITED AND
 WITH THE DEVICES DENOTING A NUMERICAL IDENTIFICATION
 AND HOW THAT CORRELATES
 WITH PANEL AND PANEL SCHEDULES IS KNOWN
 BY THIS REVIEWER/OFFICE AND WHAT COMMON
 PRACTICE IS AND HAS BEEN ACROSS THE
 COUNTRY AND THIS JURISDICTION. PLEASE
 KNOW THE INTENT OF THE COMMENT WAS NOT
 TO PLACE THE COMPLETE "SWITCH LEGS" OR
 TO SHOW ACTUAL "BRANCH CIRCUITING" ON
 SAID PLANS.
 PLEASE SEE NUMEROUS AREAS ON PLANS WHICH
 CONTAIN A NUMBER WHICH COULD CORRELATE
 TO MORE THAN ONE CIRCUIT AND PANEL.
 PLEASE SEE REDLINED PLANS FOR THESE.
 E1.01 ETC.
 PLEASE SEE ONE EXAMPLE IS THE NUMBER "4"
 ON 1.01. THIS COULD BE CIRCUITED TO A
 MINIMUM OF THREE CIRCUITS FROM THREE
 SEPARATE PANELS AS NOT ALL OF THE NUMBER
 "4"S? ARE CONNECTED, OR SEPARATED BY ANY
 LINE DENOTINGSEPARATE AREAS OR OTHER
 MEANS TO CONNECT THOSE NUMBERS TO BE ON
 ONE CIRCUIT. PLEASE SEE OTHERS ARE LIKE
 THIS ALSO. PLEASE SEE THERE ARE STILL
 SOME FIXTURES ETC WHICH CONTAIN A
 "NUMBER" HOWEVER NO CIRCUIT DESIGNATION
 ON THE ENTIRE SHEET CORRELATES TO THE
 NUMERICAL NOTATION.
 PLEASE SEE ONE SET OF PLANS HAS BEEN
 REDLINED WITH THESE AREAS AS NOTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE ALL THE CIRCUITING AND
 SWITCH LEGS ON PLANS AND LAYOUTS. PLEASE
 SEE MANY AREAS ARE LEFT TO FIGURE WHERE
 THESE DEVICES, OUTLETS, OR LIGHTING
 OUTLETS ARE BEING FED FROM AND/OR
 CONTROLLED.
 PLEASE CORRELATE WITH PANEL SCHEDULES TO
 BE SUBMITTED.
 215.5
  
 10) NOTE: NO. PLEASE KNOW IT WAS NOT THE
 INTENT OF COMMENT TO COMPLETELY REMOVE
 CORRIDORS AS THESE ARE REQUIRED. PLEASE
 KNOW AS THE FUTURE TENANT LAYOUTS ARE
 NOT KNOWN AT THIS TIME THE CORRIDORS
 WILL BE REQUIRED FROM THE BASE BUILDING
 LAYOUT. TENANT BUILD OUTS WILL NOT
 INCLUDE BASE BUILDING CORRIDOR BUILD
 OUTS AND THE ELECTRICAL ROOMS, DATA,
 TELEPHONE ROOMS SHALL BE ACCESSIBLE FOR
 BASE BUILDING DESIGN. PLEASE ALSO SEE
 BUILDING REVIEW COMMENTS FOR OTHER AREAS
 WHICH WILL REQUIRE ACCESS TO STAIR
 TOWERS ETC.
 PLEASE SEE THESE CORRIDORS ARE REQUIRED
 AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE ARCHITECTURAL PLANS
 WITH ELECTRICAL. PLEASE SEE FLOORS 6-14
 ARE SHOWN CONTAINING A CORRIDOR TO MAIN
 ELECTRICAL ROOM ON EACH OF THESE FLOORS
 ON ELECTRICAL PLANS, HOWEVERARCH DO
 NOT SHOW THESE CORRIDORS OF COMMON
 AREAS.?
 PLEASE SEE FLOORS 15 AND 16 ON BOTH A
 AND E'S DO NOT SHOW ANY CORRIDORS AND
 OBTAININGACCESS TO THE ELECTRICAL ROOM
 ON EACH OF THOSE FLOORS ARE ONLY THROUGH
 THE PROPOSED FUTURE TENANT SPACE. PLEASE
 KNOW IT IS NOT KNOWN AT THIS TIME IF
 THERE WILL BE ONE, TWO THREE OR MORE
 TENANTS ON EACH FLOOR AND ACCESS TO EACH
 TENANT?S ELECTRICAL PANEL(S) AND OVER
 CURRENT PROTECTION DEVICES MAY NOT BE
 THROUGH TENANT OCCUPANCY. PLEASE ALSO
 KNOW THE HOUSE POWER/COMMON AREAS MAY
 ALSO NOT BE ACCESSED THROUGH THE
 TENANT?S SPACE.
 PLEASE KNOW, EACH CORRIDOR AS SHOWN ON
 FLOORS 6-14 SHALL BE THE SAME ON ALL
 FLOORS AND SHOULD CORRELATE AS THE SAME
 ON ARCHITECTURAL SHEETS.
 210.25, 215.5, 240.24
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: NO, NOT ALL COULD BE VERIFIED
 AT THIS TIME AS THE MAINS AND LOCATIONS
 OF THE PARALLEL SWITCH GEAR COULD NOT BE
 LOCATE DON PLANS AND MAINS FOR THIS
 EQUIPMENT IS NOT YET VERIFIED TO CONTAIN
 THE MAINS ARE REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY ALL MAINS AND
 DISTRIBUTION EQUIPMENT CONTAINING ALL
 MAINS, GROUPING ETC PER 230.70, 230.72,
 230.76, 230.79, AND 225.31-225.39
 PLEASE KNOW, DUE TO THE INFORMATION OF
 THE SWITCH GEAR NOT SUBMITTED, SHOWN AND
 WHETHER OR NOT THESE CONTAIN MAINS, WITH
 MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT, GROUPED
 ETC. THE LOCATIONS OF SOME SERVICE
 EQUIPMENT CAN NOT REVIEWED FOR LOCATIONS
 AT THIS TIME.
  
 14) NOTE:NO. SAME NOTE. PLEASE KNOW
 THERE SEEMS TO BE SOME CONFUSION OVER
 THE PREVIOUS COMMENT. PLEASE SEE THE
 MAINS FOR THE EMERGENCY SYSTEM AND
 LEGALLY REQUIRED SYSTEM SHALL NOT BE
 LOCATED IN THE SAME ENCLOSURE AS THE
 NORMAL POWER IN SWBDB.
 PLEASE KNOW THIS OFFICE/CODE OFFICIAL
 WILL NOT ACCEPT THE EMERGENCY MAINS
 LOCATED IN THE SAME EQUIPMENT AND THERE
 WILL BE NO EXCEPTIONS OR SPECIAL
 CONDITIONS GRANTED BY THIS AHJ.
 NFPA-70, 700.12, 701.11, NFPA-110
 CHAPTER 7, 7.2 ETC
 IF A MEETING IS BEING REQUESTED THIS IS
 WILL AND SHOULD BE DONE ONCE ALL REVIEWS
 ARE DONE. IF THE DESIGNER OF RECORD AND
 DESIGN ENGINEER WOULD LIKE TO DISCUSS
 THIS OVER THE PHONE, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE AS
 DONE ON NUMEROUS OCCASIONS BEFORE THESE
 PLANS WERE SUBMITTED FOR INITIAL REVIEW.
 THIS OFFICE HAS CONSULTED WITH A MR.
 DAVID WORKS ON MANY ITEMS BEFORE
 SUBMITTING PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE EMERGENCY SYSTEMS ARE
 BEING SHOWN IN THE SAME EQUIPMENT AS THE
 NORMAL MAINS. PLEASE KNOW THESE SHALL
 NOT BE LOCATED IN THE SAME EQUIPMENT AND
 SERVED BY THE SAME SERVICE.
 PLEASE REVISE SERVICE AS SHOWN. 701.1,
 NFPA-110 CHAPTER 7 ETC.
  
 15) NOTE: OK.
  
 16) NOTE: OK.
  
 17) NOTE: OK.
  
 18) NOTE:OK, PLEASE HOWEVER SUBMIT
 THIS ELEVATION FROM THE "SLOSH" CHARTS.
 THIS SHOULD BE OBTAINED FOR RECORD SETS
 OF PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 THE PLEASE PROVIDE THE ELEVATION OF THE
 EM DISTRIBUTION SYSTEM AND EQUIPMENT.
 PLEASE SEE NFPA-110 7.2.3* WHICH
 REQUIRES THE ELEVATION TO MEET THE
 "SLOSH" PREDICTION LEVELS BASED ON A
 CATEGORY 4 STORM.
 THE ELEVATION FOR PROPERTY SHOULD BE OK,
 HOWEVER THIS ELEVATION IS REQUIRED TO BE
 STATED ON PLANS AND VERIFICATION THAT
 ALL REQUIRED EMERGENCY SYSTEMS IS ABOVE.
  
 19) NOTE: NO, PLEASE KNOW THE LIGHTING
 SUBMITTAL PACKAGE MAY BE SUBMITTED AT A
 LATER DATE ALSO. PLEASE KNOW HOWEVER ALL
 FIXTURES AND DETAILED INFORMATION FOR
 SAID FIXTURES WILL BE REQUIRED ON THE
 RECORD SET OF PLANS AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE FIXTURE SCHEDULES AND
 PLEASE CORRELATE ALL FIXTURES AS SHOWN
 ON PLANS WITH THE FIXTURES SCHEDULES
 SUBMITTED.
 215.5
  
 20) NOTE: OK, HOWEVER PLEASE SEE GF
 PROTECTION IS STILL BEING SHOWN FOR 225A
 AND 800A MAINS IN SWBDB. PLEASE SEE
 PREVIOUS COMMENT ABOVE #14 AS THESE WILL
 BE REQUIRED TO BE REMOVED FROM THE
 SWBDB.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER IS SHOWING GFI
 PROTECTION FOR SOME MAINS???
 PLEASE SEE GF (GROUND FAULT) PROTECTION
 IS REQUIRED PER 240.13, 230.95 ETC,
 HOWEVER PLEASE SEE GFI PROTECTION IS
 PERSONNEL PROTECTION.
 PLEASE SEE PROTECTION IS ALSO BEING
 SHOWN ON ALL SECONDARY OVER CURRENT
 PROTECTION??
 PLEASE KNOW, THIS IS NOT REQUIRED FOR
 THIS STRUCTURE, CLASS AND OCCUPANCY, BUT
 HOWEVER IS PERMITTED.
 PLEASE ALSO SEE GF SEEMS TO BE SHOWN ON
 THE EM SIDE OF THE DISTRIBUTION
 SYSTEM(S) WHICH IS UNCLEAR. PLEASE SEE
 700.7D, 700.26, NFPA-110
 PLEASE SEE THE CODE IS CLEAR WHEN GROUND
 FAULT PROTECTION IS REQUIRED AND WHEN
 SENSING OF SUCH GROUND FAULTS ARE
 REQUIRED , HOWEVER PLEASE KNOW GROUND
 FAULT PROTECTION IS NOT IDEALON THE
 EMERGENCY SIDE DUE TO THE NATURE OF THE
 EMERGENCY DISTRIBUTIONSYSTEM AND THE
 NEED OF MAINTAINING CERTAIN SYSTEMS ON
 DURING AN EMERGENCY.PLEASE KNOW,
 SENSING OF THE GROUND FAULT WOULD BE
 NEEDED TO CORRECT ANY SITUATION IN SUCH
 EQUIPMENT. PLEASE KNOW IT HAS BEEN
 DETERMINED BY THIS AHJ THAT THE GF
 PROTECTION ON THE REQUIRED EM SYSTEMS
 SHOULD NOT BE PROVIDED AND ONLY SENSING
 FOR THE PURPOSE AS STATED AND REQUIRED.
  
 21) NOTE:OK, GROUNDING FOR SEPARATELY
 DERIVED SYSTEM HAS NOW BEEN ADDED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, 4-POLE ATS SWITCHES ARE
 BEING SHOWN AS REQUIRED TO ACHIEVE THE
 CORRECT GROUND FAULT SENSING, HOWEVER
 THE GENERATORS DO NOT SEEM TO BE
 INDICATED A SEPARATELY DERIVED AS
 REQUIRED.
 250.30, 250.50.
  
 22) NOTE: OK.
  
 23) NOTE:NO, PLEASE PLACE NOTE ON
 PLANS FOR ROOF TOP SHEETS.
 SPEC BOOKS WERE REVIEWED FOR THIS NOTE
 AND INFORMATION IN SPECS IS OK.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE A NOTE ON PLANS MENTIONS THAT
 A LIGHTNING PROTECTION SYSTEM WILL BE
 REQUIRED.
 PLEASE KNOW, THIS SYSTEM MAY ONLY BE
 INSTALLED BY A CERTIFIED LIGHTNING
 PROTECTION CONTRACTOR WHO CAN CERTIFY
 SUCH A SYSTEM UNDER UL 96 AND NFPA-780.
 THIS SHALL BE A SEPARATE PERMIT, WITH
 PLANS AND FEES.
 PLEASE KNOW HOWEVER A NOTE SHALL BE
 PLACE ON THESE ELECTRICAL PLANS ON ROOF
 TOP PLANS STATING; "ALL OR ANY LIGHTNING PROTECTION
 SYSTEMS SHALL BE INSTALLED
 PER NFPA-780 AND LISTED PER UL 96." THIS
 WORDING SHOULD BE TO THAT SAME AFFECT,
 BUT NOT REQUIRED TO BE STATED AS ABOVE.
 PLEASE KNOW, THIS AHJ DOES NOT ACCEPT
 ANY OTHER SYSTEM NOT ACCEPTED BY
 NFPA-780. PLEASE KNOW THERE ARE MANY
 SYSTEMS ON THE MARKET WHICH CLAIM TO
 "PREVENT" OR "DISSIPATE" LIGHTNING ETC
 WHICH ARE NOT PERMITTED.
  
 24) NOTE: NO, PLEASE SEE NOTE ABOVE WITH
 RESPECT TO COMPLETED PANEL SCHEDULES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 620.23 ABC AND 620.24 ABC
 FOR REQUIRED CIRCUITS AND CONTROLS.
 PLEASE SEE ALL CAN NOT BE VERIFIED AT
 THIS TIME.
  
 25) NOTE: NO, COULD NOT LOCATE
 INFORMATION ON CALCULATIONS AND
 PERMITTED WATTAGE USAGE AND LIGHTING
 POWER DENSITIES.
 PLEASE SEE 13-415.1.AB.1,
 13-415.2.ABC.1, SEE TABLES 415.2.C.1 AND 415.2.B.1.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 2004 FBC CHAPTER 13.
 PLEASE SEE 13-413.1.ABC.1 FOR A WORST
 CASE SCENARIO TO BE PROVIDED FOR FEEDERS
 AND BRANCH CIRCUITS.
 PLEASE SEE 13-413.1.ABC.2.2.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, 13-415.1.ABC.1.3 FOR
 LIGHTING AND CONTROLS FOR ALL AREAS.
 PLEASE SEE SOME EXCEPTIONS ARE
 PERMITTED.
 PLEASE SEE OUTSIDE AREAS , TANDEM WIRING
 ETC.
  
 26) NOTE: NO, PLEASE SEE FIRST FLOOR
 FUTURE RETAIL SPACES AS MINIMAL FIXTURES
 COULD NOT BE LOCATED. THIS WAS CONFIRMED
 ONCE AGAIN WITH THE FIRE MARSHAL'S
 OFFICE AND FIRE PREVENTION CHIEF.
 PLEASE SEE ALL AREAS ON OTHER FLOORS
 WERE DONE TO PROVIDE THE MINIMAL
 LIGHTING.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE MINIMUM LIGHTING FOR EGRESS
 ETC WILL BE REQUIRED INSIDE THE FUTURE
 TENANT BUILD OUT SPACES. THIS HAS ALSO
 BEEN CONFIRMED ALSO WITH THE FIRE
 MARSHAL?S OFFICE AND WILL BE REQUIRED.
 THESE SHOULD BE WIRED INTO THE HOUSE
 PANELS AT THIS TIME AND CAN BE REMOVED
 ONCE TENANT OCCUPANCY TAKES PLACE.
 PLEASE ALSO SEE EXIT LIGHTS.
 IF THESE AREAS ARE OCCUPIED AT ANYTIME
 FOR ANY REASON BEFORE A BUILD OUT HAS
 TAKEN PLACE AND THE POWER GOES OUT,
 MINIMUM LIGHTING SHALL BE PROVIDED TO
 DIRECT ANY SAID OCCUPANTS TO THE EXIT. NFPA-101,7.8,
 7.9.
  
 27) NOTE:OK, SPECS WERE SUBMITTED
 HOWEVER STILL NEED TO VERIFY THE MANUAL
 MEANS OF DISCONNECT LOCATED ON THE
 OUTSIDE OF EQUIPMENT ALONG WITH
 ISOLATING SWITCH ETC. PLEASE SEE THE
 SPECS SUBMITTED DO NOT SEEM TO CONTAIN
 THESE?
 NFPA-20 10.4.2, 2003.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PREVIOUS NOTES ABOVE WHICH
 REQUESTED THE MANUFACTURES SPEC/CUT
 SHEETS FOR THE FIRE PUMP AND FIRE PUMP
 CONTROLLER. PLEASE KNOW, THE PLANS SHALL
 INDICATE THE OCP AND LOCKED ROTOR OCP.
 PLEASE SEE RISER NOW SEEMS TO INDICATE
 THE FPC TO BE LISTED ETC. PLEASE KNOW,
 IF THE FCP MEETS NFPA-20 FOR THE
 DISCONNECT MEANS RATED FOR THE LOAD
 SERVED LOCATE ON THE OUTSIDE OF THE
 EQUIPMENT AND CONTAINS THE OVER CURRENT
 PROTECTION SET AT LOCKED ROTOR AS
 REQUIRED BY 695.4B1 AND NFPA-20
 10.4.2,10.4.2.2, 10.3.6, 10.4.4 ETC.
 PLEASE SEE RISER SHOWS AN ADDITIONAL
 800A DISCONNECT LOCATED AHEAD OF THE
 LISTED FPC? PLEASE VERIFY AND CLARIFY
 THIS.
  
 28) NOTE:NO, PLEASE SEE RESPONSE
 LETTER MENTIONS TO SEE SPECS 2.18 FOR
 THIS , HOWEVER SHEETS IN SPEC BOOKS SEEM
 TO CONTAIN A MISSED SHEET OR MISPRINT AS
 THIS SECTION FOR THIS INFORMATION FOR
 NUMERICAL RESPONSE NOTED ABOVE COULD NOT
 BE LOCATED. PLEASE KNOW IN EITHER CASE
 THE AMOUNT OF FUEL SHALL BE STATED ON
 PLANS ALONG WITH THE GPH AND TIME FOR
 ALL LOADS AT 100%. THESE TIMES ARE
 REQUIRED ON THE PLANS.
 FBC 106.1.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FUEL IS REQUIRED PER NFPA-20
 FOR A MINIMUM OF 8HRS AT 100% FOR FIRE
 PUMP AND ALL OTHER ASSOCIATED LOADS,
 INCLUDING ETC.
 6-6.2
  
 29) NOTE: OK. SUB BASE TANK IS PART OF
 THE GEN.
  
 30) NOTE: OK AS NOTED.
  
 31) NOTE: NO, PLEASE SEE PLANS NOW
 MENTION CONDUITS AND MI CABLES AS
 OPTIONS. ?? PLEASE KNOW THE ACTUAL
 INSTALLATION SHALL BE SPECIFIED AT THIS
 TIME. REVISIONS TO THIS MAY BE DONE AT
 LATER DATE ONCE THE PERMIT IS ISSUED.
 PLEASE SEE 700.9D1 AS MENTIONED WHEN
 REQUIRED. PLEASE SEE THIS BUILDING IS
 100% SPRINKLED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY "MI" CABLES BEING SHOWN
 ON PLANS AND RISER IN MANY LOCATIONS.
 PLEASE KNOW, THIS IS ONLY A NOTE AS THIS INSTALLATION
 FOR MI CABLE IS NOT COMMON
 FOR THIS TYPE OF CABLE. THIS IS
 PERMITTED AND IS IN NO WAY A NOTE FOR
 CORRECTION. THIS IS ONLY NOTED, AS IF
 SHOWN ON PLANS, THIS WILL BE REQUIRED
 AND IN LIEU OF REVISING PLANS AT A LATER
 DATE CHANGES CAN BE MADE IF THESE ARE
 NOT INTENDED.
 PLEASE INDICATE THE CABLE DEGREE
 RATINGS.
  
 32) NOTE:OK, AS MAINS ARE NOW SHOWN ON GENERATORS AND
 GROUNDING RISER DETAILS
 SD SYSTEM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS ARE BEING SHOWN FROM THE
 GENERATORS.
 250.30
  
 33) NOTE:OK, THIS INFORMATION ON PLANS
 IS NOW BEING SHOWN. PLEASE KNOW, SPEC
 WERE NOTE ORIGINALLY SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE OCP AT THE
 GENERATORS.
 215.5
  
 34) NOTE:OK, THE SIZES OF THE
 CONDUCTORS ARE NOW VERIFIED AT THIS
 REVIEW AS THE OVER CURRENT PROTECTION IS
 NOW BEING SHOWN ON THE GENERATORS. THIS
 COULD NOT VERIFIED ON PREVIOUS REVIEW AS
 THE OCP WAS NOT SHOWN ON GENERATORS AND
 SPEC BOOKS WERE NOT SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 445.13 FOR MIN SIZES OF THE
 FEEDERS FROM THE GENERATORS.
  
 35) NOTE: NO, PLEASE SEE COMPLETED
 PANELS HAVE NOT BEEN SUBMITTED IN SETS
 FOR REVIEW. PLEASE ALSO SEE CALCULATIONS
 PROVIDED ARE UNCLEAR AS LOADS SHOWN CAN
 NOT BE VERIFIED WITH NEC. PLEASE LOADS
 AS SHOWN DO NOT DETAIL HOW LOADS WERE
 DERIVED. PLEASE ALSO SEE CONTINUOUS
 LOADS AND LARGEST MOTOR LOADS AT 125%
 COULD NOT BE LOCATED.
 WATTS PER SQ FT, KNOWN LOADS ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR THE BUILDING SERVICES
 AND PANELS.
 PLEASE SEE 220,220.3, 220.10, 220.11,
 220.13 ETC.
 PLEASE ALSO INDICATE ALL CONTINUOUS
 LOADS AND LARGEST MOTOR LOADS AT 125%.
 215.3, 230.42 ETC.
  
 36) NOTE: NO, PLEASE PROVIDE MINIMUM
 GUTTER SIZE(S) AT THIS TIME. THIS MAY BE
 REVISED ONCE CONDUITS ENTRIES ARE KNOW
 OR IF THEY ARE CHANGED AT A LATER DATE.
 THIS IS AND WILL BE REQUIRED ON PLANS BY
 THE RESPONSIBLE DESIGNER OF RECORD.
 FBC 106.1.2
  
 * PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE GUTTER SIZES ON
 RISER. THIS IS REQUIRED AT THIS TIME
 BASED ON THE MINIMUM DIMENSIONS REQUIRED
 FOR TURNING RADIUS AND BASED ON THE CONDUCTORS/FEEDERS
 ARE SHOWN ON RISER.
 368,215.5
  
 37) NOTE: NO. RESPONSE LETTER MENTIONS
 TO SEE TRANSFORMER SCHEDULE WHICH WAS ON
 PREVIOUS PLANS. PLEASE KNOW THE
 GROUNDING ELECTRODE SIZES AS NOTED ON
 TRANSFORMER SCHEDULE WAS NOT PART OF
 THIS NOTE. THE RISER SHOULD SHOW OR NOTE
 THE ATTACHMENT LOCATIONS. PLEASE ALSO
 CORRELATE WITH THE NEXT COMMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE AND SHOW ALL ATTACHMENT
 LOCATIONS FOR THE TRANSFORMERS AS SHOWN
 ON RISER. PLEASE SEE 250.50,250.30,
 250.66 ETC.
  
 38) NOTE: NO. RESPONSE MENTIONS TO SEE
 GROUND RISER ON 3.04, HOWEVER THIS
 DETAIL IS FOR THE GROUNDING ELECTRODE
 SYSTEM. PLEASE SEE PREVIOUS NOTE AS THIS
 WAS TO PROVIDE A "GROUND RISER". THIS IS
 ONE FOR THE ENTIRE BUILDING THROUGH ALL
 FLOORS ETC. PLEASE KNOW THE MINIMUM SIZE
 WILL BE 3/0. PLEASE KNOW, THIS CAN BE
 DONE ON A SEPARATE SHEET AND EXISTING
 RISER DIAGRAM SHEET CAN NOTE TO SEE THIS
 SHEET OR THIS MAY BE PLACED ON THE RISER
 SHEETS IN LIGHT GRAY.
 FBC 106.1.2, NEC 250.58, 250.50 ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A ONE-LINE GROUND RISER
 ON RISER DIAGRAM OR SEPARATE SHEET.
 250.58, 215.5
  
 39) NOTE: NO. RESPONSE MENTIONS THIS
 REVIEW AND MODIFIED IF NECESSARY. PLEASE
 KNOW THIS IS PART OF THE REVIEW BY THIS
 OFFICE AND IS REQUIRED AT THIS TIME.
 PLEASE ALSO SEE NEW NOTES FOR CHANGES IN
 PLANS FROM FIRST REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE ALL OCP DEVICES FOR
 PANELS ON RISER AND PANELS SCHEDULE WHEN SUBMITTED.
 PLEASE SEE SOME OF THIS ON
 RISER DOES NOT CORRELATE AT THIS TIME
 WITH PANELS AS NOTED.
 215.5
  
 40) NOTE:NO. RESPONSE MENTIONS 250%
 FOR PRIMARY PLUS SECONDARY ETC. PLEASE
 SEE TABLE IN 450.3 WHICH CONTAINS
 (NOTES). PLEASE SEE NOTE BELOW TABLE IN
 ORDER TO USE THE250% ETC.
 PLEASE SEE THE NOTE #3 WHICH IS NEXT TO
 THE 250% IS ATTACHED TO THIS REVIEW.
 THIS IS TAKEN DIRECTLY FROM THE NEC:
 3. A TRANSFORMER EQUIPPED WITH
 COORDINATED THERMAL OVERLOAD PROTECTION
 BY THE MANUFACTURER AND ARRANGED TO
 INTERRUPT THE PRIMARY CURRENT SHALL BE
 PERMITTED TO HAVE PRIMARY OVERCURRENT
 PROTECTION RATED OR SET AT A CURRENT
 VALUE THAT IS NOT MORE THAN SIX TIMES
 THE RATED CURRENT OF THE TRANSFORMER FOR TRANSFORMERS
 HAVING NOT MORE THAN 6
 PERCENT IMPEDANCE AND NOT MORE THAN FOUR
 TIMES THE RATED CURRENT OF THE
 TRANSFORMER FOR TRANSFORMERS HAVING MORE
 THAN 6 PERCENT BUT NOT MORE THAN 10
 PERCENT IMPEDANCE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 450.3 FOR THE MAXIMUM OCP
 FOR TRANSFORMERS TO BE AT 125%. PLEASE
 KNOW, WHEN THE OCP DOES NOT CORRELATE,
 AND THEN IT IS PERMITTED TO GO TO THE
 NEXT SIZE UP, HOWEVER IT IS NOT
 PERMITTED TO GO MORE THAN THE STANDARDS
 OCP PROTECTION DEVICES AS LISTED IN
 240.6.
 PLEASE SEE TRANSFORMERS WHICH INDICATE
 THE OCP SET HIGHER THAN THE MAX 125%.
 215.5
  
 41) NOTE: OK. LT POLES REMOVED.
  
 42) NOTE: NO, COULD NOT LOCATE NOTES AS
 PREVIOUSLY REQUESTED ON PLANS.
 REQUIRED AT THIS TIME ON RECORD SET(S)
 OF PLANS.
 FBC 106.1.2, ETC AS NOTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, IT WAS NOTED THAT THE
 RISER DIAGRAM SHEET CONTAINED A NOTED
 FOR SIGNAGE PER 230.2E. PLEASE KNOW
 HOWEVER SIGNAGE, MAPPING SHALL BE
 REQUIRED AT ALL OTHER LOCATIONS; HOWEVER
 MOST IMPORTANTLY BE REQUIRED IN FULL IN
 THE FIRE COMMAND RM.
 PLEASE PROVIDE A NOTE FOR THE SIGNAGE ON
 THE SHEET FOR THE FC ROOM. PLEASE NOTE
 THAT ALL LETTERING SHALL BE A MINIMUM OF
 1? AND ON CONTRASTING BACKGROUND.
  
 43) NOTE:NO, COULD NOT LOCATE THIS
 INFORMATION AND NOTES ON PLANS.
 REQUIRED AT THIS TIME ON RECORD SET(S)
 OF PLANS.
 FBC 106.1.2 ETC AS NOTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-72 4.4.1.4.2.2 FOR THE
 REQUIRED DISCONNECTING MEANS FOR THE
 PRIMARY OF THE FIRE ALARM SYSTEM.
 PLEASE ALSO BE SURE ALL ITEMS ARE LISTED
 ON PLANS FOR THE FIRE COMMAND ROOM AS
 SET FORTH IN NFPA-10111.8, 11.8.5
  
 44) NOTE:SAME NOTE AS THE SAME WAS
 DONE ON THE REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINED ON ONE OF THE SETS OF
 SUBMITTED PLANS BUT IS IN NO WAY ALL
 POSSIBLE ITEMS AS MENTIONED ABOVE.
  
 45) NOTE: OK, PLEASE DO THE SAME ON NEXT RESPONSE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT A TYPE WRITTEN RESPONSE
 FROM THE DESIGN TEAM FOR EACH OF THE
 ABOVE COMMENTS WILL HELP IN EXPEDITING
 THE NEXT REVIEW PROCESS.
  
 ******** NEW NOTES ***********
  
 46) NOTE: PLEASE CORRELATE THE PARALLEL
 SWITCH GEAR RISER/ELEVATION SUBMITTED ON
 E3.03 WITH THAT OF THE OVERCURRENT
 PROTECTION DEVICES AS SHOWN AND LISTED
 ON RISER DIAGRAM.
 FBC 106.1.2
 NOT ON PREVIOUS REVIEW AS INFORMATION ON
 SW GEAR WAS NOTE SHOWN.
  
 47) NOTE: ** IMPORTANT **
 PLEASE SEE FS 471.025 AND FAC
 61G15-23.002 AS THESE REQUIRED UNDER
 FLORIDA LAW THAT THE ENGINEER OF RECORD
 HOLDING SAID LICENSE AND SEAL TO SIGN,
 DATE AND SEAL ALL SAID PLANS. PLEASE
 KNOW THAT THE SIGNING OF PLANS MAY NOT
 BE NOT BE DESIGNATED TO ANYONE OTHER
 THAN THE ENGINEER HOLDING SAID LICENSE.
 PLEASE SEE MECHANICAL, ELECTRICAL,
 PLUMBING AND FIRE ALARM (FA) SHEETS ARE
 NOW SIGNED WITH COMPLETELY DIFFERENT
 SIGNATURES THAN ON PREVIOUS SETS OF
 PLANS. IT IS KNOWN BY THIS OFFICE THAT
 AFTER SIGNING MANY SHEETS THAT A
 SIGNATURE WILL VARY, HOWEVER THESE ARE
 NOT EVEN CLOSE IN RESEMBLANCE OF ONE
 ANOTHER.
 PLEASE SUBMIT SIGNED, DATED AND SEALED
 LETTERS FOR LEGAL SIGNATURE
 VERIFICATION. PLEASE KNOW THESE LETTERS
 SHALL ALSO BE NOTARIZED AS LEGALLY
 REQUIRED IN THE STATE IN WHICH NOTARY IS
 HELD. IF THIS IS DONE IN THE STATE OF
 FLORIDA PLEASE SEE FS 117.05.
 PLEASE ALSO SUBMIT A PHOTO-COPY OF THE
 DRIVER?S LICENSE FOR SAID MEP DESIGNERS
 OF RECORD. PLEASE KNOW PERSONNEL
 INFORMATION SUCH AS THE DL # AND HOME
 ADDRESS MAY BE CROSSED OUT.
 *PLEASE KNOW ONE COMPLETE SET OF PLANS
 OF ORIGINAL SUBMITTED PLANS AND NEW SETS
 ARE BEING RETAINED BY THIS OFFICE.
 PLEASE ALSO KNOW THE "S" SHEETS OF ONE
 SET ARE ALSO BEING RETAINED BY THIS
 OFFICE.
 *PLEASE KNOW THESE PLANS MAY BE
 SUBMITTED TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS AND THE STATE?S
 LEGAL COUNSEL TO THE BOARD FOR PIER
 REVIEW AND REVIEW OF SAID VIOLATIONS
 INCLUDING INFORMATION AND LICENSURE
 REQUIRED AS NOTED ON PREVIOUS REVIEW.
 NOTE #2 ABOVE.
  
 48) NOTE: PLEASE SEE ENERGY CALCULATIONS
 ARE ALSO REQUIRED TO BE SIGNED, DATED
 AND SEALED BY THE RESPONSIBLE
 DESIGNER/ENGINEER OF RECORD.
 PLEASE SEE ALL SIGNATURES ON THESE
 CALCULATIONS AT THIS TIME DO NOT
 CORRELATE WITH THE SUBMITTED PLANS AS
 NOTED IN NOTE #47 ABOVE.
 PLEASE SEE THIS IS ALSO FOR THE
 ARCHITECT MR. MICHAEL ROSSIN AS THE
 SIGNATURES DO NOT CORRELATE.
  
 49) NOTE: PLEASE SEE SHEET "S"
 SITE/SURVEY IS NOT VALID UNLESS SIGNED,
 DATED AND SEAL AS REQUIRED UNDER FS
 4712.025, FAC 61G1-17
  
 50) NOTE: PLEASE SEE ATTACHED COPY OF
 FLORIDA STATUES 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT CODE COMPLIANT COMMENTS. PLEASE
 KNOW IF PLANS HAVE ANY OF THE SAME CODE
 COMPLIANT COMMENTS NOT ADDRESSED, A 4X
 FEE SHALL BE ASSESSED BASED ON PORTION
 OF PERMIT FEE ATTRIBUTED TO THE PLAN
 REVIEW. PLEASE KNOW THIS PLAN REVIEW
 POSTION IS 30% AND THIS WOULD BE TIMES
 FOUR.
 THIS IS ONLY GIVEN AS A NOTICE AT THIS
 TIME.
  
 PLEASE BE SURE TO ALL SEE ALL COMMENTS
 FROM ALL OTHER TRADES AND THEY MAY
 AFFECT ELECTRICAL PLANS AND DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS OR
 COMMENTS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2006-07-22 00:00:00REVIEW IN PROGRESS, FOR COMPLETETION
2006-07-17 00:00:00REVIEW IN PROGRESS
 ** REVIEW STOPPED.
 REVIEW TO CONTINUE ON 7/18
 AS OF REVIEW TO THIS TIME, PLANS WILL BE
 GOING INTO A "F" STATUS WITH COMMENTS
 TO FOLLOW ONCE REVIEW HAS BEEN
 COMPLETED.
2006-07-16 00:00:00ONE ROLL OF PLANS IN ELECTRIC FOR
 REVIEW ALONG WITH SPEC BOOKS, SUBMITTALS
 ETC IN BINDERS.
 REVIEW STOPPED, TO CONTINUE ON 7/17

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-06 Cont ID  
Sent By dpalmer Date 2006-06-06 Time 20:38 Rev Time 0.00
Received By dpalmer Date 2006-06-02 Time 18:53 Sent To  
Notes
2006-06-06 00:00:00 
 ***************UNSAT ***************
  
 CITY PLACE OFFICE TOWER
 525 OKEECHOBEE BLVD.
  
  
  
 *** PLEASE KNOW PLANS AND SUBMITTED
 PAPER WORK IS NOT COMPLETE AT THIS TIME
 FOR A COMPLETE AND SUFFICIENT REVIEW.
 PLEASE KNOW THERE MAY BE FURTHER
 COMMENTS ONCE ALL INFORMATION IS
 SUBMITTED.
  
 1) NOTE: PLEASE KNOW, BEFORE
 RE-SUBMITTING PLANS. PLEASE COMPLETELY
 REMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETED
 SETS FOR REVIEW AND STAMPING. PLEASE
 KNOW SINCE MANY OF THE COMMENTS BELOW
 AFFECT ALL OF THE SHEETS IN THE SETS,
 ONLY ONE ROLL OF OLD SETS SHOULD BE
 SUBMITTED FOR REFERENCE WHEN PLANS ARE
 BROUGHT BACK. THESE SHOULD BE LABELED
 "OLD/VOIDED".
  
 2) NOTE: PLEASE SEE MISSING INFORMATION
 ON MANY OF THE TITLE BLOCKS ON PLANS.
 PLEASE SEE MISSING FIRM LICENSE NUMBERS
 WHICH ARE THE CERTIFICATE OF
 AUTHORIZATION NUMBERS FOR MORE THAN ONE
 FIRM. PLEASE SEE LANDSCAPE AND MEP
 ENGINEERING FIRMS. PLEASE ALSO SEE MANY
 SHEETS ARE MISSING THE PRINTED NAME AND
 LICENSE NUMBER FOR THE PERSON SIGNING
 AND SEALING SAID DOCUMENTS.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE
 CODE 61G1-16.004 AND 61G15-23.002.
 FLORIDA STATUES 471.023, 481.219
  
 3) NOTE: PLEASE SEE OTHER SHEETS WHICH
 CONTAIN A "STAMP" FOR THE REQUIRED
 "ORIGINAL" SIGNATURE BY THE DESIGN
 PROFESSIONAL. PLEASE SEE "S" SHEETS.
 FLORIDA STATUES 471.025
 PLEASE ALSO SEE ANY COMMENTS FROM OTHER
 TRADES WHICH RESPECT TO THE SEAL
 CONTAINING THE WORDING OF "CERTIFICATE"
 WHICH IS NOT LONGER ACCEPTED.
 FAC 61G1-16.001
  
 4) NOTE: PLEASE SEE PLANS SHALL CONTAIN
 THE FOLLOWING MIN CODES REFERENCED AND
 LISTED ON PLANS FOR DESIGN.
 THE ARCHITECTURAL LISTS THE 2004 FBC.
 PLEASE LIST:
 2002 NFPA-70 NATIONAL ELECTRICAL CODE
 2003 NFPA-101 LIFE SAFETY CODE
 2003 NFPA-20 FIRE PUMPS
 2002 NFPA-110 EMERGENCY AND.
 STANDBY POWER SYSTEMS.
 NFPA-72 2002
 THESE ARE REQUIRED AT A MIN.
  
 5) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR THE FOLLOWING.
 GENERATOR(S), ATS SWITCHES, FIRE PUMP,
 FIRE PUMP CONTROLLER, FUEL TANK,
 PARALLELING SWITCH GEAR AND OTHER
 ASSOCIATE SWITCHGEAR.
 PLEASE KNOW, NONE OF THESE WERE
 SUBMITTED AND UNABLE TO VERIFY MANY
 ITEMS FOR CODE COMPLIANCE AT THIS TIME.
 PLEASE BE SURE ALL EQUIPMENT SHEETS
 /SPECS CONTAIN LISTINGS FROM A NRTL.
  
 6) NOTE: PLEASE SEE PLANS SEEM TO
 INDICATE THE 2000KW GENERATORS LOCATED
 ON A SEPARATE PROPERTY. PLEASE KNOW,
 PROPERTY LINES MAY CHANGE, SEPARATE
 PERMIT MAY BE REQUIRED ALSO IF INDEED
 THESE ARE ON SEPARATE PROPERTIES. THERE
 MAY ALSO BE THE POSSIBILITY OF EASEMENTS
 WHICH MAY NEED TO BE GRANTED.
 PLEASE ALSO SEE THE ELEVATOR TOWER BEING
 CONSTRUCTED NEXT TO THE PARKING GARAGE
 ALSO SEEM TO BE ON A SEPARATE LEGAL
 PROPERTY BEING FED FROM THE MAIN TOWER.
 PLEASE KNOW THIS MAY NOT BE POSSIBLE
 DEPENDING ON THE OUTCOME OR CHANGES IN
 PROPERTY LINES ETC.
 PLEASE SEE THE PROPOSED WORK IN CORRIDOR
 LOCATED AT THE "B" BLOCK GARAGE
 STRUCTURE WILL BE REQUIRED UNDER A
 SEPARATE PERMIT.
 ** PLEASE ALSO SEE BUILDING REVIEW
 COMMENTS FOR ABOVE AS MANY OF THESE
 ITEMS ARE TO BE PLACED IN BUILDING
 REVIEW AND MAY AFFECT PLANS SUBMITTED.
  
 7) NOTE: PLEASE CLARIFY USE AND
 EQUIPMENT IN THE CATERING ROOM AS STATED
 ON 6TH FLOOR. PLEASE LIST ALL 15/20AMP
 120V RECEPTS AS GFI/GFI PROTECTED AS PER
 210.8B3.
 (KITCHENS IN OTHER THAN DWELLING UNITS)
  
 8) NOTE: PLEASE SEE GATES ARE INDICATED
 AT TWO DIFFERENT LOCATIONS, HOWEVER
 ELECTRICAL TO THESE DO NOT SEEM TO BE
 COMPLETE AT THIS TIME.
 PLEASE PROVIDE INFORMATION FOR ACCESS
 AND EGRESS IN THE EVENT OF POWER FAILURE
 AND/OR OVER RIDE FOR THESE. PLEASE SEE
 FIRE REVIEW COMMENTS AS THIS MAY BE IN
 QUESTION.
  
 8) NOTE: PLEASE SUBMIT COMPLETED PANEL
 SCHEDULES FOR ALL PANELS. THE PANELS ARE
 INDICATED ON E3.03 ARE NOT SUFFICIENT
 FOR REVIEW OF ALL SAID ELECTRICAL BRANCH
 CIRCUITS FOR OVERCURRENT PROTECTION,
 CONDUCTOR SIZES ETC.
 215.5
 MANY ITEMS CAN NOT BE REVIEWED AT THIS
 TIME.
 AN EQUIPMENT SCHEDULE AS SUBMITTED IS
 OK, HOWEVER THESE ITEMS SHOULD BE LISTED
 ON PANEL SCHEDULES TO BE SUBMITTED.
  
 9) NOTE: PLEASE COMPLETE ALL THE
 CIRCUITING AND SWITCH LEGS ON PLANS AND
 LAYOUTS. PLEASE SEE MANY AREAS ARE LEFT
 TO FIGURE WHERE THESE DEVICES, OUTLETS,
 OR LIGHTING OUTLETS ARE BEING FED FROM
 AND/OR CONTROLLED.
 PLEASE CORRELATE WITH PANEL SCHEDULES TO
 BE SUBMITTED.
 215.5
  
 10) NOTE: PLEASE CORRELATE ARCHITECTURAL
 PLANS WITH ELECTRICAL. PLEASE SEE FLOORS
 6-14 ARE SHOWN CONTAINING A CORRIDOR TO
 MAIN ELECTRICAL ROOM ON EACH OF THESE
 FLOORS ON ELECTRICAL PLANS, HOWEVER
 ARCH DO NOT SHOW THESE CORRIDORS OF
 COMMON AREAS.?
 PLEASE SEE FLOORS 15 AND 16 ON BOTH A
 AND E?S DO NOT SHOW ANY CORRIDORS AND
 OBTAININGACCESS TO THE ELECTRICAL ROOM
 ON EACH OF THOSE FLOORS ARE ONLY THROUGH
 THE PROPOSED FUTURE TENANT SPACE. PLEASE
 KNOW IT IS NOT KNOWN AT THIS TIME IF
 THERE WILL BE ONE, TWO THREE OR MORE
 TENANTS ON EACH FLOOR AND ACCESS TO EACH
 TENANT'S ELECTRICAL PANEL(S) AND OVER
 CURRENT PROTECTION DEVICES MAY NOT BE
 THROUGH TENANT OCCUPANCY. PLEASE ALSO
 KNOW THE HOUSE POWER/COMMON AREAS MAY
 ALSO NOT BE ACCESSED THROUGH THE
 TENANT'S SPACE.
 PLEASE KNOW, EACH CORRIDOR AS SHOWN ON
 FLOORS 6-14 SHALL BE THE SAME ON ALL
 FLOORS AND SHOULD CORRELATE AS THE SAME
 ON ARCHITECTURAL SHEETS.
 210.25, 215.5, 240.24
  
 11) NOTE: PLEASE PROVIDE EXIT/EGRESS
 LIGHTING TO THE PUBLIC RIGHT OF WAY.
 PLEASE SEE THE PUBLIC RIGHT OF WAY IS
 NOT DIRECTLY OUTSIDE THE STAIR #2 DOOR
 AND THE PUBLIC RIGHT OF WAY SEEMS TO BE
 LOCATED AROUND THE FRONT OF THE
 BUILDING. PLEASE SEE BUILDING REVIEW
 NOTES FOR EXIT CORRIDOR FOR STAIR #2.
 PLEASE SEE PLANS REDLINED FOR POSSIBLE
 CHANGE WHICH MAY BE OPTED FOR.
 NFPA-101 7.8, 7.9.
  
 12) NOTE: PLEASE SEE CONDUITS AND
 FEEDERS FROM ATS #1 AND ATS #2 ARE BEING
 NOTED AS INSTALLED IN RATED EXIT
 CORRIDOR.
 PLEASE SEE THESE CONDUITS MAY NOT BE
 LOCATED AS SHOWN ON PLANS.
 THIS IS NOT SHOWN ON ARCHITECTURAL
 SHEETS AND THIS INFORMATION WAS GIVEN TO
 THE BUILDING REVIEWER. PLEASE SEE
 BUILDING NOTES.
  
 13) NOTE: PLEASE CLARIFY ALL MAINS AND
 DISTRIBUTION EQUIPMENT CONTAINING ALL
 MAINS, GROUPING ETC PER 230.70, 230.72,
 230.76, 230.79, AND 225.31-225.39
 PLEASE KNOW, DUE TO THE INFORMATION OF
 THE SWITCH GEAR NOT SUBMITTED, SHOWN AND
 WHETHER OR NOT THESE CONTAIN MAINS, WITH
 MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT, GROUPED
 ETC. THE LOCATIONS OF SOME SERVICE
 EQUIPMENT CAN NOT REVIEWED FOR LOCATIONS
 AT THIS TIME.
  
 14) NOTE: PLEASE SEE THE EMERGENCY
 SYSTEMS ARE BEING SHOWN IN THE SAME
 EQUIPMENT AS THE NORMAL MAINS. PLEASE
 KNOW, THESE SHALL NOT BE LOCATED IN THE
 SAME EQUIPMENT AND SERVED BY THE SAME
 SERVICE.
 PLEASE REVISE SERVICE AS SHOWN.
 701.1, NFPA-110 CHAPTER 7 ETC
  
 15) NOTE: PLEASE SEE SOME AREAS AT THE
 EXIT TO THE STAIRS IN THE PARKING
 GARAGES WILL BE REQUIRED TO CONTAIN A
 BATTERY BACK UP FIXTURE OF SOME SORT
 DEPENDING ON THE OPERATION OF THE
 STAND-BY GENERATORS. PLEASE CLARIFY IF
 ORDER OF OPERATION OF THE GENERATORS AS
 WILL BE SO THAT OF THE SINGLE OCP AT THE
 800KW GEN TRIPS THE OTHER TWO STAND-BY
 GEN?S WILL COME ONLINE?
 PLEASE SEE 7.9.2.2
  
 16) NOTE: PLEASE A KNOW, A BATTERY BACK
 UP LT FIXTURE WILL BE REQUIRED IN MAIN
 ELECTRICAL ROOM(S), MAIN ELECTRICAL RM
 ON 5TH FLR, ELEVATOR EQUIPMENT ROOMS,
 FIRE PUMP ROOM, FIRE COMMAND ROOMAND
 GEN ROOM. PLEASE KNOW SOME OF THESE ARE
 SHOWN ALREADY AND DO NOT NEED TO BE
 ADDED, HOWEVER SOME ARE NOT.
 700.16,7.8.1.3,7.9.2.2 700.22 ETC.
  
 17) NOTE: PLEASE SEE SOME ELECTRICAL
 ROOMS DOORS SEEM TO SWING INTO EITHER
 ELECTRICAL EQUIPMENT OR OTHER EQUIPMENT
 SHOWN ON PLANS.
 PLEASE SEE DOOR SWINGS ON SOME DOORS
 WILL BE REQUIRED TO SWING OUT (5TH FLOOR
 MAIN RM) .
 PLEASE SEE SOME ROOMS APPEAR TO SHOW
 EQUIPMENTIN THE MIN CLEARANCE AREAS
 REQUIRED PER 110.26.
 PLEASE ALSO PLACE NOTES ON PLANS AT
 LOCATION FOR MAIN ELECTRICAL ROOMS THAT
 ALL DOORS SHALL BE EQUIPMENT WITH SUCH
 ACCEPTED PANIC HARDWARE AND OPEN ON THE
 MEANS OF EGRESS WITH OUT ANY TRIPPING
 HAZARDS.
 PLEASE KNOW THIS WILL AFFECT DOOR
 SCHEDULE ON ARCHITECTURAL PLANS AND
 POSSIBLE DOOR SWINGS ON A SHEETS AS NOW
 SHOWN.
  
 18) NOTE: PLEASE PROVIDE THE ELEVATION
 OF THE EM DISTRIBUTION SYSTEM AND
 EQUIPMENT.
 PLEASE SEE NFPA-110 7.2.3* WHICH
 REQUIRES THE ELEVATION TO MEET THE
 "SLOSH" PREDICTION LEVELS BASED ON A
 CATEGORY 4 STORM.
 THE ELEVATION FOR PROPERTY SHOULD BE OK,
 HOWEVER THIS ELEVATION IS REQUIRED TO BE
 STATED ON PLANS AND VERIFICATION THAT
 ALL REQUIRED EMERGENCY SYSTEMS ARE
 ABOVE.
 PLEASE SEE THAT "SLOSH", MEANS SEA,
 LAKE, OVERLAND, SURGES BY HURRICANES.
  
 19) NOTE: PLEASE COMPLETE FIXTURE
 SCHEDULES AND PLEASE CORRELATE ALL
 FIXTURES AS SHOWN ON PLANS WITH THE
 FIXTURES SCHEDULES SUBMITTED.
 215.5
  
 20) NOTE: PLEASE SEE RISER IS SHOWING
 GFI PROTECTION FOR SOME MAINS???
 PLEASE SEE GF (GROUND FAULT) PROTECTION
 IS REQUIRED PER 240.13, 230.95 ETC ,
 HOWEVER PLEASE SEE GFI PROTECTION IS
 PERSONNEL PROTECTION.
 PLEASE SEE PROTECTION IS ALSO BEING
 SHOWN ON ALL SECONDARY OVER CURRENT
 PROTECTION??
 PLEASE KNOW, THIS IS NOT REQUIRED FOR
 THIS STRUCTURE, CLASS AND OCCUPANCY, BUT
 HOWEVER IS PERMITTED.
 PLEASE ALSO SEE GF SEEMS TO BE SHOWN ON
 THE EM SIDE OF THE DISTRIBUTION
 SYSTEM(S) WHICH IS UNCLEAR. PLEASE SEE
 700.7D, 700.26, NFPA-110
 PLEASE SEE THE CODE IS CLEAR WHEN GROUND
 FAULT PROTECTION IS REQUIRED AND WHEN
 SENSING OF SUCH GROUND FAULTS ARE
 REQUIRED , HOWEVER PLEASE KNOW GROUND
 FAULT PROTECTION IS NOT IDEALON THE
 EMERGENCY SIDE DUE TO THE NATURE OF THE
 EMERGENCY DISTRIBUTIONSYSTEM AND THE
 NEED OF MAINTAINING CERTAIN SYSTEMS ON
 DURING AN EMERGENCY.PLEASE KNOW,
 SENSING OF THE GROUND FAULT WOULD BE
 NEEDED TO CORRECT ANY SITUATION IN SUCH
 EQUIPMENT. PLEASE KNOW, IT HAS BEEN
 DETERMINED BY THIS AHJ, THAT THE GF
 PROTECTION ON THE REQUIRED EM SYSTEMS
 SHOULD NOT BE PROVIDED AND ONLY SENSING
 FOR THE PURPOSE AS STATED AND REQUIRED.
  
 21) NOTE: PLEASE KNOW, 4-POLE ATS
 SWITCHES ARE BEING SHOWN AS REQUIRED TO
 ACHIEVE THE CORRECT GROUND FAULT
 SENSING, HOWEVER THE GENERATORS DO NOT
 SEEM TO BE INDICATED A SEPARATELY
 DERIVED AS REQUIRED.
 250.30, 250.50.
  
 22) NOTE: PLEASE SEE THE GROUNDING
 ELECTRODE SYSTEM IS REQUIRED TO SHOW THE
 FOOTER/FOUNDATION STEEL AS PART OF THE
 GROUNDING ELECTRICAL SYSTEM.
 250.50
  
 23) NOTE: PLEASE SEE A NOTE ON PLANS
 MENTIONS THAT A LIGHTNING PROTECTION
 SYSTEM WILL BE REQUIRED.
 PLEASE KNOW, THIS SYSTEM MAY ONLY BE
 INSTALLED BY A CERTIFIED LIGHTNING
 PROTECTION CONTRACTOR WHO CAN CERTIFY
 SUCH A SYSTEM UNDER UL 96 AND NFPA-780.
 THIS SHALL BE A SEPARATE PERMIT, WITH
 PLANS AND FEES.
 PLEASE KNOW HOWEVER A NOTE SHALL BE
 PLACE ON THESE ELECTRICAL PLANS ON ROOF
 TOP PLANS STATING; "ALL OR ANY LIGHTNING
 PROTECTION SYSTEMS SHALL BE INSTALLED
 PER NFPA-780 AND LISTED PER UL 96." THIS
 WORDING SHOULD BE TO THAT SAME AFFECT,
 BUT NOT REQUIRED TO BE STATED AS ABOVE.
 PLEASE KNOW, THIS AHJ DOES NOT ACCEPT
 ANY OTHER SYSTEM NOT ACCEPTED BY
 NFPA-780. PLEASE KNOW THERE ARE MANY
 SYSTEMS ON THE MARKET WHICH CLAIM TO
 "PREVENT" OR "DISSIPATE" LIGHTNING ETC
 WHICH ARE NOT PERMITTED.
  
 24) NOTE: PLEASE SEE 620.23 ABC AND
 620.24ABC FOR REQUIRED CIRCUITS AND
 CONTROLS.
 PLEASE SEE ALLCAN NOT BE VERIFIED AT
 THIS TIME.
  
 25) NOTE: PLEASE SEE 2004 FBC CHAPTER
 13.
 PLEASE SEE 13-413.1.ABC.1 FOR A WORST
 CASE SCENARIO TO BE PROVIDED FOR FEEDERS
 AND BRANCH CIRCUITS.
 PLEASE SEE 13-413.1.ABC.2.2.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, 13-415.1.ABC.1.3 FOR
 LIGHTING AND CONTROLS FOR ALL AREAS.
 PLEASE SEE SOME EXCEPTIONS ARE
 PERMITTED.
 PLEASE SEE OUTSIDE AREAS , TANDEM WIRING
 ETC.
  
 26) NOTE: PLEASE SEE MINIMUM LIGHTING
 FOR EGRESS ETC WILL BE REQUIRED INSIDE
 THE FUTURE TENANT BUILD OUT SPACES. THIS
 HAS ALSO BEEN CONFIRMED ALSO WITH THE
 FIRE MARSHAL?S OFFICE AND WILL BE
 REQUIRED.
 THESE SHOULD BE WIRED INTO THE HOUSE
 PANELS AT THIS TIME AND CAN BE REMOVED
 ONCE TENANT OCCUPANCY TAKES PLACE.
 PLEASE ALSO SEE EXIT LIGHTS.
 IF THESE AREAS ARE OCCUPIED AT ANYTIME
 FOR ANY REASON BEFORE A BUILD OUT HAS
 TAKEN PLACE AND THE POWER GOES OUT,
 MINIMUM LIGHTING SHALL BE PROVIDED TO
 DIRECT ANY SAID OCCUPANTS TO THE EXIT.
 NFPA-101,7.8,7.9
  
 27) NOTE: PLEASE SEE PREVIOUS NOTES
 ABOVE WHICH REQUESTED THE MANUFACTURES
 SPEC/CUT SHEETS FOR THE FIRE PUMP AND
 FIRE PUMP CONTROLLER. PLEASE KNOW, THE
 PLANS SHALL INDICATE THE OCP AND LOCKED
 ROTOR OCP. PLEASE SEE RISER NOW SEEMS TO
 INDICATE THE FPC TO BE LISTED ETC.
 PLEASE KNOW, IF THE FCP MEETS NFPA-20
 FOR THE DISCONNECT MEANS RATED FOR THE
 LOAD SERVED LOCATE ON THE OUTSIDE OF THE
 EQUIPMENT AND CONTAINS THE OVER CURRENT
 PROTECTION SET AT LOCKED ROTOR AS
 REQUIRED BY 695.4B1 AND NFPA-20
 10.4.2,10.4.2.2, 10.3.6, 10.4.4 ETC.
 PLEASE SEE RISER SHOWS AN ADDITIONAL
 800A DISCONNECT LOCATED AHEAD OF THE
 LISTED FPC? PLEASE VERIFY AND CLARIFY
 THIS.
  
 28) NOTE: PLEASE SEE FUEL IS REQUIRED
 PER NFPA-20 FOR A MINIMUM OF 8HRS AT
 100% FOR FIRE PUMP AND ALL OTHER
 ASSOCIATED LOADS, INCLUDING ETC.
 6-6.2
 UNABLE TO VERIFY DUE TO THE AMOUNT OF
 FUEL TANKS, GPH ETC NOT SUBMITTED FOR
 REVIEW AT THIS TIME.
  
 29) NOTE: PLEASE NOTE ON PLANS AND
 PLEASE SEE NFPA-110 7.9, PARTICULARLY
 7.9.3.1 FOR FUEL LINE TYPES.
  
 30) NOTE: PLEASE SEE MANY LOCATIONS ON
 RISER BREAKERS FOR SHELL AND FUTURE ARE
 NOTED AS ELECTRICALLY OPERATED. PLEASE
 CLARIFY IF THESE BREAKERS STILL CONTAIN
 A MANUAL MEANS OF DISCONNECT?
  
 31) NOTE: PLEASE VERIFY "MI" CABLES
 BEING SHOWN ON PLANS AND RISER IN MANY
 LOCATIONS. PLEASE KNOW, THIS IS ONLY A
 NOTE AS THIS INSTALLATION FOR MI CABLE
 IS NOT COMMON FOR THIS TYPE OF CABLE.
 THIS IS PERMITTED AND IS IN NO WAY A
 NOTE FOR CORRECTION. THIS IS ONLY NOTED,
 AS IF SHOWN ON PLANS, THIS WILL BE
 REQUIRED AND IN LIEU OF REVISING PLANS
 AT A LATER DATE CHANGES CAN BE MADE IF
 THESE ARE NOT INTENDED.
 PLEASE INDICATE THE CABLE DEGREE
 RATINGS.
  
 32) NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS ARE BEING SHOWN FROM THE
 GENERATORS.
 250.30
  
 33) NOTE: PLEASE INDICATE THE OCP AT THE
 GENERATORS.
 215.5
  
 34) NOTE: PLEASE SEE 445.13 FOR MIN
 SIZES OF THE FEEDERS FROM THE
 GENERATORS.
  
 35) NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR THE BUILDING SERVICES
 AND PANELS.
 PLEASE SEE
 220,220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO INDICATE ALL CONTINUOUS
 LOADS AND LARGEST MOTOR LOADS AT 125%.
 215.3,230.42 ETC.
  
 36) NOTE: PLEASE INDICATE THE GUTTER
 SIZES ON RISER. THIS IS REQUIRED AT THIS
 TIME BASED ON THE MINIMUM DIMENSIONS
 REQUIRED FOR TURNING RADIUS AND BASED ON
 THE CONDUCTORS/FEEDERS ARE SHOWN ON
 RISER.
 368,215.5
  
 37) NOTE: PLEASE INDICATE AND SHOW ALL
 ATTACHMENT LOCATIONS FOR THE
 TRANSFORMERS AS SHOWN ON RISER. PLEASE
 SEE 250.50,250.30,250.66 ETC.
  
 38) NOTE: PLEASE PROVIDE A ONE-LINE
 GROUND RISER ON RISER DIAGRAM OR
 SEPARATE SHEET. 250.58, 215.5
  
 39) NOTE: PLEASE CORRELATE ALL OCP
 DEVICES FOR PANELS ON RISER AND PANELS
 SCHEDULE WHEN SUBMITTED. PLEASE SEE SOME
 OF THIS ON RISER DOES NOT CORRELATE AT
 THIS TIME WITH PANELS AS NOTED.
 215.5
  
 40) NOTE: PLEASE SEE 450.3 FOR THE
 MAXIMUM OCP FOR TRANSFORMERS TO BE AT
 125%. PLEASE KNOW, WHEN THE OCP DOES NOT
 CORRELATE, AND THEN IT IS PERMITTED TO
 GO TO THE NEXT SIZE UP, HOWEVER IT IS
 NOT PERMITTED TO GO MORE THAN THE
 STANDARDS OCP PROTECTION DEVICES AS
 LISTED IN 240.6.
 PLEASE SEE TRANSFORMERS WHICH INDICATE
 THE OCP SET HIGHER THAN THE MAX 125%.
 215.5
  
 41) NOTE: PLEASE PROVIDE ANY WIND
 LOADING ON LIGHT POLES OUTSIDE. PLEASE
 KNOW, THE RATINGS SHALL BE BASED ON FBC
 2004 140MPH. THESE CALCULATIONS WILL BE
 REVIEWED BY THE STRUCTURAL REVIEWER WHEN
 SUBMITTED.
  
 42) NOTE: PLEASE KNOW, IT WAS NOTED THAT
 THE RISER DIAGRAM SHEET CONTAINED A
 NOTED FOR SIGNAGE PER 230.2E. PLEASE
 KNOW HOWEVER SIGNAGE, MAPPING SHALL BE
 REQUIRED AT ALL OTHER LOCATIONS; HOWEVER
 MOST IMPORTANTLY BE REQUIRED IN FULL IN
 THE FIRE COMMAND RM.
 PLEASE PROVIDE A NOTE FOR THE SIGNAGE ON
 THE SHEET FOR THE FC ROOM. PLEASE NOTE
 THAT ALL LETTERING SHALL BE A MINIMUM OF
 1" AND ON CONTRASTING BACKGROUND.
  
 43) NOTE: PLEASE SEE NFPA-72 4.4.1.4.2.2
 FOR THE REQUIRED DISCONNECTING MEANS FOR
 THE PRIMARY OF THE FIRE ALARM SYSTEM.
 PLEASE ALSO BE SURE ALL ITEMS ARE LISTED
 ON PLANS FOR THE FIRE COMMAND ROOM AS
 SET FORTH IN NFPA-10111.8, 11.8.5
  
 44) NOTE: PLEASE KNOW MANY OF THE ABOVE
 ITEMS HAVE BEEN REDLINED ON ONE OF THE
 SETS OF SUBMITTED PLANS BUT IS IN NO WAY
 ALL POSSIBLE ITEMS AS MENTIONED ABOVE.
  
 45) NOTE: PLEASE SEE THAT A TYPE WRITTEN
 RESPONSE FROM THE DESIGN TEAM FOR EACH
 OF THE ABOVE COMMENTS WILL HELP IN
 EXPEDITING THE NEXT REVIEW PROCESS.
  
 PLEASE BE SURE TO ALL SEE ALL COMMENTS
 FROM ALL OTHER TRADES AND THEY MAY
 AFFECT ELECTRICAL PLANS AND DESIGN.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS OR
 COMMENTS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2006-06-05 00:00:00REVIEW IN PROGRESS
2006-06-02 00:00:00ONE ROLL OF PLANS AND ONE SET OF BOOKS
 IN ELECTRICAL FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 9 Status N Date 2008-05-07 Cont ID  
Sent By rchokshi Date 2008-05-07 Time 16:06 Rev Time 0.00
Received By rchokshi Date 2008-05-07 Time 16:06 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 8 Status P Date 2008-03-13 Cont ID  
Sent By rchokshi Date 2008-03-13 Time 11:38 Rev Time 0.00
Received By rchokshi Date 2008-03-13 Time 11:34 Sent To  
Notes
2008-03-13 11:38:33E-MAIL FROM PAT GIBNEY, 3/12/08, OF CRAVEN THOMPSON
 EXPLAINED THAT THERE WERE NO MAJOR CHANGES IN THE
 PROJECT. ONE SET OF REVISED DRAWINGS IS ATTACHED WITH
 THE PERMIT FILE AND THE OTHER 2 SETS TO BE GIVEN BACK
 TO CONTRACTOR.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 7 Status F Date 2008-01-11 Cont ID  
Sent By rchokshi Date 2008-01-11 Time 11:13 Rev Time 0.00
Received By rchokshi Date 2008-01-11 Time 11:01 Sent To  
Notes
2008-01-11 11:13:15*****FAILED*****
  
 CALLEDNATHAN D. @ 718-0935 ON 1/10/08 LEFT MESSAGE.
 CALLED AGAIN 1/11/08HE SAID HE WILL CALL BACK. THEIR
 CHANGES ARE NOT CLEAR ON DRAWINGS.
 THE REASONS TO CALL WAS TO EXPEDITE PASSING JOB BECAUSE
 IT FAILED LAST TWO TIMES.
  
 RASIKCHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 6 Status F Date 2007-10-22 Cont ID  
Sent By rchokshi Date 2007-10-22 Time 09:35 Rev Time 0.00
Received By rchokshi Date 2007-10-22 Time 09:33 Sent To  
Notes
2007-10-22 09:35:47**** FAILED ***
 NOTCLEAR ABOUT CHANGES YOU MADE FROM LAST TIME
 PASSED.
 PLEASE EXPLAIN WHAT DID YOU CHANGE IN WATER/SEWER
 SYSTEMS, STORM WATER SYSTEM??
 DID YOU INCREASE, DECREASEIMPERVIOUS/PERVIOUS AREA?
 DID YOU MAKE ANY CHANGES IN PARKING/HANDICAP PARKING
 LOT, DUMPSTER ENCLOSURE,????
  
 PLEASE EXPLAIN IN DETAIL EACH ITEM TO EXPEDITE THE
 PERMITTING PROCESS.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 5 Status F Date 2007-08-20 Cont ID  
Sent By rchokshi Date 2007-08-20 Time 14:16 Rev Time 0.00
Received By rchokshi Date 2007-08-20 Time 14:09 Sent To  
Notes
2007-08-20 14:15:54**** FAILED ***
  
 PLEASE EXPLAIN WHAT DID YOU CHANGE IN WATER/SEWER
 SYSTEMS, STORM WATER SYSTEM??
 DID YOU INCREASE, DECREASEIMPERVIOUS/PERVIOUS AREA?
 DID YOU MAKE ANY CHANGES IN PARKING/HANDICAP PARKING
 LOT, DUMPSTER ENCLOSURE,????
  
 PLEASE EXPLAIN IN DETAIL EACH ITEM TO EXPEDITE THE
 PERMITTING PROCESS.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2007-06-08 Cont ID  
Sent By rchokshi Date 2007-06-08 Time 09:12 Rev Time 0.00
Received By rchokshi Date 2007-06-08 Time 09:12 Sent To  
Notes
2007-06-08 09:18:24ENGINEERING REVIEW NOT REQUIRED.
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-10-27 Cont ID  
Sent By rchokshi Date 2006-10-27 Time 16:10 Rev Time 0.00
Received By rchokshi Date 2006-10-27 Time 16:09 Sent To  
Notes
2006-10-27 16:09:51OK, PASSED

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2006-08-02 Cont ID  
Sent By rchokshi Date 2006-08-02 Time 10:39 Rev Time 0.00
Received By rchokshi Date 2006-08-02 Time 10:16 Sent To  
Notes
2006-08-02 00:00:00FAILED FOR FOLLOWING REASONS:
 1. NEED STORM WATER/DRAINAGE
 CAL.,PERVIOUS,IMPERVIOUS AREA
 CAL.,RUNOFF CAL., EXFILTRATION TRENCH
 CAL. DETAI, CONTOL STRUCTURES DETAIS,
 GEOTECHNICAL ENG CAL.,SFWMP PERMIT,
  
 2. NEED UTILITY REVIEW FROM 45 STREET
  
 3. NEED POLLUTION PREVENTION PLANS
 DETAILS
  
 4. NEED CITY OF WPB NOTES, MARKINGS &
 DETAILS ON DRAWINGS FOR HANDICAP
 PARKINGS(ADA),DRIVEWAY APPROACH,ETC
  
 5. HOW HIGH IS FINISHED FLOOR ELEVATION
 FROM CENTER LINE OF THE OF THE ROAD
 (MINIMUM)?
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2006-06-15 Cont ID  
Sent By dpalmer Date 2006-06-15 Time 11:58 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2006-06-15 00:00:00******** NOTE **********
  
 AS DIRECTED BY NEIL MELICK BUILDING
 OFFICAL: MS. LYNN HARRIS REPRESENTING
 CITY PLACE OFFICE LLC HAS REQUESTED
 PLANS TO BE REMOVED FROM THEPLAN
 REVIEW PROCESS.
 WHEN PLANS COME BACK IN FOR REVIEW, IT
 WILL BE 1ST RESUB NO FEE. DV PALMER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 18 Status P Date 2008-05-19 Cont ID  
Sent By mawillia Date 2008-05-19 Time 15:18 Rev Time 0.00
Received By mawillia Date 2008-05-16 Time 14:57 Sent To  
Notes
2008-05-19 15:21:28*****REVIEWED*****
  
  
 SUBMITTAL FOR SMOKE CONTROL SYSTEM WAS REVIEWED BY FIRE
 MARSHAL MIKE CARSILLO.
  
  
 561-804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 17 Status P Date 2008-05-08 Cont ID  
Sent By mwennerg Date 2008-05-08 Time 13:42 Rev Time 0.00
Received By mwennerg Date 2008-05-08 Time 13:42 Sent To  
Notes
2008-05-08 13:43:02REVISED PLAN SHEET FA1.01, ADDITION OF SMOKE DETCTORS
 IN LOBBY COMMON AREA.

Review Stop FIRE FIRE DEPARTMENT
Rev No 16 Status P Date 2008-05-19 Cont ID  
Sent By mawillia Date 2008-02-26 Time 14:55 Rev Time 0.00
Received By mawillia Date 2008-02-26 Time 12:06 Sent To  
Notes
2008-02-26 13:17:23*****REVISION #33, DATED 2/8/08, APPROVED*****
  
  
 REVISED PLAN SHEETS FA1.02, FA1.04, FA1.05, FA1.06,
 FA1.07, FA1.08, FA1.09, AND FA1.15 THRU FA1.18 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 15 Status P Date 2008-02-26 Cont ID  
Sent By mawillia Date 2008-02-26 Time 12:00 Rev Time 0.00
Received By mawillia Date 2008-02-26 Time 10:37 Sent To  
Notes
2008-02-26 10:46:02*****REVISION #33, DATED 2/8/08, APPROVED*****
  
  
 REVISED PLAN SHEETS FP1.04, FP1.05, FP1.07, AND FP1.17
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status P Date 2008-01-09 Cont ID  
Sent By mwennerg Date 2008-01-09 Time 09:43 Rev Time 0.00
Received By mwennerg Date 2008-01-09 Time 09:43 Sent To  
Notes
2008-01-09 09:44:28REVISED SHEETS FA 1.05 AND FP 1.05. SHEETS STAMPED,
 SIGNED AND DATED ON THIS DATE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status P Date 2007-11-05 Cont ID  
Sent By mawillia Date 2007-11-05 Time 16:56 Rev Time 0.00
Received By mawillia Date 2007-11-05 Time 15:49 Sent To  
Notes
2007-11-05 16:56:47*****APPROVED, REVISION DATED 8/3/07
  
  
  
 REVISED PLAN SHEETS A0.23 AND A0.24 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2007-11-01 Cont ID  
Sent By mawillia Date 2007-11-01 Time 16:06 Rev Time 0.00
Received By mawillia Date 2007-11-01 Time 15:27 Sent To  
Notes
2007-11-01 16:01:24*****APPROVED REVISION #23, DATED 09/13/07 *****
  
  
 REVISED PLAN SHEETS FA0.01 AND FA1.17 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2007-10-25 Cont ID  
Sent By mawillia Date 2007-10-25 Time 11:48 Rev Time 0.00
Received By mawillia Date 2007-10-25 Time 11:14 Sent To  
Notes
2007-10-25 11:39:49*****APPROVED REVISION #19, DATED 8/03/07 *****
  
  
 REVISED PLAN SHEETS FP1.06, FP1.07, FP1.08 AND FP1.09
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2007-10-25 Cont ID  
Sent By mawillia Date 2007-10-25 Time 11:07 Rev Time 0.00
Received By mawillia Date 2007-10-25 Time 10:08 Sent To  
Notes
2007-10-25 11:11:43*****APPROVED REVISION #19, DATED 8/03/07 *****
  
  
 REVISED PLAN SHEETS FA1.06, FA1.07, FA1.08 AND FA1.09
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2007-09-06 Cont ID  
Sent By mawillia Date 2007-09-06 Time 13:26 Rev Time 0.00
Received By mawillia Date 2007-09-06 Time 12:03 Sent To  
Notes
2007-09-06 13:26:19*****APPROVED*****
  
  
 CAPT. WENNERGREN'S COMMENTS OF 05/17/07 (REV.#7) HAVE
 BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2007-08-13 Cont ID  
Sent By adarroug Date 2007-09-05 Time 10:55 Rev Time 0.00
Received By mawillia Date 2007-08-13 Time 15:50 Sent To  
Notes
2007-08-13 16:15:45*****APPROVED*****
  
 REVISIONS OF 07/18/07 TO FIRE ALARM SHEETS:PLAN
 SHEETS FA1.01 THRU FA1.05 STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status F Date 2007-05-17 Cont ID  
Sent By mwennerg Date 2007-05-17 Time 09:04 Rev Time 0.00
Received By mwennerg Date 2007-05-17 Time 09:04 Sent To  
Notes
2007-05-17 09:11:35***DENIED***
  
 1) PLEASE NOTE THAT SOME SHEETS HAVE BEEN SUBMITTED FOR
 REVISION, HOWEVER NO REVISIONS ARE SHOWN. LS A0.24
  
 2) WILL THE ACCES DOOR REMAIN LOCKED AT LEVEL-6?
 A1.06
  
 3) AFTER THE PERMITS HAVE BEEN ISSUED, ANY
 REVIONS/CHANGES TO FIRE PROTECTION SYSTEMS NEED TO BE
 SUBMITTED UNDER THAT SPECIFIC PERMIT.
  
 4) FIRE DEPARTMENT VALVES ARE SHOWN WITH 2 1/2"
 CONNECTIONS. PLEASE MAKE NOTE OR ILLUSTRATE ON PLANS
 SHOWING 1 1/2" REDUCER WITH CHAIN.
  
 5) PLEASE PROVIDE CLARIFICATIONREGARDING NUMBER OF
 (DACT) PHONE LINES FOR FA SYSTEM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2007-03-06 Cont ID  
Sent By mawillia Date 2007-03-06 Time 10:08 Rev Time 0.00
Received By mawillia Date 2007-03-06 Time 09:51 Sent To  
Notes
2007-03-06 09:53:36*****APPROVED*****
  
  
 **REVISED PLAN SHEETS DATED 12/15/2006E1.01 AND
 E1.06 WERE STAMPED, INITIALED, AND DATED.**
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-01-10 Cont ID  
Sent By mawillia Date 2007-01-10 Time 17:24 Rev Time 0.00
Received By mawillia Date 2007-01-10 Time 17:24 Sent To E
Notes
2007-01-10 18:37:11*****APPROVED*****
  
  
 **REVISED PLAN SHEETS DATED 11/10/2006:H1.02, H1.16,
 FP1.01,FA1.01, 1.02, 1.03, 1.04, 1.05, 1.06, 1.15,
 1.16, 1.17, AND 1.18WERE STAMPED, INITIALED, AND
 DATED.**
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-10-31 Cont ID  
Sent By mcarsill Date 2006-10-31 Time 13:19 Rev Time 0.00
Received By mcarsill Date 2006-10-31 Time 13:05 Sent To  
Notes
2006-10-31 13:19:54ON OCTOBER 30, 2006 A MEETING WAS HELD AT CONSTRUCTION
 SERVICES REGARDING THE PROJECT. THE MEETING CONCERNED
 FIRE PLAN REVIEW COMMENTS THAT WERE PREVIOUSLY PLACED
 INTO THE SYSTEM. EACH ITEM WAS DISCUSSED AND AGREEMENTS
 WERE REACHED.ON OCTOBER 31, 2006, AN ELECTRONIC
 E-MAIL WAS RECEIVED BY THIS OFFICE OFFICIALLY
 COMMENTING ON THE PLAN REVIEW COMMENTS PROVIDED BY FIRE
 RESCUE. SOME FUTURE CHANGES TO CERTAIN SHEETS OF THE
 PLANS AND APPROPRIATE FIRE SAFETY EQUIPMENT SHOP
 DRAWINGS WILL NEED TO BE MODIFIED.THE PLANS ARE
 APPROVED PROVISO AT THIS TIME. THE COMMENT RESPONSE
 LETTER WILL BE RETAINED IN THE FILES OF THE FRE
 PREVENTION BUREAU.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-10-26 Cont ID  
Sent By mcarsill Date 2006-10-26 Time 14:10 Rev Time 0.00
Received By mcarsill Date 2006-10-26 Time 13:45 Sent To  
Notes
2006-10-26 14:10:011. REQUIRED FIRE PROTECTION SYSTEMS # 10 NOTE NEEDS TO
 BE REVISED ON PAGE A0.20. STANDPIPE VALVES WILL NOT BE
 ACCEPTED ON INTERMEDIATE FLOORS BUT AT VERY FLOOR LEVEL
 WITHIN STAIRWELLS.
 2. B GARAGE IS A SPRINKLER PROTECTED BUILDING. ITEM # 6
 ON PAGE A0.20. STATES THAT IT IS NOT.
 3. PLEASE DECLARE HOW ACCESS IS ACHEIVED TO THE SIAMESE
 CONNECTION FOR THE B BLOCK GARAGE STANDPIPE SYSTEM.
 4. REVIEWED DATA FOR THE SECURITY TURNSTILE PLANNED FOR
 USE. PLEASE INDICATE ON THE PLANS THAT NO INTERFERENCE
 WITH EXITING WILL OCCUR BY USING THESE DEVICES.
 5. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR THE TENSION CABLES SHOWN ON PAGE A4.03.
 6. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR
 LOCATIONS.
 7. PLEASE EXPLAIN HOW THE ELEVATOR LOBBIES ARE BEING
 SEPARATED FROM THE REMAINDER OF THE BUILDINGS FLOORS
 6-14 ON PAGE A1.06.
 8. IT APPEARS THAT THE COMMON BATHROOMS ARE EQUIPPED
 WITH LF1 FIXTURES. IN THE EVENT OF LOSS OF POWER THESE
 ROOMS POSSIBLE BE DARK.
 9. ON PAGE FP1.01 SEVERAL ROOMS ARE PLANNED TO BE
 EXCLUDED FROM FIRE SPRINKLER PROTECTION. WHAT
 ALTERNATIVE FIRE PROTECTION IS PLANNED FOR THSES AREAS.
 HIGH-RISE BUILDINGS ARE TO BE COMPLETELY PROTECTED BY
 AUTOMATIC FIRE SPRINKLER SYSTEMS.
 10. FUTURE TENANT SPACES WILL BE REQUIRED TO BE
 EQUIPPED WITH EXIT SIGNS AND EMERGENCY LIGHTING WHEN
 COMPLETED.
 11. SMOKE DETECTORS APPEAR TO BE MISSING FROM SEVERAL
 STORAGE ROOMS ON THE FIRE ALARM DRAWINGS.
 12. PLEASE EXPLAIN EXHAUST LOVER LOCATED NEXT TO STAIR
 # 1 EXIT DOOR ON PAGE H1.01.
 13. PLEASE EXPLAIN SF1 ON PAGE H1.03 LOCATED ADJACENT
 TO GARAGE PROPER.
 14. CO DETECTORS APPEAR TO BE LOCATED IN TENANT SPACES.
 PLEASE EXPLAIN. SOME DETECTORS CONTAIN MORE DETECTORS
 THAN OTHER ONES.
 15. ALL FIRE DAMPERS SHALL BE DROP TESTED TO ENSURE
 PROPER OPERATION AFTER INSTALLATION.
 16. THE SYMBOLS FOR SMOKE DETECTORS ARE IDENTICAL TO
 ONES USED FOR EXIT SIGNS. A REVIEW WAS CONFUSING AS THE
 SYMBOL USED IS UNIVERSALLY USED FOR EXIT SIGNS WHICH
 CAUSES CONFUSION.
 17. THE PROPOSED FUEL TANK WILL PROBABLY NEED TO BE
 REGISTERED WITH PBC DERM DUE TO FACT THAT THE SIZE
 EXCEEDS 550 GALLONS. PLEASE CONTACT THEM IMMEDIATELY.
 18. THE PHOENIX DRAWING FOR THE FUEL TANK FOR THE
 GENERATOR FAILS TO DISPLAY ANY LISTINGS OR APPROVALS.
 19. PLEASE CONTACT THIS OFFICE AT 804-4709 TO DISCUSS
 THE FUEL TANK INSTALLATION.
 20. HOW IS ACCESS ACHEIVED TO THE TWO EXITS SHOWN ON
 PAGE A1.02. AT LEAST FOUR SECURITY DEVICES ARE LOCATED
 ADJACENT TO THE AUTO DETAILING AREA.
 21. NATURAL GAS INSTALLATION TO COMPLY WITH THE
 APPROPRIATE NFPA STANDARDS.
  
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER
 804-4709
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-09-08 Cont ID  
Sent By mwennerg Date 2006-09-08 Time 07:31 Rev Time 0.00
Received By mwennerg Date 2006-09-08 Time 07:31 Sent To  
Notes
2006-09-08 00:00:00*DENIED***
  
 1) WORK SHALL COMPLY WITH NFPA 101, 2003
 EDITION CHAPTER 11 HIGHRISE BUILDINGS.
  
 2) ANY RELOCATED FIRE HYDRANTS SHALL BE
 OPERATIONAL PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 3) SHEET C-8 ILLUSTRATES AN EXISTING
 FIRE DEPARTMENT CONNECTION TO REMAIN.
 PLEASE VERIFY WHAT STRUCTURE IS BEING
 SERVICED BY THAT CONNECTION.
  
 4) ELECTRONIC SWITCHES IN ADDITION TO
 CHAIN AND LOCK IS REQUIRED FOR DOUBLE
 CHECK DETECTOR ASSEMBLY. OK ON SHEET
 FP0.01.
  
 5) LANDSCAPING SHALL NOT OBTSRUCT OR
 INTERFERE WITH FIRE PROTECTION
 EQUIPMENT. PROPER CLEARANCES SHALL BE
 MAINTAINED AT ALL TIMES.
  
 6) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 7) STAIRS TO KEEP UP WITH CONSTRUCTION.
  
 8) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN BUILDING REACHES (3) STORIES OR
 (30)' IN HEIGHT.
  
 9) MORE DETAILS ARE REQUIRED FOR
 GENERATORS ICLUDING ALL MANUFACTURER
 SPEC SHEETS .
  
 10) SITE PLAN ON SHEET A0.21 ONLY
 ILLUSRATES (1) FIRE DEPARTMENT
 CONNECTION. OK ON FP SHEETS.
  
 11) LIFE SAFETY PLAN SHALL INCLUDE ALL
 COMMON PATHS OF TRAVEL TO EXITS. IT
 APPEARS THAT (1) IS SHOWN ON SHEET
 A0.22.
  
 12) PLANS INDICATE THAT ROOF ACCESS IS
 NOT AVAILABLE TO GENERAL PUBLIC. WHAT
 SAFEGUARDS ARE BEING USED TO ASSURE
 THIS?
  
 13) 2A-10B,C RATED FIRE EXTINGUISHERS
 SHALL BE MOUNTED AT DISTANCES TO SATISFY
 THE 75' TRAVEL DISTANCE REQUIREMENT.
  
 14) PLEASE PROVIDE MORE DETAILS
 REGARDING CANOPIES.
  
 15) PLEASE CLEARLY ILLUSTRATE EXITING
 FROM EXISTING PARKING GARAGE AS IT
 REALATES TO THE NEW STRUCTURE.WILL THE
 NEW STRUCTURE IMPACT EXITING FROM THE
 EXISTING PARKING GARAGE?
  
 16) COOLING TOWERS TO COMPLY WITH NFPA
 214.
  
 17) NO STORAGE IS ALLOWED IN ELECTRICAL
 OR MECHANICAL ROOMS THAT WILL BE
 REQUIRED TO BE INSPECTED.
  
 18) ADDRESS IS REQUIRED ON BUILDING, AND
 SHALL BE A MINIMUM OF 6" IN HEIGHT, 1"
 WIDTH AND CONTRASTING TO THE BACKGROUND.
  
 19) ALL STAIRS AND RAMPS SHALL HAVE
 HANDRAILS ON BOTH SIDES.
  
 20) HOW WILL THE HIGHRISE IMPACT THE
 EXISTING PARKING STRUCTURE SHOULD AN
 EMERGENCY OCCUR ON UPPER LEVELS OF THE
 PARKING GARAGE?
  
 21) PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING IN TERMS OF CLASS A,B OR C IN
 ACCORDANCE WITH NFPA 101, SECTION 10.2.
  
 22) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 23) FIRE ALARM SYSTEM TO COMPLY WITH
 SURVIVABILITY REQUIREMENTS OF NFPA 72
 FOR HIGHRISE BUILDINGS.
  
 24) PLEASE PROVIDE ALL MANUFACTURER SPEC
 SHEETS FOR FIRE PUMP AND ASSOCIATED
 EQUIPMENT.
  
 25) FIRE ALARM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 26) FIRE ALARM TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
 27) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 28) KNOX LOCKING CAPS ARE REQUIRED FOR
 NEW FIRE DEPARTMENT CONNECTIONS.
  
 29) WHERE PROVIDED, SMOKE MANAGEMENT
 PANELS SHALL PROVIDE GRAPHIC
 REPRESENTAION OF THE BUILDING. HOA
 SWITCHES WITH NO OVERLAY OF THE BUILDING
 WILL NOT BE ACCEPTABLE. SHT FA1.01
  
 30) EXITS SIGNS SHALL BE PROVIDED WHERE
 ALL PARTS OF THE MEANS OF EGRESS ARE
 CLEAR AND OBVIOUS. IT WOULD APPEAR THAT
 MORE SIGNS ARE NEEDED ON THE 1ST FLOOR W
 SIDE OF CORRIDOR.
  
 31) NO EMERGENCY LIGHTS CAN BE FOUND IN
 CORRIDORS NEAR STAIR #2.
  
 32) MORE DETAILS REQUIRED FOR CO PANEL
 AND EQIPMENT IN PARKING GARAGE.
  
 33) KNOX BOXES WILL BE REQUIRED. PLEASE
 CONTACT THE BUREAU OF FIRE PREVENTION AT
 (561) 804-4724 FOR APPLICATIONS.
  
 34) FIRE DEPARTMENT VALVES TO BE 2 1/2"-
 1 1/2" REDUCERS WITH CHAINS.
  
 35) FP 1.15 AND FP 1.16 ARE SHOWING ALL
 UPRIGHT SPRINKLERS I CORE AREAS. CAN YOU
 PLEASE VERIFY IF THIS IS CORRECT?
  
 36) PLEASE INDICATE WHAT ELEVATORS ARE
 STRETCHER ACCESSIBLE.
  
 37) NO EQUIPMENT SHALL BE ALLOWED INSIDE
 OR PENETRATE EXIT ENCLOSURES UNLESS THE
 EXCEPTIONS OF NFPA 101, SECTION
 7.1.3.2.1.(6) ARE MET.
  
 38) NO CUTTING OR WELDING OPERATIONS TO
 OCCUR WITHOUT APPROVAL OF THE FIRE
 PREVENTION BUREAU AND COMPLIANCE WITH
 NFPA 51B.
  
 39) BUILDING SHALL COMPLY WITH ALL
 REQUIREMENTS OF NFPA 101, 2003 EDITION
 SECTION 11.8 FOR HIGHRISE BUILDINGS.
  
 40) THE ANTICIPATED STACK EFFECT WORDING
 NOTE SHALL BE ADDED TO MECHANICAL
 SHEETS.
  
 41) WILL SECURITY GATES HAVE AN IMPACT
 ON MEANS OF EGRESS? SHEET A1.01.
  
 42) ANY PROPOSED SOFFITS SHALL NOT
 INTERFERE WITH OR OBSTRUCT REQUIRED FIRE
 SPRINKLER COVERAGE.
  
 43) PLEASE ILLUSTRATE ALL EXIT DISCHARGE
 LOCATIONS FROM THE BUILDING. EXIT
 DISHARGE LOCATIONS SHALL COMPLY WITH
 APPLICABLE FIRE CODE REQUIREMENTS.
  
 44) ELEVATORS TO COMPLY WITH ASME A17.1.
  
 45) WARNING SIGNS ARE REQUIRED IN
 ELEVATOR LOBBIES.
  
 46) ALL FIRE DOORS AND WINDOWS TO COMPLY
 WITH NFPA 80, FIRE DOORS AND WINDOWS.
  
  
 MIKE WENNERGREN, CAPTAI/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2006-06-15 Cont ID  
Sent By dpalmer Date 2006-06-15 Time 12:03 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2006-06-15 00:00:00******** NOTE **********
  
 AS DIRECTED BY NEIL MELICK BUILDING
 OFFICAL: MS. LYNN HARRIS REPRESENTING
 CITY PLACE OFFICE LLC HAS REQUESTED
 PLANS TO BE REMOVED FROM THEPLAN
 REVIEW PROCESS.
 WHEN PLANS COME BACK IN FOR REVIEW, IT
 WILL BE 1ST RESUB NO FEE. DV PALMER.

Review Stop G GAS REVIEW
Rev No 5 Status N Date 2007-03-25 Cont ID  
Sent By pschmitz Date 2007-03-25 Time 10:45 Rev Time 0.00
Received By pschmitz Date 2007-03-25 Time 10:45 Sent To  
Notes
2007-03-25 10:48:08PREVIOUS NOTE: REVISION: SHT P0.2 APPROVED.

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2006-12-09 Cont ID  
Sent By pschmitz Date 2006-12-09 Time 13:45 Rev Time 0.00
Received By pschmitz Date 2006-12-09 Time 13:44 Sent To  
Notes
2006-12-09 13:44:48REVISION: SHT P0.2 APPROVED.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-10-21 Cont ID  
Sent By pschmitz Date 2006-10-21 Time 08:33 Rev Time 0.00
Received By pschmitz Date 2006-10-21 Time 08:32 Sent To  
Notes
2006-10-21 09:23:58 RE-SUB

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-07-30 Cont ID  
Sent By pschmitz Date 2006-07-30 Time 15:17 Rev Time 0.00
Received By pschmitz Date 2006-07-15 Time   Sent To  
Notes
2006-07-30 00:00:00******** NOTE **********
  
 AS DIRECTED BY NEIL MELICK BUILDING
 OFFICAL: MS. LYNN HARRIS REPRESENTING
 CITY PLACE OFFICE LLC HAS REQUESTED
 PLANS TO BE REMOVED FROM THEPLAN
 REVIEW PROCESS.
 WHEN PLANS COME BACK IN FOR REVIEW, IT
 WILL BE 1ST RESUB NO FEE. DV PALMER.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-30 Cont ID  
Sent By pschmitz Date 2006-07-30 Time 14:30 Rev Time 0.00
Received By pschmitz Date 2006-07-30 Time 14:30 Sent To  
Notes
2006-07-30 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
 A) PLEASE SEE ELECTRICAL PLAN REVIEW
 COMMENTS, WITH RESPECT TO DESIGN
 PROFESSIONAL, SIGNED AND SEALED PLANS
 AND MISSING LICENSE INFORMATION.
  
 B) PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT PLUMBING
 PLANS.
  
 C) SHT. P0.2NATURAL GAS PLAN
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304
 .
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 QUESTIONS 561-805-6692PAUL SCHMITZ

Review Stop I INCOMING/PROCESSING
Rev No 114 Status N Date 2008-08-15 Cont ID  
Sent By adarroug Date 2008-08-15 Time 13:54 Rev Time 0.00
Received By adarroug Date 2008-08-15 Time 13:54 Sent To  
Notes
2008-08-15 13:59:10TO "COMM" BD#53--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 113 Status N Date 2008-06-18 Cont ID  
Sent By adarroug Date 2008-06-18 Time 10:38 Rev Time 0.00
Received By adarroug Date 2008-06-18 Time 10:38 Sent To E
Notes
2008-06-18 10:39:27TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 112 Status N Date 2008-06-02 Cont ID  
Sent By adarroug Date 2008-06-02 Time 12:23 Rev Time 0.00
Received By adarroug Date 2008-06-02 Time 12:23 Sent To E
Notes
2008-06-02 12:24:59TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 111 Status N Date 2008-05-29 Cont ID  
Sent By adarroug Date 2008-05-29 Time 10:32 Rev Time 0.00
Received By adarroug Date 2008-05-29 Time 10:32 Sent To E
Notes
2008-05-29 10:32:51TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 110 Status N Date 2008-05-21 Cont ID  
Sent By adarroug Date 2008-05-21 Time 11:45 Rev Time 0.00
Received By adarroug Date 2008-05-21 Time 11:44 Sent To E
Notes
2008-05-21 11:45:05TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 109 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 14:24 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 14:24 Sent To M
Notes
2008-05-19 14:24:33TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 108 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 11:41 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 11:41 Sent To B
Notes
2008-05-14 11:41:45TO "RBROWN DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 107 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 16:26 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 16:26 Sent To E
Notes
2008-05-12 16:27:22TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 106 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 14:32 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 14:32 Sent To P
Notes
2008-05-12 14:32:42TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 105 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 13:21 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 13:21 Sent To  
Notes
2008-05-12 13:22:13TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 104 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 10:03 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 10:03 Sent To E
Notes
2008-05-12 10:03:43TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 103 Status N Date 2008-05-07 Cont ID  
Sent By adarroug Date 2008-05-07 Time 09:08 Rev Time 0.00
Received By adarroug Date 2008-05-07 Time 09:08 Sent To M
Notes
2008-05-07 09:11:04TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 102 Status N Date 2008-05-06 Cont ID  
Sent By adarroug Date 2008-05-06 Time 16:22 Rev Time 0.00
Received By adarroug Date 2008-05-06 Time 16:22 Sent To B
Notes
2008-05-06 16:22:43TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 101 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 10:54 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 10:54 Sent To  
Notes
2008-05-02 10:54:35TO "COMM" BD#33--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 100 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 10:29 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 10:29 Sent To B
Notes
2008-05-02 10:29:41TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 99 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 10:25 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 10:25 Sent To E
Notes
2008-05-02 10:26:02TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 98 Status N Date 2008-05-01 Cont ID  
Sent By adarroug Date 2008-05-01 Time 14:41 Rev Time 0.00
Received By adarroug Date 2008-05-01 Time 14:41 Sent To B
Notes
2008-05-01 14:42:09TO "JWITMER" DESK/2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 97 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 14:13 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 14:13 Sent To  
Notes
2008-04-30 14:14:03TO "COMM" BD#22

Review Stop I INCOMING/PROCESSING
Rev No 96 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 12:48 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 12:48 Sent To B
Notes
2008-04-29 12:48:27TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 95 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 09:14 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 09:14 Sent To B
Notes
2008-04-29 09:15:09TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 94 Status N Date 2008-04-24 Cont ID  
Sent By adarroug Date 2008-04-24 Time 14:38 Rev Time 0.00
Received By adarroug Date 2008-04-24 Time 14:38 Sent To B
Notes
2008-04-24 14:38:57TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 93 Status N Date 2008-04-21 Cont ID  
Sent By adarroug Date 2008-04-21 Time 12:50 Rev Time 0.00
Received By adarroug Date 2008-04-21 Time 12:50 Sent To B
Notes
2008-04-21 12:51:08TO "SHILL" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 92 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 14:37 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 14:37 Sent To B
Notes
2008-04-17 14:38:30TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 91 Status N Date 2008-04-16 Cont ID  
Sent By adarroug Date 2008-04-16 Time 11:52 Rev Time 0.00
Received By adarroug Date 2008-04-16 Time 11:52 Sent To B
Notes
2008-04-16 11:52:39TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 90 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 14:39 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 14:39 Sent To P
Notes
2008-04-10 14:39:38TO "P" BOX/2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 89 Status N Date 2008-04-07 Cont ID  
Sent By adarroug Date 2008-04-07 Time 09:11 Rev Time 0.00
Received By adarroug Date 2008-04-07 Time 09:11 Sent To B
Notes
2008-04-07 09:11:55TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 88 Status N Date 2008-04-03 Cont ID  
Sent By adarroug Date 2008-04-03 Time 08:19 Rev Time 0.00
Received By adarroug Date 2008-04-03 Time 08:19 Sent To B
Notes
2008-04-03 08:20:06TO "JWITMER" DESK/3 ROLLS/3 BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 87 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 10:13 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 10:13 Sent To B
Notes
2008-04-02 10:14:13TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 86 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 10:07 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 10:07 Sent To P
Notes
2008-04-02 10:07:32TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 85 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 09:59 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 09:59 Sent To M
Notes
2008-04-02 10:00:37TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 84 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 16:40 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 16:40 Sent To B
Notes
2008-03-27 16:41:12TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 83 Status N Date 2008-03-21 Cont ID  
Sent By adarroug Date 2008-03-21 Time 09:39 Rev Time 0.00
Received By adarroug Date 2008-03-21 Time 09:39 Sent To  
Notes
2008-03-21 09:42:06TO "COMM" BD#13--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 82 Status N Date 2008-03-10 Cont ID  
Sent By adarroug Date 2008-03-10 Time 11:37 Rev Time 0.00
Received By adarroug Date 2008-03-10 Time 11:37 Sent To B
Notes
2008-03-10 11:37:38TO "JWITMER" DESK/ 3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 81 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 14:59 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 14:59 Sent To  
Notes
2008-02-29 15:00:12TO "COMM" BD#48--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 80 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 14:31 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 14:31 Sent To E
Notes
2008-02-29 14:34:01TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 79 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 16:21 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 16:21 Sent To B
Notes
2008-02-20 16:21:57TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 78 Status N Date 2008-02-13 Cont ID  
Sent By shill Date 2008-02-13 Time 13:15 Rev Time 0.00
Received By shill Date 2008-02-13 Time 13:15 Sent To FIRE
Notes
2008-02-13 13:16:00TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 77 Status N Date 2008-02-13 Cont ID  
Sent By shill Date 2008-02-13 Time 11:55 Rev Time 0.00
Received By shill Date 2008-02-13 Time 11:55 Sent To E
Notes
2008-02-13 11:55:24TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2008-02-13 Cont ID  
Sent By shill Date 2008-02-13 Time 11:51 Rev Time 0.00
Received By shill Date 2008-02-13 Time 11:51 Sent To M
Notes
2008-02-13 11:52:15TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2008-02-13 Cont ID  
Sent By shill Date 2008-02-13 Time 11:47 Rev Time 0.00
Received By shill Date 2008-02-13 Time 11:47 Sent To FIRE
Notes
2008-02-13 11:47:34TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 74 Status N Date 2008-02-13 Cont ID  
Sent By shill Date 2008-02-13 Time 11:46 Rev Time 0.00
Received By shill Date 2008-02-13 Time 11:46 Sent To P
Notes
2008-02-13 11:47:13TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 73 Status N Date 2008-01-30 Cont ID  
Sent By adarroug Date 2008-01-30 Time 11:23 Rev Time 0.00
Received By adarroug Date 2008-01-30 Time 11:23 Sent To B
Notes
2008-01-30 11:23:24TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 14:30 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 14:30 Sent To B
Notes
2008-01-29 14:31:11TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 11:05 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 11:05 Sent To B
Notes
2008-01-29 11:06:07TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 11:53 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 11:53 Sent To P
Notes
2008-01-23 11:53:40TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2008-01-22 Cont ID  
Sent By adarroug Date 2008-01-22 Time 10:30 Rev Time 0.00
Received By adarroug Date 2008-01-22 Time 10:29 Sent To B
Notes
2008-01-22 10:30:18TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 68 Status N Date 2008-01-10 Cont ID  
Sent By spalmer Date 2008-01-10 Time 08:55 Rev Time 0.00
Received By spalmer Date 2008-01-10 Time 08:55 Sent To  
Notes
2008-01-10 08:55:40COMM BOARD # 37

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2007-12-21 Cont ID  
Sent By spalmer Date 2007-12-21 Time 16:13 Rev Time 0.00
Received By spalmer Date 2007-12-21 Time 16:13 Sent To M
Notes
2007-12-21 16:14:25TO RON REGUEIRO

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2007-12-20 Cont ID  
Sent By mmiller Date 2007-12-20 Time 17:31 Rev Time 0.00
Received By mmiller Date 2007-12-20 Time 17:31 Sent To  
Notes
2007-12-20 17:31:42SENT TO DEWEY PALMER'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2007-12-20 Cont ID  
Sent By mmiller Date 2007-12-20 Time 17:20 Rev Time 0.00
Received By mmiller Date 2007-12-20 Time 17:20 Sent To  
Notes
2007-12-20 17:20:25SENT TO JIM WITMER'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2007-12-20 Cont ID  
Sent By mmiller Date 2007-12-20 Time 17:06 Rev Time 0.00
Received By mmiller Date 2007-12-20 Time 17:05 Sent To  
Notes
2007-12-20 17:06:20SENT TO JIM WITMER'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 13:49 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 13:49 Sent To P
Notes
2007-12-10 13:49:42TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 09:26 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 09:26 Sent To E
Notes
2007-12-07 09:27:46TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2007-12-04 Cont ID  
Sent By adarroug Date 2007-12-04 Time 11:22 Rev Time 0.00
Received By adarroug Date 2007-12-04 Time 11:21 Sent To B
Notes
2007-12-04 11:22:26TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 14:24 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 14:24 Sent To FIRE
Notes
2007-11-28 14:25:20TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 14:18 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 14:18 Sent To M
Notes
2007-11-28 14:19:20TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 12:47 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 12:47 Sent To E
Notes
2007-11-28 12:47:36TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 16:43 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 16:43 Sent To B
Notes
2007-11-27 16:43:57TO "JWITMER' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 11:39 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 11:39 Sent To FIRE
Notes
2007-11-19 11:39:31TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 14:28 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 14:28 Sent To B
Notes
2007-11-16 14:29:01TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2007-10-31 Cont ID  
Sent By adarroug Date 2007-10-31 Time 09:14 Rev Time 0.00
Received By adarroug Date 2007-10-31 Time 09:14 Sent To B
Notes
2007-10-31 09:15:15TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 14:16 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 14:16 Sent To  
Notes
2007-11-07 13:22:42TO "COMM" BD#37
2007-10-23 14:16:58WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 13:00 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 13:00 Sent To E
Notes
2007-10-23 13:03:33TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 12:59 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 12:59 Sent To FIRE
Notes
2007-10-23 12:59:21TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 12:55 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 12:55 Sent To M
Notes
2007-10-23 12:56:34TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 09:17 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 09:17 Sent To B
Notes
2007-10-17 09:19:21TO "JWITMER" DESK/5 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 08:25 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 08:25 Sent To ENG
Notes
2007-10-15 08:27:12TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 09:00 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 09:00 Sent To B
Notes
2007-10-11 09:00:22TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 08:55 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 08:56 Sent To Z
Notes
2007-10-11 08:56:03TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 08:50 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 08:50 Sent To  
Notes
2007-11-05 09:01:04TO "COMM" BD#37
2007-10-11 08:51:11WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 14:11 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 14:11 Sent To B
Notes
2007-10-10 14:11:37TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 11:03 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 11:03 Sent To B
Notes
2007-10-10 11:03:24TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2007-10-09 Cont ID  
Sent By adarroug Date 2007-10-09 Time 11:34 Rev Time 0.00
Received By adarroug Date 2007-10-09 Time 11:34 Sent To P
Notes
2007-10-09 11:34:51TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2007-10-02 Cont ID  
Sent By adarroug Date 2007-10-02 Time 16:13 Rev Time 0.00
Received By adarroug Date 2007-10-02 Time 16:13 Sent To B
Notes
2007-10-02 16:14:10TO "JWITMER" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 15:34 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 15:34 Sent To B
Notes
2007-09-24 15:34:57TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 16:25 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 16:25 Sent To B
Notes
2007-09-17 16:25:52TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 16:17 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 16:17 Sent To B
Notes
2007-09-17 16:17:36TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 15:58 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 15:58 Sent To B
Notes
2007-09-17 15:58:26TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 15:51 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 15:51 Sent To B
Notes
2007-09-17 15:51:26TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 15:42 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 15:42 Sent To B
Notes
2007-09-17 15:42:51TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 15:51 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 15:51 Sent To M
Notes
2007-09-13 15:52:22TO "RREGUIERO" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 10:55 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 10:55 Sent To B
Notes
2007-09-05 09:54:17TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 10:12 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 10:12 Sent To M
Notes
2007-09-05 09:52:38TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 10:11 Sent To FIRE
Notes
2007-09-05 09:50:16TO "F" BOX-/REV

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 09:48 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 09:48 Sent To P
Notes
2007-09-05 09:48:21TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 09:44 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 09:44 Sent To FIRE
Notes
2007-09-05 09:44:54TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2007-09-04 Cont ID  
Sent By adarroug Date 2007-09-04 Time 12:21 Rev Time 0.00
Received By adarroug Date 2007-09-04 Time 12:21 Sent To E
Notes
2007-09-04 12:23:05TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 10:08 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 10:08 Sent To B
Notes
2007-08-30 10:08:37TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 09:17 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 09:17 Sent To B
Notes
2007-08-29 09:17:50TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2007-08-24 Cont ID  
Sent By adarroug Date 2007-08-24 Time 15:13 Rev Time 0.00
Received By adarroug Date 2007-08-24 Time 15:13 Sent To B
Notes
2007-08-24 15:14:36TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2007-08-24 Cont ID  
Sent By adarroug Date 2007-08-24 Time 10:38 Rev Time 0.00
Received By adarroug Date 2007-08-24 Time 10:38 Sent To B
Notes
2007-08-24 10:39:40TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2007-08-24 Cont ID  
Sent By adarroug Date 2007-08-24 Time 08:20 Rev Time 0.00
Received By adarroug Date 2007-08-24 Time 08:20 Sent To B
Notes
2007-08-24 08:21:27TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 08:20 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 08:20 Sent To B
Notes
2007-08-10 08:20:59TO JW'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 08:21 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 08:21 Sent To B
Notes
2007-08-10 08:21:22TO JW'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 08:07 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 08:07 Sent To B
Notes
2007-08-10 08:07:23TO JW'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2007-07-23 Cont ID  
Sent By adarroug Date 2007-07-23 Time 10:12 Rev Time 0.00
Received By adarroug Date 2007-07-23 Time 10:12 Sent To M
Notes
2007-07-23 10:13:03TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2007-07-23 Cont ID  
Sent By adarroug Date 2007-07-23 Time 09:46 Rev Time 0.00
Received By adarroug Date 2007-07-23 Time 09:46 Sent To  
Notes
2007-07-23 09:46:42WAITING FOR "COMM" BD--LANDSCAPE SHEETS SUBMITTED WITH
 ELECT. REV.

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2007-07-23 Cont ID  
Sent By adarroug Date 2007-07-23 Time 09:37 Rev Time 0.00
Received By adarroug Date 2007-07-23 Time 09:37 Sent To P
Notes
2007-07-23 09:38:10TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2007-07-23 Cont ID  
Sent By adarroug Date 2007-07-23 Time 09:35 Rev Time 0.00
Received By adarroug Date 2007-07-23 Time 09:35 Sent To  
Notes
2007-07-23 09:35:59TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 16:27 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 16:27 Sent To  
Notes
2007-07-09 14:56:51TO "COMM" BD#58/PLANS ON RACK--3 ROLLS
2007-06-20 16:27:35WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-06-04 Cont ID  
Sent By adarroug Date 2007-06-04 Time 08:58 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 08:58 Sent To P
Notes
2007-06-04 08:58:28TO "PSCHMITZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-05-11 Cont ID  
Sent By adarroug Date 2007-05-11 Time 14:48 Rev Time 0.00
Received By adarroug Date 2007-05-11 Time 14:48 Sent To B
Notes
2007-05-11 14:49:01TO "JWITMER' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 11:10 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 11:10 Sent To M
Notes
2007-05-02 11:11:40TO "RREGUIERO" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-05-01 Cont ID  
Sent By adarroug Date 2007-05-01 Time 16:26 Rev Time 0.00
Received By adarroug Date 2007-05-01 Time 16:26 Sent To B
Notes
2007-05-01 16:26:56TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-03-12 Cont ID  
Sent By adarroug Date 2007-03-12 Time 16:00 Rev Time 0.00
Received By adarroug Date 2007-03-12 Time 16:00 Sent To  
Notes
2007-03-12 16:03:40TO "COMM" BD#50/ PLANS ON RACK--3 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-03-05 Cont ID  
Sent By adarroug Date 2007-03-05 Time 14:50 Rev Time 0.00
Received By adarroug Date 2007-03-05 Time 14:50 Sent To B
Notes
2007-03-05 14:50:33TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 14:40 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 14:40 Sent To B
Notes
2007-02-14 14:41:03TO "JWITMER" DESK/4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-01-30 Cont ID  
Sent By adarroug Date 2007-01-30 Time 18:14 Rev Time 0.00
Received By adarroug Date 2007-01-30 Time 18:14 Sent To  
Notes
2007-02-07 16:28:57TO "COMM" BD#12
2007-01-30 18:14:33WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-01-18 Cont ID  
Sent By adarroug Date 2007-01-18 Time 12:54 Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 12:54 Sent To B
Notes
2007-01-18 12:54:45TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-30 Cont ID  
Sent By adarroug Date 2006-11-30 Time 11:54 Rev Time 0.00
Received By adarroug Date 2006-11-30 Time 11:54 Sent To B
Notes
2006-11-30 11:54:49TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 16:41 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 16:41 Sent To  
Notes
2006-11-29 16:12:08TO COMM BOARD #59,
  
 THESE ARE REVISIONS, CONTRACTOR TO COME IN AND PAY FOR
 REVISIONS. SPOKE TO DUANE.11/29
2006-11-16 16:42:05WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-09-27 Time 08:38 Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 08:38 Sent To  
Notes
2006-10-17 08:52:11TO "COMM" BD#36/PLANS BY "LMARTINEZ" OFFICE
2006-10-02 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 09:47 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 09:47 Sent To  
Notes
2006-06-29 00:00:00TO "COMM" BD#20--EXPEDITED PERMIT-RESUB
 ONLY REVIEWED BY BLDG AND ELEC.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-15 Time   Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 08:41 Sent To  
Notes
2006-06-02 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#24-EXPEDITED PERMIT ROLLS
 BY JENNIFER'S CUBE

Review Stop M MECHANICAL (A/C)
Rev No 27 Status P Date 2008-08-26 Cont ID  
Sent By rregueir Date 2008-08-26 Time 11:27 Rev Time 0.00
Received By rregueir Date 2008-08-26 Time 11:05 Sent To  
Notes
2008-08-26 11:27:23PAGE H0.02 REV #52 AND ENERGY CALCULATIONS DATED
 8/13/08

Review Stop M MECHANICAL (A/C)
Rev No 26 Status F Date 2008-07-25 Cont ID  
Sent By rregueir Date 2008-07-25 Time 11:28 Rev Time 0.00
Received By rregueir Date 2008-07-22 Time 16:33 Sent To  
Notes
2008-07-25 11:28:45REVIEW OF CALCS WAS PLACED ON HOLD PENDING CONFERENCE
 CALL WITH AHA DESIGN TEAM WHICH TOOK PLACE 7/25/08 AT
 APPROX. 8:15 AM.
  
 CLARIFICATION IS REQUIRED TO COORDINATE THE INPUT DATA
 REPORT (IDR) WITH THE PLANS. THE FOLLOWING ISSUES SHALL
 BE ADDRESSED:
  
 1. PAGE 104 OF THE IDR SHOWS A SYSTEM 7 WITH HP-3. THIS
 SYSTEM ON THE PLANS CALLS FOR A 3 TON SYSTEM WHILE THE
 IDR CALS FOR A 5 TON SYSTEM. PLEASE COODINATE THIS
 SYSTEM ON BOTH DOCUMENTS.
  
 2. PAGE 105 OF THE IDR SHOWS A SYSTEM 9 WITH HP-1. THIS
 SYSTEM ON BASE BUILDING PLANS HAS BEEN DELETED. PLEASE
 IDENTIFY WHERE THIS SYSTEM IS LOCATED AND PROVIDE A
 DESIGNATION WHICH IDENTIFIES ITS LOCATION IF NOT PART
 OF THE BASE BUILDING.
  
 3. PAGE H0.02 OF THE BASE BUILDING PLANS SHOWS AN HP-2
 ON THE HEAT PUMP SCHEDULE. THIS SYSTEM IS NOT
 REPRESENTED IN THE ENERGY CALCULATIONS AND COULD NOT BE
 FOUND IN THE IDR. PLEASE COORDINATE THIS SYSTEM ON BOTH
 DOCUMENTS.
  
 ALL OTHER LISTED SYSTEM COMPONENTS ARE IN COMPLIANCE
 AND REQUIRE NO FURTHER ACTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
2008-07-22 16:33:38REVIEW OF REVISED CALCS IN PROGRESS...

Review Stop M MECHANICAL (A/C)
Rev No 25 Status N Date 2008-05-23 Cont ID  
Sent By rregueir Date 2008-05-23 Time 08:16 Rev Time 0.00
Received By rregueir Date 2008-05-23 Time 08:11 Sent To PC
Notes
2008-05-23 08:16:20T&B REPORT FOR THE BASE BUILDING HVAC SYSTEM SUBMITTED
 ON 5/16/08 WAS WITHDRAWN BY CONTRACTER PER EMAIL
 REQUIEST FROM NATHAN DUCOTE OF BALFOUR BEATTY
 CONSTRUCTION. A FINAL T&B REPORT SHALL BE SUBMITTED TO
 THE BUILDING OWNER IN ACCORDANCE WITH FBCB
 13-410.1.ABC.4.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 24 Status F Date 2008-05-14 Cont ID  
Sent By rregueir Date 2008-05-14 Time 13:23 Rev Time 0.00
Received By rregueir Date 2008-05-14 Time 09:02 Sent To E
Notes
2008-05-14 13:23:43REVISED ENERGY CALCULATIONS DATED 5/7/08:
  
 1. THE MAX TONNAGE SHOWN ON THE FRONT OF THE FORM IS
 SHOWN AS 80 TONS. THIS DOES NOT CORRESPOND WITH THE
 APPLIANCE SCHEDULE ON PG H0.02. THE SCHEDULE SHOWS
 PAC-3 AS 90 TONS. PLEASE COORDINATE ENERGY CALCULATIONS
 WITH BUILDING PLANS IN ACCORDANCE WITH FBCB 13-103.2.
  
 2. THE COMPLIANCE CERTIFICATION PAGE HAS NOT BEEN
 COMPLETED. EXAMPLE: THIS PAGE INDICATES THE
 CALCULATIONS WERE PREPARED BY DENNIS J STROER. THE
 BUILDING OFFICIAL SHALL REQUIRE, SUBJECT TO THE
 EXCEPTIONS IN SECTION 481.229, FLORIDA STATUTES, AND
 SECTION 471.003, FLORIDA STATUTES, THAT PLANS AND
 SPECIFICATIONS, INCLUDING THE ENERGY CODE CALCULATIONS,
 BE PREPARED BY AN ENGINEER OR ARCHITECT LICENSED TO
 PRACTICE IN THE STATE OF FLORIDA IN ACCORDANCE WITH
 FBCB 13-103.2. THERE IS NO LICENSE INFORMATION OR
 SIGNATURE AND SEAL FROM THIS PERSON SHOWING THEM TO
 MEET THESE CRITERIA. THIS PERSON HAS NOT CERTIFIED
 THESE CALCULATIONS OR THIS BUILDING TO BE IN COMPLIANCE
 WITH THE FLORIDA ENERGY EFFICIENCY CODE AS REQUIRED ON
 THE COMPLIANCE CERTIFICATION FORM. PLEASE CORRECT AND
 RESUBMIT.
  
 3. DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW
 FOR THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND
 PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY
 COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY
 SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION
 NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE
 PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 EXCEPTION: TYPED NAMES AND REGISTRATION NUMBERS MAY BE
 PROVIDED IN LIEU OF A SIGNATURE WHERE ALL RELEVANT
 INFORMATION HAS BEEN INCLUDED ON SIGNED AND SEALED
 PLANS.
 NEITHER OF THESE WAS PROVIDED AS REQUIRED IN ACCORDANCE
 WITH FBCB 13-103.1.1. PLEASE SEE ALL AREAS OF THE
 COMPLIANCE CERTIFICATION FORM WHICH HAVE NOT BEEN
 FILLED OUT. CORRECT AND RESUBMIT.
  
 4. THERE ARE DISCREPANCIES BETWEEN THE INPUT DATA
 REPORT (IDR) AND THE PLANS REGARDING THE COOLING
 CAPACITIES OF THE MECHANICAL APPLIANCES. EXAMPLE: PAC
 1-16 IN THE IDR, WHICH CORRESPONDS WITH PAC-3 ON THE
 APPLIANCE SCHEDULE ON PAGE H0.02, IS SHOWN TO HAVE A
 COOLING CAPACITY OF 960,000 BTU/H WHILE THE PLANS SHOW
 A CAPACITY OF 1,066,000 BTU/H.
  
 THIS IS ONLY ONE EXAMPLE. THERE ARE OTHER
 DISCREPANCIES. PLEASE VERIFY ALL VALUES ENTERED IN THE
 (IDR) CORRESPOND WITH THE MECHANICAL SYSTEMS ON THE
 PLANS, CORRECT AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 23 Status P Date 2008-05-14 Cont ID  
Sent By rregueir Date 2008-05-14 Time 08:52 Rev Time 0.00
Received By rregueir Date 2008-05-14 Time 08:51 Sent To PC
Notes
2008-05-14 08:52:14REV 47 PAGE H2.01 CONDENSER WATER SCHEMATIC

Review Stop M MECHANICAL (A/C)
Rev No 22 Status P Date 2008-05-13 Cont ID  
Sent By rregueir Date 2008-05-13 Time 17:02 Rev Time 0.00
Received By rregueir Date 2008-05-13 Time 16:01 Sent To M
Notes
2008-05-13 17:02:14OK FROM PLAN REVIEW. SENT TO HAROLD MOSER FOR FINAL
 MECHANICAL APPROVAL. ALSO REVIEW BY FIRE MARSHAL
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 21 Status P Date 2008-05-08 Cont ID  
Sent By rregueir Date 2008-05-08 Time 13:11 Rev Time 0.00
Received By rregueir Date 2008-05-08 Time 11:34 Sent To PC
Notes
2008-05-08 13:11:22REV.45 PAGES H1.07 AND H1.09

Review Stop M MECHANICAL (A/C)
Rev No 20 Status P Date 2008-05-08 Cont ID  
Sent By rregueir Date 2008-05-08 Time 11:29 Rev Time 0.00
Received By rregueir Date 2008-05-08 Time 11:24 Sent To FIRE
Notes
2008-05-08 11:25:52REV.42 PAGES H1.01, H2.04

Review Stop M MECHANICAL (A/C)
Rev No 19 Status P Date 2008-04-17 Cont ID  
Sent By rregueir Date 2008-04-17 Time 08:10 Rev Time 0.00
Received By rregueir Date 2008-04-17 Time 08:08 Sent To PC
Notes
2008-04-17 08:10:35REV.41 PG H1.01, H1.03, H1.07

Review Stop M MECHANICAL (A/C)
Rev No 18 Status P Date 2008-04-17 Cont ID  
Sent By rregueir Date 2008-04-17 Time 08:07 Rev Time 0.00
Received By rregueir Date 2008-04-16 Time 15:01 Sent To PC
Notes
2008-04-17 08:07:24REV.40 PG H1.106

Review Stop M MECHANICAL (A/C)
Rev No 17 Status P Date 2008-03-27 Cont ID  
Sent By rregueir Date 2008-03-27 Time 10:31 Rev Time 0.00
Received By rregueir Date 2008-03-27 Time 10:30 Sent To PC
Notes
2008-03-27 10:31:28PAGES A1.02 THROUGH A1.05 REV.36 FOR GARAGE EXHAUST
 FANS OK. MECH PLANS ALREADY COORDINATED WITH THESE
 CHANGES.

Review Stop M MECHANICAL (A/C)
Rev No 16 Status P Date 2008-03-10 Cont ID  
Sent By rregueir Date 2008-03-10 Time 07:57 Rev Time 0.00
Received By rregueir Date 2008-03-10 Time 16:49 Sent To  
Notes
2008-03-25 07:57:27REV 33 PAGES:
 H0.02
 H1.01
 H1.02
 H1.03
 H1.05
 H1.06
 H1.07
 H1.08
 H1.09
 H1.15
 H1.16
 H1.17
 H1.18
 H2.01
 H2.02

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date 2008-01-07 Cont ID  
Sent By rregueir Date 2008-01-07 Time 13:47 Rev Time 0.00
Received By rregueir Date 2008-01-07 Time 11:08 Sent To PC
Notes
2008-01-07 11:09:10REV. 32 PAGES H0.02, H1.06, H1.07, H1.09.

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2007-12-20 Cont ID  
Sent By rregueir Date 2007-12-20 Time 15:52 Rev Time 0.00
Received By rregueir Date 2007-12-20 Time 11:05 Sent To PC
Notes
2007-12-20 15:53:52REV 29 PAGES:
 H1.01
 H1.02
 H1.03
 H1.05
 H1.06
 H1.07
 H1.08
 H1.09
 H1.15
 H1.16
 H1.17
 H1.18
 H2.02
 H2.04

Review Stop M MECHANICAL (A/C)
Rev No 13 Status F Date 2007-11-10 Cont ID  
Sent By rregueir Date 2007-11-10 Time 15:33 Rev Time 0.00
Received By rregueir Date 2007-11-10 Time 15:12 Sent To PC
Notes
2007-11-10 15:33:21REVISION #: 23
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 REVISION FOR H0.02, H1.16, H1.17, H2.04
 REVISION FOR SMOKE CONTROL NARRATIVE AND RATIONAL
 ANALYSIS.
  
 NO EXCEPTION IS TAKEN TO THE REVISIONS ON H0.02, H1.16
 AND H1.17. HOWEVER, THESE PLANS WILL NOT BE
 INCORPORATED INTO THE PERMIT SET PRIOR TO ACCEPANCE OF
 THE SMOKE CONTROL SEQUENCE WHICH GOVERNS THE
 FUNCTIONALITY OF THE NEWLY ADDED EQUIPMENT.
 1. ON PG H2.04 THE SEQUENCE CONTAINS CONFLICTING
 INSTRUCTIONS.
 IN SEQUENCE (B) FOR FLOORS 6 THROUGH 16, SUBSECTION (E)
 INDICATES THAT FLOORS 15 AND 16 ARE STILL BEING TREATED
 AS INDIVIDUAL ZONES RATHER THAN ONE ZONE. THIS DOES NOT
 CORRELATE WITH ACTIONS CALLED FOR UNDER SEQUENCE (C)
 FOR THE 14TH FLOOR AND IT IS IN CONFLICT WITH SEQUENCE
 (D) WHICH DOES CALL FOR THE 15TH AND 16TH FLOORS TO BE
 TREATED AS ONE ZONE.
  
 2. THE NARRATIVE/ANALYSIS CONTAINS SIMILAR CONFLICTING
 INFORMATION. ON PAGE 3, PARAGRAPH 4 INDICATES THAT THE
 16TH FLOOR WILL BE TREATED AS AN INDIVIDUAL SMOKE ZONE.
 PARAGRAPH 5 EXPLAINS THAT FLOORS 15 AND 16 ARE ONE
 ZONE.
  
 ONCE THE CONFLICTING INFORMATION IS REMOVED AND/OR
 CORRELATED IN THE NARRATIVE AND ON THE PLANS, THE
 ADJUSTMENTS BEING MADE TO TREAT FLOORS 15 AND 16 AS ONE
 SMOKE ZONE MAY BE IN ORDER, DEPENDIG ON HOW THESE
 COMMENTS ARE ADDRESSD. PLEASE MAKE THE NECESSARY
 CORRCTIONS AND CLARIFICATIONS, THEN RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2007-10-11 Cont ID  
Sent By rregueir Date 2007-10-11 Time 08:34 Rev Time 0.00
Received By rregueir Date 2007-10-06 Time 15:33 Sent To  
Notes
2007-10-11 08:43:32**************PROVISO****************
  
 1. H1.07 THRU H1.16: VAV BOX HAS BEEN ADDED TO HVAC
 SYSTEM TO CONDITION EXEC. VESTIBULE. THIS BOX DOES NOT
 HAVE AN EQUIPMENT DESIGNATION ON FLOOR PLAN. ALSO, THE
 VAV SCHEDULE ON H0.02 HAS NOT BEEN REVISED TO SHOW THIS
 NEW SIZE VAV. PLEASE REVISE BOTH PAGES, PROVIDING
 MISSING INFORMATION AND SHOWING COORDINATION BETWEEN
 FLOOR PLANS AND EQUIPMENT SCHEDULES. FBC 106.1.1,
 106.1.3
  
 2. H1.07 THRU H1.16: RISER 8 HORIZONTAL DUCTS ARE NOT
 SHOWN TO HAVE REQUIRED OPENING PROTECTIVES WHERE THEY
 PENETRATE THE SHAFT WALL AT EACH LEVEL. RATHER, THE FSD
 IS SHOWN AT A WALL ON THE OTHER SIDE OF THE SERVICE
 VESTIBULE. PLEASE REVISE PLANS TO SHOW HOW THE SHAFT
 RATING IS TO BE MAINTAINED IN ACCORDANCE WITH FBC,M
 607.5.5.1.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 11 Status   Date 2007-09-15 Cont ID  
Sent By rregueir Date 2007-09-15 Time 15:34 Rev Time 0.00
Received By rregueir Date 2007-09-15 Time 15:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2007-07-30 Cont ID  
Sent By rregueir Date 2007-07-30 Time 16:40 Rev Time 0.00
Received By rregueir Date 2007-07-28 Time 15:50 Sent To  
Notes
2007-07-30 16:42:22REVISED PAGES H0.01 THROUGH H2.04, WHICH IS THE ENTIRE
 MECHANICAL SET OF PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status F Date 2007-07-02 Cont ID  
Sent By rregueir Date 2007-07-02 Time 09:44 Rev Time 0.00
Received By rregueir Date 2007-06-30 Time 14:58 Sent To  
Notes
2007-07-02 09:43:39FBC 2004 CODE FAMILY W/2005 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF
 CONTINUITY.
  
 1. OK
  
 2. REVISION 6 IS THE LAST REVISION THAT WAS STAMPED AND
 FILED AT THIS OFFICE, BUT THE SUBMITTED PLANS HAVE
 DELTAS FOR LATER REVISIONS WHICH ARE NOT CLEARLY MARKED
 (NO CLOUDS). PLEASE CLEARLY INDICATE ON PLANS EVERY
 CHANGE WHICH HAS TAKEN PLACE AFTER REVISION 6
 (11-10-06). ALSO, SF-2 ON FAN SCHEDULE INDICATES REMARK
 #1 APPLIES. HOWEVER, SF-2 DOES NOT OCCUR ON FLOORS 2,
 3, 4 AND 5 AS REMARK #1 STATES. IT IS ONLY ON THE 5TH
 FLOOR. SEF-1A AND SEF-1B DO NOT APPEAR ON FLOOR PLANS
 OR RISER DIAGRAM (H1.17 AND H2.04), RATHER, THERE IS
 ONLY ONE SEF 1 SHOWN. PLEASE CLARIFY AND COORDINATE
 FLOOR PLANS WITH SCHEDULES.
  
 3. PLEASE REMOVE THE ?18? MIN.? NOTATION FROM DETAIL
 25. IT MAY OR MAY NOT BE CODE COMPLIANT DEPENDING ON
 THE WIDTH OF THE EQUIPMENT. PERHAPS A NOTE REFERENCING
 DETAIL 50 ON H0.04 FOR REQUIRED EQUIPMENT HEIGHTS WOULD
 BE MORE APPROPRIATE. ALSO, NO INFORMATION OR DETAIL
 COULD BE FOUND IN REVISION 15 STRUCTURAL PLANS
 REGARDING WIND LOADS AS WAS INDICATED IN THE COMMENT
 RESPONSE LETTER.
  
 4. NO INFORMATION COULD BE FOUND ON REVISION 15
 STRUCTURAL PLANS REGARDING WIND LOADS OR ATTACHMENT
 DETAILS RELATED TO ROOFTOP DUCTWORK. ALSO, A NOTE
 REFERENCING DETAIL 50 FOR REQUIRED CLEARANCES WOULD BE
 APPROPRIATE.
  
 COMMENTS 5 THROUGH 8: OK
  
 9. THE12X16 DUCT WHICH WAS REVISED TO 18X8 IS STILL
 MISSING A FIRE DAMPER IN THE DUCT RUNNING FROM
 ELECTRICAL ROOM (105) INTO RETAIL 1 (106). PLEASE SHOW
 OPENING PROTECTIVE AS REQUIRED BY FBC,M 607.5.
  
 10. H1.06 THROUGH H1.16 STILL SHOW A NOTE STATING THAT
 A 2? CONDENSATE DRAIN IS TO BE ROUTED TO AND DISCHARGE
 INTO A FLOOR DRAIN. PLEASE CLARIFY AND COORDINATE WITH
 PLUMBING PLANS.
  
 COMMENTS 11 THROUGH 19: OK
  
 20.THE DUCT RELATED TO SF-2 FOR ELEVATOR LOBBIES
 TRAVELS FROM THE 5TH FLOOR DOWN TO THE 2ND FLOOR. AS
 SUCH, A SHAFT ENCLOSURE IS REQUIRED PER FBC 707.2. ALL
 SHAFT PENETRATIONS SHALL BE PROTECTED PER FBC,M
 607.5.5.1. THE INTAKE LOCATION FOR SF-2 SHALL BE
 LOCATED A MINIMUM OF 10 FEET FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS?
 FBC,M 401.5.1
  
 COMMENTS 21 AND 22: OK
  
 23. PLEASE SEE COMMENT #20 RELATED TO ELEVATOR LOBBY
 VENTILATION.
  
 COMMENTS 24 THROUGH 31: OK
  
 32. PLEASE SEE COMMENT #20 REGARDING ELEVATOR LOBBY
 VENTILATION.
  
 33. SMOKE CONTROL SYSTEM:
 NOTE: THE ADDITION OF THE SMOKE CONTROL SYSTEM DOES NOT
 ONLY PROVIDE COMPLIANCE WITH FBC 909, IT ALSO PROVIDES
 COORDINATION WITH THE PERMIT SET OF FIRE ALARM PLANS
 WHICH HAVE CALLED FOR A SMOKE CONTROL PANEL WITH HOA IN
 THE FIRE COMMAND ROOM (SEE FA1.01) SINCE AT LEAST
 REVISION #6 (DATED 11-10-06). THE FOLLOWING ARE
 COMMENTS RELATED TO THE SMOKE CONTROL SYSTEM AS
 SUBMITTED:
  
 1) THE 3 COPIES OF THE SMOKE CONTROL SYSTEM NARRATIVE
 REPORT SHALL BE SIGNED AND SEALED BY THE DESIGNER(S) OF
 RECORD.
 2) SUBMITTAL OF THE SMOKE CONTROL NARRATIVE IS NOTED.
 HOWEVER, PLEASE INCLUDE SEQUENCE OF OPERATIONS AND
 CONTROL DETAILS ON HVAC AND FIRE ALARM PLANS AS NEEDED
 TO CLEARLY DEMONSTRATE THE SCOPE OF WORK REQUIRED FOR A
 FULLY FUNCTIONAL AND CODE COMPLIANT SMOKE CONTROL
 SYSTEM. FBC 106.1.1 AND 106.3.5.1.1
  
 A: FLOORS 6-16
  
 (B) STAIR PRESSURIZATION SHALL BE MINIMUM 0.15? WC AND
 A MAXIMUM OF 0.35? WC IN THE SHAFT RELATIVE TO THE
 BUILDING MEASURED WITH ALL STAIRWAY DOORS CLOSED UNDER
 MAXIMUM ANTICIPATED STACK PRESSURES. THE NOTE ON STAIR
 1 RELIEF DAMPER (H1.18) WILL ALSO NEED TO BE CORRECTED.
 STAIR 2 RELIEF DAMPER COULD NOT BE LOCATED ON PLANS. BY
 WHAT MEANS IS THE PRESSURE TO BE BALANCED IN THIS
 SHAFT?
 (D) PLEASE INDICATE IN SEQUENCE SPECIFICALLY WHICH FSD
 WILL OPEN WHEN ALL OTHER FSD?S WILL CLOSE.
 (F) PLEASE SEE COMMENT #2 REGARDING SEF-1 DESIGNATION
 ON EQUIPMENT SCHEDULE (H0.02).
  
 B: FIRST FLOOR MAIN LOBBY
  
 (B) PLEASE INDICATE IN SEQUENCE SPECIFICALLY WHICH FSD
 WILL OPEN WHEN ALL OTHER FSD?S WILL CLOSE. THERE IS NO
 FSD SHOWN ON SEF-2 DUCT WHERE IT EXITS THE SHAFT ON
 FLOOR PLAN (H1.01) OR RISER 9 DIAGRAM (H2.04). WHAT IS
 THE PURPOSE OF OPENING THE MOTORIZED DAMPER FOR SEF-1
 IN THIS PART OF THE SEQUENCE? IT ONLY SERVES THE UPPER
 FLOORS.
 (C) NO ASSOCIATED FSD IS SHOWN ON PLANS. SEF-2 ACCESS
 DOOR (H1.05), IS THERE A STEEL GIRDER OR BEAM WHICH
 WILL INTERFERE WITH ACCESS? SEF-2 DISCHARGES ADJACENT
 TO THE SIDE OF THE PARKING GARAGE WHICH IS OPEN TO THE
 OUTDOORS. WHAT WILL THE STATUS OF GARAGE EXHAUST FANS
 (PF-1 THROUGH PF-12 AND SF-1) BE WHEN SEF-2 IS ACTIVE
 (SINCE THAT LOCATION IS THE SOURCE OF MAKE-UP AIR FOR
 THESE FANS)? ARE THERE PROVISIONS TO ENSURE PF?S AND
 SF-1 WILL NOT DRAW SMOKE INTO PARKING GARAGE? SEF-2
 INTAKE ON H2.04 RISER DIAGRAM IS SHOWN ABOVE THE
 CEILING IN RETAIL 1 AREA. THIS DOES NOT CORRELATE WITH
 FLOOR PLAN AND IS NOT FUNCTIONAL FOR PROVIDING SMOKE
 CONTROL TO THE MAIN LOBBY AREA.
 (D) SEQUENCE INDICATES DOORS WILL OPEN FOR SMOKE
 EXHAUST MAKE-UP AIR, BUT PLAN SHOWS LOUVERS WITH
 MOTORIZED DAMPERS ABOVE THE DOORS ADDED IN THIS
 REVISION. IS THIS IN ADDITION TO THE LOBBY DOORS OR
 INSTEAD OF THEM? PLEASE CLARIFY. IF THE LOUVERS AND
 MOTORIZED DAMPER ARE TO BE USED, PLEASE ADJUST SEQUENCE
 ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2007-05-04 Cont ID  
Sent By rregueir Date 2007-05-04 Time 07:08 Rev Time 0.00
Received By rregueir Date 2007-05-02 Time 18:58 Sent To P
Notes
2007-05-03 15:55:16--------------DENIED-----------------
  
 THE CHANGES SHOWN ON PLANS APPEAR TO ADEQUATELY ADDRESS
 THE OUTSTANDING CONDENSATE DISPOSAL ISSUES. HOWEVER,
 THE CONDENSATE CHANGES HAVE BEEN INCORPORATED ONTO THE
 SAME MECHANICAL PAGES WHICH WERE REJECTED DURING THE
 PREVIOUS MECHANICAL PLAN REVIEW WHICH WAS COMPLETED ON
 4/20/07. THESE PAGES CAN NOT BE APPROVED UNTILL ALL
 PLAN REVIEW COMMENTS RELATED TO THESE PAGES HAVE BEEN
 ADDRESSED. IF THE CONDENSATE CHANGES HAD BEEN
 INCORPORATED ONTO THE CURRENT PERMITTED SET OF PLANS,
 THE CONDENSATE CHANGES COULD HAVE BEEN APPROVED
 INDEPENDENT OF THE PREVIOUS REVISION WITH THE
 OUTSTANDING COMMENTS. AT THIS TIME YOU MAY EITHER
 RESUBMIT THE CONDENSATE CHANGES ON PLANS WHICH
 OTHERWISE MATCH THE CURRENT PERMITTED SET OF PLANS OR
 YOU MAY RESUBMIT THE CONDENSATE REVISIONS IN
 CONJUNCTION WITH RESPONSES TO THE OUTSTANDING
 COMMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2007-04-20 Cont ID  
Sent By rregueir Date 2007-04-20 Time 08:29 Rev Time 0.00
Received By rregueir Date 2007-04-16 Time 16:47 Sent To  
Notes
2007-04-19 16:11:36-------------------DENIED---------------------
  
 FBC 2004 CODE FAMILY W/2005 REVISIONS
 FBC CH 1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 -COMMENTS ARE ORGANIZED BY PAGE NUMBER UNLESS COMMENT
 APPLIES TO THE ENTIRE BUILDING.
 -15 PAGES WERE SUBMITTED AS A PACKAGE FOR THIS
 REVISION. THAT COMPRISES EVERY PAGE OF THE ORIGINAL
 PERMITTED SET OF PLANS.
 -EQUIPMENT CHANGES AS STATED ON REVISED PAGE H0.02 WILL
 REQUIRE REVISED ENERGY CALCULATIONS TO BE SUBMITTED
 WHEN THE FOLLOWING COMMENTS ARE ADDRESSED AND
 RESUBMITTED.
 -SUBMITTED PLANS (1 SET) HAVE BEEN MARKED WHEN
 PRACTICAL TO SHOW AREAS BEING ADDRESSED BY PLAN REVIEW
 COMMENTS.
  
 1. H0.01: THERE HAS BEEN A CHANGE TO THIS PAGE BUT THE
 CHANGED WAS NOT MARKED ON THE PLAN AS A REVISION.
  
 2. H0.02: THIS PAGE HAS BEEN MODIFIED BY REVISIONS 7
 AND 10, YET ONLY REVISION 10 HAS BEEN MARKED AS A
 CHANGE. THE LAST REVISION SUBMITTED TO THIS OFFICE
 RELATED TO THIS PAGE WAS REVISION 6 DATED 11/10/06. ANY
 CHANGES FROM THAT DATE FORWARD SHOULD BE CLEARLY MARKED
 TO FACILITATE AN ACCURATE REVIEW AS WELL AS TO MAINTAIN
 CONTINUITY OF CONSTRUCTION DOCUMENTS. FBC 106.1.3.
  
 3. H0.03 DETAIL 25: HEIGHT OF ROOFTOP EQUIPMENT IS TO
 BE DETERMINED BY FBC TABLE 1509.7. ALSO, PLEASE SHOW
 STRUCTURAL DATA (FROM STRUCTURAL ENGINEER) FOR ALL
 ROOFTOP EQUIPMENT WITH WIND LOAD CALCULATIONS PER FBC
 1603.1.4 ALONG WITH DETAILED INFORMATION RELATED TO
 ATTACHMENTS OF ALL EQUIPMENT TO STRUCTURE NEEDED TO
 MEET WIND LOAD REQUIREMENTS. THIS APPLIES TO ALL
 ROOFTOP AND OUTDOOR EQUIPMENT.
  
 4. H0.04: SEE ABOVE COMMENT REGARDING DETAIL 31,
 EXTERIOR DUCTWORK.
  
 5. H1.01 & H1.02: PLAN SHOWS SOME KIND OF SHAFT WALL IN
 MECHANICAL RM 204 FOR PAC 2 DUCTS TO REACH 1ST FLOOR.
 HOWEVER, REVISED PG A1.02 DOES NOT SHOW ANY SHAFT WALL.
 WHERE ARE THESE RATED PENETRATIONS TO TAKE PLACE? IF A
 SHAFT IS TO BE USED, OPENINGS MUST BE PROTECTED WHERE
 THE DUCTS ENTER AND LEAVE THE SHAFT. PLEASE CLARIFY AND
 COORDINATE WITH ARCHITECTURAL DRAWINGS. PERHAPS AN
 ENLARGED DRAWING OF MECHANICAL ROOMS WITH PLAN AND
 ELEVATION VIEWS ARE NEEDED TO CLEARLY SHOW THE SCOPE OF
 WORK. FBC,M 106.1.1.
  
 6. H1.01: PLEASE SHOW LOCATION OF ALL GRILLS/REGISTERS
 AS THEY ARE SHOWN ON REFLECTIVE CEILING PLAN TO SHOW
 HOW BALANCED RETURN IS TO BE ACHIEVED IN VARIOUS AREAS.
 FBC,M 601.4.
  
 7. H1.01: FRESH AIR INTAKE FOR THE LOADING DOCK SHALL
 BE A MINIMUM OF 10' AWAY FROM STREETS, ALLEYS, PARKING
 LOTS AND LOADING DOCKS PER FBC,M 401.5.1.
  
 8. H1.01 HP-3 IN LOADING DOCK: WHAT IS THE ELEVATION TO
 THE BOTTOM OF HEAT PUMP? APPLIANCES IN PUBLIC GARAGES
 OR OTHER AREAS FREQUENTED BY MOTOR VEHICLES EXCEEDING 6
 FEET IN HEIGHT SHALL BE INSTALLLED A MINIMUM OF 2 FEET
 HIGHER ABOVE THE FLOOR THAN THE HEIGHT OF THE TALLEST
 VEHICLE. FBC,M 304.5
  
 9. H1.01: 12X16 DUCT IS SHOWN PENETRATING RATED WALL AT
 RETAIL 1. PLEASE SHOW METHOD OF OPENING PROTECTIVE TO
 BE USED PER FBC,M 607.5.
  
 10. H1.01 THROUGH H1.18: A/C CONDENSATE SHALL NOT
 DISCHARGE INTO CITY WASTE WATER FACILITY PIPING PER
 W.P.B. MUNICIPAL CODE SEC 90-125(B)(5). PLUMBING PLANS
 EXAMINER MAY BE ABLE TO HELP IN DETERMINING THE BEST
 WAY TO DISPOSE OF CONDENSATE IN THE STORM WATER DRAIN
 SYSTEM.
  
 11. H1.01: WHAT IS THE SIZE OF EXHAUST DUCT BETWEEN
 CIF-6 AND THE 22X22 EXHAUST RISER DUCT? IS THERE ROOM
 FOR A 22" TALL DUCT TO CROSS THE DRIVEWAY? PLEASE SEE
 COMMENT 8 REGARDING VEHICLE HEIGHTS AND REQUIRED
 CLEARANCE.
  
 12. H1.02 STAIR 2: RISER 2 DUCT IN STAIR 2 IN 1ST FLOOR
 DOES NOT APPEAR TO BE IN A RATED ENCLOSURE AS IT IS ON
 OTHER FLOORS. THE RISER DIAGRAM SHOWS IT LEAVING THE
 SHAFT, TRAVELING THROUGH THE STAIRWAY AND INTO THE
 CEILING OF RETAIL 1. PLEASE CLARIFY.
  
 13. PLEASE SHOW HANGNG DETAIL FOR HORIZONTAL AHU'S AND
 HEAT PUMPS, SHOWING COMPLIANCE WITH FBC,M 307.2.3
 RELATED TO SECONDARY/AUXILIARY DRAIN PROTECTION.
  
 14. H1.02: LIFE SAFETY PLAN A0.22 SHOWS 1 HOUR RATED
 WALL BETWEEN STORAGE ROOM 205 AND ELEVATOR LOBBY. HOW
 WILL THIS OPENING BE PROTECTED? PLEASE SHOW COMPLIANCE
 WITH FBC,M 607.5.
  
 15. H1.02: ACCU'S IN GARAGE ARE ONLY PROTECTED FROM
 VEHICLE DAMAGE ON 2 SIDES. PLEASE SHOW PROTECTION ON 3
 SIDES. ALSO, WE HAVE STILL NOT RECEIVED DOCUMENTATION
 FROM THE EQUIPMENT MANUFACTURER REGARDING THE
 SUITABILITY OF ACCU'S BEING INSTALLED INDOORS. FBC,M
 304.5
  
 16. H1.02: WHAT IS THE HEIGHT TO THE BOTTOM OF PF-1 AND
 PF-2? APPLIANCES LOCATED IN PUBLIC GARAGES SHALL BE
 INSTALLED A MINIMUM OF 8 FEET ABOVE THE FLOOR OR 2'
 ABOVE THE HEIGHT OF ANY VEHICLE OVER 6' HIGH HAVING
 ACCESS TO THE GARAGE UNLESS PROTECTED FROM MOTOR
 VEHICLE IMPACT. FBC,M 304.5.
  
 17. H1.02: WHAT IS THE HEIGHT OF O.A. DUCT AND PIPING
 FROM RISERS 5 & 6 TO MECHANICAL RM 204? PLEASE NOTE:
 THESE RUN OVER A VAN ACCESSIBLE DISABLED PARKING
 SPACE.
  
 18. H1.02: R-1 RISER DUCT AT STAIR 1 IS SHWON OUTSIDE
 THE SHAFT ENCLOSURE. IS THIS TO BE FLAMEBAR DUCT?
 PLEASE CLARIFY PER FBC 106.1.1.
  
 19. H1.02 SECTION AA: IS IT THE INTENTION OF THE
 DESIGNER THAT PAC-2 SITS ON A BIG NEOPRENE PAD? IS THIS
 INTENDED TO BE A CONCRETE HOUSEKEEPING PAD? PLEASE
 CLARIFY PER FBC 106.1.1.
  
 20. H1.02: WHAT IS THE MEANS AND RATE OF MECHANICAL
 VENTILATIONFOR THE FOLLOWING AREAS:
 STORAGE 202
 SERVICE VESTIBULE 203
 ELECTRICAL RM 209
 STORAGE 205
 ELEVATOR LOBBIES - ALSO SEE FBC,M 404.3
 ELEVATOR MACHINE ROOM.
 NOTE: RECIRCULATION OF AIR FROM GARAGE IS PROHIBITED
 PER FBC,M 403.2.1(1).
  
 21. H1.02 AND ALL PARKING LEVELS: SF-1 SUPPLY FAN FOR
 PARKING GARAGE INTAKE IS LOCATED WITHIN THE PARKING
 GARAGE. OUTDOOR AIR IS REQUIRED PER FBC,M 403.2 AND CAN
 NOT BE DRAWN FROM WITHIN THE ENCLOSED PARKING GARAGE.
 SF-1 INTAKE OPENING SHALL BE LOCATED IN COMPLIANCE WITH
 FBC,M 401.5.1.
  
 22. H1.02 AND ALL PARKING LEVELS: SF-1 ON FAN SCHEDULE
 IS SHOWN TO PRODUCE 5,000 CFM. DESIGNER'S CALCULATIONS
 SHOW 45,000 CFM OF VENTILATION REQUIRED. VENTILATION
 SUPPLY SYSTEMS SHALL BE DESIGNED TO DELIVER THE
 REQUIRED RATE OF SUPPLY AIR (45,000 CFM) TO THE
 OCCUPIED ZONE WITHIN THE OCCUPIED SPACE. THE AMOUNT OF
 SUPPLY AIR SHALL BE APPROXIMATELY EQUAL TO THE AMOUNT
 OF EXHAUST AIR PER FBC,M 403.1.
  
 23. H1.03: SEE REVIEW COMMENT 20 REGARDING
 VENTILATION.
  
 24. H1.03: SEE REVIEW COMMENT 16 REGARDING
 ELEVATION/PROTECTION OF GARAGE FANS.
  
 25. H1.03 & H1.05: PLEASE INDICATE ON PLANS WHETHER R-1
 RISER DUCT IS TO BE ENCLOSED IN A RETED ENCLOSURE OR
 CONSTRUCTED OF FLAMEBAR. FBC 106.1.1.
  
 26. H1.03: LIFE SAFETY PLAN A0.22 SHOWS STORAGE RM 304
 TO BE ONE-HOUR RATED AND 405 TO BE TWO-HOUR RATED.
 PLEASE SHOW HOW DUCT PENETRATIONS ARE TO BE PROTECTED
 PER FBC,M 607.5.
  
 27. H1.03: EMERGENCY ELECTRICAL RM 405: 400 CFM OF
 MAKE-UP AIR IS NEEDED FOR CIF-3. WHAT IS THE SOURCE?
 FBC 403.2.1.
  
 28. H1.05PLAN SHOWS DUCTS PENETRATING STORAGE RM 502 &
 504. PLEASE SHOW HOW DUCT PENETRATIONS ARE TO BE
 PROTECTED PER FBC,M 607.5.
  
 29. H1.05: PLEASE SHOW FIRE/SMOKE DAMPER WHERE R-4 DUCT
 LEAVES SHAFT PER FBC,M 607.5.5.1.
  
 30. H1.05: R-1 RISER DUCT SHOWS A FIRE DAMPER WHERE
 DUCT LEAVES THE SHAFT AND ENTERS ELECTRICAL ROOM. WHERE
 A FIRE DAMPER WILL INTERFERE WITH THE OPERATIONOF A
 REQUIRED SMOKE CONTROL SYSTEM (SUCH AS STAIRWELL
 PRESSURIZATION), APPROVED ALTERNATIVE PROTECTION SHALL
 BE UTILIZED. FBC,M 607.2.1
  
 31. H1.05: WHAT IS BOTTOM ELEVATION OF GARAGE FANS?
 PLEASE SEE REVIEW COMMENT 16 REGARDING
 ELEVATION/PROTECTION IN PUBLIC GARAGES.
  
 32. H1.05: PLEASE SEE REVIEW COMMENT 20 REGARDING
 VENTILATION.
  
 33. SMOKE CONTROL: BUILDINGS REQUIRED BY THIS CODE TO
 HAVE A SMOKE CONTROL SYSTEM SHALL HAVE SUCH SYSTEMS
 DESIGNED IN ACCORDANCE WITH THE APPLICABLE REQUIREMENTS
 OF FBC SECTION 909 AND THE GENERALLY ACCEPTED AND
 WELL-ESTABLISHED PRINCIPLES OF ENGINEERING RELEVANT TO
 THE DESIGN. THE CONSTRUCTION DOCUMENTS SHALL INCLUDE
 SUFFICIENT INFORMATION AND DETAIL TO DESCRIBE
 ADEQUATELY THE ELEMENTS OF THE DESIGN NECESSARY FOR THE
 PROPER IMPLEMENTATION OF THE SMOKE CONTROL SYSTEMS.
 THESE DOCUMENTS SHALL BE ACCOMPANIED WITH SUFFICIENT
 INFORMATION AND ANALYSIS TO DEMONSTRATE COMPLIANCE WITH
 THESE PROVISIONS. FBC,M 513.2
  
 34. H1.01 THRU H1.05: PROVIDE SIZE OF CEILING ACCESS
 DOORS FOR HEAT PUMPS AND ACCU'S ABOVE HARD CEILINGS.
 SHOW COMPLIANCE WITH FBC,M 306.1.
  
 35. H1.06 HVAC ALTERNATE #1 NOTES: PLEASE CHOOSE A
 METHOD OF DUCT CONSTRUCTION AND SPECIFY PER FBC
 106.1.1. ALSO, FUTURE TENANT SUPPLY DUCT SHOULD EITHER
 BE INCLUDED IN THIS SCOPE OF WORK FOR REVIEW AS A
 REVISION OR SHOULD BE REMOVED FROM THIS PLAN AND BE
 SHOWN ON TENANT BUILD-OUT PLANS AT THE TIME OF
 APPLICATION.
  
 36. H1.06: THIS PLAN SHEET IS TITLED FOR 6TH FLOOR
 ONLY. THERE ARE INDICATIONS ON THIS SHEET OF WORK TO BE
 DONE ON OTHER FLOORS (7-14). THERE ARE SIGNIFICANT
 ARCHITECTURAL AND MECHANICAL DIFFERENCES ON THESE
 FLOORS. PLEASE PROVIDE SEPARATE PLANS FOR FLOORS WHEN
 THEY ARE NOT TYPICAL TO FACILITATE A COMPLETE REVIEW
 AND TO ALLOW FOR PROPER INSPECTION IN THE FUTURE. FBC
 106.1.1. THERE MAY BE ADDITIONAL COMMENTS ONCE THE
 PLANS FOR FLOORS 7-14 ARE SEPARATED FROM THIS SHEET.
  
 37. H1.06: FLEX RUNOUTS ARE LIMITED TO 3 FEET IN LENGTH
 ON H0.03 DETAIL. ALSO, THE VAV MANUFACTURER MAY HAVE
 LIMITS TO THE ALLOWABLE LENGTHS OF FLEX DUCT FOR MEDIUM
 PRESSURE SYSTEMS. PLEASE PROVIDE MANUFACTURER'S
 INSTRUCTIONS TO SHOW MAXIMUM ALLOWABLE LENGTH OF FLEX
 AND INCLUDE THAT INFORMATION IN THE VAV DETAIL ON
 H0.03.
  
 38. MECHANICAL RM 605: THIS ROOM IS A RETURN AIR
 PLENUM. RETURN AIR PLENUMS SHALL BE SEALED WITH AN
 APPROVED CONTINUOUS AIR BARRIER. AN OPEN FLOOR DRAIN
 CAN NOT BE LOCATED IN A RETURN AIR PLENUM. FBC CH
 13-410.1.ABC.3.7
  
 39. H1.06: WHAT TYPE OF COOKING OR HEATING APPLIANCES
 WILL BE IN CATERING RM 615? PLEASE VERIFY THAT THERE
 WILL BE NO APPLIANCES REQUIRING A HOOD IN ACCORDANCE
 WITH FBC,M 507.2.
  
 40. H1.06: EF-6 IS LOCATED IN A RETURN AIR PLENUM.
 EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT BE
 LOCATED IN A PLENUM PER FBC,M 601.3.
  
 41. H1.06: CONFERENCE CENTER 613 IS RECEIVING 2500 CFM
 OF SUPPLY AIR. THERE IS ONE RETURN GRILL AND ONE
 TRANSFER DUCT. THE TRANSFER DUCT SIZING SCHEDULE ON
 H0.03 ONLY GIVES SIZES FOR TRANSFER DUCTS UP TO 1300
 CFM. PLEASE SHOW HOW BALANCED RETURN IS TO BE ACHIEVED
 IN THIS AREA PER FBC,M 601.4.
  
 42. H1.06: ALL WALLS AROUND ROOMS 613,614 AND 615 ARE
 SHOWN TO BE FIRE RATED TYPE 6A WALLS AS SHWON ON A2.06
 AND A0.31. PLEASE SHOW HOW DUCT PENETRATIONS ARE TO BE
 PROTECTED PER FBC,M 607.5.
  
 43. H1.15: PLEASE SEE REVIEW COMMENTS 35 AND 38 FOR
 CORRECTIONS NEEDED ON THIS PAGE.
  
 44. H1.16: PLEASE SEE REVIEW COMMENTS 35 AND 38 FOR
 CORRECTIONS NEEDED ON THIS PAGE.
  
 45. H1.15 AND H1.16: DRAWING NOTE #4 IS SHWON ON FLOOR
 PLAN BUT IS NOT EXPLAINED IN NOTES. PLEASE CORRECT. FBC
 106.1.1
  
 46. H1.17: OAF-1 DUCT AND HOISTWAY RELIEF LOUVERS ARE
 SHWON TO BE PENETRATING TWO-HOUR RATED WALLS. PLEASE
 SHOW OPENING PROTECTIVES PER FBC,M 607.5.
  
 47. H1.18: HOISTWAY VENT SHOWN PENETRATING TWO-HOUR
 RATED WALL. PLEASE SHOW OPENING PROTECTIVES PER FBC,M
 607.5.
  
 IF YOU HAVE ANY QUESTIONS ABOUT THIS REVIEW, PLEASE
 CONTACT:
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-02-27 Cont ID  
Sent By tgordon Date 2007-02-27 Time 07:58 Rev Time 0.25
Received By tgordon Date 2007-02-27 Time 07:58 Sent To  
Notes
2007-02-27 07:59:46REVISION TO MECH. PLANS PAGE H0.03.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-12-11 Cont ID  
Sent By pkrauss Date 2006-12-11 Time 09:31 Rev Time 0.00
Received By pkrauss Date 2006-12-11 Time 09:31 Sent To  
Notes
2006-12-11 10:17:14REVISION:
  
 SHEETS H0.02, H1.01 ARE APPROVED.THE RESPONSE LETTER
 SUBMITTED AHA CONSULTING ENGINEERS, INC. COMMENTS 1, 2,
 3, & 15 ARE ACCEPTABLE.
  
 PROVISO:
 PLEASE PROVIDE ADDTIONAL INFORMATION FOR THE
 FOLLOWING:
 H0.03 - DETAIL #26 CONDENSING UNIT MOUNTING DETAIL. THE
 DETAIL DOES NOT PROVIDE SPECIFIC INFORMATION FOR
 ANCHORING, IT ONLY PROVIDES A NOTE THAT THE UNIT LEGS
 ARE TO BE BOLTED TO CONCRETE PAD.PLEASE INDICATE BOLT
 SIZE.
  
 RESPONSE LETTER - COMMENT 6 WITH REGARDS TO THE
 CONDENSING UNITS LOCATED IN THE GARAGE AREA. RESPONSE
 INDICATES A MEMO FROM TRANE STATING THE INSTALLATION OF
 CONDENSING UNITS IN THE GARAGE IS ACCEPTABLE.THIS
 MEMO WAS NOT SUBMITTED TO THE CITY OF WEST PALM BEACH
 IN THE REVISION PACKAGE.
  
 RESPONSE LETTER COMMENT 7 & 8, CO SENSORS HAVE BEEN
 PROVIDED IN STORAGE AREAS THAT ARE TRANSFERING AIR FROM
 THE GARAGE FOR VENTILATION PURPOSES.THE GENERAL
 DRAWING NOTE ON SHEETS H1.02, H1.03, H1.05,IT STATES
 THE SENSORS ARE TO BE INSTALLED PER MANUFACTURER'S
 INSTRUCTION.PLEASE NOTE, CO SENSORS ARE TO BE SET TO
 ACTIVATE VENTILATION SYSTEM AT A MAXIMUM OF 25 PPM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-10-31 Cont ID  
Sent By pkrauss Date 2006-10-31 Time 13:49 Rev Time 0.00
Received By pkrauss Date 2006-10-31 Time 13:48 Sent To  
Notes
2006-10-31 14:00:46PROVISO:
 THE FOLLOWING ITEMS ARE TO BE SUBMITTED AS REVISIONS
  
 RESPONSE TO COMMENT 1:PLAN SHEET H0.03 REVISED DETAIL
 25 FOR THE ACCU 1 & 2.
  
 PLEASE CLARIFYTHE CONCRETE SLABFOR THE CONDENSING
 UNIT ON THE ROOF TOP.PLEASE SPECIFY THE ROOF MATERIAL
 THIS SLAB WILL BE SETTING ON.IT APPEARS THESE UNITS
 ARE ACTUALLY INSTALLED IN THE GARAGE AREAS.
  
  
 RESPONSE TO COMMENT 2:PLANS SHEET H0.03 REVISED
 DETAIL 26.THE RESPONSE INDICATES THE CURB WILL BE 18"
 HIGH.
  
 ACCORDING TO THE DETAIL THE 18" DEMINSION IS THE
 CLEARANCE BETWEEN THE ROOF SURFACE AND THE BOTTOM OF
 THE ACCU.IS THESE CURBS "PATE CURBS"WILL THE
 FLASHING HAVE TO EXTEND UNDERNEATH THE ACCU?PLEASE
 NOTE, THE CLEARANCE BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF ACCU IS DETERMINED BY THE WIDTH OF THE UNIT
 IN ACCORDANCE WITH 2004 FBE 1509.7.
  
  
 RESPONSE TO COMMENT 3:PLAN SHEET H1.01 INDICATES THE
 TERMINATION OF CIF-6 IS 10 FT ABOVE GRADE.
  
 PLEASE NOTE, THE EXHAUST FROM THIS IS FROM THE LOADING
 DOCK FOR THE REMOVAL OF CARBON MONOXIDE.PER 2004 FMC
 401.5.1HAZAROUS OR NOXIOUS CONTAMINANT SHALL BE LOCATED
 A MINIMUM OF 10 FROM OPENINGS.PER 501.2 AIR REMOVED
 BY EVERY MECHANICAL EXHAUST SHALL DISCHARGE OUTDOORS AT
 A POINT WHERE IT WILL NOT CAUSE A NUISANCE.BY
 DEFINITION A NUISANCE IS CONSIDERED THAT WHICH IS
 DETRIMENTAL TO HEALTH, WHICH CARBON MONOXIDE IS.
  
  
 RESPONSE TO COMMENT 4 & 5 WERE ADDRESSED.
  
 COMMENT 6 WAS NOT ADDRESSED:PLAN SHEET H1.02, H1.03,
 & H1.05, PLEASE INDICATE IF THE CONDENSING UNITS ARE
 LOCATED IN SIDE THE GARAGE AREA.PLEASE PROVIDE
 INSTALLATION INSTRUCTIONS INDICATING THIS IS ACCEPTABLE
 TO THE MANUFACTURER.
  
  
 COMMENT 7 & 8 WERE NOT ADDRESSED:VENTILATION FOR THE
 STORAGE AREAS - PER OUR CONVERSATION, CO SENSORS ARE TO
 BE INSTALLED INTO NON-HABITABLE SPACES WHEN THE MAKE-UP
 AIR BEING PROVIDED IS ACHIEVED THROUGH THE GARAGE
 SPACE.
  
 COMMENT 9 THROUGH 14 WERE ADDRESSED.
  
 PLEASE NOTE, ADDITIONAL PERMIT REQUIRED FOR THE FUEL
 TANK, FUEL PIPING AND GENERATOR.PLANS FOR THE FUEL
 TANK NEED APPROVAL FROM DERM.PLANS MAY BE SUBMITTED
 TO:
 THE ATTENTION OF CHIP GREEN
 3323 BELVEDERE RD. BUILDING #502
 WEST PALM BEACH, FL
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-10-26 Cont ID  
Sent By pkrauss Date 2006-10-26 Time 14:52 Rev Time 0.00
Received By pkrauss Date 2006-10-26 Time 14:52 Sent To  
Notes
2006-10-26 15:23:41THANK YOU FOR THE RESPONSE LETTER (SEPT 26,2006)
 ADDRESSING COMMENTS FROM THE MECHANICAL PLAN REVIEW.
 PLEASE NOTE, FURTHER CLARIFICATION IS REQUIRED FOR THE
 FOLLOWING ITMES:
  
 RESPONSE TO COMMENT 1:PLAN SHEET H0.03 REVISED DETAIL
 25 FOR THE ACCU 1 & 2.
  
 PLEASE CLARIFYTHE CONCRETE SLABFOR THE CONDENSING
 UNIT ON THE ROOF TOP.PLEASE SPECIFY THE ROOF MATERIAL
 THIS SLAB WILL BE SETTING ON.IT APPEARS THESE UNITS
 ARE ACTUALLY INSTALLED IN THE GARAGE AREAS.
  
  
 RESPONSE TO COMMENT 2:PLANS SHEET H0.03 REVISED
 DETAIL 26.THE RESPONSE INDICATES THE CURB WILL BE 18"
 HIGH.
  
 ACCORDING TO THE DETAIL THE 18" DEMINSION IS THE
 CLEARANCE BETWEEN THE ROOF SURFACE AND THE BOTTOM OF
 THE ACCU.IS THESE CURBS "PATE CURBS"WILL THE
 FLASHING HAVE TO EXTEND UNDERNEATH THE ACCU?PLEASE
 NOTE, THE CLEARANCE BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF ACCU IS DETERMINED BY THE WIDTH OF THE UNIT
 IN ACCORDANCE WITH 2004 FBE 1509.7.
  
  
 RESPONSE TO COMMENT 3:PLAN SHEET H1.01 INDICATES THE
 TERMINATION OF CIF-6 IS 10 FT ABOVE GRADE.
  
 PLEASE NOTE, THE EXHAUST FROM THIS IS FROM THE LOADING
 DOCK FOR THE REMOVAL OF CARBON MONOXIDE.PER 2004 FMC
 401.5.1HAZAROUS OR NOXIOUS CONTAMINANT SHALL BE LOCATED
 A MINIMUM OF 10 FROM OPENINGS.PER 501.2 AIR REMOVED
 BY EVERY MECHANICAL EXHAUST SHALL DISCHARGE OUTDOORS AT
 A POINT WHERE IT WILL NOT CAUSE A NUISANCE.BY
 DEFINITION A NUISANCE IS CONSIDERED THAT WHICH IS
 DETRIMENTAL TO HEALTH, WHICH CARBON MONOXIDE IS.
  
  
 RESPONSE TO COMMENT 4 & 5 WERE ADDRESSED.
  
 COMMENT 6 WAS NOT ADDRESSED:PLAN SHEET H1.02, H1.03,
 & H1.05, PLEASE INDICATE IF THE CONDENSING UNITS ARE
 LOCATED IN SIDE THE GARAGE AREA.PLEASE PROVIDE
 INSTALLATION INSTRUCTIONS INDICATING THIS IS ACCEPTABLE
 TO THE MANUFACTURER.
  
  
 COMMENT 7 & 8 WERE NOT ADDRESSED:VENTILATION FOR THE
 STORAGE AREAS - PER OUR CONVERSATION, CO SENSORS ARE TO
 BE INSTALLED INTO NON-HABITABLE SPACES WHEN THE MAKE-UP
 AIR BEING PROVIDED IS ACHIEVED THROUGH THE GARAGE
 SPACE.
  
 COMMENT 9 THROUGH 14 WERE ADDRESSED.
  
  
  
 NEW COMMENTS:
 PLEASE NOTE, SMOKE, FIRE AND OR COMBINATION DAMPERS MAY
 BE REQUIRED IN THE FUTURE TENANT BUILDOUT DEPENING ON
 THE OCCUPANCIES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-09-21 Cont ID  
Sent By pkrauss Date 2006-09-21 Time 10:02 Rev Time 0.00
Received By pkrauss Date 2006-09-20 Time 13:39 Sent To  
Notes
2006-09-25 00:00:00***** PLEASE KNOW AS OF 9/25/06
 MECHANICAL REVIEW NOTES NOT COMPLETE,
 PLANS MAY BE PICKED , HOWEVER PLEASE BE
 AWARE NOTES FOR MECHANICAL MAY FOLLOW.
2006-09-21 00:00:00DENIED:
 1.PLAN SHEET H0.03 DETAIL 26 - ROOFTOP
 MOUNTING DETAIL FOR THE CONDENSING UNIT
 DOES NOT COMPLY WITH 2004 FBC 1509.7.
  
 2.PLAN SHEET H0.03 DETAIL 30 - CURB
 DETAIL DOES NOT SPECIFY HEIGHT OF THE
 CURB.PER 2004 FBC 1509.7, RAISED CURBS
 SHALL BE A MINIMUM OF 8" ABOVE THE ROOF
 SURFACE.
  
 3.H1.01 EXHAUST TERMINATION FROM CIF-6
 IS 5' X 3' LOUVER OVER A DOOR.PER 2004
 FMC 401.5.2 EXHAUST AIR SHALL BE LOCATED
 AS NOT TO CREATE A NUISANCE, AIR SHALL
 NOT BE DIRECTED ONTO WALKWAYS.
  
 4.PLAN SHEET H1.02, CO SENSORS ARE
 INDICATED, PLAN DOES NOT SPECIFY AT WHAT
 PARTS PER MILLION (PPM).PER 2004 FMC
 404.1, A MAXIMUM OF 25 PPM IS THE
 REQUIREMENT FOR THE ACTIVATION OF THE
 FANS.
  
 5.PLAN SHEET H1.02 PF-1 & 2 GARAGE
 EXHAUST, PLEASE CLARIFY AIR MAKE-UP FOR
 EACH FLOOR.PLEASE PROVIDE
 CALCULATIONS.CO SENSORS SHALL BE TIED
 TO THE EMERGENCY POWER.
  
 6.PLAN SHEET H1.02 PLEASE INDICATE IF
 THE CONDENSING UNITS ARE LOCATED INSIDE
 OR OUTDOORS.
  
 7.PLAN SHEET H1.03 CIF-3 EXHAUST FAN
 FROM STORAGE ROOM 304 TERMINATES INTO
 THE GARAGE INSTEAD OF THE OUTDOORS AS
 REQUIRED BY 2004 FMC 501.2
  
 8.PLAN SHEET H1.03, H1.05PLEASE
 CLARIFY STORAGE (RMS 302,402,502)
 MAKE-UP AIR FROM THE GARAGE AREA &
 EXHAUST TERMINATES INTO THE GARAGE AREA
 ALSO.
  
 9.PLAN SHEET H1.06 RM 614 INDICATES A
 6"X6" SUPPLY DUCT PENETRATING THE 1 HR
 PARTITION.PLEASE NOTE, DUCT SHALL
 COMPLY WITH THE EXCEPTIONS IN FMC
 607.5.3 OF THE 2004 CODE OR INSTALL A
 FIRE DAMPER.PLEASE CLARIFY.
  
 9.PLAN SHEET H1.17 INDICATES 4 FT
 STEEL DUNNAGE, PLEASE PROVIDE DETAIL OF
 THE SUPPORT ANCHORING TO THE ROOF,
 CLEARANCE BETWEEN THE ROOF SURFACE AND
 SUPORT RAIL, AND THE ACHORING OF SPRING
 ISOLATORS TO THE STEEL.
  
 11. PLAN SHEET H1.18 & DETAIL 26 ON PLAN
 SHEET H0.03.SUPPORTS FOR ACCU1
 & ACCU2 ON SLEEPERS.PER 2004 FBC
 1509.7ROOF MOUNTED EQUIPMENT WHERE
 ROOFING MATERIALS ARE UNDERNEATH THE
 EQUIPMENT A ROOF STAND IS REQUIRED IN
 ACCORDANCE WITH TABLE 1509.PLEASE SHOW
 THE ANCHORING DETAILS.
  
 12. PLEASE PROVIDE SUBMITTALS FOR
 EQUIPMENT.
  
 13. PROVIDE INFORMATION ABOUT THE
 EMERGENCY GENERATOR.PLEASE INDICATE
 FUEL TYPE & STORAGE.PROVIDE
 VENTILATION INFORMATION SHOULD THE
 GENERATOR BE LOCATED INSIDE THE
 BUILDING.
  
 14. PLANS ARE TO BE SIGNED, SEALED, AND
 DATED BY THE ENGINEER IN ACCORDANCE WITH
 FS 471.025 & FAC 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 EMAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-06-15 Cont ID  
Sent By dpalmer Date 2006-06-15 Time 12:03 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2006-06-15 00:00:00******** NOTE **********
  
 AS DIRECTED BY NEIL MELICK BUILDING
 OFFICAL: MS. LYNN HARRIS REPRESENTING
 CITY PLACE OFFICE LLC HAS REQUESTED
 PLANS TO BE REMOVED FROM THEPLAN
 REVIEW PROCESS.
 WHEN PLANS COME BACK IN FOR REVIEW, IT
 WILL BE 1ST RESUB NO FEE. DV PALMER.

Review Stop P PLUMBING
Rev No 28 Status P Date 2008-05-15 Cont ID  
Sent By kstevens Date 2008-05-15 Time 09:15 Rev Time 0.00
Received By kstevens Date 2008-05-15 Time 09:15 Sent To  
Notes
2008-05-15 09:51:58REVISIONS OK--SHTS P0.4A (NEW) - P1.09 - P1.10 -
 P1.11

Review Stop P PLUMBING
Rev No 27 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 26 Status P Date 2008-05-02 Cont ID  
Sent By kstevens Date 2008-05-02 Time 10:40 Rev Time 0.00
Received By kstevens Date 2008-04-30 Time 14:52 Sent To  
Notes
2008-05-02 10:42:13SUBMITTALS OK --THROUGH PENETRATION FIRESTOP SYSTEMS
 C-AJ-1427, C-AJ-2214, W-J-2110 & C-AJ-3164

Review Stop P PLUMBING
Rev No 25 Status P Date 2008-04-23 Cont ID  
Sent By kstevens Date 2008-04-23 Time 13:02 Rev Time 0.00
Received By kstevens Date 2008-04-23 Time 13:02 Sent To  
Notes
2008-04-23 14:03:13REVISIONS APPROVED--SHTS P1.01 & P1.02.--SHT
 P1.02 NOTE FROM MARCH 17, 2008 REVISION AS FOLLOWS(
 REVISIONS REQUIRED FOR ALL CONDENSATE, STORM, SANITARY
 RISERS TO REFLECT THE CHANGES SHOWN ON ALL APPLICABLE
 SHEETS). NOT ADDRESSED.

Review Stop P PLUMBING
Rev No 24 Status F Date 2008-04-23 Cont ID  
Sent By kstevens Date 2008-04-23 Time 12:41 Rev Time 0.00
Received By kstevens Date 2008-04-23 Time 12:41 Sent To  
Notes
2008-04-23 12:44:16REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P0.4A REV. #38 NOT APPROVED AS IT DOES NOT
 REFLECT THE REVISION #38 SUBMITTTED FOR THE FLOOR PLAN
 SHT P1.11.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 23 Status P Date 2008-04-23 Cont ID  
Sent By kstevens Date 2008-04-23 Time 12:40 Rev Time 0.00
Received By kstevens Date 2008-04-23 Time 12:40 Sent To  
Notes
2008-04-23 12:41:21REVISION OK --SHT P1.11

Review Stop P PLUMBING
Rev No 22 Status P Date 2008-04-12 Cont ID  
Sent By kstevens Date 2008-04-12 Time 09:33 Rev Time 0.00
Received By kstevens Date 2008-04-12 Time 09:33 Sent To  
Notes
2008-04-12 09:33:58REVISION OK--SHTS L-4 & L-5 IRRIGATION.

Review Stop P PLUMBING
Rev No 21 Status F Date 2008-03-25 Cont ID  
Sent By kstevens Date 2008-03-25 Time 16:05 Rev Time 0.00
Received By kstevens Date 2008-03-25 Time 16:05 Sent To  
Notes
2008-03-25 16:35:30REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES.
  
 1. IRRIGATION SHEETS SUBMITTED FOR REVISIONS ARE SHTS
 L-4 & L-5. IRRIGATION SHEETS REVIEWED AND ON RECORD ARE
 SHTS L-3 & L-4. PLEASE CLARIFY. SECTION 106.1.2.
  
 2. SHTS L-4 & L-5. THE SIGNATURE OF THE LANDSCAPE
 ARCHITECT DOES NOT REFLECT THE SIGNATURE OF THE THE
 PLANS ON FILE. PLEASE SUBMIT A SIGNED, SEALED NOTORIZED
 LETTER INDICATING THE LEGAL SIGNATURE OF THE DESIGN
 PROFESSIONAL. ONE SET OF IRRIGATION REVISIONS HAS BEEN
 RETAINED BY THIS OFFICE. FAC 61G1-16.003,
 61G1-16.004(6) & FAC 481.306.
  
 3. SHTS L-4 & L-5 THE PREVIOUS REVISIONS INDICATED ON
 THE REVIEWED SET OF PLAN WERE NUMBERS 1, 2 & 4.
 REVISION NUMBERS SUBMITTED THIS REVISION ARE 5, 6, 12,
 22, 33 & 37, NONE OF THE REVISIONS WERE CLOUDED, OR
 NUMBERED FOR REVIEW. PLEASE INDICATE THE LOCATION OF
 EACHREVISION SUBMITTED WITH A CLOUD AND SHOW THE
 REVISION NUMBER FOR EACH REVISION SUBMITTED. SECTION
 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 20 Status F Date 2008-03-18 Cont ID  
Sent By kstevens Date 2008-03-18 Time 08:22 Rev Time 0.00
Received By kstevens Date 2008-03-18 Time 08:22 Sent To  
Notes
2008-03-18 08:23:54DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P1.01 A VENT IS REQUIRED FOR THE FLOOR DRAIN.
 SECTION 901.2.1 & TABLE 906.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 19 Status P Date 2008-03-18 Cont ID  
Sent By kstevens Date 2008-03-18 Time 08:18 Rev Time 0.00
Received By kstevens Date 2008-03-17 Time 15:45 Sent To  
Notes
2008-03-18 08:21:52REVISIONS APPROVED--SHTS PU1.01, P1.02, P1,05,
 P1.06, P1.08, P1.15, P1.16, P1.17.--REVISIONS
 REQUIRED FOR ALL CONDENSATE, STORM, SANITARY RISERS TO
 REFLECT THE CHANGES SHOWN ON ALL APPLICABLE SHEETS.--
 REVISION 32 FOUND ON SHTS P1.08, P1.16 & P1.17 NOT
 FOUND, NOT APPROVED.

Review Stop P PLUMBING
Rev No 18 Status F Date 2008-02-12 Cont ID  
Sent By kstevens Date 2008-02-12 Time 10:24 Rev Time 0.00
Received By kstevens Date 2008-02-12 Time 10:24 Sent To  
Notes
2008-02-12 10:30:52REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. NEW SHT P0.4A RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. RISER 3" DN AT COLUMN LINE K-3 NOT SHOWN,
 RISER 3" DN NEAR COLUMN LINE K1-L/2-3 NOT SHOWN, RISER
 3" DN AT COLUMN LINE L-8 NOT SHOWN & 4" DN NEAR COLUMN
 LINE K1-4/7-8 NOT SHOWN. ISOMETRIC FOR THE 12TH FLOOR
 ALSO SHOWS THE 14TH FLOOR. PLEASE CLARIFY. SEE COMMENT
 NUMBER 3 FROM PREVIOUS REVISION REVIEW DATED 12/17/07.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 17 Status P Date 2008-02-12 Cont ID  
Sent By kstevens Date 2008-02-12 Time 10:23 Rev Time 0.00
Received By kstevens Date 2008-02-12 Time 10:23 Sent To  
Notes
2008-02-12 10:24:41REVISION OK--NEW SHEET P1.11

Review Stop P PLUMBING
Rev No 16 Status N Date 2007-12-17 Cont ID  
Sent By dpalmer Date 2008-01-03 Time 10:14 Rev Time 0.00
Received By kstevens Date 2007-12-17 Time 17:29 Sent To B1
Notes
2007-12-17 17:29:56SUBMITTAL FOR WATER WALL OK

Review Stop P PLUMBING
Rev No 15 Status F Date 2007-12-17 Cont ID  
Sent By kstevens Date 2007-12-17 Time 14:44 Rev Time 0.00
Received By kstevens Date 2007-12-17 Time 14:44 Sent To  
Notes
2007-12-17 17:18:30DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1.08 SANITARY PIPING ON THE REVISION IS UNCLEAR
 AS TO ITS INTENT. SOME AREAS STATE "EXISTING PHASE 1 4"
 SANITARY THAT IS NOT SHOWN ON PREVIOUS SHEETS. THERE IS
 PIPING THAT IS INDICATED AS RUNNING IN THE 11TH FLOOR
 CEILING BUT IS INDICATED AS "3IN WASTE DN (FD)AT
 TENANT'S 12 FLOOR. IF PIPING IS IN THE 11TH FLOOR,
 WOULDNT IT BE UP TO THE 12TH FLOOR? SOME RISERS NOT
 IDENTIFIED OR PIPE SIZES NOT SHOWN. NOTES INDICATE 4"
 DOWN TO TENANT'S 10TH FLOOR CEILINGAND PLUG FOR
 FUTURE EXTENTION. THESE LINES SHALL CONNECT TO THE
 SANITARY RISER AT THE TIME OF PIPE INSTALLATION.AREA
 AT JUNCTION OF COL K/4 SHOWS A THREE INCH LINE THAT IS
 INDICATED AS 3" W CAPPED FOR FUTURE,SHOWS A CAP THEN
 EXTENDS ON 1-1/2" STRAIGHT AND 3" OFF TO THE LEFT. ONE
 LINE SHOWS A NOTE 4"S DOWN, PLUG 6" ABOVE TENANT'S 12TH
 FLOOR. IF PIPING IS ON THE 11TH FLOOR THAN IT SHOULD BE
 SHOWN AS 4"S "UP" NOT DOWN. PLEASE CLARIFY.SECTION
 106.1.1.
  
 2.THIS REVISION IS ONLY SHOWN ON THE 11TH FLOOR, AND
 AS SUCH ONLY THE 11TH FLOOR SHALL BE REVISIED. PLEASE
 SUBMIT A REVISION FOR THE 11TH FLOOR ONLY ON A NEW
 SHEET, (MAYBE P1.08B). THAT WILL CLEAR UP ALL CONFUSION
 THAT HAVING INFORMATION FOR FOUR OTHER FLOORS THAT IS
 SHOWN ON SHT P1.08. SECTION 106.1.1.
  
 3. SUBMIT A SANITARY RISER DIAGRAM THAT REFLECT THE
 CHANGES ON THE 11TH FLOOR. THIS SHALL SHOW THE
 CONNECTION ON THE 10TH FLOOR AND THE FUTURE PIPING UP
 THRU THE 12TH FLOOR AS WELL. SECTION 106.3.5.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 14 Status P Date 2007-12-06 Cont ID  
Sent By kstevens Date 2007-12-06 Time 18:48 Rev Time 0.00
Received By kstevens Date 2007-12-06 Time 18:48 Sent To  
Notes
2007-12-06 18:49:12REVISIONS OK - SHTS P0.2, P1.01 & P1.17

Review Stop P PLUMBING
Rev No 13 Status P Date 2007-12-06 Cont ID  
Sent By kstevens Date 2007-12-06 Time 18:48 Rev Time 0.00
Received By kstevens Date 2007-12-06 Time 18:47 Sent To  
Notes
2007-12-06 18:50:14REVISIONS OK - SHTS P1.06, P1.07, P1.08 & P1.09

Review Stop P PLUMBING
Rev No 12 Status P Date 2007-09-10 Cont ID  
Sent By kstevens Date 2007-09-10 Time 10:22 Rev Time 0.00
Received By kstevens Date 2007-09-10 Time 10:22 Sent To  
Notes
2007-09-10 10:24:37REVISIONS OK - SHTS P0.4, P1.01, P1.02, P1.03, P1.04,
 P1.05, P1.06, P1.15, P1.16. REVISION #16

Review Stop P PLUMBING
Rev No 11 Status F Date 2007-09-10 Cont ID  
Sent By kstevens Date 2007-09-10 Time 10:13 Rev Time 0.00
Received By kstevens Date 2007-09-10 Time 10:13 Sent To  
Notes
2007-09-10 10:21:25REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1.01 RWL NOTE BY COL. LINE 1/F.9 INDICATES 3"
 RWL UP TO CANOPY DRAIN & 3" COND. DOWN. PLEASE CLARIFY
 AS CONDENSATE SHALL DRAIN OUT OF THE BUILDING
 SEPARATELY FROM THE STORM WATER. SECTION 106.1.1.
  
 2. SHT P1.01 4" DRAIN NEAR COL. LINE 5/H IS NOT
 INDICATED WITH A CLOUD, NOR DOES IT HAVE A REVISION
 NUMBER. ALSO THIS DRAIN LINE IS NOT INDICATED ON THE
 UNDERGROUND PIPING. PLEASE INDICATE WHERE THIS NEW
 DRAIN LINE CONNECTS TO THE UNDERGROUND BUILDING DRAIN
 LINE. SECTION 106.1.2. PLEASE CLOUD AND NUMBER ALL
 REVISIONS.
  
 3. SHT P1.17 NOTE INDICATES A FLOOR DRAIN FOR INDIRECT
 WASTE. FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE
 RECEPTORS. A FLOOR SINK WILL BE REQUIRED PER SECTION
 802.3. PLEASE CHANGE NOTE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 10 Status P Date 2007-08-23 Cont ID  
Sent By kstevens Date 2007-08-23 Time 18:15 Rev Time 0.00
Received By kstevens Date 2007-08-23 Time 18:15 Sent To  
Notes
2007-08-23 18:16:00 
  
 REVISION OK - IRRIGATION SHEETS L-4 & L-5
  
 P E R M I TR E Q U I R E D

Review Stop P PLUMBING
Rev No 9 Status P Date 2007-06-08 Cont ID  
Sent By pschmitz Date 2007-06-08 Time 11:45 Rev Time 0.00
Received By pschmitz Date 2007-06-08 Time 11:41 Sent To  
Notes
2007-06-08 11:43:42PROVISO
 CONTACTED MR DAVID ALLEN
 DELETED REFERENCE TO SCREEN AND CLAMP ON RELIEF VENT
 TYPICAL.

Review Stop P PLUMBING
Rev No 8 Status F Date 2007-05-07 Cont ID  
Sent By pschmitz Date 2007-05-07 Time 15:32 Rev Time 0.00
Received By pschmitz Date 2007-05-07 Time 15:32 Sent To  
Notes
2007-05-07 15:33:275-7-07PES REVISIONS REVIEWIN PROGRESS.
  
 PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
  
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
  
 REVISION DATED 5-2-07 DENIED
  
 1)ALL PLUMBING COMMENTS DENIED, EXCEPT REFERENCE TO
 DOMESTIC WATER RISER, HYDRA-RESTER ( SHOCK ABSORBER)
 SHT PO.3
  
 2) MEET WITH MR DAVID ALLEN, PE.
 PLANS TO REFELECT A SEPERATE CONDENSATE DRAINAGE
 SYSTEM.
 TERMINATING OUT SIDE THE BUILDING, CONNECTINGTO THE
 STORM WATER DRAIN, WITH A RELIEF 6" ABOVE GRADE.
  
 END OF COMMENTS, QUESTIOINS 561-805-6692

Review Stop P PLUMBING
Rev No 7 Status F Date 2007-03-24 Cont ID  
Sent By pschmitz Date 2007-03-24 Time 14:12 Rev Time 0.00
Received By pschmitz Date 2007-03-24 Time 06:38 Sent To  
Notes
2007-03-24 14:11:42PAUL SCHMITZ
 [email protected] FBC 2004 PLUMBING
 CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 REVISION DENIED
  
 1) SHTS L-3, L-4IRRIGATION: NOT INCLUDED WITH THIS
 SET OF PLANS.
  
 2) CIVIL PLANS, SHTS I, THROUGH 14 SHOW LOCATION OF
 STORM DRAIN TIE IN.
  
 CONTINUE NOTES 3-26-07.DECIDED TO COME IN 3-25-07 TO
 COMPLETE REVIEW NOTES.
  
 3) SHT H2.01 FLOW DIAGRAM, REFERENCE TO COLD WATER FILL
 NO BACK FLOW PREVENTER.
  
 4) SHT P0.1, DETAIL EWH-1,2 EXPANSION TANK ON COLD
 WATER, "QUESTION IF THIS SHOULD BE ON THE HOT WATER
 LINE"
  
 5) SHT P0.3(1) WATER RISER : HYDRA-RESTER, SIOUX
 CHIEF, PROVIDE MFG TABLE FOR SIZE AND LOCATION AND WERE
 REQUIRED.
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 6 A)SHT P0.1 AND PUI.01 PROVIDE CALCULATIONS FOR THE
 SIZE OFOIL,SAND INTERCEPTOR.
 B)PROVIDE CALCULATIONS FOR THE SIZING OF THE GW
 SYSTEM,
 C) LOCATIION OF TD'C AND TD'B
  
 7) SHT P0.02 CAR WASH: SHOW LOCATION OF THE DRAIN AND
 CONNECTION TO OIL SEPERATOR.
 1003.4 OIL SEPARATORS REQUIRED.
 AT REPAIR GARAGES, CARWASHING FACILITIES WITH ENGINE OR
 UNDERCARRIAGE CLEANING CAPABILITY AND AT FACTORIES
 WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED,
 SEPARATORS SHALL BE INSTALLED INTO WHICH ALL
 OIL-BEARING, GREASE-BEARING OR FLAMMABLE WASTES SHALL
 BE DISCHARGED BEFORE EMPTYING IN THE BUILDING DRAINAGE
 SYSTEM OR OTHER POINT OF DISPOSAL.
 1003.4.1 SEPARATION OF LIQUIDS.
 A MIXTURE OF TREATED OR UNTREATED LIGHT AND HEAVY
 LIQUIDS WITH VARIOUS SPECIFIC GRAVITIES SHALL BE
 SEPARATED IN AN APPROVED RECEPTACLE.
 1003.4.2 OIL SEPARATOR DESIGN.
 OIL SEPARATORS SHALL BE DESIGNED IN ACCORDANCE WITH
 SECTIONS 1003.4.2.1 AND 1003.4.2.2.
 1003.4.2.1 GENERAL DESIGN REQUIREMENTS.
 OIL SEPARATORS SHALL HAVE A DEPTH OF NOT LESS THAN 2
 FEET (610 MM) BELOW THE INVERT OF THE DISCHARGE DRAIN.
 THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE NOT LESS
 THAN AN 18-INCH (457 MM) WATER SEAL.
  
 8) SHT P0.3 DRAIN WASTE & VENT ISOMETRIC, DOES NOT SHOW
 THE TIE IN OF THE UGW SYSTEM,TO SANITARY SYSTEM.
  
 9) SHT P0.4 LOWER SANITARY WASTE & VENT RISER DIAGRAM:
 INDIRECT WASTE CONNECTION FROM AHU, SEE SHT H0.03
 DETAIL (24)
 NOT APPROVED TO SANITARY SYSTEM, SEPERATE SYSTEM
 REQUIRED.TERMINATE TO STORM, OUT SIDE OF THE
 BUILDING. DRY WELL OR PLANTER.
  
 10) SHTS P1.05, P1.15, P1.16, P1.17PRIMARY ROOF
 DRAINS: PROVIDE THE CALCIULATIONS FOR THS SIZING OF THE
 ROOF DRAINAGE SYSTEM, BASED ON THE FOLLOWING CODE
 SECTIONS
 1101.7 ROOF DESIGN.
 ROOFS SHALL BE DESIGNED FOR THE MAXIMUM POSSIBLE DEPTH
 OF WATER THAT WILL POND THEREON AS DETERMINED BY THE
 RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS,
 SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION
 WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING
 THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF
 DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED.
 SEE TA\BLES 1106.2 AND 1106.3
 1106.4 VERTICAL WALLS.
 IN SIZING ROOF DRAINS AND STORM DRAINAGE PIPING,
 ONE-HALF OF THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF SHALL BE ADDED TO THE PROJECTED
 ROOF AREA FOR INCLUSION IN CALCULATING THE REQUIRED
 SIZE OF VERTICAL CONDUCTORS, LEADERS AND HORIZONTAL
 STORM DRAINAGE PIPING.
 1106.5 PARAPET WALL SCUPPER LOCATION.
  
 11) SHTS P1.05, P1.15, P1.16, P1.17 SECONDARY DRAINS:
 PROVIDE THE CALCIULATIONS FOR THS SIZING OF THE
 SECONDARY ROOF DRAINAGE SYSTEM, BASED ON THE FOLLOWING
 CODE SECTIONS.
 1106.4 VERTICAL WALLS.
 IN SIZING ROOF DRAINS AND STORM DRAINAGE PIPING,
 ONE-HALF OF THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF SHALL BE ADDED TO THE PROJECTED
 ROOF AREA FOR INCLUSION IN CALCULATING THE REQUIRED
 SIZE OF VERTICAL CONDUCTORS, LEADERS AND HORIZONTAL
 STORM DRAINAGE PIPING.
 1106.5 PARAPET WALL SCUPPER LOCATION.
 SECTION 1107
 SECONDARY (EMERGENCY) ROOF DRAINS
 1107.1 SECONDARY DRAINAGE REQUIRED.
 SECONDARY (EMERGENCY) ROOF DRAINS OR SCUPPERS SHALL BE
 PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS
 ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE
 ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY
 REASON.
 1107.2 SEPARATE SYSTEMS REQUIRED.
 SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE END POINT
 OF DISCHARGE SEPARATE FROM THE PRIMARY SYSTEM.
 DISCHARGE SHALL BE ABOVE GRADE, IN A LOCATION WHICH
 WOULD NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR
 MAINTENANCE PERSONNEL.
 1107.3 SIZING OF SECONDARY DRAINS.
 SECONDARY (EMERGENCY) ROOF DRAIN SYSTEMS SHALL BE SIZED
 IN ACCORDANCE WITH SECTION 1106 BASED ON THE RAINFALL
 RATE FOR WHICH THE PRIMARY SYSTEM IS SIZED IN TABLES
 1106.2, 1106.3 AND 1106.6. SCUPPERS SHALL BE SIZED TO
 PREVENT THE DEPTH OF PONDING WATER FROM EXCEEDING THAT
 FOR WHICH THE ROOF WAS DESIGNED AS DETERMINED BY
 SECTION 1101.7. SCUPPERS SHALL NOT HAVE AN OPENING
 DIMENSION OF LESS THAN 4 INCHES (102 MM). THE FLOW
 THROUGH THE PRIMARY SYSTEM SHALL NOT BE CONSIDERED WHEN
 SIZING THE SECONDARY ROOF DRAIN SYSTEM.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 6 Status N Date 2007-03-17 Cont ID  
Sent By pschmitz Date 2007-03-17 Time 10:40 Rev Time 0.00
Received By pschmitz Date 2007-03-17 Time 09:33 Sent To  
Notes
2007-03-17 10:46:58E- MAILED R BROWN AS TO WHY THERE IS A HOLD.

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-03-17 Cont ID  
Sent By pschmitz Date 2007-02-24 Time 09:32 Rev Time 0.00
Received By pschmitz Date 2007-02-24 Time 11:07 Sent To  
Notes
2007-02-24 11:09:12SHT. PU1.01 FILED WITH OFFICE COPY

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-12-09 Cont ID  
Sent By pschmitz Date 2006-12-09 Time 13:59 Rev Time 0.00
Received By pschmitz Date 2006-12-09 Time 13:46 Sent To  
Notes
2006-12-09 13:53:52 
 PAUL SCHMITZ [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 (1)REVISION SHT PO.2APPROVED
  
 (2) REVISIONSHT PU1.01 DENIED
 SHT PU1.01NUMBE THEDART, CLOUD REVISION.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-10-21 Cont ID  
Sent By pschmitz Date 2006-10-21 Time 09:41 Rev Time 0.00
Received By pschmitz Date 2006-10-21 Time 09:41 Sent To  
Notes
2006-10-21 11:43:43RE-SUB

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-07-30 Cont ID  
Sent By pschmitz Date 2006-07-30 Time 15:19 Rev Time 0.00
Received By pschmitz Date 2006-07-30 Time 15:19 Sent To  
Notes
2006-07-30 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1)PLEASE SEE ELECTRICAL PLAN REVIEW
 COMMENTS, WITH RESPECT TO DESIGN
 PROFESSIONAL, SIGNED AND SEALED PLANS
 AND MISSING LICENSE INFORMATION.
 2) PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT PLUMBING
 PLANS.
  
 3) SHT L-5 IRRIGATION NOTES REFERENCE TO
 PVB. SEC. 608 PROTECTION OF WATER SUPPLY
 AND TABLE 608.1 RPBFP IS REQUIRED FOR
 THIS DEGREE OF HAZARD WITH BACK PSI.
  
 4)SHT A1.06 SECTION 403
 MINIMUM PLUMBING FACILITIES
 403.1 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED FOR
 THE TYPE OF OCCUPANCY AND IN THE MINIMUM
 NUMBER SHOWN IN TABLE 403.1. TYPES OF
 OCCUPANCIES NOT SHOWN IN TABLE 403.1
 SHALL BE CONSIDERED INDIVIDUALLY BY THE
 CODE OFFICIAL. THE NUMBER OF OCCUPANTS
 SHALL BE DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING. OCCUPANCY
 CLASSIFICATION SHALL BE DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 5) SHT.A8.71DETAIL 8 TOILET RM ELV.
 SHOW MOUNTING HEIGTHFOR LAV'S FROM FF
  
 6)SHT P0.1OIL TRAP DIAGRAM:
 CONTACT W P BEACHWATERPLANT LAB
 SUPERVISOR,INDUSTRIAL COORDINATOR.
 LYNN MASSON
 OFFICE 561-822-2271
 E-MAIL [email protected]
  
 7)SHT P0.3, P0.4 SANITARY WASTE, VENT
 STACKS.SECTION 914
 RELIEF VENTS?STACKS OF MORE THAN
 10 BRANCH INTERVALS
 914.1 WHERE REQUIRED.
 SOIL AND WASTE STACKS IN BUILDINGS
 HAVING MORE THAN 10 BRANCH INTERVALS
 SHALL BE PROVIDED WITH A RELIEF VENT AT
 EACH TENTH INTERVAL INSTALLED, BEGINNING
 WITH THE TOP FLOOR.
 914.2 SIZE AND CONNECTION.
 THE SIZE OF THE RELIEF VENT SHALL BE
 EQUAL TO THE SIZE OF THE VENT STACK TO
 WHICH IT CONNECTS. THE LOWER END OF EACH
 RELIEF VENT SHALL CONNECT TO THE SOIL OR
 WASTE STACK THROUGH A WYE BELOW THE
 HORIZONTAL BRANCH SERVING THE FLOOR, AND
 THE UPPER END SHALL CONNECT TO THE VENT
 STACK THROUGH A WYE NOT LESS THAN 3 FEET
 (914 MM) ABOVE THE FLOOR.
  
 8) SHT P0.4STACK "G", "H"
 SECTION 903.3 VENT TERMINATION.
 EVERY VENT STACK OR STACK VENT SHALL
 EXTEND OUTDOORS AND TERMINATE TO THE
 OPEN AIR.
  
 9) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT.
  
 10)PLEASE COMPLETELY REMOVE ANY
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 END OF COMMENTS, QUESTIIONS 561-805-6692
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-15 Cont ID  
Sent By dpalmer Date 2006-06-15 Time 12:04 Rev Time 0.00
Received By pschmitz Date 2006-07-15 Time 15:19 Sent To  
Notes
2006-06-15 00:00:00******** NOTE **********
  
 AS DIRECTED BY NEIL MELICK BUILDING
 OFFICAL: MS. LYNN HARRIS REPRESENTING
 CITY PLACE OFFICE LLC HAS REQUESTED
 PLANS TO BE REMOVED FROM THEPLAN
 REVIEW PROCESS.
 WHEN PLANS COME BACK IN FOR REVIEW, IT
 WILL BE 1ST RESUB NO FEE. DV PALMER.

Review Stop Z ZONING
Rev No 15 Status F Date 2008-05-08 Cont ID  
Sent By choops Date 2008-05-08 Time 14:51 Rev Time 0.00
Received By choops Date 2008-05-08 Time 14:51 Sent To  
Notes
2008-05-08 14:54:14***FAILED - SUBMITTAL #03450-020 - SIGN CONNECTION
 DETAILS***
  
  
 1)AS SIGNAGE IS NOT INCLUDED UNDER THE SCOPE OF WORK
 FOR THIS PERMIT, A SEPARATE PERMIT SHALL BE APPLIED FOR
 REGARDING ALL SIGNAGE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 14 Status P Date 2008-05-05 Cont ID  
Sent By eschneid Date 2008-05-05 Time 17:34 Rev Time 0.00
Received By eschneid Date 2008-05-05 Time 17:34 Sent To  
Notes
2008-05-05 17:35:22REVISION #43
  
 PASSED
  
 PLEASE PROVIDE THE PLANNING AND ZONING DEPARTMENT WITH
 4 COPIES OF THIS APPROVED REVISION (MAY BE PHOTO
 COPIES) FOR OUR FILE.

Review Stop Z ZONING
Rev No 13 Status P Date 2008-03-26 Cont ID  
Sent By eschneid Date 2008-03-26 Time 14:09 Rev Time 0.00
Received By eschneid Date 2008-03-26 Time 14:09 Sent To  
Notes
2008-03-26 14:10:53PASSED REVISED SHEETS A1.02, A1.03, A1.04 AND A1.05 TO
 REFLECT SMALL PARKING SPACES RELOCATED TO THE WEST END
 OF THE MIDDLE PARKING ROW TO REPLACE THOSE LOST TO THE
 REDESIGNED EXHAUST VENTS.

Review Stop Z ZONING
Rev No 12 Status P Date 2008-03-20 Cont ID  
Sent By eschneid Date 2008-03-20 Time 17:52 Rev Time 0.00
Received By eschneid Date 2008-03-20 Time 17:52 Sent To  
Notes
2008-03-20 18:00:30PASSED W/PROVISOREVISION NO. 37
  
 1) PROVISO - NEW ROYAL PALMS SHALL MATCH THE HEIGHT OF
 THE ADJACENT ROYAL PALMS ALONG OKEECHOBEE BLVD.THE
 PLANT LIST HAS BEEN REDLINED TO STATE THIS.
  
 2) NOTE - THE VINE WIRE TRELLIS IS ON THE B-BLOCK
 PARCEL, SO IT SHALL BE APPROVED UNDER A SEPARATE
 PERMIT.
  
 3) NOTE - ALL SIGNS SHALL BE APPROVED UNDER A SEPARATE
 PERMIT.
  
 CONTACT ERIC SCHNEIDER @ 822-1435.

Review Stop Z ZONING
Rev No 11 Status F Date 2008-03-20 Cont ID  
Sent By eschneid Date 2008-03-20 Time 18:02 Rev Time 0.00
Received By eschneid Date 2008-03-19 Time 12:31 Sent To  
Notes
2008-03-20 18:03:36REVISION #37 - SEE NEXT REVIEW STOP.

Review Stop Z ZONING
Rev No 10 Status F Date 2008-01-22 Cont ID  
Sent By eschneid Date 2008-01-22 Time 11:58 Rev Time 0.00
Received By eschneid Date 2008-01-22 Time 11:58 Sent To  
Notes
2008-01-22 12:20:02FAILED
  
 1) SHEET A0.21 DOES NOT MATCH THE CURRENT CONDITIONS -
 BUILDING (CLEAVLAND CLINIC REVISIONS), THE LOCATION OF
 THE WATERMAIN, AND THE ADJACENT B-DECK GARAGE CHANGES.
  
 2) CIVIL PLANS DO NOT AGREE WITH THE LANDSCAPE PLANS -
 THE RELOCATED ROYAL PALM, INC. HARDSCAPE CHANGES AND
 THE SITE PLAN - THE LOCATION OF THE NEW SIGN.
  
 3) THE LANDSCAPE PLAN DOES NOT MATCH THE JUNE 27, 2007
 VERSION, APPROVED AS PART OF A MINOR AMENDMENT.ROYAL
 PALM HAS BEEN RELOCATED.
  
 4) THE IRRIGATION PLAN HAS NOT BEEN UPDATED TO REFLECT
 THE MOVED ROYAL PALM OR THE NEW SIGN LOCATION.
  
 5) THE FREE STANDING SIGN (HEIGHT AND LOCATION) HAVE
 NOT YET BEEN APPROVED BY THE CITY COMMISSION.NOTES
 SHALL BE ADDED THAT THE SIGNS ARE TO BE APPROVED UNDER
 SEPARATE PERMIT.
  
 6) SHEETS A1.02, A1.03, A1.04 AND A1.05 SHOW CHANGES TO
 THE SMALL SPACES IN THE SOUTHWEST CORNER OF THE PARKING
 GARAGE (SPACES NOW 8 FEET WIDE).PROVIDE 4 COPIES OF
 THIS PLAN TO THE PLANNING AND ZONING DEPARTMENT SO THAT
 THE DEPARTMENT'S RECORDS MAY BE UPDATED ACCORDINGLY.
  
 7) SHEET C-12 SHALL CORRECTLY SHOW THE BUILDING
 FOOTPRINT ALONG OKEECHOBEE.THERE IS A PORTION SHOW IN
 THE EASEMENT AND ACROSS THE PROPERTY LINE.THE
 EASEMENT INFORMATION SHALL BE COMBINED WITH THE NEW
 LANDSCAPE LAYOUT AND SIGNAGE LOCATIONS TO VERIFY THAT
 THERE ARE NOT CONFLICTS.
  
 8) THE LANDSCAPE PLAN SHOWS THE SIDEWALK ARCING AROUND
 SOME EXISTING LIGHT POLES ON THE EAST SIDE OF THE
 DRIVEWAY, BUT THIS IS NOT SHOWN ON THE CIVIL OR SITE
 PLANS.ALL PLANS NEED TO SHOW THE SAME CONDITIONS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 9 Status F Date 2007-10-12 Cont ID  
Sent By eschneid Date 2007-10-12 Time 15:36 Rev Time 0.00
Received By eschneid Date 2007-10-12 Time 15:36 Sent To I
Notes
2007-10-12 15:38:06FAILED
  
 1) FREE STANDING SIGNAGE REQUIRES APPROVAL OF A MAJOR
 PLANNED DEVELOPMENT AMENDMENT.
  
 2) SIGN PACKAGE AMENDMENT HAS BEEN DISCUSSED WITH LYNDA
 HARRIS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 8 Status P Date 2007-07-16 Cont ID  
Sent By eschneid Date 2007-07-16 Time 16:33 Rev Time 0.00
Received By eschneid Date 2007-07-16 Time 16:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 7 Status F Date 2007-03-28 Cont ID  
Sent By eschneid Date 2007-03-28 Time 17:50 Rev Time 0.00
Received By eschneid Date 2007-03-28 Time 17:50 Sent To  
Notes
2007-03-28 17:52:39FAILED
  
 1) THE CORNICE LINE HAS CHANGED FROM THE APPROVED PLANS
 ALONG THE TOP OF THE 5TH LEVEL.PLANNING STAFF WILL
 NOT SUPPORT A CHANGE TO THE APPROVED CORNICE LINE.
  
 2) THE LANDSCAPE AND FRONT PLAZA AREA HAS CHANGED FROM
 THE APPROVED PLANS (MINOR AMENDMENT ON MARCH 8, 2007).
 PLANNING STAFF WILL NOT SUPPORT THE CHANGE AS
 PRESENTED.
 A. THE PLANTER BOX MAY NOT ENCROACH PAST THE PROPERTY
 LINE.
 B. THE LOCATION OF THE ROYAL PALMS, INCLUDING THE
 REMOVAL FROM ONE IN FRONT OF THE BUILDING, IS NOT
 SUPPORTED.RECOMMEND MEETING WITH THE LANDSCAPE
 ARCHITECT TO DISCUSS OPTIONS.
 C. THE FINAL LAYOUT WILL NEED TO BE APPROVED THROUGH A
 MINOR AMENDMENT.
 D. 30 FOOT OF GREYWOOD (NOT 20 FEET) WAS APPROVED FOR
 THE ROYAL PALMS SO AS TO MATCH EXISTING ALONG
 OKEECHOBEE BOULEVARD.
 E. THE GAS LINE RUNNING PARALLEL TO OKEECHOBEE
 BOULEVARD SHALL BE SHOWN ON THE LANDSCAPE PLANS.
 F. PROVIDE INFORMATION TO VERIFY THE DISTANCE THE ROOTS
 ARE REQUIRED TO BE FROM THE GAS LINE.
 G. TREES SHALL BE PLANTED IN STRUCTURAL SOIL.
  
 3) CIVIL PLANS DO NOT MATCH THE REVISIONS ON THE SITE
 AND LANDSCAPE PLANS.CIVIL PLANS DO MATCH LATEST
 ZONING APPROVED PLANS.
  
 4) PARKING LEVELS DO NOT MEET THE PLANS APPROVED BY THE
 MINOR AMENDMENT ON MARCH 8, 2007.THESE PLANS WERE
 SIGNED AND SEALED BY PAUL TWITTY ON FEBRUARY 19, 2007,
 AND REFERRED TO AS REVISION 7 - SHEETS A1.02, A1.03 AND
 A1.04 AND REVISION 11 - SHEETS A0.20 AND A1.05.
  
 5) SITE PLAN DOES NOT MATCH LATEST ZONING APPROVAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 6 Status F Date 2007-02-13 Cont ID  
Sent By eschneid Date 2007-02-13 Time 15:45 Rev Time 0.00
Received By eschneid Date 2007-02-13 Time 15:45 Sent To  
Notes
2007-02-13 16:55:12FAILED
  
 1) PARKING SPACE NUMBERS SHALL BE CORRECTLY LABELED ON
 SHEET A1.05.
  
 A. REGULAR PARKING SPACE COUNT NUMBERS JUMP FROM 127 TO
 130 (MISSING NUMBER 128 & 129) AT THE NORTHEAST CORNER
 OF THE GARAGE.
  
 B. REGULAR PARKING SPACE NUMBERS 89, 90, 91, 92 AND 93
 ARE NOT SHOWN.STAFF ASSUMES THEY ARE ON THE RAMP
 UNDER SPACES 132 TO 135.PLEASE PROVIDE A SHEET
 SHOWING THESE SPACES.
  
 C. THE SMALL PARKING SPACES ON THE RAMP UP FROM LEVEL 4
 TO 5 ARE NOT LABELED AND COUNTED (STAFF ASSUMES THESE
 ARE IN FRONT OF THE SUPPORT BEAMS AT "L' AND "K").
 PLEASE PROVIDE A SHEET SHOWING THESE SPACES.
  
 2) THE REVISED PARKING COUNT WILL AFFECT THE REQUIRED
 SMALL SPACE WAIVER THAT IS PART OF THE MINOR AMENDMENT
 THAT HAS BEEN SUBMITTED BUT NOT YET APPROVED.
  
 3) THE UPDATED SHEETS (REVISED TO REFLECT THE COMMENTS
 ABOVE) HAVE NOT BEEN SUBMITTED TO THE PLANNING AND
 ZONING DEPARTMENT FOR INCLUSION IN THE PENDING MINOR
 AMENDMENT.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 5 Status F Date 2006-12-08 Cont ID  
Sent By eschneid Date 2006-12-07 Time 17:38 Rev Time 0.00
Received By eschneid Date 2006-12-07 Time 17:37 Sent To  
Notes
2006-12-07 17:45:23FAILED
  
 1) THE PARKING TABLE ON SHEET A0.20 DOES NOT ACURATELY
 STATE THE NUMBER OF COMPACT AND REGULAR SPACES WITHIN
 THE BUILDING.I COUNT 118 COMPACT SPACES AND 136
 REGULAR SPACES.RECOMMENDED THAT THE PARKING SPACES BE
 MARKED WITH A NUMBER.
  
 2) THE REVISED PARKING COUNT WILL AFFECT THE REQUIRED
 SMALL SPACE WAIVER THAT IS PART OF THE MINOR AMENDMENT
 APPROVAL.
  
 3) THE UPDATED SHEETS WERE NEVER SUBMITTED TO THE
 PLANNING AND ZONING DEPARTMENT FOR INCLUSION IN THE
 PENDING MINOR AMENDMENT.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status P Date 2006-10-31 Cont ID  
Sent By eschneid Date 2006-10-31 Time 12:18 Rev Time 0.00
Received By eschneid Date 2006-10-31 Time 12:17 Sent To  
Notes
2006-10-31 12:21:57PASSED WITH PROVISO
  
 1) SHEETS A1.02 THROUGH A1.05 SHALL BE REVISED AS BELOW
 AND THE REVISED SHEETS SHALL BE SUBMITTED TO THE
 CONSTRUCTION SERVICES DEPARTMENT NO LATER THAN NOVEMBER
 30, 2006.
  
 A) PARKING SPACESSHALL BE SHOWN AS DOUBLE STRIPED OR
 A NOTE SHALL BE ADDED ON EACH SHEET THAT THE SPACES
 WILL BE STRIPED IN ACCORDANCE WITH THE DETAILS ON SHEET
 A5.62.
  
 B) SHOW 24 FOOT WIDE DRIVE AISLES AND THE ADJACENT
 PARKING SHALL BE ADJUSTED ACCORDINGLY AND LABLED AS
 SMALL SPACES.
  
 C) THE PARKING TABLE ON SHEET A0.20 SHALL BE REVISED TO
 REFLECT THE NEW SMALL SPACE COUNT.
  
 2) THE SHEETS REFERENCED ABOVE SHALL BE SUBMITTED TO
 THE PLANNING DEPARTMENT FOR INCLUSION IN THE PENDING
 MINOR AMENDMENT.
  
 ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2006-10-30 Cont ID  
Sent By eschneid Date 2006-10-30 Time 10:22 Rev Time 0.00
Received By eschneid Date 2006-10-27 Time 16:28 Sent To  
Notes
2006-10-30 10:32:41FAILED
  
 1) SHEET A0.21 "CODE COMPLIANCE SITE PLAN" DOES NOT
 MATCH THE BUILDING FOOTPRINT ON THE CIVIL, SITE AND
 LANDSCAPE PLANS.
  
 2) PARKING SPACES ON SHEETS A1.02 THOUGH A1.05 SHALL BE
 SHOWN AS DOUBLE STRIPED OR A NOTE SHALL BE ADDED ON
 EACH SHEET THAT THE SPACES WILL BE STRIPED IN
 ACCORDANCE WITH THE DETAILS ON SHEET A5.62.
  
 3) SHEETS A1.02 THROUGH A1.05 SHALL BE REVISED TO SHOW
 24 FOOT WIDE DRIVE AISLES AND THE ADJACENT PARKING
 SHALL BE ADJUSTED ACCORDINGLY AND LABLED AS SMALL
 SPACES.
  
 4) THE CHART ON SHEET A0.20 SHALL BE REVISED TO REFLECT
 THE NEW SMALL SPACE COUNT.
  
 5) THE SHEETS REFERENCED IN 3 AND 4 ABOVE SHALL BE
 SUBMITTED TO THE PLANNING DEPARTMENT FOR INCLUSION IN
 THE PENDING MINOR AMENDMENT.
  
 ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-20 Cont ID  
Sent By eschneid Date 2006-07-20 Time 17:38 Rev Time 0.00
Received By eschneid Date 2006-07-20 Time 17:38 Sent To  
Notes
2006-07-20 00:00:001) A MEETING INCLUDING THE PLANNING AND
 ZONING DEPARTMENT WAS NOT HELD TO
 DISCUSS VEHICULAR CIRCULATION PER
 RESOLUTION NO. 414-05 CONDITION.
  
 2) THE BUILDING LOCATION, DRIVEWAY
 WIDTHS AND LANDSCAPE AREAS DO NOT MATCH
 ON THE CIVIL PLANS AND THE APPROVED SITE
 AND LANDSCAPE PLANS.SHOW DIMENSION
 LINES ON ALL PLANS.
  
 3) A SITE DATA TABLE LISTING SQUARE
 FOOTAGES OF USE, PARKING COUNTS, ETC.
 WAS NOT PROVIDED.
  
 4) PROVIDE A PARKING DETAIL MEETING CITY
 OF WEST PALM BEACH REQUIREMENTS.
  
 5) DIMENSION LINES ARE REQUIRED FOR THE
 PARKING SPACES AND AISLES.
  
 6) IT APPEARS THERE IS A
 DISPROPORTIONATE NUMBER OF SMALL PARKING
 SPACES IN THE BUILDING.CITY ALLOWS A
 MAXIMUM OF 30%.IT DOES NOT SEEM THAT
 40+% OF A PARKING GARAGE AS COMPACT
 SPACES LENDS ITSELF WELL TO CLASS A
 OFFICE.
  
 7) A MINOR AMENDMENT IS REQUIRED FOR THE
 REVISED LANDSCAPE PLANS.STAFF WOULD
 LIKE TO SEE MORE THAN 6 ROYAL PALMS
 ALONG OKEECHOBEE (8 ARE ON THE APPROVED
 PLAN).
  
 8) HOW WILL THE DUMPSTERS BE RELOCATED
 IN THE REVISED SERVICE YARD?
  
 CONTACT ERIC SCHNEIDER @ (561)822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-27 Cont ID  
Sent By dpalmer Date 2006-06-15 Time 12:04 Rev Time  
Received By jleahy Date   Time   Sent To  
Notes
2006-06-15 00:00:00******** NOTE **********
  
 AS DIRECTED BY NEIL MELICK BUILDING
 OFFICAL: MS. LYNN HARRIS REPRESENTING
 CITY PLACE OFFICE LLC HAS REQUESTED
 PLANS TO BE REMOVED FROM THEPLAN
 REVIEW PROCESS.
 WHEN PLANS COME BACK IN FOR REVIEW, IT
 WILL BE 1ST RESUB NO FEE. DV PALMER.