Plan Review Details - Permit 06040955
Plan Review Stops For Permit 06040955
Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 14:50 Rev Time 0.00
Received By shill Date 2010-03-16 Time 14:50 Sent To  
Notes
2010-03-16 14:50:46EQUIPMENT CURB AND STAND INFO, REVIEW BY EOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2009-11-12 Cont ID  
Sent By shill Date 2009-11-12 Time 07:51 Rev Time 0.00
Received By shill Date 2009-11-10 Time 17:17 Sent To  
Notes
2009-11-12 07:59:17****REVISION PASSED WITH PROVISO****
 ****A-1A, A-1B, A4 REVISION #12****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FS471, CHANGES TO THE PLAN ARE TO BE DONE BY THE
 ENGINEER WHO SEALED THE PLAN. THIS REVISION IS PASSED
 SUBJECT TO INSPECTOR'S DISCRETION. THE CHANGES ON A1-B
 DO NOT MATCH THE DETAILS ON OTHER SHEETS. THESE CHANGES
 ARE SUBJECT TO FIELD INSPECTOR'S DISCRETION. A LETTER
 OF CLARIFICATION OR REVISION TO THE PLAN MAY BE
 REQUIRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2009-11-02 Cont ID  
Sent By shill Date 2009-11-02 Time 07:49 Rev Time 0.00
Received By shill Date 2009-11-02 Time 07:49 Sent To  
Notes
2009-11-02 07:51:09REVISION; STOREFRONT GLASS SHOPS, CALCS & PRODUCT
 APPROVALS
  
 ***PROVISO*** DESIGNER OF RECORD APPROVAL REQUIRED
 PRIOR TO FINAL INSPECTION
 ISSUED AT CONTRACTOR'S RISK
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2009-10-29 Cont ID  
Sent By shill Date 2009-10-29 Time 12:16 Rev Time 0.00
Received By shill Date 2009-10-29 Time 12:16 Sent To  
Notes
2009-10-29 12:16:38REVISION, PAGE A4
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2009-10-26 Cont ID  
Sent By shill Date 2009-10-26 Time 08:38 Rev Time 0.00
Received By shill Date 2009-10-26 Time 08:38 Sent To  
Notes
2009-10-26 08:39:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE THE RHEEM "UNIT TIE DOWN INSTRUCTIONS"
 (ST-A1024-01). IT STATES "MINIMUM 18 GA. X 1" WIDE
 GALV. STEEL STRAP (G90) OR EQUIVALENT (TYPE. 1 EACH
 CORNER)." CURB INSTALLATION DETAILS ALSO DO NOT SPECIFY
 A SPECIFIC PRODUCT.
  
 THE TEXT SPECIFIES A STRAP, BUT THE GRAPHIC DEPICTS AN
 ANGLE. I WAS UNABLE TO LOCATE A HURRICANE CONNECTOR
 WHICH MEETS THIS DESCRIPTION. PLEASE SPECIFY WHICH
 HURRICANE CONNECTOR WOULD BE ACCEPTABLE FOR EACH DETAIL
 TO BE USED ON THIS JOB.
  
 2. PLEASE SEE PAGE 11 OF THE SIMPSON STRONG-TIE
 CONNECTOR WOOD CONSTRUCTION CONNECTOR CATALOG:
 HTTP://WWW.STRONGTIE.COM/LITERATURE/C-2009.HTML
  
 OR THE USP CONNECTOR CATALOG "CORROSION INFORMATION":
 HTTP://WWW.USPCONNECTORS.COM/PDF-FULL-LINE-2009/CATEGOR
 IES/CORROSION55.PDF
  
  
 G90 HAS BEEN SPECIFIED, BUT THE CONNECTOR MANUFACTURERS
 RECOMMEND THAT G90 FINISH BE USED ONLY IN LOW EXPOSURE
 STRUCTURAL APPLICATIONS. IF THE CONNECTOR SPECIFIED IN
 RESPONSE TO COMMENT #1 IS OF A G90 FINISH, PLEASE HAVE
 BOTH THE MANUFACTURER'S ENGINEER AND THE EOR FOR THE
 PROJECT ACKNOWLEDGE THIS INFORMATION.
  
 3. SPECIFY THE LOCATION OF HURRICANE ANGLE
 INSTALLATION. THE DRAWING APPEARS TO SHOW ANGLES AT
 EACH CORNER OF THE LONG SIDE OF THE UNIT AND ONE IN THE
 CENTER (WITH A NOTE STATING THAT CENTER TO CENTER NOT
 TO EXCEED 48"), BUT NONE ON THE SHORT SIDE. IF
 INSTALLED AS DEPICTED GRAPHICALLY, THE UNIT WILL NOT
 RESIST WIND FROM ALL DIRECTIONS. FBC1609.
  
 4. PROVIDE EITHER A SHOP DRAWING REVIEW STAMP FROM THE
 ENGINEER OF RECORD OR A SIGNED AND SEALED LETTER
 STATING THAT HE HAS REVIEWED THE STAND AND CURB PRODUCT
 APPROVALS, INSTALLATION INSTRUCTIONS, AND CERTIFICATION
 FOR WIND RESISTANCE. FBC*106.
  
 5. PLEASE CLARIFY METHOD OF INSTALLATION. THE PLAN
 STATES THAT THE UNITS WILL BE INSTALLED ON ROOF CURBS.
 ROOF CURB INSTALLATION DETAILS WERE SUBMITTED AND A
 ROOF STAND DETAIL AND PRODUCT APPROVAL WERE SUBMITTED.
 ARE THE UNITS TO BE INSTALLED ON A CURB, STAND, OR ONE
 OF EACH? ONE OF THE DETAILS IS FOR A CURB WITH AN
 ATTACHMENT, DOES THAT DETAIL ALSO APPLY TO THIS JOB?
 PLEASE REMOVE DETAILS WHICH DO NOT PERTAIN TO THIS JOB,
 AND REVISE THE DETAILS WHICH DO PERTAIN TO THIS JOB TO
 SPECIFY HURRICANE ANCHORS.
  
 6. THIS ISSUE MAY BE RESOLVED VIA EMAIL (WITH THE
 EXCEPTION OF ITEM 4). THE ENGINEER (EITHER EOR OR RHEEM
 ENGINEER) CAN SPECIFY HURRICANE STRAPS OR ANGLES VIA
 EMAIL. PRIOR TO ISSUANCE, THE SHOP DRAWING REVIEW STAMP
 OR LETTER FROM EOR IS REQUIRED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU NEED ASSISTANCE.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2009-09-01 Cont ID  
Sent By lmartine Date 2009-09-01 Time 18:18 Rev Time 0.00
Received By lmartine Date 2009-09-01 Time 18:17 Sent To  
Notes
2009-09-01 18:19:07REVISON APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2009-05-21 Cont ID  
Sent By lmartine Date 2009-05-21 Time 15:42 Rev Time 0.00
Received By lmartine Date 2009-05-21 Time 15:42 Sent To  
Notes
2009-05-21 15:45:44SPOKE WITH ENGINEER'S OFFICE (JAVIOR). ASKED FOR COLUMN
 ANCHORS AND TO EXPLAIN EXISTING FOOTER.
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-03-03 Cont ID  
Sent By shill Date 2009-03-03 Time 17:01 Rev Time 0.00
Received By shill Date 2009-03-03 Time 17:01 Sent To  
Notes
2009-03-03 17:04:24***PROVISO***
 PER CONTRACTOR - AREA EXCLUDES WALK IN COOLER. PROVIDE
 COPY OF EMAIL FROM ENGINEER TO DCA REQUESTING
 CONFIRMATION THAT THIS IS ACCEPTABLE FOR METHOD "A".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2009-02-09 Cont ID  
Sent By shill Date 2009-02-09 Time 17:27 Rev Time 0.00
Received By shill Date 2009-02-09 Time 17:08 Sent To  
Notes
2009-02-09 17:27:19****CORRECTIONS****
 ****THIRD PERMIT PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004EXISTING BUILDING CODE
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS LISTS, NOT ADDRESSED
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.) IMPACT FEES MAY BE OWED TO PALM
 BEACH COUNTY. THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025.
  
 THIS ITEM HAS BEEN ADDRESSED. PLEASE KEEP THE IMPACT
 FEE RECEIPT AND THE STAMPED PLAN IN THE PERMIT PACKAGE
 WHEN RESUBMITTING.
  
 3-30.) ADDRESSED.
  
 NEW COMMENT (ENERGY CALCS NOT INCLUDED IN PREVIOUS
 REVIEW):
  
 31.) PLEASE EXPLAIN; ENERGY CALCS STATE 1486
 CONDITIONED & UNCONDITIONED AREA, BUT PLANS STATE THAT
 THE BUILDING IS 1980 SF.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2009-01-07 Cont ID  
Sent By efabian Date 2009-01-07 Time 12:32 Rev Time 0.00
Received By efabian Date 2009-01-07 Time 12:15 Sent To  
Notes
2009-01-07 12:33:18REVIEW IN ERROR
2009-01-07 12:18:21REFER TO DATA IN ENG ROW
2009-01-07 11:39:47NO COMMENTS
  
  
  
  
  
2008-12-19 15:09:39****CORRECTIONS****
 ****SECOND PERMIT PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004EXISTING BUILDING CODE
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS LISTS, NOT ADDRESSED
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.) IMPACT FEES MAY BE OWED TO PALM
 BEACH COUNTY. THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025.
  
 THE PLANS WERE STAMPED BUT THE RECEIPT WAS NOT
 PROVIDED. PLEASE PROVIDE.
  
 3.-4.) ADDRESSED.
  
 5.) DECLARE AN OCCUPANT LOAD, FBC10.
  
 HOW HAVE YOU ARRIVED AT AN OCCUPANT LOAD OF 16, 1000/8
 X 1980? SEE FBC1004.1, MUST USE EITHER DESIGN LOAD OR
 BASED ON FBC TABLE 1004.1.2, WHICHEVER IS GREATER. M
 AND B HAVE DIFFERENT OCCUPANT LOADS. SEE FBC309; IT
 APPEARS THAT HIS IS M OCCUPANCY, NOT B. PROVIDE MORE
 INFORMATION IN REGARDS TO THE USE OF THIS BUILDING TO
 JUSTIFY THE B OCCUPANCY CLASSIFICATION.
  
 4TH REVIEW, OCCUPANT LOAD SHOULD BE SF AREA / 30 PER
 FBC TABLE 1004.1.2. PLEASE REVISE OR EXPLAIN OCCUPANT
 LOAD.
  
 5TH REVIEW, OCCUPANT LOAD IS NOW CALCULATED AT 300SF
 PER OCCUPANT FOR MERCANTILE AREA. SEE PREVIOUS REVIEW
 AND FBC TABLE 1004.1.2, OCCUPANT LOAD CANNOT BE LESS
 THAN THE TABLE, 30 SF PER PERSON. A1-B SHOWS 1512 SF
 STOCKROOM AREA, WHERE IS THE STOCKROOM? THE BUILDING IS
 ONLY 1980SF, YET YOU ARE STATING THAT 1512 IS A STORAGE
 AREA, ONLY 468 MERCANTILE. OCCUPANT LOAD MUST BE
 DETERMINED. SEE OTHER COMMENTS.
  
 6.) ADDRESSED.
  
 7.) SEE PREVIOUS LIST. A/C STAND PRODUCT APPROVAL
 REQUIRED FAC9B72.
  
 8.) PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 10-16.) ADDRESSED.
  
 17.) PROVIDE ENERGY CALCS AND SIGN IN
 ALL APPLICABLE PLACES, INCLUDING THE
 OWNER/AGENT LINE FBC13-103.1.
  
 INCLUDE THE STRUCTURAL ENGINEER TO CERTIFY ENERGY
 COMPLIANCE, FBC13-103.1.1.1 AS HE IS REPONSIBLE FOR THE
 BUILDING SHELL.
  
 5TH REVIEW, ENERGY CALCS WERE NOT INCLUDED IN THE
 RESUBMITTAL. NO RESPONSE PROVIDED FOR THIS ITEM ON THE
 RESPONSE LETTER.
  
 18-26.) ADDRESSED.
  
 27.) IT APPEARS THAT THE ENGINEER HAS NOT DELCARED THE
 CORRECT OCCUPANT LOAD AND TWO EXITS ARE REQUIRED. THE
 TWO EXITS ARE TO BE REMOTELY LOCATED, FBC1014.2.1. THIS
 REQUIREMENT CANNOT BE DETERMINED DUE TO THE ENGINEER'S
 FAILURE TO ADDRESS THE COMMENT REGARDING OCCUPANT LOAD
 AND OCCUPANCY CLASSIFICATION.
  
 5TH REVIEW, ALL DOORS TO THE OUTSIDE ARE SHOWN AS
 EXITS. THE "EXIT" AT THE VESTIBULE IS OBSTRUCTED BY THE
 STORAGE ROOM DOOR, SEE FBC 1005.2. SHOW THE TWO
 REQUIRED EXITS AND COMPLIANCE WITH THE REQUIREMENT TO
 BE REMOTELY LOCATED. DOORS MARKED AS EXIT DOORS MUST
 COMPLY WITH THE REQUIREMENTS OF FBC CHAPTER 10.
  
 28.) ADDRESSED.
  
 29.) THE PLANS DO NOT SHOW THE ISO BOARD REQUIRED FOR
 THE WALLS (ENERGY CALCS). PLEASE CORRELATE. NOTE
 EXISTING CONDITIONS FOR EXISTING WALLS. ALL INFORMATION
 IS TO BE ON THE PLAN IF A TYPED NAME IS USED IN LIEU OF
 A SIGNATURE, SEE FBC13-103.1.1.1.
  
 5TH REVIEW, ENERGY CALCS HAVE BEEN REMOVED. BUILDING
 COMPONENTS CANNOT BE CONFIRMED.
  
 30.) ADDRESSED.
  
 CONTRACTOR WAS CALLED IN AN ATTEMPT TO RESOLVE SOME OF
 THE OUTSTANDING ISSUES.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-01-07 Cont ID  
Sent By shill Date 2008-11-07 Time 10:28 Rev Time 0.00
Received By shill Date 2008-11-07 Time 10:28 Sent To  
Notes
2008-11-07 10:53:39****CORRECTIONS****
 ****FIRST PERMIT PLAN REVIEW (CONVERTED FROM PLAN CHECK
 TO PERMIT APPLICATION)****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004EXISTING BUILDING CODE
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS LISTS, NOT ADDRESSED
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.) IMPACT FEES MAY BE OWED TO PALM
 BEACH COUNTY. THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025.
  
 **10/10, CONFIRMED WITH PALM BEACH COUNTY, IMPACT FEE
 ASSESSMENT REQUIRED***
  
 3.) DECLARE THE LEVEL OF ALTERATION,
 FBC EB 301.
  
 4.) DECLARE OCCUPANCY FBC309.
  
 M AND B WAS DECLARED. PROVIDE SF AREA FOR EACH
 OCCUPANCY SO THAT OCCUPANT LOAD CAN BE DETERMINED.
  
 4TH REVIEW, APPEARS TO BE M. PLEASE EXPLAIN WHY PLANS
 STATE B M. SEE FBC309.1.
  
 5.) DECLARE AN OCCUPANT LOAD, FBC10.
  
 HOW HAVE YOU ARRIVED AT AN OCCUPANT LOAD OF 16, 1000/8
 X 1980? SEE FBC1004.1, MUST USE EITHER DESIGN LOAD OR
 BASED ON FBC TABLE 1004.1.2, WHICHEVER IS GREATER. M
 AND B HAVE DIFFERENT OCCUPANT LOADS. SEE FBC309; IT
 APPEARS THAT HIS IS M OCCUPANCY, NOT B. PROVIDE MORE
 INFORMATION IN REGARDS TO THE USE OF THIS BUILDING TO
 JUSTIFY THE B OCCUPANCY CLASSIFICATION.
  
 4TH REVIEW, OCCUPANT LOAD SHOULD BE SF AREA / 30 PER
 FBC TABLE 1004.1.2. PLEASE REVISE OR EXPLAIN OCCUPANT
 LOAD.
  
 6.) ADDRESSED.
  
 7.) PRODUCT APPROVALS REQUIRED FOR THE
 STOREFRONT AND DOORS. FLORIDA STATE OR
 LOCAL PRODUCT APPROVALS REQUIRED
 FAC9B72. WWW.FLORIDABUILDING.ORG
  
 4TH REVIEW, NO PRODUCT APPROVALS SUBMITTED. ALSO NOTE
 THAT A/C STAND IS SHOWN ON M SHEETS; PRODUCT APPROVAL
 REQUIRED. RESOLVE CONFLICTS/INCONSISTENCIES BETWEEN
 PLANS AND PRODUCT APPRPOVAL, IF ANY, PRIOR TO
 RESUBMITTAL.
  
 8.) PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 10-16.) ADDRESSED.
  
 17.) PROVIDE ENERGY CALCS AND SIGN IN
 ALL APPLICABLE PLACES, INCLUDING THE
 OWNER/AGENT LINE FBC13-103.1.
  
 INCLUDE THE STRUCTURAL ENGINEER TO CERTIFY ENERGY
 COMPLIANCE, FBC13-103.1.1.1 AS HE IS REPONSIBLE FOR THE
 BUILDING SHELL.
  
 18-19.) ADDRESSED.
  
 20.) M2 WAS REVISED AS PER PREVIOUS
 LIST, BUT STILL REFERS TO HIGH VELOCITY.
 CITY OF WEST PALM BEACH IS NOT IN THE
 HIGH VELOCITY ZONE.
  
 THE CHART IS FROM HVHZ, PLEASE USE THE APPROPRIATE
 CHART FROM FBC TABLE 1509.7. ALSO, THERE IS A TYPO ON
 LINE 3 (27).
  
 4TH REVIEW, REMOVE REFERENCE TO HVHZ.
  
 21.) WHEN RESUBMITTING, PLEASE REMOVE
 OLD SHEETS.
  
 BUT PLEASE PROVIDE THEM FOR REFERENCE.
  
 4TH REVIEW, OLD SHEETS NOT SUBMITTED. A SET HAS BEEN
 RETAINED.
  
 22.) N/A
  
 23.) IT APPEARS THAT MANY COMMENTS WERE
 NOT ADDRESSED. TO EXPEDITE PLAN REVIEW,
 PLEASE INCLUDE A RESPONSE LETTER
 INDICATING HOW AND WHERE EACH ITEM WAS
 ADDRESSED.
  
 PLEASE SUBMIT BOTH THE OLD SHEETS AND A RESPONSE LETTER
 WHEN RESUBMITTING. FAILURE TO DO SO REQUIRES A
 COMPLETELY NEW PLAN REVIEW AND INCREASES THE
 POSSIBILITY OF NEW COMMENTS.
  
 24-25.) ADDRESSED.
  
 26.) ALL CHANGES ARE TO BE CLOUDED.
  
 27.) IT APPEARS THAT THE ENGINEER HAS NOT DELCARED THE
 CORRECT OCCUPANT LOAD AND TWO EXITS ARE REQUIRED. THE
 TWO EXITS ARE TO BE REMOTELY LOCATED, FBC1014.2.1. THIS
 REQUIREMENT CANNOT BE DETERMINED DUE TO THE ENGINEER'S
 FAILURE TO ADDRESS THE COMMENT REGARDING OCCUPANT LOAD
 AND OCCUPANCY CLASSIFICATION.
  
 28.) SOMEONE HAS REVISED THE PLAN A1B. INCORPORATE
 CHANGES INTO THE SIGNED AND SEALED PLAN. SOMEONE WROTE
 "SLIDING" DOOR (RATHER THAN SWINGING). THE DOOR IS TO
 COMPLY WITH FBC1008.1.3.3; NOTE REQUIREMENTS ON PLAN
 AND REVISE ELECTRIC SHEETS.
  
 29.) THE PLANS DO NOT SHOW THE ISO BOARD REQUIRED FOR
 THE WALLS (ENERGY CALCS). PLEASE CORRELATE. NOTE
 EXISTING CONDITIONS FOR EXISTING WALLS. ALL INFORMATION
 IS TO BE ON THE PLAN IF A TYPED NAME IS USED IN LIEU OF
 A SIGNATURE, SEE FBC13-103.1.1.1.
  
 30.) SHEET 2, WHAT DO THE ARROWS REPRESENT ON THE
 ACCESSIBLE PARKING DETAIL?
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-22 Cont ID  
Sent By shill Date 2007-03-22 Time 12:55 Rev Time 0.00
Received By shill Date 2007-03-21 Time 15:03 Sent To  
Notes
2007-03-22 12:56:09****CORRECTIONS****
 ****PLAN CHECK ONLY, NOT A PERMIT
 APPLICATION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS LISTS, NOT
 ADDRESSED
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.)IMPACT FEES MAY BE OWED TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025.
  
 **10/10, CONFIRMED WITH PALM BEACH COUNTY, IMPACT FEE
 ASSESSMENT REQUIRED***
  
 3.)DECLARE THE LEVEL OF ALTERATION,
 FBC EB 301.
  
 4.)DECLARE OCCUPANCY FBC309, MINIMUM
 BUILDING TYPE FBC6.TYPE V WAS
 DECLARED, NEED TO ALSO DECLARE A OR B.
  
 M AND B WAS DECLARED.PROVIDE SF AREA FOR EACH
 OCCUPANCY SO THAT OCCUPANT LOAD CAN BE DETERMINED.
  
 5.)DECLARE AN OCCUPANT LOAD, FBC10.
  
 HOW HAVE YOU ARRIVED AT AN OCCUPANT LOAD OF 16, 1000/8
 X 1980?SEE FBC1004.1, MUST USE EITHER DESIGN LOAD OR
 BASED ON FBC TABLE 1004.1.2, WHICHEVER IS GREATER.M
 AND B HAVE DIFFERENT OCCUPANT LOADS.SEE FBC309; IT
 APPEARS THAT HIS IS M OCCUPANCY, NOT B.PROVIDE MORE
 INFORMATION IN REGARDS TO THE USE OF THIS BUILDING TO
 JUSTIFY THE B OCCUPANCY CLASSIFICATION.
  
 6.)ADDRESSED.
  
 7.)PRODUCT APPROVALS REQUIRED FOR THE
 STOREFRONT AND DOORS.FLORIDA STATE OR
 LOCAL PRODUCT APPROVALS REQUIRED
 FAC9B72. WWW.FLORIDABUILDING.ORG
  
 8.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 10.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4.THIS WAS PROVIDED BUT PLEASE CLARIFY HOW
 YOU HAVE ARRIVED AT A -.25 INTERNAL PRESSURE
 COEFFICIENT.THIS MAY BE DONE IN A SIGNED, SEALED
 LETTER (DOES NOT HAVE TO BE ON THE PLAN).THIS APPEARS
 TO BE A FULLY ENCLOSED BUILDING, AND TYPICALLY THE
 INTERNAL PRESSURE COEFFICIENT IS -.18.IT IS
 ACCEPTABLE TO EXCEED MINIMUM CODE REQUIREMENTS BUT I AM
 REQUESTING CLARIFICATION.
  
 11-15.)ADDRESSED.
  
 16.)PROVIDE A BREAKDOWN OF COSTS TO
 DETERMINE WHETHER OR NOT ENERGY CALCS
 ARE REQUIRED AND TO CONFIRM VALUATION
 PROVIDED.SEE FBC 13-101.1, FBC13-202,
 FBC EB708.1.
  
 PROVIDE ENERGY CALCS, INCREASE IN
 CONDITIONED FLOOR AREA.SEE
 FBC13-1-1.1.2, DEFINITION OF ADDITION
 FBC13-202.
  
 THE BREAKDOWN OF COSTS WAS PROVIDED, BUT NO ENERGY
 CALCS WERE SUBMITTED.
  
 17.)PROVIDE ENERGY CALCS AND SIGN IN
 ALL APPLICABLE PLACES, INCLUDING THE
 OWNER/AGENT LINE FBC13-103.1.
  
 18-19.)ADDRESSED.
  
 20.)M2 WAS REVISED AS PER PREVIOUS
 LIST, BUT STILL REFERS TO HIGH VELOCITY.
 CITY OF WEST PALM BEACH IS NOT IN THE
 HIGH VELOCITY ZONE.
  
 THE CHART IS FROM HVHZ, PLEASE USE THE APPROPRIATE
 CHART FROM FBC TABLE 1509.7.ALSO, THERE IS A TYPE ON
 LINE 3 (27).
  
 21.)WHEN RESUBMITTING, PLEASE REMOVE
 OLD SHEETS.
  
 BUT PLEASE PROVIDE THEM FOR REFERENCE.
  
 22.)N/A
  
 23.)IT APPEARS THAT MANY COMMENTS WERE
 NOT ADDRESSED.TO EXPEDITE PLAN REVIEW,
 PLEASE INCLUDE A RESPONSE LETTER
 INDICATING HOW AND WHERE EACH ITEM WAS
 ADDRESSED.
  
 PLEASE SUBMIT BOTH THE OLD SHEETS AND A RESPONSE LETTER
 WHEN RESUBMITTING.FAILURE TO DO SO REQUIRES A
 COMPLETELY NEW PLAN REVIEW AND INCREASES THE
 POSSIBILITY OF NEW COMMENTS.
  
 24.)NEW COMMENT; EDGE PROTECTION REQUIRED
 FBC11-4.8.7.
  
 25.)SHEET 2, SHOW SIDEWALK WIDTH (ACCESSIBLE ROUTE
 FBC11-4.1).
  
 26.)ALL CHANGES ARE TO BE CLOUDED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-06 Cont ID  
Sent By shill Date 2006-10-06 Time 08:13 Rev Time 0.00
Received By shill Date 2006-10-05 Time 17:08 Sent To  
Notes
2006-10-06 00:00:00****CORRECTIONS****
 ****PLAN CHECK ONLY, NOT A PERMIT
 APPLICATION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS LIST, NOT
 ADDRESSED
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.)IMPACT FEES MAY BE OWED TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025.PENDING RETURN
 TELEPHONE CALL FROM PBC.
  
 **10/10, CONFIRMED WITH PALM BEACH COUNTY, IMPACT FEE
 ASSESSMENT REQUIRED***
  
 3.)DECLARE THE LEVEL OF ALTERATION,
 FBC EB 301.
  
 4.)DECLARE OCCUPANCY FBC309, MINIMUM
 BUILDING TYPE FBC6.TYPE V WAS
 DECLARED, NEED TO ALSO DECLARE A OR B.
  
 5.)DECLARE AN OCCUPANT LOAD, FBC10.
  
 6.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR EGN, INC. IS TO BE ON EACH
 SHEET, FAC61G15-23.002.
  
 7.)PRODUCT APPROVALS REQUIRED FOR THE
 STOREFRONT AND DOORS.FLORIDA STATE OR
 LOCAL PRODUCT APPROVALS REQUIRED
 FAC9B72. WWW.FLORIDABUILDING.ORG
  
 8.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 10.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4.
  
 11.)EXIT ACCESS SHALL NOT GO THROUGH
 STORAGE ROOMS, FBC1013.2.
  
 12.)ADDRESSED.
  
 13.)PARKING IS NOT SHOWN ON THE PLAN.
 IF PARKING IS PROVIDED, ACCESSIBLE
 PARKING IS REQUIRED FBC11-4.6.SEE
 ATTACHED DETAIL.PLEASE PROVIDE
 ACCESSIBLE PARKING DETAIL, SHOW
 LOCATION.
  
 14.)ADDRESSED.
  
 15.)PLANS INDICATE THAT THE EXISTING
 MANSARD IS TO BE RESURFACED A3.ROOF
 PERMIT REQUIRED.
  
 16.)PROVIDE A BREAKDOWN OF COSTS TO
 DETERMINE WHETHER OR NOT ENERGY CALCS
 ARE REQUIRED AND TO CONFIRM VALUATION
 PROVIDED.SEE FBC 13-101.1, FBC13-202,
 FBC EB708.1.
  
 PROVIDE ENERGY CALCS, INCREASE IN
 CONDITIONED FLOOR AREA.SEE
 FBC13-1-1.1.2, DEFINITION OF ADDITION
 FBC13-202.
  
 17.)PROVIDE ENERGY CALCS AND SIGN IN
 ALL APPLICABLE PLACES, INCLUDING THE
 OWNER/AGENT LINE FBC13-103.1.
  
 18.)SPECIFY INTERIOR FINISH
 CLASSIFICATION, FBC TABLE 803.5.
  
 19.)THERE IS A NOTE ON M2 STATING THAT
 EQUIPMENT IS TO BE ANCHORED PER FBC 15
 AND 16 AND TO WITHSTAND 146MPH.SPECIFY ANCHORING.
  
 20.)M2 WAS REVISED AS PER PREVIOUS
 LIST, BUT STILL REFERS TO HIGH VELOCITY.
 CITY OF WEST PALM BEACH IS NOT IN THE
 HIGH VELOCITY ZONE.
  
 NEW COMMENTS:
  
 21.)WHEN RESUBMITTING, PLEASE REMOVE
 OLD SHEETS.
  
 22.)PLEASE NOTE THAT THE "CANOPY"
 SHOULD BE INCLUDED IN BUILDING AREA, SEE DEFINITIONS,
 FBC5.
  
 23.)IT APPEARS THAT MANY COMMENTS WERE
 NOT ADDRESSED.TO EXPEDITE PLAN REVIEW,
 PLEASE INCLUDE A RESPONSE LETTER
 INDICATING HOW AND WHERE EACH ITEM WAS
 ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU
 NEED ASSISTANCE WITH ANY OF THE ABOVE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-17 Cont ID  
Sent By shill Date 2006-05-17 Time 15:57 Rev Time 0.00
Received By shill Date 2006-05-15 Time 16:48 Sent To  
Notes
2006-05-17 00:00:00****CORRECTIONS****
 ****PLAN CHECK ONLY, NOT A PERMIT
 APPLICATION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)DECLARE THE LEVEL OF ALTERATION,
 FBC EB 301.
  
 4.)DECLARE OCCUPANCY FBC309, MINIMUM
 BUILDING TYPE FBC6.
  
 5.)DECLARE AN OCCUPANT LOAD, FBC10.
  
 6.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR ENG, INC. IS TO BE ON EACH
 SHEET, FAC61G15-23.002.
  
 7.)PRODUCT APPROVALS REQUIRED FOR THE
 STOREFRONT AND DOORS.FLORIDA STATE OR
 LOCAL PRODUCT APPROVALS REQUIRED
 FAC9B72. WWW.FLORIDABUILDING.ORG
  
 8.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 9.)A-1B HAS A NOTE REFERRING TO
 HURRICANE SHUTTERS.USE OF REMOVABLE
 SHUTTERS ON COMMERCIAL BUILDINGS MUST BE
 APPROVED BY THE BUILDING OFFICIAL.SEE
 ATTACHED MISSILE IMPACT PROTECTION
 STANDARD, ITEM 13.THE PLANS WILL NOT
 BE APPROVED WITH THIS REFERENCE TO
 HURRICANE SHUTTERS UNLESS THE
 INSTALLATION PLAN REFERRED TO IN THE
 STANDARD IS APPROVED.THE PLAN MAY BE
 SUBMITTED SEPARATELY AND PRIOR TO
 RESUBMITTAL OF THE CONSTRUCTION PERMIT
 PLANS.
  
 10.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4.
  
 11.)EXIT ACCESS SHALL NOT GO THROUGH
 STORAGE ROOMS, FBC1013.2.
  
 12.)THE BOTTOM OF EACH RAMP SHALL HAVE
 72IN STRAIGHT AND LEVEL CLEARANCE,
 FBC11-4.8.4(2).
  
 13.)PARKING IS NOT SHOWN ON THE PLAN.
 IF PARKING IS PROVIDED, ACCESSIBLE
 PARKING IS REQUIRED FBC11-4.6.SEE
 ATTACHED DETAIL.
  
 14.)SEE 11-7.2, SHOW COMPLIANCE FOR
 THE SALES COUNTER AT THE POS.THE
 HEIGHT IS SHOWN GRAPHICALLY A-A4 BUT
 PLEASE ADD THE DIMENSION TO THE COUNTER
 WHICH HAS A HEIGHT REQUIREMENT (SALES
 AREA SIDE).
  
 15.)PLANS INDICATE THAT THE EXISTING
 MANSARD IS TO BE RESURFACED A3.ROOF
 PERMIT REQUIRED.
  
 16.)PROVIDE A BREAKDOWN OF COSTS TO
 DETERMINE WHETHER OR NOT ENERGY CALCS
 ARE REQUIRED AND TO CONFIRM VALUATION
 PROVIDED.SEE FBC 13-101.1, FBC13-202,
 FBC EB708.1.
  
 17.)IF ENERGY CALCS ARE REQUIRED,
 PLEASE PROVIDE AND SIGN IN ALL
 APPLICABLE PLACES, INCLUDING THE
 OWNER/AGENT LINE FBC13-103.1.
  
 18.)SPECIFY INTERIOR FINISH
 CLASSIFICATION, FBC TABLE 803.5.
  
 19.)THERE IS A NOTE ON M2 STATING THAT
 EQUIPMENT IS TO BE ANCHORED PER FBC 15
 AND 16 AND TO WITHSTAND 146MPH.SPECIFY
 ANCHORING.
  
 20.)THE TABLE ON M2 IS FROM HIGH
 VELOCITY, NOT COMPLIANT FOR NON HIGH
 VELOCITY.THE EQUIPMENT CLEARANCE IS TO
 COMPLY WITH FBC1509.7.
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-03-03 Cont ID  
Sent By dpalmer Date 2009-03-03 Time 19:07 Rev Time 0.00
Received By dpalmer Date 2009-03-03 Time 19:07 Sent To  
Notes
2009-03-03 19:10:14ELECTRICAL OK.
 ENERGY CALCULATIONS COORDINATE WITH PLANS.
 PLANS WERE REVISED TO INCLUDE SEVERAL NEW A/C UNITS NOT
 ON PREVIOUS PLANS.
 PENDING ZONING REVIEW FOR FINAL PROCESSING. E-MAIL SENT
 TO ZONING ALONG WITH A PHONE MESSAGE.
 FEE BALANCE IS STILL REQUIRED BEFORE PERMIT CAN BE
 ISSUED.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-02-06 Cont ID  
Sent By dpalmer Date 2009-02-06 Time 17:40 Rev Time 0.00
Received By dpalmer Date 2009-02-06 Time 17:40 Sent To  
Notes
2009-02-06 17:40:15** DENIED REVIEW **
  
 ** 6TH REVIEW FAILED. THIS IS THE THIRD REVIEW UNDER
 ACTUAL PERMIT APPLICATION.
  
 1) NOTE: PLEASE SEE ALL PREVIOUS REVIEWS WITH RESPECT
 TO MINIMUM CODE COMPLIANCE REQUIRED FOR CHAPTER 13.
 PLEASE SEE THAT COMPLIANCE FOR FLORIDA BUILDING CODE
 CHAPTER 13 HAS NOT BEEN ACHIEVED.
 THE SUBMITTED METHOD *A* CALCULATIONS ARE FOR *WHOLE
 BUILDING COMPLIANCE*. WHEN SUBMITTING ENERGY
 CALCULATIONS FOR WHOLE BUILDING COMPLIANCE THAT IS JUST
 WHAT THE CODE REQUIRES. PLEASE SEE SECTION13-400.0.A,
 13-400.2.A.2 WHICH IS JUST TWO SECTIONS WHICH STATES
 ONCE ALL BUILDING COMPONENTS ARE KNOWN THEN AND ONLY
 THEN IS METHOD *A* PERMITTED TO BE USED.
 ON PREVIOUS REVIEWS THIS REVIEW GAVE ITEMS ON PLANS
 WHICH WERE NOT IN THE ENERGY CALCULATIONS AND ITEMS ON
 THE PLANS WHICH WERE NOT IN THE INPUT DATA REPORT OF
 THE SUBMITTED CALCULATIONS.
 IT IS CLEAR ON THE PLANS THAT THE INFORMATION ON PLANS
 DOES NOT COORDINATE WITH PLANS. SOME EXAMPLES WILL BE
 GIVEN ONCE AGAIN AS A BENEFIT TO DESIGN TEAM IN AN
 EFFORT TO MEET ABSOLUTE *MINIMUM CODE COMPLIANCE*.
  
 FOR EXAMPLE: INTERIOR LIGHTING ON THE IDR STATES A
 TOTAL OF 45-32WATT FIXTURES AND A TOTAL OF 30-32WATT
 FIXTURES. THIS IS NOT POSSIBLE WHEN THE FIXTURES ON THE
 FIXTURE LEGEND ARE NOT EVEN 32WATT FIXTURES. IN FACT
 ONE FIXTURE WHICH IS FIXTURE *A* STATES THERE ARE 4-40W
 BULBS AND THE OTHER STATES 2-40W BULBS.
 THE *A* FIXTURE WHICH STATES 4-40W BULBS CAN NOT
 POSSIBLY BE 32WATTS BASED ON THE INFORMATION STATED ON
 THE INPUT DATA REPORT OF THE SUBMITTED SIGNED AND
 SEALED ENERGY CALCULATIONS.
  
 FOR EXAMPLE: THE EXTERIOR LIGHTS ON THE IDR ONLY STATES
 2-150W FIXTURES. THIS IS NOT POSSIBLE. THIS METHOD OF
 CALCULATION SUBMITTED IS METHOD *A* FOR WHOLE BUILDING
 COMPLIANCE AND THE LIGHTING SHOWN ON THE ELECTRICAL
 PLANS IS FAR GREATER THAN THAT SHOWN ON THE IDR. IN
 FACT THE FIXTURES ON THE PLANS ARE 100W, 320W AND 400W
 FIXTURES. HOW IS IT POSSIBLE THAT THE IDR ONLY SHOWS
 TWO 150W FIXTURES?
  
 THE COMMENT FROM PREVIOUS REVIEW AS WELL AS THIS REVIEW
 IS ALSO FOR ALL INFORMATION ON PLANS TO COORDINATE WITH
 THE INPUT DATA REPORT. THIS COMMENT IS FOR ALL TRADES
 AND FOR ALL REVIEWS WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
 PLEASE SEE FBC 13-101.1, 13-400.3.A, 13-400.3.B,
 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3. THESE ARE
 ONLY A FEW SECTIONS NOTED FOR ELECTRICAL LIGHTING.
 PLEASE ALSO SEE 13-400 THROUGH 13-414 FOR COMPLIANCE OF
 ALL OTHER BUILDING COMPONENTS SUCH AS INSULATIONS,
 DOORS, WINDOWS, FLOOR, PIPING, WATER HEATING ETC. THESE
 ARE ONLY A FEW ITEMS NOTED.
 PLEASE SEE CHAPTER 13.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE
 REQUIRED TRANSFER SWITCH REQUIRED TO MEET HB 7121,
 701.7, 110.3. THE PROPOSED *BOLT-ON* LOCKS NOT ONLY
 WOULD VOID LISTING OF EQUIPMENT IT ALSO DOES NOT MEET
 THE SECTIONS OF THE CODE GIVEN.
 ANY EQUIPMENT USED TO TRANSFER POWER SHALL BE LISTED
 FOR ITS USE.
 THE ITEM BEING SUBMITTED FOR USE IS NOT PERMITTED.
 ANYONE WHO HAS TWO KEYS COULD OPERATE BOTH BREAKERS AT
 THE SAME TIME WHICH WOULD PERMIT POWER FROM BOTH SIDES
 BEING ON AT THE SAME TIME. THIS IS NOT ONLY A FIRE
 HAZARD BUT AS WELL AS A LIFE SAFETY HAZARD.
  
  
 3) NOTE: PLANS HAVE BEEN SUBMITTED FOR SIX REVIEWS. ON
 THE LAST/PREVIOUS REVIEW A NOTICE WAS GIVEN WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE PER FS
 553.80(2)(B).
 WHEN SPECIFIC CODE SECTIONS ARE REPEATED THREE OR MORE
 TIMES FOR THE SAME CODE SECTION VIOLATION THE STATE
 STATUTE REQUIRES A FEE ASSESSED. THIS FEE AS NOTED PER
 STATUTE SECTION GIVEN IS BASED ON THE AMOUNT OF THE
 BASE PERMIT FEE ATTRIBUTED TO PLAN REVIEW TIMES FOUR.
 IN THE CITY OF WEST PALM BEACH THE PORTION OF THE BASE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW IS 30% (PERCENT)
 OF THE BASE PERMIT FEE. THE BASE PERMIT FEE ON THIS
 PROJECT IS $4,500.00. THIS IS NOT THE OTHER FEES FOR
 FIRE REVIEW ETC.
 THE 30% OF THE $4,500.00 IS $1,350.00. THIS IS THE
 AMOUNT TIMES FOUR.
 $1,350.00 TIMES FOUR IS $5,400.00. THIS IS THE AMOUNT
 REQUIRED BY FLORIDA STATUTES TO BE ASSESSED. THIS IS
 NOT A LOCAL FEE OR LOCALLY REQUIRED. THIS IS A REQUIRED
 FEE BY THE STATE.
 IT IS IMPORTANT TO KNOW THAT THE FEE IS FOR EACH TIME
 AFTER THEREFORE IT IS IMPERATIVE FOR CORRECTIONS TO BE
 MADE AND FOR PLANS AND SUBMITTED ENERGY CALCULATIONS TO
 MATCH AND TO MEET MINIMUM CODE. ONE SET OF ELECTRICAL
 PLANS, AND CALCULATIONS ARE BEING RETAINED BY THIS
 OFFICE FOR FILE. IT IS NOT THE INTENT OF THIS OFFICE TO
 SEND PLANS TO THE FLORIDA BOARD OF ENGINEERS FOR REVIEW
 AT THIS TIME HOWEVER THIS OFFICE MAY NOT BE LEFT WITH
 ANY CHOICE BASED ON THE NEXT REVIEW. PLEASE MAKE
 CORRECTIONS AS NOTED.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-12-23 Cont ID  
Sent By dpalmer Date 2008-12-23 Time 13:58 Rev Time 0.00
Received By dpalmer Date 2008-12-23 Time 13:58 Sent To  
Notes
2008-12-23 13:58:21** DENIED 5TH REVIEW**
  
 2ND REVIEW UNDER PERMIT APPLICATION.
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS THE 5TH
 REVIEW FOR SOME ITEMS NOT BEING CODE COMPLIANT AND THE
 2ND REVIEW UNDER PERMIT APPLICATION AND STILL NOT
 HAVING CODE COMPLIANCE FOR SOME ITEMS. PLEASE SEE
 COMMENTS BELOW. PLEASE BE AWARE OF STATUTE AS THIS MAY
 BECOME AN ISSUE ON THE NEXT REVIEW IF COMMENTS ARE NOT
 ADDRESSED.
  
 2) NOTE: PLEASE SEE THAT COMPLIANCE FOR FLORIDA
 BUILDING CODE CHAPTER 13 HAS NOT BEEN ACHIEVED. ON THE
 PREVIOUS REVIEW THE COMMENT WAS MADE THAT THE VERSION
 SUBMITTED WAS NO LONGER IN EFFECT AS THE CODE HAD
 CHANGED. THE COMMENT WAS ALSO FOR ALL INFORMATION ON
 PLANS TO COORDINATE WITH THE INPUT DATA REPORT. THIS
 COMMENT IS FOR ALL TRADES AND FOR ALL REVIEWS WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADES.
 PLEASE SEE FBC 13-101.1, 13-400.3.A, 13-400.3.B,
 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3. THESE ARE
 ONLY A FEW SECTIONS NOTED FOR ELECTRICAL LIGHTING.
 PLEASE ALSO SEE 13-400 THROUGH 13-414 FOR COMPLIANCE OF
 ALL OTHER BUILDING COMPONENTS SUCH AS INSULATIONS,
 DOORS, WINDOWS, FLOOR, PIPING, WATER HEATING ETC. THESE
 ARE ONLY A FEW ITEMS NOTED.
 PLEASE SEE CHAPTER 13.
 THE RESPONSE NOTES FOR ELECTRICAL DO NOT CONTAIN ANY
 RESPONSE FOR THE PREVIOUS NOTE WITH RESPECT TO ENERGY
 CALCULATIONS.
  
 3) NOTE: PREVIOUS NOTES WERE MADE WITH RESPECT TO HOUSE
 BILL 7121 AND THE REQUIRED BACK UP POWER. THE RISER HAS
 NOW BEEN REVISED HOWEVER NO TRANSFER SWITCH DEVICE
 LISTED PER UL 1081 IS SHOWN. IN FACT THERE SEEMS TO BE
 SOME SORT OF INTER-LOCK WHICH MAY OR MAY NOT MEET
 701.7, 702.6, 110.3 ETC.
 PLEASE KNOW THE DEVICE MUST BE LISTED AND MEET THE FAIL
 SAFE OPERATION TO PREVENT SERIOUS INJURY OR DEATH.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS.
  
  
 4) NOTE: THE PLANS ARE STILL LISTING THE INCORRECT
 CODES IN DIFFERENT LOCATIONS. PLANS STILL SHOW THE 2002
 NFPA-70 FOR EXAMPLE. PLEASE SEE D-1, A-1A ETC.
 THE CODES SHALL BE LISTED AS FOLLOWS.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 ** THIS IS A MINIMUM FOR THIS TRADE ALONE. THIS DOES
 NOT INCLUDE OTHER CODES REQUIRED AS PART OF DESIGN
 INCLUDING NFPA-30A.
 FS 553.73, FBC 2004.
 ** PLANS WERE NEVER SUBMITTED FOR PERMIT APPLICATION
 UNTIL 10/2008 THEREFORE CODES WHICH WERE IN EFFECT IN
 2006 ARE NO LONGER VALID. THIS WAS NOTED IN ALL
 PREVIOUS REVIEW YET THIS IS STILL NOT ADDRESSED.
  
 5) NOTE: LIGHTING CONTROLS MUST COMPLY WITH FBC
 13-415.1.ABC.1.4. PLEASE BE SURE TO NOTE TIME CLOCK AS
 ASTRONOMICAL WITH A MINIMUM OF 10HR BATTERY BACK UP FOR
 PROGRAMMING.
  
 6) NOTE: PLEASE SEE 250..110,250.122 ETC FOR MISSING
 EQUIPMENT GROUNDING CONDUCTOR FROM WHAT IS BEING CALLED
 A PRE-WIRED GENERATOR TAP BOX.
 AS SHOWN THERE IS NOT EQUIPMENT GROUNDING CONDUCTOR FOR
 ANY METALLIC BONDING.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-10-28 Cont ID  
Sent By dpalmer Date 2008-10-28 Time 11:51 Rev Time 0.00
Received By dpalmer Date 2008-10-28 Time 11:51 Sent To  
Notes
2008-10-28 11:51:26 
 ** DENIED 4TH REVIEW**
  
 ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
 SCOPE OF WORK NOT COMPLETE. PLANS AND PERMIT PACKAGE
 NOT COMPLETE FOR MINIMUM CODE COMPLIANT REQUIRED.
 ** THE SAME PLANS ARE BEING RESUBMITTED WITHOUT ANY
 CORRECTIONS. THE LAST REVISED PLAN DATE IS FROM SEPT OF
 2006.
  
  
 1) NOTE: PLEASE CLEARLY LABEL AND IDENTIFY ALL
 CLASS/DIVISION LOCATIONS PER NEC 514, NFPA-30.
 PLEASE PROVIDE LAYOUT FOR DISTANCES OF DISCONNECTING
 MEANS FOR PUMPS ETC.
 THIS WAS NOTED ON PREVIOUS REVIEWS.
  
 2) NOTE: PLANS REFLECT THE 2002 NFPA-70 WHICH IS NO
 LONGER ADOPTED. PLEASE SEE THE 2004 FBC WITH THE
 2006/2007 REVISIONS WHICH ADOPTED THE 2005 NFPA-70
  
 3) NOTE: PLEASE SEE SEALS NEED TO BE CLEAR AND VISIBLE
 WITH ALL INFORMATION ON SAID SEALS.
 FAC 61G15-23.002, FS 471.025
 THE NEW SEALS ON PLANS ARE VERY FAINT.
  
 4) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NO LONGER VALID BASED ON THE LATEST ADOPTED
 VERSION. AS THE PERMIT APPLICATION WAS NOT MADE UNTIL
 RECENTLY THE DATE OF APPLICATION STATES THE CODE AND
 DESIGN.
 PLEASE SEE 13-400.3.A, .3.B, .3.C AS THE ADOPTED
 VERSIONS SHALL BE 2.5.
 PLEASE BE SURE ALL COMPONENTS ON PLANS ARE ACCURATE IN
 THE INPUT DATA REPORT.
 THE LIGHTING ETC DOES NOT CORRELATE.
 PLEASE SEE THE SUBMITTED VERSION IS METHOD *A*. PLEASE
 SEE 13-101.1.3 FOR REQUIRED METHOD FOR RENOVATED
 BUILDINGS..
 PLEASE BE SURE TO SEE 13-415.2.ABC.1.1,.1.2 AND .1.3
 FOR LIGHTING PERFORMANCE.
  
 5) NOTE: THIS IS THE FORTH TIME THE RISER IS STILL
 SHOWING *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE
 FIRST MEANS IF DISCONNECT WHICH IS NOT PERMITTED.
 250.6,250.24 ETC
  
 6) NOTE: PLEASE SHOW A DETAIL FOR THE DISCONNECTING
 MEANS. A MUSHROOM BUTTON IS SHOWN, HOWEVER NO
 INFORMATION/DETAIL IS SHOWN ON HOW THIS WILL BE TIED
 INTO THE BRANCH CIRCUITS REQUIRED TO BE SHUT DOWN.
 514.11
 PLEASE SEE 514 IN HAND BOOK AS EXAMPLES ARE SHOWN.
  
 7) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS
 HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY
 1ST, 2006. PLEASE SEE FS 252 ETC, WHICH NOW REQUIRES
 ALL FUEL STATIONS UPON BEING NEW OR SUBSTANTIAL
 REMODEL, ETC INSTALL PROVISIONS FOR A COMPLETE
 EMERGENCY BACK UP GENERATOR SYSTEM. THIS WILL
 SUBSTANTIALLY CHANGE THE PLANS SUBMITTED.
 PLEASE SEE 701 AND 2002 NFPA-110
 PLEASE SUBMIT SITE PLANS, ALL REQUIRED LOCATIONS PER
 NEC 500. PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR ALL EQUIPMENT, ATS, MTS, GEN, FUEL PRIME
 MOVER ETC ETC.
 PLEASE KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3
 ETC
  
 8) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST ETC EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED. IN FACT THE PERMIT APPLICATION HAD AN APPLIED
 VALUE OF $400K AND WAS REDUCED TO $200K.
  
  
  
 ** AS THERE ARE SEVERAL ITEMS NOT YET SHOWN A COMPLETE
 REVIEW COULD NOT YET BE DONE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-02-11 Cont ID  
Sent By dpalmer Date 2007-02-11 Time 17:23 Rev Time 0.00
Received By dpalmer Date 2007-02-11 Time 16:40 Sent To  
Notes
2007-02-11 17:24:48** UNSAT 3ND REVIEW**
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS TWO REVIEWS ARE
 STILL IN NEED OF ADDRESSING ALONG WITH NEW INFORMATION
 FOR REVIEW OF GAS DISPENSING STATIONS, PLANS SUBMITTED
 AND THE FACT THAT PERMIT HAS NOT YET BEEN APPLIED FOR.
  
  
  
  
 1) NOTE: PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED
 FOR "PLAN REVIEW" ONLY ONCE AGAIN AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
 PLEASE KNOW THAT SINCE APPLICATION FOR PERMIT HAS NOT
 YET BEEN MADE AND THE STATE OF FLORIDA HAS ADOPTED NEW
 CODES SINCE THE LAST REVIEW, PLEASE SEE PLANS WILL NOW
 NEED TO BE REVISED TO INDICATE THE NEW CODES AND
 REVISED FOR ALL NEW DESIGNS UNDER THE NEW CODES. PLEASE
 SEE NOTES ON PREVIOUS REVIEWS WHICH MENTION THAT PLANS
 HAD NOT YET BEEN SUBMITTED FOR PERMIT. PLEASE THE STATE
 HAS NOW ADOPTED THE 2005 NFPA-70 AND THE 2006 REVISIONS
 TO THE 2004 FBC FOR ALL TRADES.
  
 2) NOTE: PLEASE SEE VALUATION FOR COMPLETE SCOPE OF
 SHALL BE ADJUSTED FOR ALL LABOR AND MATERIALS, EVEN IF
 ANY MATERIALS ARE OWNER SUPPLIED. FBC 108.3.
 VALUE CAN NOT BE VERIFIED UNTIL APPLICATION FOR PERMIT
 IS MADE.
  
 3) NOTE: THERE WAS NO RESPONSE TO THIS; THE G-1 PLAN(S)
 DO NOT SHOW ALL LOCATIONS.
 PLEASE CLEARLY LABEL AND IDENTIFY ALL CLASS/DIVISION
 LOCATIONS PER NEC 514, NFPA-30.
 PLEASE PROVIDE LAYOUT FOR DISTANCES OF DISCONNECTING
 MEANS FOR PUMPS ETC.
 THIS WAS NOTED ON PREVIOUS REVIEW.
  
 4) NOTE: PLEASE SHOW A DETAIL FOR THE DISCONNECTING
 MEANS. A MUSHROOM BUTTON IS SHOWN, HOWEVER NO
 INFORMATION/DETAIL IS SHOWN ON HOW THIS WILL BE TIED
 INTO THE BRANCH CIRCUITS REQUIRED TO BE SHUT DOWN.
 514.11
 PLEASE SEE 514 IN HAND BOOK AS EXAMPLES ARE SHOWN.
  
 5) NOTE: PLEASE SEE THIS COMMENT HAS BEEN MADE ON ALL
 THREE REVIEWS AND NO CHANGE HAS BEEN MADE TO RISER
 PERTAINING TO THIS????
 PLEASE SEE AN "EQUIPMENT GROUNDING CONDUCTOR" IS BEING
 SHOWN BEFORE THE FIRST MEANS OF DISCONNECT FOR THE
 SERVICE. PLEASE SEE 250.6, 250.24B, AS THIS IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF DISCONNECT.
  
  
  
  
 6) NOTE: PLEASE SEE THE OLD NON-VALID SEAL IS STILL
 BEING USED ON SOME SHEETS WHICH ARE STILL IN SETS.
 PLEASE SEE SOME OF THE OLD SHEETS WERE LEFT IN SETS
 WITH OUT INSERTING NEW SHEETS FOR THESE.
 PLEASE SEE NOTE AS STATED IN PREVIOUS REVIEW.
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
 * PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.001.
 MUST CONTAIN THE WORDING "LICENSE" AND MAY NO LONGER
 CONTAIN THE WORDING "CERTIFICATE".
 PLEASE ALSO KNOW, THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 7) NOTE: PLEASE SEE FLORIDA STATUE 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE
 KNOW, ONE COPY OF PLANS SUBMITTED IS BEING RETAINED.
 THE 4X FEE HAS NOT BEEN ASSESSED AS LEGAL PERMIT
 APPLICATION HAS NOT BEEN MADE.
  
 8) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS
 HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY
 1ST, 2006. PLEASE SEE FS 252 ETC, WHICH NOW REQUIRES
 ALL FUEL STATIONS UPON BEING NEW OR SUBSTANTIAL
 REMODEL, ETC INSTALL A COMPLETE EMERGENCY BACK UP
 GENERATOR SYSTEM. THIS WILL SUBSTANTIALLY CHANGE THE
 PLANS SUBMITTED.
 PLEASE INDICATE HOW THE GENERATOR WILL BE CONNECTED
 INTO THE BUILDINGS MAIN ELECTRICAL SERVICE.
 PLEASE SEE 701 AND 2002 NFPA-110
 PLEASE SUBMIT SITE PLANS, ALL REQUIRED LOCATIONS PER
 NEC 500. PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR ALL EQUIPMENT, ATS, MTS, GEN, FUEL PRIME
 MOVER ETC ETC.
 PLEASE KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3
 ETC
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-12 Cont ID  
Sent By dpalmer Date 2006-10-12 Time 12:21 Rev Time 0.00
Received By dpalmer Date 2006-10-12 Time 11:57 Sent To  
Notes
2006-10-12 14:06:09******* UNSAT 2ND REVIEW********
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLYONCE AGAIN
 AND HAVE NOT BEEN SUBMITTED FOR PERMIT.
  
 ** PLEASE SEE VALUATION FOR COMPLETE
 SCOPE OF SHALL BE ADJUSTED FOR ALL LABOR
 AND MATERIALS, EVEN IF ANY MATERIALS ARE
 OWNER SUPPLIED. FBC 108.3.
 VALUE SHOWN SEEMS LOW FOR SCOPE OF WORK
 SHOWN ON PLANS.
 PLEASE ADJUST.
  
 *** PLEASE SEE MANY OF THE SAME COMMENTS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS ADDED TO THE BOTTOM OF REVIEW.
  
 1) NOTE: NO, SAME COMMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ALL CURRENT CODES
 ADOPTED BY THE STATE SHALL BE REFERENCE
 ON PLANS. 2002, NFPA-70, 2004 FBC ETC.
 PLEASE ALSO SEE ALL CURRENT CODES.
 PLEASE ALSO SEE PLANS INDICATE "PALM
 BEACH COUNTY BUILDING DEPARTMENT".
 PLEASE KNOW, THIS SCOPE OF WORK IS DONE
 IN THE "CITY OF WEST PALM BEACH".
  
 2) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLEARLY LABEL AND
 IDENTIFY ALL CLASS/DIVISION LOCATIONS
 PER NEC 514, NFPA-30.
 PLEASE PROVIDE LAYOUT FOR DISTANES OF DISCONNECTING
 MEANS FOR PUMPS ETC.
  
 3) NOTE:NO, SAME NOTE .
  
 ** PREVIOUSREVIEW NOTE **
 PLEASE SHOW A DETAIL FOR THE DISCONNECTING MEANS. A
 MUSHROOM BUTTON
 IS SHOWN, HOWEVER NO INFORMATION/DETAIL
 IS SHOWN ON HOW THIS WILL BE TIED INTO
 THE BRANCH CIRCUITS REQUIRED TO BE SHUT
 DOWN.
 514.11
 PLEASE SEE 514 IN HAND BOOK AS EXAMPLES
 ARE SHOWN.
  
 4) NOTE: OK.
  
 5) NOTE: NO, PLEASE STILL SEE PANEL "C".
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRLEATE PANEL SIZES,
 CIRCUITING ETC.
 24 CIR 225A ?? PLEASE VERIFY AS 225A
 PANELS ARE NOT COMMON FOR 24 CIRCUITS?
 PLEASE SEE PANELS SHOWN AS 30 CIRCUIT,
 YET RISER SHOWS THESE AS 42 CIRCUIT?
  
 6) NOTE: NO, PLEASE SEE THIS POSSIBLE MISPRINT, BELOW
 PANEL "A", AS "FEEDER, 2001"?
  
 ** PREIVOUS REVIEW NOTE **
 PLEASE SEE PANEL "A" SHOWN AS
 200I)??
 PLEASE CLARIFY THIS.
 215.5
  
 7) NOTE: OK.
  
 8) NOTE: NO, SAME NOTE, STILL BEING SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE AN "EQUIPMENT
 GROUNDING CONDUCTOR" IS BEING SHOWN
 BEFORE THE FIRST MEANS OF DISCONNECT FOR
 THE SERVICE. PLEASE SEE 250.6, 250.24B,
 AS THIS IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 9) NOTE: NO, SAME NOTE. PLANS MENTIONS CONTRACTOR TO
 VERIFY, HOWEVER THIS IS THE RESPONSIBILITY OF THE
 DESIGNER OF RECORD AND IS REQUIRED ON PLANS AT THIS
 TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE SIZE OF THE
 EXISITNG OR NEW SEC'S ON RISER.
 215.5
 CAN NOT VERIFY AT THIS TIME.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE:NO, SAME NOTE. PLEASE ALSO SEE NEW NOTES FOR
 SEAL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS PER FAC
 61G15-23.002, FS 471.023.
 MISSING CERTIFICATE OF AUTHORIZATION #.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
  
  
 ****** NEW NOTES *****
  
 15) NOTE: PLEASE SEE SEAL BEING USED ON ALL SHEETS FOR
 NEW PLANS SUBMITTED IS NO LONGER VALID WITH TEH STATE
 OF FLORIDA PER FLORIDA ADMINSITRATIVE CODE
 61G15-23.001.
 PLEASE KNOW, THIS WAS NOT A COMMENT ON PREVIOUS REVIEW
 AS SHEETS ARE BEING SEALED WITH A COMPLETELY DIFFERENT
 SEAL.
 MUST CONTAIN THE WORDING "LICENSE" AND MAY NO LONGER
 CONTAIN THE OWRDING "CERTIFICATE".
 PLEASE ALSO KNOW, THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 16) NOTE:PLEASE SEE FLORIDA STATUE 553.80(2)(B) WITH
 RESPECT TO REPEAT COPMMENTS FOR CODE COMPLIANCE. PLEASE
 KNOW, ONE COPY OF PLANS SUBMITTED ARE BEING RETAINED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-16 Cont ID  
Sent By dpalmer Date 2006-05-16 Time 20:14 Rev Time 0.00
Received By dpalmer Date 2006-05-16 Time 19:39 Sent To  
Notes
2006-05-16 00:00:00******* UNSAT ********
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT.
  
 ** PLEASE SEE VALUATION FOR COMPLETE
 SCOPE OF SHALL BE ADJUSTED FOR ALL LABOR
 AND MATERIALS, EVEN IF ANY MATERIALS ARE
 OWNER SUPPLIED. FBC 108.3.
 VALUE SHOWN SEEMS LOW FOR SCOPE OF WORK
 SHOWN ON PLANS.
 PLEASE ADJUST.
  
 1) NOTE: PLEASE SEE ALL CURRENT CODES
 ADOPTED BY THE STATE SHALL BE REFERENCE
 ON PLANS. 2002, NFPA-70, 2004 FBC ETC.
 PLEASE ALSO SEE ALL CURRENT CODES.
 PLEASE ALSO SEE PLANS INDICATE "PALM
 BEACH COUNTY BUILDING DEPARTMENT".
 PLEASE KNOW, THIS SCOPE OF WORK IS DONE
 IN THE "CITY OF WEST PALM BEACH".
  
 2) NOTE: PLEASE CLEARLY LABEL AND
 IDENTIFY ALL CLASS/DIVISION LOCATIONS
 PER NEC 514, NFPA-30.
 PLEASE PROVIDE LAYOUT FOR DISTANES OF DISCONNECTING
 MEANS FOR PUMPS ETC.
  
 3) NOTE: PLEASE SHOW A DETAIL FOR THE DISCONNECTING
 MEANS. A MUSHROOM BUTTON
 IS SHOWN, HOWEVER NO INFORMATION/DETAIL
 IS SHOWN ON HOW THIS WILL BE TIED INTO
 THE BRANCH CIRCUITS REQUIRED TO BE SHUT
 DOWN.
 514.11
 PLEASE SEE 514 IN HAND BOOK AS EXAMPLES
 ARE SHOWN.
  
 4) NOTE: PLEASE CORRELATE SERVICES,
 PANELS ON RISER DIAGRAM.
 PLEASE SEE SERVICE IS SHOWN W/ 1-PHASE DISCONNECTS, YET
 PANEL SHOWN AS 3-PHASE?
 PLEASE SEE FEEDERS SHOWN AS 1-PHASE AND
 3-PHASE ON THE LINE SIDE OF SERVICE
 MAINS??
 215.5
  
 5) NOTE: PLEASE CORRLEATE PANEL SIZES,
 CIRCUITING ETC.
 24 CIR 225A ?? PLEASE VERIFY AS 225A
 PANELS ARE NOT COMMON FOR 24 CIRCUITS?
 PLEASE SEE PANELS SHOWN AS 30 CIRCUIT,
 YET RISER SHOWS THESE AS 42 CIRCUIT?
  
 6) NOTE: PLEASE SEE PANEL "A" SHOWN AS
 200I)??
 PLEASE CLARIFY THIS.
 215.5
  
 7) NOTE: PLEASE SEE RISER SHOWS THE GEC
 GOING TO THE FOUNDATION STEEL. PLEASE
 KNOW, THIS IS PERMITTED, HOWEVER NOT
 REQUIRED ON AN EXISTING BUILDING.
 PLEASE KNOW, THE STRUCTURAL INTEGRITY OF
 THIS FOOTER MAY BE AFFECT DUE TO THE AGE
 OF THE EXISTING BUILDING.
 250.50 THIS MAY BE DONE, AS IF THIS IS
 SHOWN ON PLANS, THEN THIS ATTACHMENT
 WILL BE REQUIRED.
  
 8) NOTE: PLEASE SEE AN "EQUIPMENT
 GROUNDING CONDUCTOR" IS BEING SHOWN
 BEFORE THE FIRST MEANS OF DISCONNECT FOR
 THE SERVICE. PLEASE SEE 250.6, 250.24B,
 AS THIS IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 9) NOTE: PLEASE INDICATE THE SIZE OF THE
 EXISITNG OR NEW SEC'S ON RISER.
 215.5
 CAN NOT VERIFY AT THIS TIME.
  
 10) NOTE: PLEASE SEE SOME PANELS ARE
 SHOWN AS 120/240V AND OTHERS AS
 120/208V?
 PLEASE CORRELATE AND ADJUST ALL LOAD
 CALCS.
 215.5
  
 11) NOTE: PLEASE SEE CALCS ARE SHOWN FOR
 3-PHASE, HOWEVER THIS IS NOT CLEAR AS
 SERVICE IS ALSO SHOWN AS 1-PHASE??
  
 12) NOTE: PLEASE SEE 210.8B3 IN KITCHEN
 AREAS IN OTHER THAN DWELLING UNITS.
  
 13) NOTE: PLEASE SEE ANY OUTSIDE RECEPTS
 FO ICE ETC SHALL BE GFI. ONLY NOTED.
  
 14) NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS PER FAC
 61G15-23.002, FS 471.023.
 MISSING CERTIFICATE OF AUTHORIZATION #.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 ** PLEASE KNOW, AS PLANS ARE NOT
 COMPLETE AT THIS TIME, A FULL REVIEW FOR
 CODE COMPLIANCE CAN NOT BE DONE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-01-07 Cont ID  
Sent By efabian Date 2009-01-07 Time   Rev Time 1.00
Received By efabian Date 2009-01-07 Time   Sent To  
Notes
2009-01-07 11:52:02NO COMMENTS

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2009-05-20 Cont ID  
Sent By mawillia Date 2009-05-20 Time 15:50 Rev Time 0.00
Received By mawillia Date 2009-05-20 Time 15:22 Sent To B
Notes
2009-05-20 15:40:29*****REVISIONS, DATED 5/09/2009, APPROVED*****
  
 REVISED PLAN SHEETS (OF 5) A-1A, AND A-3 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2009-02-13 Cont ID  
Sent By mwennerg Date 2009-02-13 Time 13:30 Rev Time 0.00
Received By mwennerg Date 2009-02-13 Time 13:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-12-26 Cont ID  
Sent By mwennerg Date 2008-12-26 Time 14:22 Rev Time 0.00
Received By mwennerg Date 2008-12-26 Time 14:22 Sent To  
Notes
2008-12-26 14:22:55PLANS WILL BE STAMPED WHEN ALL REVIEW COMMENTS HAVE
 BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-10-30 Cont ID  
Sent By mwennerg Date 2008-10-30 Time 09:33 Rev Time 0.00
Received By mwennerg Date 2008-10-30 Time 09:33 Sent To  
Notes
2008-10-30 09:43:35PLANS WILL BE STAMPED WHEN ALL REVIEW COMMENTS HAVE
 BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-27 Cont ID  
Sent By mawillia Date 2007-02-27 Time 16:50 Rev Time 0.00
Received By mawillia Date 2007-02-27 Time 16:50 Sent To  
Notes
2007-02-27 16:52:16*****PROVISO*****
  
  
 PLANS TO BE STAMPED WHEN ALL OTHER REVIEWS HAVE BEEN
 SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-11-01 Cont ID  
Sent By mwennerg Date 2006-11-01 Time 13:15 Rev Time 0.00
Received By mwennerg Date 2006-11-01 Time 13:15 Sent To E
Notes
2006-11-01 13:17:46***PROVISO***
  
 FIRE REVIEW COMMENTS HAVE BEEN ADDRESSED. PLANS WILL BE
 STAMPED WHEN RETURNED FOR OTHER REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By mcarsill Date 2006-06-16 Time 09:33 Rev Time 0.00
Received By mcarsill Date 2006-06-16 Time 09:19 Sent To  
Notes
2006-06-16 00:00:001. THE PLANNED REMOVAL OF THE
 UNDERGROUND FUEL STORAGE TANKS (UST'S)
 SHALL BE DONE IN ACCORDANCE WITH NFPA
 30.
  
 2. NEW UNDERGROUND STORAGE TANK
 INSTALLATION TO COMPLY WITH NFPA 30.
  
 3. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 4. DEMOLITION DEBRIS SHALL BE REMOVED
 FROM THE SITE DAILY.
  
 5. INTERIOR FINISH ON WALLS AND CEILINGS
 SHALL BE CLASS A OR B.
  
 6. APPROPRIATE WARNING SIGNS SHALL BE
 PROVIDED ON THE FUEL DISPENSERS AND AT
 THE EMERGENCY STOP BUTTON USED TO SHUT
 DOWN FUEL PUMPS.
  
 7. BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF AT LEAST 6" HIGH
 NUMBERS ARE REQUIRED ON THE PROPER
 ELEVATION.
  
 8. FIRE EXTINGUISHERS THAT ARE
 IDENTIFIED ON PAGE A-1B IN THE NOTES
 SECTION SHALL BE PROPERLY SERVICE
 TAGGED.
  
 9. ALL FIRE AND LIFE SAFETY SYSTEMS
 SHALL BE INSPECTED, TESTED, AND APPROVED
 PRIOR TO USE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-11-10 Cont ID  
Sent By lmartine Date 2009-11-10 Time 13:33 Rev Time 0.00
Received By lmartine Date 2009-11-10 Time 13:33 Sent To  
Notes
2009-11-10 13:34:42*******************EXPEDITED *****************
 REVISION GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2009-11-04 Cont ID  
Sent By lmartine Date 2009-11-04 Time 17:00 Rev Time 0.00
Received By lmartine Date 2009-11-04 Time 17:00 Sent To  
Notes
2009-11-04 17:01:37*****************EXPEDITED*****************
 GAVE TO KENNY

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-10-28 Cont ID  
Sent By lmartine Date 2009-10-28 Time 14:00 Rev Time 0.00
Received By lmartine Date 2009-10-28 Time 14:00 Sent To  
Notes
2009-10-28 14:01:16************EXPEDITED************
 GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-10-22 Cont ID  
Sent By lmartine Date 2009-10-22 Time 16:09 Rev Time 0.00
Received By lmartine Date 2009-10-22 Time 16:09 Sent To  
Notes
2009-10-22 16:31:43***************EXPEDITED*****************
 GAVE TO SAMANTHA
 A/C ROOF STANDS, PER RON'S PROVISO

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-09-23 Cont ID  
Sent By lmartine Date 2009-09-23 Time 17:26 Rev Time 0.00
Received By lmartine Date 2009-09-23 Time 17:25 Sent To  
Notes
2009-09-23 17:27:23GAVE TO KEN S.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-09-01 Cont ID  
Sent By lmartine Date 2009-09-01 Time 17:49 Rev Time 0.00
Received By lmartine Date 2009-09-01 Time 17:49 Sent To  
Notes
2009-09-01 17:50:54GAVE TO KEN ************EXPEDITED******************

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-09-01 Cont ID  
Sent By lmartine Date 2009-09-01 Time 17:48 Rev Time 0.00
Received By lmartine Date 2009-05-13 Time 08:27 Sent To  
Notes
2009-05-13 08:28:32INCOMING TO COMMERCIAL: C-13

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-03-03 Cont ID  
Sent By shill Date 2009-03-03 Time 17:25 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2009-03-03 17:26:15BUILDING REVIEW COMPLETED; PLANS TO DVP DESK SMH

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-02-04 Cont ID  
Sent By adarroug Date 2009-02-04 Time 16:27 Rev Time 0.00
Received By adarroug Date 2009-02-04 Time 16:27 Sent To  
Notes
2009-02-04 16:29:50TO "COMM" BD#23

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-04 Cont ID  
Sent By adarroug Date 2008-12-04 Time 10:08 Rev Time 0.00
Received By adarroug Date 2008-12-04 Time 10:08 Sent To  
Notes
2008-12-04 10:09:13TO "COMM" BD#18

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-02 Cont ID  
Sent By adarroug Date 2008-10-02 Time 14:45 Rev Time 0.00
Received By adarroug Date 2008-10-02 Time 14:45 Sent To  
Notes
2009-01-07 11:20:01NO COMMENTS
2008-10-02 14:51:29TO "COMM" BD#64

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 16:54 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 16:54 Sent To  
Notes
2007-02-07 16:52:12TO "COMM" BD#9
2007-02-01 16:54:21WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-19 Cont ID  
Sent By adarroug Date 2006-09-19 Time 11:17 Rev Time 0.00
Received By adarroug Date 2006-09-19 Time 11:17 Sent To  
Notes
2006-10-03 00:00:00TO "COMM" BD#7
2006-09-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 11:11 Rev Time 0.00
Received By adarroug Date 2006-04-25 Time 08:22 Sent To  
Notes
2006-05-11 00:00:00TO "COMM" BD#16
2006-04-25 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2009-03-03 Cont ID  
Sent By rregueir Date 2009-03-03 Time 18:40 Rev Time 0.00
Received By rregueir Date 2009-03-03 Time 18:07 Sent To  
Notes
2009-03-03 18:40:11REVIEW #: 3RD (FOR PERMIT)
 ACTION: PASS W/ PROVISO
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 *******PROVISO*******
 PLEASE ADDRESS THE FOLLOWING PROIR TO INSTALLATION AND
 INSPECTION OF OUTDOOR MECHANICAL APPLIANCES:
 1. CONDENSER STANDS ARE DEFINED AS STRUCTURAL
 COMPONENTS PER FAC RULE 9B-72. PRODUCT APPROVAL IS
 REQUIRED. PROVIDE PRODUCT APPROVAL WITH APPROVING
 AGENCY COVER AND CORRESPONDING INSTALLATION
 INSTRUCTIONS.
 2. CONDENSERS ARE < 10' FROM THE ROOF EDGE. GUARDS ARE
 REQUIRED AT THIS LOCATION IN ACCORDANCE WITH FBCM
 304.10.
 3. PROVIDE SUBMITTAL DATA FROM OUTDOOR APPLIANCE
 MANUFACTURERS SHOWING THESE APPLIANCES ARE DESIGNED TO
 RESIST WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-12-20 Cont ID  
Sent By rregueir Date 2008-12-20 Time 11:44 Rev Time 0.00
Received By rregueir Date 2008-12-20 Time 11:24 Sent To  
Notes
2008-12-20 11:44:21REVIEW #: 2ND (FOR PERMIT)
 ACTION: PASS W/ PROVISO
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 *******PROVISO*******
 PLEASE ADDRESS THE FOLLOWING PROIR TO INSTALLATION AND
 INSPECTION OF OUTDOOR MECHANICAL APPLIANCES:
 1. CONDENSER STANDS ARE DEFINED AS STRUCTURAL
 COMPONENTS PER FAC RULE 9B-72. PRODUCT APPROVAL IS
 REQUIRED. PROVIDE PRODUCT APPROVAL WITH APPROVING
 AGENCY COVER AND CORRESPONDING INSTALLATION
 INSTRUCTIONS.
 2. CONDENSERS ARE < 10' FROM THE ROOF EDGE. GUARDS ARE
 REQUIRED AT THIS LOCATION IN ACCORDANCE WITH FBCM
 304.10.
 3. PROVIDE SUBMITTAL DATA FROM OUTDOOR APPLIANCE
 MANUFACTURERS SHOWING THESE APPLIANCES ARE DESIGNED TO
 RESIST WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-10-06 Cont ID  
Sent By hmoser Date 2008-10-06 Time 10:03 Rev Time 0.00
Received By hmoser Date 2008-10-06 Time 09:43 Sent To  
Notes
2008-10-06 10:02:5910/05/08
 REMOVE PAGES G-1,G-2 AND G-3 FROM PLANS ,REFER TO
 PERMIT # 08060526.
 PLEASE REFER TO SECTION 607.7 FLEXIBLE DUCTS AND
 CONNECTORS.2004 FBC(M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hmoser Date 2007-02-24 Time 08:21 Sent To  
Notes
2007-02-24 08:32:37PLAN DENIED
 1) ADDITIONAL MECHANICAL PERMITS ARE REQUIRED FOR TANK
 REMOVEL, FUEL, WALK IN COOLERS.
 2) PLEASE REFER TO SECTION 606 2004 FBC (M) SMOKE
 DETECTION SYSTEMS COMTROL . AND SECTION 606.4.1
 SUPERVISON
 3) PLEASE REFER TO NOTE # 1 ON ELECTRICAL REVIEW
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-21 Cont ID  
Sent By hmoser Date 2006-10-21 Time 13:41 Rev Time 0.00
Received By hmoser Date 2006-10-21 Time 13:41 Sent To  
Notes
2006-10-21 13:44:431) REGARDING NOTE # 1 FROM LAST REVIEW ,PLEASE SUBMIT
 PLANS WITH DERMS APPROVEL .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-09 Cont ID  
Sent By pkrauss Date 2006-06-09 Time 08:10 Rev Time 0.00
Received By pkrauss Date 2006-06-09 Time 07:36 Sent To  
Notes
2006-06-09 00:00:00DENIED:
  
 1.PLANS ARE TO BE SUBMITTED TO DERM
 FOR APPROVAL.PLANS MAY BE SUBMITTED AT
 3323 BELVEDERE RD. BUILDING #502 WEST
 PALM BEACH, FLORIDA. IF YOU NEED FURTHER
 INFORMATION FROM DERM, PLEASE CONTACT
 CHIP GREEN AT (561)233-2400.
  
 2.PLEASE SUBMIT PLANS WITH DERM'S
 APPROVAL.
  
 3.PLAN SHEET M2 THE EXHAUST FAN DETAIL
 INDICATES THE ROOF CURB AS BEING 6"
 ABOVE THE ROOF.PER 2004 FBC 1509.7,
 CURBS SHALL BE A MINIMUM OF 8" ABOVE THE
 ROOF SURFACE.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED IN ACCORDANCE WITH 2004 FMC
 606.2.1 & 606.2.2.
  
 5.ADDITIONAL PERMITS REQUIRED FOR FUEL
 & WALK-IN COOLERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  
  

Review Stop P PLUMBING
Rev No 8 Status P Date 2009-11-06 Cont ID  
Sent By kstevens Date 2009-11-06 Time 11:16 Rev Time 0.00
Received By kstevens Date 2009-11-06 Time 11:16 Sent To  
Notes
2009-11-06 11:18:52IRRIGATION PERMIT REQUIRED -- SEPARATE BACKFLOW PERMIT
 REQUIRED BY LICENSED PLUMBING CONTRACTOR -- 1" METER
 REQUIRED FOR ALL GPM OVER 15.

Review Stop P PLUMBING
Rev No 7 Status P Date 2009-09-29 Cont ID  
Sent By kstevens Date 2009-09-29 Time 17:53 Rev Time 0.00
Received By kstevens Date 2009-09-29 Time 17:53 Sent To B
Notes
2009-09-29 17:53:49REVISION OK -- SHT P-1.

Review Stop P PLUMBING
Rev No 6 Status F Date 2009-09-02 Cont ID  
Sent By kstevens Date 2009-09-02 Time 17:51 Rev Time 0.00
Received By kstevens Date 2009-09-02 Time 17:51 Sent To  
Notes
2009-09-02 17:59:28REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT P-1 SANITARY RISER DIAGRAM AND PLUMBING PLAN
 SHOW A DRY HORIZONTAL VENT UPSTREAM OF THE WATER
 CLOSETS. SECTION 905.3. EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. ONE W/C CAN CONNECT ON THE
 VERTICAL RISE OF THE VENT TO CORRECT THE CODE
 DEFICIENCY.
  
 2. SHT P-1 SANITARY RISER DIAGRAM AND PLUMBING PLAN. A
 CLEANOUT IS REQUIRED NEAR THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER PER SECTION 708.3.5. AN
 APPROVED TWO-WAY CLEANOUT SERVING BOTH THE SEWER AND
 THE BLDG DRAIN IS APPROVED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-12-18 Cont ID  
Sent By kstevens Date 2008-12-18 Time 12:42 Rev Time 0.00
Received By kstevens Date 2008-12-18 Time 12:42 Sent To  
Notes
2008-12-18 12:45:55 
  
  
  
 PASSED/PROVISO
  
 SHT P-1 REVISIONS REQUIRED SHOWING THE SANITARY PIPING
 TO THE FIXTURES IN THE TOILET ROOMS ON THE FLOOR PLAN
 AND FOR THE SANITARY RISER DIAGRAM TO REFLECT THESE
 REVISIONS. -- AIR CHAMBERS ARE NOT APPROVED AT THE
 WATER HEATER.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-10-22 Cont ID  
Sent By kstevens Date 2008-10-22 Time 07:15 Rev Time 0.00
Received By kstevens Date 2008-10-22 Time 07:15 Sent To  
Notes
2008-10-22 07:18:53 
  
 PASSED/PROVISO
 THERMAL EXPANSION CONTROL REQUIRED PER SECTION 607.3.2
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-02-26 Cont ID  
Sent By kstevens Date 2007-02-26 Time 09:08 Rev Time 0.00
Received By kstevens Date 2007-02-24 Time 18:15 Sent To  
Notes
2007-02-26 10:17:20DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB MUNICIPAL CODES
  
 PLAN REVIEW ONLY
  
 ...FROM PREVIOUS REVIEWS:
  
 1. DELETED
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 A. OK
 B. OK
 7. OK
 A. OK
 B. OK
 8. OK
  
 9. SHT P-1 SANITARY RISER DIAGRAM AND
 FLOOR PLAN, FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS. A
 FLOOR SINK OR HUB IS REQUIRED FOR
 INDIRECT WASTE. FLOOR SINKS SHALL BE
 LOCATED AS TO NOT BE A TRIPPING HAZARD
 AND SHALL BE LOCATED UNDER THE COUNTER
 SPACE OR EQUIPMENT. SECTION SECTIONS
 802.3 AND 802.3.2.
 ****RESPONSE NOTED, BUT THE CONDENSATE FROM THE COOLER
 IS STILL INDICATED AS DRAINING INTO A FLOOR SINK, AND
 SAFE WASTES ARE NOT APPROVED. EACH FLOOR SINK SHALL BE
 INDIVIDUALLY CONNECTED TO THE VENTED LINE AND HAVE ITS
 OWN TRAP. SECTIONS 901.2.1 AND 1002.1.
 ******RESPONSE NOTED, BUT INDICATE THE TYPE OF FIXTURE
 DRAINING INTO THE '2" IW W/AIR GAP'. THE DRAIN
 CONNECTING TO THE MOP SINK DRAIN AS SHOWN IS A SAFE
 WASTE AND IS NOT APPROVED. ALL INDICREC WASTE RECEPTORS
 SHALL BE SEPARATELY TRAPPED AND CONNECT TO THE VENTED
 STACK SEPARATELY AS INDICATED IN THE PREVIOUS REVIEW.
 NO DRAIN IS INDICATED FOR THE ICE MAKER. PLEASE
 INDICATE WHERE THIS WILL BE DRAINING TO. AN INDIRECT
 WASTE RECEPTOR WILL BE REQUIRED FOR THE ICE MAKER.
 SECTION 802.
  
 10. SHT P-1 WATER HEATER DETAIL: AIR
 CHAMBERS OK
 - THERMAL EXPANSION CONTROL IS
 REQUIRED AT THE WATER HEATER. PLEASE
 INDICATE METHOD. SECTION 607.3.2.
 ****NOT ADDRESSED
 ******RESPONSE NOTED, BUT THE P/T DISCHARGE VALVE IS
 NOT APPROVED FOR THERMAL EXPANSION CONTROL. PLEASE SEE
 SECTION 504.4.
  
 11. OK
 12. OK
  
 13. GREASE INTECEPTOR SHALL BE INSPECTED
 AND SIZED BY LYNN MASSON ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HER AT (TEL)
 (561) 822- 2271, (FAX) (561) 822-2279,
 OR E-MAIL [email protected]. MUNICIPAL
 CODE SECTION 3434.
 ****WAITING FOR A RESPONSE FROM LYNN. I WILL CONTACT
 HER.
 ******A NEW 750 GAL. INTERCEPTOR IS REQUIRED PER
 ENVIRONMENTAL COMPLIANCE. SEE ATTACHED SHEET. PLEASE
 INDICATE ON PLANS. A SEPARATE PERMIT IS REQUIRED FOR
 THE GREASE INTERCEPTOR.
  
 14. OK
  
 **************NEW COMMENT**************
  
 1B. OK (PLEASE REMOVE ALL VOIDED SHEETS FROM THE ONE
 SET OF PLANS).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SUBMIT ONE SET OF REPLACED SHEETS FOR COMPARISON
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-18 Cont ID  
Sent By kstevens Date 2006-10-18 Time 07:11 Rev Time 0.00
Received By kstevens Date 2006-10-17 Time 13:54 Sent To  
Notes
2006-10-18 07:43:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB MUNICIPAL CODES
  
 PLAN REVIEW ONLY
  
 ...FROM PREVIOUS REVIEW:
  
 1. SURVEY SHEET, PER SURVEYORS
 CERTIFICATION STATEMENT, "NOT VALID
 WITHOUT THE SIGNATURE AND THE ORIGINAL
 RAISED SEAL OF A LICENSED SURVEYOR AND
 MAPER. NO SIGNATURE OR SEAL ON PLANS.
 FAC 61G17-6.003(2)(C) & FS 472.025.
 ****NO RESPONSE, NOT ADDRESSED
  
 2. ALL ARCHITECTURAL & PM&E SHEETS.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. NO CERTIFICATE
 OF AUTHORIZATION SHOWN. FAC
 61G15-23.002(2) AND FS 471.025.
 ****NO RESPONSE, NOT ADDRESSED
  
 3. OK
 4. OK).
 5. OK
 6. SHT A-1B. HANDICAPPED RESTROOM NOTES:
 GRAB BARS OK
 TOILET PAPER DISPENSER OK
 ALSO SHOW THE FOLLOWING:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ****NOT ADDRESSED
 B. 11-4.16.5 FLUSH CONTROLS
 ****NOT ADDRESSED
  
 7. SHT A-1B. INTERIOR ELEVATIONS SHOW
 THE FOLLOWING FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
 ****NO RESPONSE, NOT ADDRESSED
  
 8. OK
  
 9. SHT P-1 SANITARY RISER DIAGRAM AND
 FLOOR PLAN, FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS. A
 FLOOR SINK OR HUB IS REQUIRED FOR
 INDIRECT WASTE. FLOOR SINKS SHALL BE
 LOCATED AS TO NOT BE A TRIPPING HAZARD
 AND SHALL BE LOCATED UNDER THE COUNTER
 SPACE OR EQUIPMENT. SECTION SECTIONS
 802.3 AND 802.3.2.
 ****RESPONSE NOTED, BUT THE CONDENSATE FROM THE COOLER
 IS STILL INDICATED AS DRAINING INTO A FLOOR SINK, AND
 SAFE WASTES ARE NOT APPROVED. EACH FLOOR SINK SHALL BE
 INDIVIDUALLY CONNECTED TO THE VENTED LINE AND HAVE ITS
 OWN TRAP. SECTIONS 901.2.1 AND 1002.1.
  
 10. SHT P-1 WATER HEATER DETAIL: AIR
 CHAMBERS OK
 - THERMAL EXPANSION CONTROL IS
 REQUIRED AT THE WATER HEATER. PLEASE
 INDICATE METHOD. SECTION 607.3.2.
 ****NOT ADDRESSED
  
 11. OK
 12. OK
  
 13. GREASE INTECEPTOR SHALL BE INSPECTED
 AND SIZED BY LYNN MASSON ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HER AT (TEL)
 (561) 822- 2271, (FAX) (561) 822-2279,
 OR E-MAIL [email protected]. MUNICIPAL
 CODE SECTION 3434.
 ****WAITING FOR A RESPONSE FROM LYNN. I WILL CONTACT
 HER.
  
 14. OK IF THERE IS AN EXISTING RPZV BACKFLOW.
  
 **************NEW COMMENT**************
  
 1B. ENGINEERS SEAL IS NOT APPROVED. SEE ATTACHED SHEET
 FROM THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SUBMIT ONE SET OF REPLACED SHEETS FOR COMPARISON
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By kstevens Date 2006-06-19 Time 18:16 Rev Time 0.00
Received By kstevens Date 2006-06-19 Time 18:16 Sent To  
Notes
2006-06-19 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB MUNICIPAL CODES
  
 1. SURVEY SHEET, PER SURVEYORS
 CERTIFICATION STATEMENT, "NOT VALID
 WITHOUT THE SIGNATURE AND THE ORIGINAL
 RAISED SEAL OF A LICENSED SURVEYOR AND
 MAPER. NO SIGNATURE OR SEAL ON PLANS.
 FAC 61G17-6.003(2)(C) & FS 472.025.
  
 2. ALL ARCHITECTURAL & PM&E SHEETS.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. NO CERTIFICATE
 OF AUTHORIZATION SHOWN. FAC
 61G15-23.002(2) AND FS 471.025.
  
 3. SHT A-1A. FLOOR PLAN, A DRINKING
 FOUNTAIN IS REQUIRED PER TABLE 403.1.
  
 4. SHT A-1A. SCOPE OF WORK, PLEASE
 INDICATE DESIGN BY FBC-2004, AND CITY
 WEST PALM BEACH UNDER SCOPE OF WORK.
 (NOT PALM BEACH COUNTY).
  
 5. SHT A-1A. UNDER SCOPE OF WORK -
 PROPOSED LINE 1) INDICATES (SEE SHEET
 A-1). SHT A-1 HAS NOT BEEN SUBMITTED.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 6. SHT A-1B. HANDICAPPED RESTROOM NOTES:
 GRAB BARS INDICATED AS 32-1/2 TO 33"
 AFF. SECTION 11-4.16.4 REQUIRES GRAB
 BARS TO BE 33" TO 36". (FIG 29). -
 TOILET PAPER DISPENSER IS INDICATED AS
 17" AFF. MINIMUM 19" PER 11-4.16.6. -
 ALSO SHOW THE FOLLOWING:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
  
 7. SHT A-1B. INTERIOR ELEVATIONS SHOW
 THE FOLLOWING FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
  
 8. SHT P-1 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. WATER HAMMER
 ARRESTORS ARE REQUIRED AT THE ICE MAKER
 AND SHALL BE LOCATED NEAR THE FIXTURE IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING.
 SECTION 604.9, PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
  
 9. SHT P-1 SANITARY RISER DIAGRAM AND
 FLOOR PLAN, FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS. A
 FLOOR SINK OR HUB IS REQUIRED FOR
 INDIRECT WASTE. FLOOR SINKS SHALL BE
 LOCATED AS TO NOT BE A TRIPPING HAZARD
 AND SHALL BE LOCATED UNDER THE COUNTER
 SPACE OR EQUIPMENT. SECTION SECTIONS
 802.3 AND 802.3.2.
  
 10. SHT P-1 WATER HEATER DETAIL: AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 DETAIL. - THERMAL EXPANSION CONTROL IS
 REQUIRED AT THE WATER HEATER. PLEASE
 INDICATE METHOD. SECTION 607.3.2.
  
 11. SHT P-1 HANDICAPPED RESTROOM NOTES:
 (SEE COMMENT NUMBER 6).
  
 12 SHT P-1 NOTES: FIXTURES TO COMPLY
 WITH CITY OF WEST PALM BEACH AND
 FBC-2004 CHAPTER 11 CODE NOT PALM BEACH
 COUNTY CODES.
  
 13. GREASE INTECEPTOR SHALL BE INSPECTED
 AND SIZED BY LYNN MASSON ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HER AT (TEL)
 (561) 822- 2271, (FAX) (561) 822-2279,
 OR E-MAIL [email protected]. MUNICIPAL
 CODE SECTION 3434.
  
 14. AN RPZV BACKFLOW PREVENTOR IS
 REQUIRED. SECTION 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 7 Status P Date 2009-03-04 Cont ID  
Sent By kdfreema Date 2009-03-04 Time 14:42 Rev Time 0.00
Received By kdfreema Date 2009-03-04 Time 14:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 6 Status F Date 2009-02-13 Cont ID  
Sent By kdfreema Date 2009-02-13 Time 10:10 Rev Time 0.00
Received By kdfreema Date 2009-02-13 Time 10:10 Sent To  
Notes
2009-02-13 10:13:20***FAILED***
  
 ZONING COMMENTS HAVE BEEN ADDRESSED, HOWEVER, IT
 APPEARS THAT THE PBC TRAFFIC CONCURRENCY HAS EXPIRED AS
 OF DEC 31, 2008. PLEASE PROVIDE AN UPDATED LETTER FROM
 PALM BEACH COUNTY TRAFFIC TO REPLACE THE EXPIRED
 LETTER.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 5 Status F Date 2008-12-04 Cont ID  
Sent By kdfreema Date 2008-12-04 Time 16:59 Rev Time 0.00
Received By kdfreema Date 2009-02-13 Time 10:09 Sent To  
Notes
2008-12-04 17:00:39***FAILED***
  
 LANDSCAPE PLANS SHALL BE PROVIDED WITH THE BUILDING
 PERMIT.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.
  
 POLICE COMMENTS BELOW:
  
 * REMOVE THE INTERIOR CASHIER ENCLOSURE DRYWALL AND
 REPLACE THE WALL WITH BULLET RESISTANT GLASS (ALL FOUR
 SIDES OF ENCLOSURE SHOULD BE BULLET RESISTANT GLASS)
  
 * DOOR ON THE SOUTH SIDE SHOWS SWING DOOR, BUT STATES
 SLIDE
  
 * NO LOCK ON THE VESTIBULE DOOR?
  
 * NO CANOPY LIGHTING SHOWN, NEED TO SEE THE PLAN
  
 * NO SECURITY CAMERA PLAN SHOWN, NEED TO SEE THE PLAN
  
 * CONVEX MIRRORS SHALL BE INSTALLED AND SIGNS AND
 SHELVES SHALL BE KEPT LOW, WHERE THEY DON?T OBSTRUCT
 EMPLOYEE VIEW.
  
 * DROP SAFE SHALL BE INSTALLED.
  
 * SILENT ALARMS TO NOTIFY POLICE IN THE EVENT OF A
 PROBLEM SHALL BE INSTALLED.
  
 * DOORS NOT IN USE SHALL BE KEPT LOCKED.
  
 * DOOR DETECTORS TO ALERT EMPLOYEES WHEN PERSONS ENTER
 THE STORE SHALL BE INSTALLED.
  
 * BATHROOMS SHOULD BE CONTROLLED BY KEY ACCESS.
  
 CONTACT KELLY CARSILLO AT 561-822-1620 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 4 Status F Date 2008-10-12 Cont ID  
Sent By bpowell Date 2008-10-12 Time 18:17 Rev Time 0.00
Received By bpowell Date 2008-10-12 Time 18:17 Sent To  
Notes
2008-10-12 18:24:151. THE CONDITIONS OF APPROVAL THAT WERE PLACED ON THIS
 PERMIT AT THE SEPTEMBER 4, 2008 ZONING BOARD OF APPEALS
 (ZBA) MEETING WERE NOT COMPLIED WITH.
 A) THE SITE PLAN SHALL PROVIDE ADEQUATE ROAD MARKINGS
 AND THE APPROPRIATE SIGNAGE INDICATING ONE-WAY TRAFFIC
 FLOW CLOCK-WISE ON THE SITE.
 B) THE DOORS ON THE EAST SHALL BE CONFIGURED TO ALLOW
 FOR A CLEAR PATH CONCURRENT WITH THE AMERICANS WITH
 DISABILITIES ACT (ADA) STANDARDS.
  
 IF YOU HAVE ANY QUESTIONS OR COMMENTS PLEASE CONTACT;
 BOBBY POWELL JR., [email protected], (561) 822-1401

Review Stop Z ZONING
Rev No 3 Status F Date 2007-02-08 Cont ID  
Sent By kdfreema Date 2007-02-08 Time 17:45 Rev Time 0.00
Received By kdfreema Date 2007-02-08 Time 17:44 Sent To  
Notes
2007-02-08 17:45:29**FAILED**
  
 EDGE OF FUEL STORAGE TANKS MUST BE
 LOCATED A MINIMUM OF 15 FEET FROM THE
 WEST PROPERTY LINE AND 5' FROM THE
 SOUTH, NORTH, AND EAST PROPERTY LINES.
  
 ZONING DEPARTMENT CANNOT APPROVE PLANS
 UNTIL A CLASS B SPECIAL USE PERMIT HAS
 BEEN ISSUED FOR THE EXPANSION OF THE
 C-STORE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER,
 WITH ANY QUESTIONS YOU MAY HAVE.
 (561)822-1435) OR [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2006-10-04 Cont ID  
Sent By kdfreema Date 2006-10-04 Time 08:52 Rev Time 0.00
Received By kdfreema Date 2006-10-04 Time 08:52 Sent To  
Notes
2006-10-04 00:00:00**FAILED**
  
 EDGE OF FUEL STORAGE TANKS MUST BE
 LOCATED A MINIMUM OF 15 FEET FROM THE
 WEST PROPERTY LINE AND 5' FROM THE
 SOUTH, NORTH, AND EAST PROPERTY LINES.
  
 ZONING DEPARTMENT CANNOT APPROVE PLANS
 UNTIL A CLASS B SPECIAL USE PERMIT HAS
 BEEN ISSUED FOR THE EXPANSION OF THE
 C-STORE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER,
 WITH ANY QUESTIONS YOU MAY HAVE.
 (561)822-1435) OR [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2009-02-09 Cont ID  
Sent By kdfreema Date 2006-07-27 Time 08:25 Rev Time 1.00
Received By kdfreema Date 2006-07-27 Time 08:25 Sent To  
Notes
2006-07-27 00:00:00ADDITION/EXPANSION OF ACCESSORY
 CONVENIENCE STORE REQUIRES AS CLASS B
 SPECIAL USE PERMIT.


Account Summary | Usage Policy | Privacy Policy