| Plan Review Stops For Permit 06040942 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-10-17 |
Time |
10:05 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2006-10-17 |
Time |
09:40 |
Sent To |
PC |
|
| Notes |
| 2006-10-17 09:49:04 | REVISION: ELIMINATE FUEL LINE TO POOL HEATER AND 2ND | | | WATER HEATER (180,000 BTU). CHANGE FUTURE GENERATOR TO | | | PERMANENT WITH GEN/RES PERMIT #06050007. | | | | | | | | | IF WATER HEATER ROOM IS A CONFINED | | | SPACE, OPENINGS REQUIRED PER SECTION | | | 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 2,500 CUBIC FEET REQUIRED. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2006-04-26 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-04-26 |
Time |
09:28 |
Rev Time |
1.00 |
| Received By |
mperson |
Date |
2006-04-26 |
Time |
09:28 |
Sent To |
PC |
|
| Notes |
| 2006-04-26 00:00:00 | | | | | | | ******PROVISO****** | | | FUTURE GENERATOR GAS PIPING AT OWN RISK, | | | SEPERATE GEN/RES PERMIT REQUIRED WITH | | | ZONING APPROVAL OF GENERATOR PLACEMENT. | | | NOTE: FUTURE GENERATOR AND POOL TO BE | | | HARD (PRESSURE) CAPPED FOR FINAL GAS | | | INSPECTION. | | | | | | IF 50,000 BTU WATER HEATER ROOM IS A | | | CONFINED SPACE, OPENINGS REQUIRED PER | | | SECTION 304.5 OR SECTION 304.6. SHALL BE | | | INSTALLED. | | | MINIMUM 2,500 CUBIC FEET REQUIRED. | | | | | | IF 180,000 BTU WATER HEATER ROOM IS A | | | CONFINED SPACE, OPENINGS REQUIRED PER | | | SECTION 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 9,000 CUBIC FEET REQUIRED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-04-26 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-04-26 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2006-04-24 |
Time |
15:13 |
Sent To |
PC |
|
| Notes |
| 2006-04-24 00:00:00 | TO "G" BOX |
|
|
|