Plan Review Details - Permit 06040933
Plan Review Stops For Permit 06040933
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By alange Date 2006-05-31 Time 16:06 Rev Time 0.75
Received By alange Date 2006-05-31 Time 16:03 Sent To  
Notes
2006-05-31 00:00:00DENIED
  
 1.SUBMIT A DETAILED SCOPE OF WORK THAT
 WILL BE COMPLETED UNDER THIS PERMIT.
  
 2.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 3.ALL PLANS SUBMITTED SHALL BE
 ORIGINAL SIGNED AND SEALED DOCUMENTS.
  
 4.ADDITIONAL COMMENTS MAY ARISE ONCE
 NEW SCOPE OF WORK IS SUBMITTED WITH NEW
 PLANS.
  
 5.PERMIT VALUATION SHOULD REFLECT COST
 OF WORK TO BE DONE UNDER THIS PERMIT.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By btrobaug Date 2006-05-12 Time 13:15 Rev Time 1.00
Received By btrobaug Date 2006-05-12 Time 12:16 Sent To P
Notes
2006-05-12 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE ARE TWO RISERS ON SHEET #5,
 REMOVE THE ONE NOT BEING USED.
  
 2} THE "SUB -PANEL" SHOWN ON BOTH RISERS
 MUST BE GROUNDED PER 250.32, AN DHAV EA
 DISCONNECTING MEANS PER 225.31.
  
 3} THERE IS A METER SHOWN ON THE POOL
 HOUSE, PLEASE VERIFY, ADD TO RISER.
  
 4} LOCATE THE SUB PANEL AT THE POOLHOUSE
 ON THE PLAN.
  
 5} THE "NEW BATH" SHOWN ON THE PLAN MUST
 COMPLY WITH 210.11(C)(3).
  
 6} PROVIDE A PANEL SCHEDULE FOR THE POOL
 SUB PANEL.
  
 7} SEE 106.1 FBC. THE PERSON TAKING
 RESPONSIBILITY FOR THE PLAN MUST PRINT
 AND SIGN NAME ON SAME.
  
 8} PLEASE SEE ARTICLE 108.3 FBC AS
 AMMENDED FOR VALUATION OF THE PROJECT,
 INCREASE VALUE AT THE FRONT COUNTER
 PRIOR TO RESUBMITTING.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 11:39 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 11:39 Sent To E
Notes
2006-05-11 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-31 Cont ID  
Sent By alange Date 2006-05-31 Time 16:07 Rev Time 0.00
Received By alange Date 2006-04-25 Time 09:52 Sent To  
Notes
2006-04-25 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-05-30 Cont ID  
Sent By tgordon Date 2006-05-30 Time 13:44 Rev Time 0.20
Received By tgordon Date 2006-05-30 Time 13:44 Sent To B
Notes
2006-05-30 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-26 Cont ID  
Sent By mperson Date 2006-05-26 Time 09:42 Rev Time 1.00
Received By mperson Date 2006-05-26 Time 09:42 Sent To M
Notes
2006-05-26 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW FOR A PERMIT:
  
 1. THE PRINTS SUBMITTED ARE COPIES WITH
 NO RAISED SEAL THE FOLLOWING IS REQUIRED
 BY STATE STATUTES.
 (A) 106.1 SUBMITTAL DOCUMENTS. IF THE
 DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER LEGALLY REGISTERED UNDER THE
 LAWS OF THIS STATE REGULATING THE
 PRACTICE OF ARCHITECTURE AS PROVIDED FOR
 IN CHAPTER 481, FLORIDA STATUTES, PART
 1, OR ENGINEERING AS PROVIDED FOR IN
 CHAPTER 471, FLORIDA STATUTES, THEN HE
 OR SHE SHALL AFFIX HIS OR HER SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA, AS
 REQUIRED BY FLORIDA STATUTES.
 2. THE SANITARY ISOMETRIC RISER DIAGRAM
 DOEN'T REFLECT THE FLOOR PLAN, FLOOR
 PLAN ON SHEET 1 INDICATES A SHOWER, AND
 THE RISER DIAGRAM ON SHEET 5 INDICATES A
 TUB PLEASE CORRELATE PER THE FOLLOWING
 (A) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL.
 3. ON SHEET 5 THE SANITARY RISER DIAGRAM
 INDICATES A 3" TRAP FOR THE W/C, THIS
 TRAP ISN'T REQUIRED BECAUSE THE W/C HAS
 AN INTREGRAL TRAP. PLEASE REMOVE 3" TRAP
 FOR RESUBMITTAL. ALSO ON SHEET 5 RUNNING
 TRAPS ARE INDICATED FOR THE LAV AND
 SHOWER RUNNING TRAPS ARE ILLEGAL PER
 SEC. 1002.3 PLEASE REMOVE RUNNING TRAPS
 FOR RESUBMITTAL.
 4. THE FOLLOWING IS REQUIRED FOR CLEAN-
 OUTS ON THE RISER DIAGRAM ON SHEET 5.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-10 Cont ID  
Sent By mmclean Date 2006-05-10 Time 12:35 Rev Time 0.00
Received By mmclean Date 2006-05-10 Time 12:35 Sent To I
Notes
2006-05-10 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE PROPOSED WITH
 SETBACK.
 (THE OLD PLANS ARE FILED IN RECORD
 RETENTIN AND CANNOT BE USED TO VERIFY
 THE OLD PERMIT 05010754)
 2. THE PROPOSED SHELLROCK DRIVEWAY IS
 NOT ALLOWED, MUST BE A SMOOTH
 NON-DUSTING SURFACE.
 3. THE SITEPLAN SUBMITTED DOES NOT
 PROVIDE THE SETBACK OF THE PROPOSED
 ADDITION AND DOES NOT SHOW THE WHOLE
 COMPLETE PROPERTY (DOUBLE FRONTAGE LOT).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720