Plan Review Details - Permit 06040879
Plan Review Stops For Permit 06040879
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-05 Cont ID  
Sent By shill Date 2006-10-05 Time 11:34 Rev Time 0.00
Received By shill Date 2006-10-05 Time 11:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By shill Date 2006-08-11 Time 11:36 Rev Time 0.00
Received By shill Date 2006-08-11 Time 11:36 Sent To  
Notes
2006-08-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS REVIEW:
  
 1.)DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS.
 FAC61G15-23.002.
  
 THE SEAL IS EXPIRED, SHOULD SAY
 "LICENSE" RATHER THAN "CERTIFICATE",
 FAC61G15-23.
  
 2.)CERTIFICATE OF AUTHORIZATION IS TO
 BE PRINTED ON THE PLAN, EACH SHEET,
 FAC61G15-23.002.
  
 3.)THE CALCULATIONS ARE TO HAVE A
 TITLE BLOCK ON EACH SHEET WITH ALL
 INFORMATION REQUIRED.EACH SHEET IS TO
 BE SIGNED, SEALED,AND DATED OR A COVER
 SHEET OR INDEX SHEET IS TO BE USED BUT
 MUST COMPLY WITH THE REQUIREMENTS OF
 FAC61G15-23.002.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-15 Cont ID  
Sent By shill Date 2006-05-15 Time 16:07 Rev Time 0.00
Received By shill Date 2006-05-15 Time 16:05 Sent To  
Notes
2006-05-15 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS.
 FAC61G15-23.002.
  
 2.)CERTIFICATE OF AUTHORIZATION IS TO
 BE PRINTED ON THE PLAN, EACH SHEET,
 FAC61G15-23.002.
  
 3.)THE CALCULATIONS ARE TO HAVE A
 TITLE BLOCK ON EACH SHEET WITH ALL
 INFORMATION REQUIRED.EACH SHEET IS TO
 BE SIGNED, SEALED,AND DATED OR A COVER
 SHEET OR INDEX SHEET IS TO BE USED BUT
 MUST COMPLY WITH THE REQUIREMENTS OF
 FAC61G15-23.002.
  
 4.)PROVIDE A SITE PLAN.NO
 INFORMATION WAS PROVIDED IN REGARDS TO
 WHERE THE GENERATOR WILL BE INSTALLED.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-27 Cont ID  
Sent By dpalmer Date 2006-09-27 Time 12:17 Rev Time 0.00
Received By dpalmer Date 2006-09-27 Time 12:17 Sent To  
Notes
2006-09-27 00:00:00PERMIT APPL BROUGHT IN, CHANGED TO "P".

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 10:12 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 09:48 Sent To  
Notes
2006-09-24 00:00:00**** IN TEMP FAILED STATUS,AS THE
 ORIGINAL PERMIT APPLICATIONWAS NOT
 SUBMITTED BACK WITH PACKAGE.
 ONLY THE GAS APPLICATIONWAS IN PACKAGE.
 CALLED POWERCOM AND LEFT MESSAGE.
 WILL CHANGE TO "P" ONCE ORIG APPL COMES
 IN.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-06 Cont ID  
Sent By dpalmer Date 2006-08-06 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 17:41 Sent To  
Notes
2006-08-06 00:00:00******* UNSAT 2ND REVIEW ******
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED AS THE
 SAME ELECTRICAL RISER DIAGRAM WAS
 SUBMITTED BACK FOR REVIEW.
 PLEASE ALSO NEW COMMENTS DUE TO
 PLANS/DESIGNS ETC SUBMITTED.
 PLEASE SEE COMMENT BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
 * NEW NOTE ARE ADDED AT BOTTOM.
  
 1)NOTE:OK, HOWEVER PLEASE SEE BLDG
 REVIEW COMMEWNTS ALSO AS THE SLAB DETAIL
 PAPERWORK NOW CONTAINS A SEL BY THE
 ENEGINEER WHICH IS NO LONGER VALID AND
 CAN NOT BE USED. PLEASE SEE RULING BY
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS IN FEB 04 WHICH RULE
 61G15-23.001 CHANGED AND ENGINEER'S MUST
 OBTIAN NEW SEALS BY DEC 31ST, 2005.
 PLEASE KNOW THE SEAL WITH THE WORDING OF
 "CERTIFICATE" IS NOT ACCEPTABLE AND MUST
 CONTAIN THE WORDING OF "LICENSE".
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE BLDG REVIEW COMMENTS
 AS DETAIL FOR SLAB.MUST CONTAIN A
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLAN.
  
 2)NOTE:NO, THIS WAS NOT DONE. THE SAME
 PLANS WERE SUBMITTED BACK.
 ** PLEASE KNOW GENERATOR IS BEING SHOWN
 UP AGAINST BUILDING. IT IS KNOWN TO THIS
 OFFICE THIS GENERATOR FROM GENERAC
 REQUIRES 5'FT MIN FROM ALL SURROUNDING
 BLDG/WALLS.
 110.3,90.8
 IF DISTANCE IS LESS, MUST CONTAIN
 SPECIFIC MIN CLEARENCES FROM
 MANUFACTURE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE AN OVERVIEW/LAYOUT OF ALL
 EQUIPMENT AND WHERE THIS IS LOCATED AT
 SITE. PLEASE KNOW THIS IS NEED FOR
 VERIFICATION FOR MEANS OF DISCONNECT.
 PLEASE ALSO SEE ZONING COMMENTS AS A
 SITE PLAN WAS NOT SUBMITTED INDICATIING
 ALL SETBACKS.
  
 3)NOTE: NO, SAME PLANS SUBMITTED BACK.
 NO DISOCNNECTING MEANS IS SHOWN FOR
 FEEDERS EITHER FROM GEN TO THE ATS
 GROUPED WITH EXISTING MAIN OR DISCONNECT
 ON THE LOAD SIDE OF THE ATS GROUPED WIHT
 EXISTING MAINS.
 PLEASE KNOW, IF THERE IS A SERVICE MAIN
 DISCONNETC ON THE LINE SIDE OF TEH ATS,
 THIS ATS IS NOT REQUIRED TO BE "SERVICE
 ENTRANCE" RATED, ONLY RATED AS "SERVICE
 EQUIPMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY IF THE EXISTING
 PANEL (#8) IS LOCATED WITH OTHER MAINS?
 PLEASE KNOW, A MEANS OF DISCONNECT WILL
 BE REQUIRED EITHER ON THE LINE SIDE OF
 ATS FROM GEN OR THE LOAD SIDE OF THE
 ATS. THIS DISCONNECT WILL NOT REQUIRED
 OCP, ONLY A DISCONNECTING MENS FOR THE
 LOAD SERVED.
 PLEASE ALSO KNOW, SPECS SUBMITTED
 INDICATE A SERVICE ENTRANCE RATED ATS???
 PLEASE KNOW, SINCE A MAIN IS SHOWN ON
 THE LINE SIDE OF ATS , A SE RATED ATS IS
 NOT REQUIRED. THIS ATS AS SHOWN ONLY
 DISCONNECTS THE FEED COMING FROM THE
 NORMAL POWER SIDE.
 PLEASE SEE 225.31-225.39.
  
  
 4)NOTE: OK, VALUE WAS INCREASED ON NEW
 CONTRACTORS APPLICATION, HOWEVER THE
 ADDITIONALS FEES WERE NOT PAID FOR WHEN
 PLANS WERE RESUBMITTED. OWES $425.65
 MUST BE PAID BEFORE PERMIT CAN BE
 ISSUED.
  
 ** PREVIOUS REVIEW NOTE ** PLEASE SEE
 VALUATION IS BASED ON
 COMPLETE SCOPE PF WORK WHICH IS TO
 INCLUDE ALL LABOUR AND MATERIALS, EVEN
 OF ANY EQUIPMENT IS OWNER SUPPLIED.
 VALUE AS SHOWN IS WAY LOW AND MAY BE
 ADJUSTED BY THIS OFFICE IF AN
 APPROPRIATE VALUE IS NOT INCREASED.
 THIS IS TO BE INCREASED WHEN
 RESUBMITTING PLANS AFTER ALL REVIEWS ARE
 COMPLETED.
 PLEASE SEE THE VALUE OF $2K MUST REFLECT
 ALL SCOPE. FBC 108.3
  
 5)NOTE: OK, HOWEVER PLEASE STATE
 OCCUPANCY
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE INTENDED LOADS
 FOR GENERATOR. GEN MUST BE SIZED FOR
 LOADS SERVED. PLEASE SEE LOAD SUMMARY
 PROVIDED THIS DOES NOT SEEM TO ADD UP?
 PLEASE VERIFY LOADS AS SHOWN FOR UNIT.
 PLEASE KNOW THE UNTI MUST BE SIZED FOR
 THE LOADS SERVED OR PLEASE DETAIL
 "AUTOMATIC LOAD SHEEDING METHOD BEING
 USED.
 220, 215.5, 702.5
  
  
 6) NOTE: NO, THIS IS REQUIRED FOR ALL
 SHEETS INCLUDING RISER DIAGRAM ETC WHICH
 IS TO B REVISED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT ALL PLANS AND
 SHEETS CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 SAID PLANS AND DRAWINGS.
 104.2.1, 106.1.2 FBC
  
 ** NEW NOTE **
  
 7) NOTE: PLEASE SEE FS 553.80(2)B) WITH
 REPSECT THE DESIGN PROFESSIONAL AND
 REPEAT CODE COMPLIANT COMMENTS.
 THIS IS ONLY BEING GIVEN AS A NOTE AT
 THIS TIME.
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-09 Cont ID  
Sent By dpalmer Date 2006-05-09 Time 18:04 Rev Time 0.00
Received By dpalmer Date 2006-05-09 Time 18:04 Sent To  
Notes
2006-05-09 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS DETAIL FOR SLAB.MUST CONTAIN A
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLAN.
  
 2)NOTE: PLEASE PROVIDE AN
 OVERVIEW/LAYOUT OF ALL EQUIPMENT AND
 WHERE THIS IS LOCATED AT SITE. PLEASE
 KNOW THIS IS NEED FOR VERIFICATION FOR
 MEANS OF DISCONNECT.
 PLEASE ALSO SEE ZONING COMMENTS AS A
 SITE PLAN WAS NOT SUBMITTED INDICATIING
 ALL SETBACKS.
  
 3)NOTE: PLEASE CLAROFY IF THE EXISTING
 PANEL (#8) IS LOCATED WITH OTHER MAINS?
 PLEASE KNOW, A MEANS OF DISCONNECT WILL
 BE REQUIRED EITHER ON THE LINE SIDE OF
 ATS FROM GEN OR THE LOAD SIDE OF THE
 ATS. THIS DISCONNECT WILL NOT REQUIRED
 OCP, ONLY A DISCONNECTING MENS FOR THE
 LOAD SERVED.
 PLEASE ALSO KNOW, SPECS SUBMITTED
 INDICATE A SERVICE ENTRANCE RATED ATS???
 PLEASE KNOW, SINCE A MAIN IS SHOWN ON
 THE LINE SIDE OF ATS , A SE RATED ATS IS
 NOT REQUIRED. THIS ATS AS SHOWN ONLY
 DISCONNECTS THE FEED COMING FROM THE
 NORMAL POWER SIDE.
 PLEASE SEE 225.31-225.39.
  
  
 4)NOTE: PLEASE SEE VALUATION IS BASED ON
 COMPLETE SCOPE PF WORK WHICH IS TO
 INCLUDE ALL LABOUR AND MATERIALS, EVEN
 OF ANY EQUIPMENT IS OWNER SUPPLIED.
 VALUE AS SHOWN IS WAY LOW AND MAY BE
 ADJUSTED BY THIS OFFICE IF AN
 APPROPRIATE VALUE IS NOT INCREASED.
 THIS IS TO BE INCREASED WHEN
 RESUBMITTING PLANS AFTER ALL REVIEWS ARE
 COMPLETED.
 PLEASE SEE THE VALUE OF $2K MUST REFLECT
 ALL SCOPE.
  
 5)NOTE: PLEASE SUBMIT THE INTENDED LOADS
 FOR GENERATOR. GEN MUST BE SIZED FOR
 LOADS SERVED. PLEASE SEE LOAD SUMMARY
 PROVIDED THIS DOES NOT SEEM TO ADD UP?
 PLEASE VERIFY LOADS AS SHOWN FOR UNIT.
 PLEASE KNOW THE UNTI MUST BE SIZED FOR
 THE LOADS SERVED OR PLEASE DETAIL
 "AUTOMATIC LOAD SHEEDING METHOD BEING
 USED.
 220, 215.5, 702.5
  
 ***
 6) NOTE: PLEASE SEE THAT ALL PLANS AND
 SHEETS CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 SAID PLANS AND DRAWINGS.
 104.2.1
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-17 Cont ID  
Sent By mwennerg Date 2006-10-17 Time 15:21 Rev Time 0.00
Received By mwennerg Date 2006-10-17 Time 15:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-09-05 Cont ID  
Sent By mwennerg Date 2006-09-05 Time 14:16 Rev Time 0.00
Received By mwennerg Date 2006-09-05 Time 14:16 Sent To  
Notes
2006-09-05 00:00:00***DENIED***
  
 IT APPEARS THAT THE FIRST FIRE REVIEW
 WAS NOT ADDRESSED OR ACKNOWLEDGED.
 PLEASE SEE SOME FOLLOWING NOTES TAKEN
 DIRECTLY FROM THE FIREST FIRE REVIEW:
  
 1) SITE PLAN IS DIFFICULT TO READ. SITE
 PLAN APPEARS TO BE OLD FIRE SPRINKLER
 INSTALLATION DRAWING THAT HAS BEEN
 COPIED.
  
 2) PLEASE INDICATE IF ANY EXIT DOORS OR
 WINDOWS ARE LOCATED NEAR THE PROPOSED
 GENERATOR LOCATION.
  
 3) OK
  
 4) PLEASE DEMONSTRATE COMPLIANCE WITH
 NFPA 37.
  
 5) A SURVEY APPEARS TO BE NECESSARY TO
 DETERMINE DISTANCES FROM PROPOSED
 EQUIPMENT.
  
 6) INFORMATION SUBMITTED FOR PERMIT
 PURPOSES SHALL BE CLEAR CONCISE AND
 LEGIBLE TO DETERMINE CODE COMPLIANCE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By mcarsill Date 2006-06-16 Time 09:45 Rev Time 0.00
Received By mcarsill Date 2006-06-16 Time 09:38 Sent To  
Notes
2006-06-16 00:00:001. SITE PLAN IS DIFFICULT TO READ. SITE
 PLAN APPEARS TO BE OLD FIRE SPRINKLER
 INSTALLATION DRAWING THAT HAS BEEN
 COPIED.
  
 2. PLEASE INDICATE IF ANY EXIT DOORS OR
 WINDOWS ARE LOCATED NEAR THE PROPOSED
 GENERATOR LOCATION.
  
 3. PLEASE SUBMIT PRODUCT APPROVALS FOR
 THE PROPOSED GENERATOR. COULD NOT LOCATE
 ANY WITHIN THE PERMIT PACKAGE.
  
 4. PLEASE DEMONSTRATE COMPLIANCE WITH
 NFPA 37.
  
 5. A SURVEY APPEARS TO BE NECESSARY TO
 DETERMINE DISTANCES FROM PROPOSED
 EQUIPMENT.
  
 6. INFORMATION SUBMITTED FOR PERMIT
 PURPOSES SHALL BE CLEAR CONCISE AND
 LEGIBLE TO DETERMINE CODE COMPLIANCE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-09-23 Cont ID  
Sent By pschmitz Date 2006-09-23 Time 14:18 Rev Time 0.00
Received By pschmitz Date 2006-09-23 Time 14:16 Sent To  
Notes
2006-09-23 00:00:00RE-SUB
  
 OK TP PRINT GAS PERMIT #06040881, WHEN
 MASTER #06040879 IS APPROVED.
 QUESTIONS 561-805-6692

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-08-12 Cont ID  
Sent By pschmitz Date 2006-08-12 Time 08:13 Rev Time 0.00
Received By pschmitz Date 2006-08-12 Time 08:13 Sent To  
Notes
2006-08-12 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 DENIED
 SEE COMMENTS FROM OTHER PLAN REVIEWERS.
 SEE ENGINEERING DATA FOR 100% LOAD, 560K
  
 OK TP PRINT GAS PERMIT #06040881, WHEN
 MASTER #06040879 IS APPROVED.
 QUESTIONS 561-805-6692

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-18 Cont ID  
Sent By pschmitz Date 2006-06-18 Time 13:27 Rev Time 0.00
Received By pschmitz Date 2006-06-18 Time 13:27 Sent To  
Notes
2006-06-18 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 DENIED
 SEE COMMENTS FROM OTHER PLAN REVIEWERS.
 SEE ENGINEERING DATA FOR 100% LOAD, 560K
  
 OK TP PRINT GAS PERMIT #06040881, WHEN
 MASTER #06040879 IS APPROVED.
 QUESTIONS 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 09:32 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 09:32 Sent To  
Notes
2006-09-20 00:00:00TO "COMM" BD#34
2006-09-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 14:10 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 14:10 Sent To  
Notes
2006-08-05 00:00:00TO COMM BOARD #19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-19 Cont ID  
Sent By adarroug Date 2006-07-19 Time 16:40 Rev Time 0.00
Received By adarroug Date 2006-07-19 Time 16:40 Sent To  
Notes
2006-07-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-19 Cont ID  
Sent By adarroug Date 2006-06-18 Time 16:40 Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 09:16 Sent To  
Notes
2006-05-08 00:00:00TO "COMM" BD#15
2006-04-24 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-08-21 Cont ID  
Sent By pkrauss Date 2006-08-21 Time 12:39 Rev Time 0.00
Received By pkrauss Date 2006-08-21 Time 12:39 Sent To  
Notes
2006-08-21 00:00:00NATURAL GAS GENERATOR - SEE COMMENTS BY
 PLUMBING PLANS EXAMINER, PAUL SCHMITZ.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-09 Cont ID  
Sent By pkrauss Date 2006-06-09 Time 07:19 Rev Time 0.00
Received By pkrauss Date 2006-06-09 Time 07:12 Sent To  
Notes
2006-06-09 00:00:00DENIED:
 ELECTRICAL PERMIT - 06040880
 GAS PERMIT 06040881
  
 PLEASE PROVIDE DISTANCE FROM THE
 PROPERTY LINES, FRESH AIR INTAKES,
 WINDOWS, DOORS, ETC.SHOW COMPLIANCE
 WITH THE ATTACHED.
  
 PER 2004 FMC 303.4 EQUIPMENT SHALL NOT
 BE INSTALLED IN A LOCATION WHERE SUBJECT
 TO DAMAGE UNLESS PROTECTED BY APPROVED
 BARRIERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-14 Cont ID  
Sent By mmclean Date 2006-08-14 Time 13:34 Rev Time 0.00
Received By mmclean Date 2006-08-14 Time 13:34 Sent To  
Notes
2006-08-14 00:00:00NOTE: GENERATOR SHALL HAVE A LANDSCAPE
 BUFFER FROM THE PUBLIC.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By mmclean Date 2006-06-13 Time 11:43 Rev Time 0.00
Received By mmclean Date 2006-06-13 Time 11:43 Sent To  
Notes
2006-06-13 00:00:00DENIED,
 1. MUST PROVIDE A CURRENT SURVEY OR
 SITEPLAN THAT SHOWS THE SETBACK OF THE
 EXISTING STRUCTURE FROM PROPERTY LINE
 2. MUST SHOWING THE EXISTING PARKING
 (AND PROVIDE THE APPROVED PARKING FOR
 THE STRUCTURE).
 3. MUST PROVIDE ON THE TWO COPY OF
 SURVEY OR SITEPLAN WITH THE SETBACK OF
 THE PROPOSED GENERATOR FROM STRUCTURE &
 FRONT PROPERTY LINE.
 4. NEED TO SHOW THE LOCATION OF THE
 ELECTRICAL EQUIPMENT.
 5. ALL EQUIPMENT MUST BE BUFFER FROM
 VIEW.
  
 NOTE:
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720