Plan Review Details - Permit 06040875
Plan Review Stops For Permit 06040875
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-22 Cont ID  
Sent By alange Date 2006-11-22 Time 08:54 Rev Time 0.00
Received By alange Date 2006-11-22 Time 08:53 Sent To  
Notes
2006-11-22 08:54:39KOHLER SPEC DOWN LOADED AND STAMPED.3FT. MIN
 SEPERATION REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-05-11 Cont ID  
Sent By alange Date 2006-05-11 Time 08:26 Rev Time 0.50
Received By alange Date 2006-05-11 Time 08:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-06 Cont ID  
Sent By btrobaug Date 2006-06-06 Time 07:48 Rev Time 0.50
Received By btrobaug Date 2006-06-02 Time 17:15 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-03 Cont ID  
Sent By btrobaug Date 2006-05-03 Time 07:20 Rev Time 0.50
Received By btrobaug Date 2006-05-03 Time 07:02 Sent To M
Notes
2006-05-03 00:00:00 
  
 THE GENERATOR OUTPUT IS NOT ADEQUATE FOR
 THE LOAD SERVED, 702.5. THE GENERATOR
 OUTPUT IS 112 AMPS PER SPEC, AND THE
 LOAD IN PANEL "A" CALCULATED @ 160 AMPS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-05-03 Cont ID  
Sent By mperson Date 2006-05-03 Time 15:13 Rev Time 0.15
Received By mperson Date 2006-05-03 Time 15:13 Sent To B
Notes
2006-05-03 00:00:00NOTE: GAS PERMIT REQUIRED. GAS
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APPLICATION. ALL GAS INSPECTIONS TO BE
 COMPLETE BEFORE FINAL GEN/RES
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 13:59 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 13:59 Sent To B
Notes
2006-11-17 13:59:54TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-30 Cont ID  
Sent By adarroug Date 2006-05-30 Time 11:39 Rev Time 0.00
Received By adarroug Date 2006-05-30 Time 11:39 Sent To E
Notes
2006-05-30 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-23 Cont ID  
Sent By adarroug Date 2006-05-23 Time 15:56 Rev Time 0.00
Received By adarroug Date 2006-05-23 Time 15:56 Sent To Z
Notes
2006-05-23 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 09:36 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 09:36 Sent To E
Notes
2006-05-02 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-11 Cont ID  
Sent By alange Date 2006-05-11 Time 08:27 Rev Time 0.00
Received By alange Date 2006-04-25 Time 13:45 Sent To  
Notes
2006-04-25 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-05-03 Cont ID  
Sent By tgordon Date 2006-05-03 Time 08:47 Rev Time 0.15
Received By tgordon Date 2006-05-03 Time 08:47 Sent To P
Notes
2006-05-03 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-05-03 Cont ID  
Sent By mperson Date 2006-05-03 Time 15:12 Rev Time 0.00
Received By mperson Date 2006-05-03 Time 15:12 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-30 Cont ID  
Sent By mmclean Date 2006-05-30 Time 08:31 Rev Time 0.00
Received By mmclean Date 2006-05-30 Time 08:31 Sent To I
Notes
2006-05-30 00:00:00NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO A SETBACK & CANNOT BE LOCATED IN
 THE 2.5FT UTILITY EASEMENT IN REAR OF
 PROPERTY.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-30 Cont ID  
Sent By mmclean Date 2006-04-30 Time 12:15 Rev Time 0.00
Received By mmclean Date 2006-04-30 Time 12:15 Sent To I
Notes
2006-04-30 00:00:00DENIED,
 1. NEED TO PROVIDE A COPY OF CURRENT
 SURVEY.
  
 NOTE: THE PROPOSED GENERATOR CAN ONLY
 ENCROACH 4FT INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720