Plan Review Details - Permit 06040857
| Plan Review Stops For Permit 06040857 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-05-11 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-05-11 |
Time |
08:04 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2006-05-11 |
Time |
08:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-05-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-05-04 |
Time |
17:47 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-05-04 |
Time |
17:46 |
Sent To |
M |
|
| Notes |
| 2006-05-04 00:00:00 | THE VALUE ON THE APPLICATION MUST | | | INCLUDE THE TOTAL COST OF LABOR AND | | | MATERIAL FOR THE GENERATOR , EQUIPMENT | | | (TRANSFER SWITCHES, PANELS ETC.)AND PAD | | | PER 108.3 FBC AS AMMENDED. | | | | | | PLEASE SUBMIT A SITE PLAN AND LOCATE ALL | | | THE SERVICE AND GENERATOR GEAR ON SAME | | | SO THAT COMPLIANCE WITH | | | 230.72(GROUPING), 225.31-39 FOR THE | | | DISCONNECTING MEANS REQUIREMENTS AND | | | 250.32 FOR GROUNDING CAN BE REVIEWED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2006-05-05 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-05-05 |
Time |
13:57 |
Rev Time |
0.15 |
| Received By |
mperson |
Date |
2006-05-05 |
Time |
13:56 |
Sent To |
B |
|
| Notes |
| 2006-05-05 00:00:00 | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | | BEFORE FINAL GEN/RES INSPECTION. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-05-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-02 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-02 |
Time |
09:28 |
Sent To |
E |
|
| Notes |
| 2006-05-02 00:00:00 | TO "GEN-RES" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-05-11 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-05-11 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-04-21 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2006-04-21 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-05-05 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-05-05 |
Time |
09:07 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2006-05-05 |
Time |
09:07 |
Sent To |
P |
|
| Notes |
| 2006-05-05 00:00:00 | *** DENIED *** | | | 1) PLEASE SEE ZONING NOTES. | | | | | | 2) PLEASE BE ADVISED,GENERATOR EXHUST | | | MUST BE TEN FEET AWAY FROM ANY BUILDING | | | OPENINGS (WINDOWS, DOORS, ROOF & EAVE | | | VENTS), AND TEN FEET AWAY FROM ADJECENT | | | BUILDING OPENS. PER 2004 FBC/M 401.5.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-05-05 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-05-05 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2006-05-05 |
Time |
13:56 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-04-29 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-04-29 |
Time |
14:05 |
Sent To |
I |
|
| Notes |
| 2006-04-29 00:00:00 | DENIED, | | | 1. THE GENERATOR IS SHOWN INSIDE THE THE | | | STRUCTURE (AS HIGHLIGHTED ON SURVEY) | | | 2. GENERATOR MUST BE LOCATED BEYOND THE | | | 25FT FRONT SETBACK. | | | 3. GENERATOR CAN ONLY ENCROACH 4FT INTO | | | A SETBACK. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
|