Plan Review Details - Permit 06040854
Plan Review Stops For Permit 06040854
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-05-11 Cont ID  
Sent By alange Date 2006-05-11 Time 08:03 Rev Time 0.50
Received By alange Date 2006-05-11 Time 08:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-05 Cont ID  
Sent By btrobaug Date 2006-05-05 Time 06:52 Rev Time 0.50
Received By btrobaug Date 2006-05-05 Time 06:51 Sent To M
Notes
2006-05-05 00:00:00 
  
  
 THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR , EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)AND PAD
 PER 108.3 FBC AS AMMENDED.
  
 PLEASE SUBMIT A SITE PLAN AND LOCATE ALL
 THE SERVICE AND GENERATOR GEAR ON SAME
 SO THAT COMPLIANCE WITH
 230.72(GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-05-05 Cont ID  
Sent By mperson Date 2006-05-05 Time 13:48 Rev Time 0.15
Received By mperson Date 2006-05-05 Time 13:48 Sent To B
Notes
2006-05-05 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 09:31 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 09:31 Sent To E
Notes
2006-05-02 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-11 Cont ID  
Sent By alange Date 2006-05-11 Time 08:03 Rev Time 0.00
Received By alange Date 2006-04-21 Time 16:00 Sent To  
Notes
2006-04-21 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-05-05 Cont ID  
Sent By tgordon Date 2006-05-05 Time 09:31 Rev Time 0.15
Received By tgordon Date 2006-05-05 Time 09:31 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-05-05 Cont ID  
Sent By mperson Date 2006-05-05 Time 13:48 Rev Time 0.00
Received By mperson Date 2006-05-05 Time 13:48 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-29 Cont ID  
Sent By mmclean Date 2006-04-29 Time 14:09 Rev Time 0.00
Received By mmclean Date 2006-04-29 Time 14:09 Sent To I
Notes
2006-04-29 00:00:00NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO A SETBACK.