| Plan Review Stops For Permit 06040841 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-05-04 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-05-04 |
Time |
14:11 |
Rev Time |
0.50 |
| Received By |
amorse |
Date |
2006-05-04 |
Time |
14:11 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-04-20 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-04-20 |
Time |
15:49 |
Rev Time |
0.50 |
| Received By |
amorse |
Date |
2006-04-20 |
Time |
15:49 |
Sent To |
PC |
|
| Notes |
| 2006-04-20 00:00:00 | | | | | | | DENIED | | | | | | 1) PRODUCT APPROVAL IS OUTDATED AND NOT | | | APPROVED UNDER THE 2004 CODE. PLEASE | | | SUBMIT MIAMI-DADE NOA 01-0919.11 FOR | | | 5V-CRIMP METAL ROOF PANELS AS IT HAS | | | ALREADY RECEIVED LOCAL PRODUCT APPROVAL. | | | | | | 2) THIS PRODUCT DOES NOT MEET THE DESIGN | | | PRESSURES FOR 140 MPH EXP. B AT | | | PERIMITER AND CORNERS. ENHACED FASTENING | | | IS REQUIRED AND MUST BE CALCULATED BY AN | | | ENGINEER, ARCHITECT OR ROOFING | | | CONSULTANT. (SEE PAGE 4 IN THIS NOA OR 5 | | | OF THE NEW NOA) | | | | | | 3) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | |
|
|
|