Plan Review Details - Permit 06040769
Plan Review Stops For Permit 06040769
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-08 Cont ID  
Sent By alange Date 2006-06-08 Time 08:23 Rev Time 0.50
Received By alange Date 2006-06-08 Time 08:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-09 Cont ID  
Sent By alange Date 2006-05-09 Time 10:27 Rev Time 0.50
Received By alange Date 2006-05-09 Time 10:27 Sent To  
Notes
2006-05-09 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-07 Cont ID  
Sent By btrobaug Date 2006-06-07 Time 15:11 Rev Time 0.50
Received By btrobaug Date 2006-06-07 Time 14:51 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-04 Cont ID  
Sent By btrobaug Date 2006-05-04 Time 17:27 Rev Time 0.33
Received By btrobaug Date 2006-05-04 Time 17:21 Sent To M
Notes
2006-05-04 00:00:00 
  
  
 PLEASE SUBMIT A SITE PLAN AND LOCATE ALL
 THE SERVICE AND GENERATOR GEAR ON SAME
 SO THAT COMPLIANCE WITH
 230.72(GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-05-05 Cont ID  
Sent By mperson Date 2006-05-05 Time 13:22 Rev Time 0.15
Received By mperson Date 2006-05-05 Time 13:22 Sent To B
Notes
2006-05-05 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-25 Cont ID  
Sent By adarroug Date 2006-05-25 Time 11:49 Rev Time 0.00
Received By adarroug Date 2006-05-25 Time 11:49 Sent To E
Notes
2006-05-25 00:00:00TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-25 Cont ID  
Sent By adarroug Date 2006-04-25 Time 11:05 Rev Time 0.00
Received By adarroug Date 2006-04-25 Time 11:05 Sent To E
Notes
2006-04-25 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-25 Cont ID  
Sent By alange Date 2006-05-09 Time 10:28 Rev Time 0.00
Received By adarroug Date 2006-04-20 Time 15:39 Sent To  
Notes
2006-04-20 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-05-05 Cont ID  
Sent By tgordon Date 2006-05-05 Time 09:34 Rev Time 0.15
Received By tgordon Date 2006-05-05 Time 09:34 Sent To P
Notes
2006-05-05 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-05-05 Cont ID  
Sent By mperson Date 2006-05-05 Time 13:21 Rev Time 0.00
Received By mperson Date 2006-05-05 Time 13:21 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-24 Cont ID  
Sent By mmclean Date 2006-04-24 Time 13:55 Rev Time 0.00
Received By mmclean Date 2006-04-24 Time 13:55 Sent To I
Notes
2006-04-24 00:00:00NOTE: THE PROPOSED GENERATOR CAN ONLY
 ENCROACH 4FT INTO A SETBACK.