Plan Review Details - Permit 06040695
Plan Review Stops For Permit 06040695
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-27 Cont ID  
Sent By alange Date 2006-06-27 Time 08:36 Rev Time 1.50
Received By alange Date 2006-06-27 Time 08:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-18 Cont ID  
Sent By alange Date 2006-05-18 Time 08:17 Rev Time 1.50
Received By alange Date 2006-05-18 Time 08:17 Sent To  
Notes
2006-05-18 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 5.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-27 Cont ID  
Sent By alange Date 2006-04-27 Time 08:18 Rev Time 2.50
Received By alange Date 2006-04-27 Time 08:17 Sent To  
Notes
2006-04-27 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $116,388.00.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 4.NOT ALL STATE PRODUCT APPROVALS
 SUBMITTTED ARE COMPLETE. SEVERAL HAVE
 ONLY ONE PAGE AND DO NOT SHOW MODEL OR
 APPROVED STATUS.
 ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 5.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 6.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 7.ENGINEER SEAL USED IS OLD, NEW SEAL
 SHOULD SHOW "LICENSED" 61G1-16.001
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 15:51 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 15:24 Sent To M
Notes
2006-05-14 00:00:00REDLINED PLANS.
  
 PLANS MENTIONS SLAB CONDUIT/ SEC'S PER
 "FBC"? THIS SHOULD BE NEC.230.70
  
 PLEASE SEE KITCHEN COUNTER SPACE STILL
 SEEMS TO BE MISSING GFI PER 210.52C1
  
 SD OUTSIDE MASTER BEDRM SAHLL BE
 PHOTO-ELECTRIC OR RESETTING TYOE PER
 NFPA-72 11.8.3.5 AS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-24 Cont ID  
Sent By dpalmer Date 2006-04-24 Time 07:22 Rev Time 0.00
Received By dpalmer Date 2006-04-24 Time 07:07 Sent To M
Notes
2006-04-24 00:00:00********** UNSAT ********
  
  
 1 )NOTE: PLEASE SEE PLANS MUST BE
 RE-SEALED AS THE SEAL AS SHOWN IS NO
 LONGER ACCEPTABLE AS PUBLIC RECORD FOR
 THE FLORIDA BOARD OF PROFESSINAL
 ENGINEER'S. PLEASE SEE FAC 61G15-23.001
 WHICH IN FEB 04 CHANGED TO NOW REQUIRE
 ALL SEALS TO CONTAIN THE WORDING OF
 "LICENSE" AND COULD NO LONGER USE
 "CERTIFICATE". PLEASE KNOW, AN EXTENSION
 WAS GRANTED TO THE DATE OF 12/31/05 TO
 GIVE ALL ENGINEERS 2 YRS TO OBTAIN NEW
 SEALS. WE CAN NO LONGER ACCEPT OLD
 SEALS.
 THIS IS REQUIRED OF ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWERS.
  
 2) NOTE: PLEASE LIST ALL THE REQUIRED
 ARC FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 2002 NEC.
 210.12, REQUIRES ARC FAULT FOR ALL
 OUTLETS IN BEDRMS. (RECEPTS, LTS, FANS,
 SD'S ECT).
  
 3) NOTE: PLEASE SEE MISSING GFI(S) ALONG
 KITCHEN COUNTER SPACE PER 210.52C1
  
 4) NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS FOR 2',6',12' RULE.
 PLEASE SEE REDLINED PLANS.
  
  
 5) NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTSWITH RESPECT TO VALUATION ON
 APPLIACTION. FBC ADMINISTRATIVE SECTION,
 108.3
  
 6) NOTE: PLEASE SEE MISSING SD OUTSIDE
 MAST BEDRM.
 NFPA-72 2002, 11.5.1.1, 11.8.3.5
  
 7) NOTE: PLEASE DETAIL SEC'S FROM METER
 TO MCB PANEL, PLEASE KNOW, THESE MUST BE
 IN SLAB OR A MAIN WITH OCP WILL BE
 REQUIRED OUTSIDE AS NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS ARE PERMITTED IN
 DWELLING. 230.70.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2006-06-16 Cont ID  
Sent By ssherman Date 2006-06-16 Time 13:42 Rev Time 0.00
Received By ssherman Date 2006-06-16 Time 13:42 Sent To  
Notes
2006-06-16 00:00:00HISTORIC APPROVAL PER J PAPA

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-04-18 Cont ID  
Sent By ptjomsto Date 2006-04-18 Time 13:40 Rev Time 0.00
Received By ptjomsto Date 2006-04-18 Time 13:40 Sent To  
Notes
2006-04-18 00:00:00HISTORIC APPROVED 4/18/06 WITH
 CONDITION/
 WINDOWS SHALL HAVE DIMENSIONAL EXTERIOR
 MUNTINS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 14:00 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 14:00 Sent To B
Notes
2006-06-20 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 14:49 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 14:49 Sent To E
Notes
2006-05-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-27 Cont ID  
Sent By alange Date 2006-04-27 Time 08:23 Rev Time 0.00
Received By alange Date 2006-04-20 Time 11:35 Sent To  
Notes
2006-04-20 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By tgordon Date 2006-05-15 Time 11:15 Rev Time 0.25
Received By tgordon Date 2006-05-15 Time 11:15 Sent To P
Notes
2006-05-15 00:00:00*** PROVISO ***
 1) CLOTHES DRYER VENT TERMINATION MUST
 BE A MIN. OF 4 FT. FROM A/C CONDENSER
 UNIT, PER 2004 FBC/M 501.2 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-26 Cont ID  
Sent By tgordon Date 2006-04-26 Time 14:34 Rev Time 0.30
Received By tgordon Date 2006-04-26 Time 14:34 Sent To B
Notes
2006-04-26 00:00:00*** DENIED ***
 1) PLANS WITH AN ENGINEER'S NAME IN THE
 TITLE BLOCK MUST HAVE HIS SEAL ON THEM,
 PER FAC 61G15-23.002 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By jleech Date 2006-05-15 Time 12:27 Rev Time 0.00
Received By jleech Date 2006-05-15 Time 12:27 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-24 Cont ID  
Sent By jleech Date 2006-04-24 Time 13:21 Rev Time 0.00
Received By jleech Date 2006-04-24 Time 13:21 Sent To M
Notes
2006-04-24 00:00:00DENIED;
 1. SEE ELECTRICAL PLAN REVIEW'S NOTE 1.
 2.SANITARY RISER DIAGRAM DOES NOT MATCH
 FLOOR PLAN. (ONE RISER DIAGRAM MARKED IN
 RED.
 3.THE AUTOMATIC CLOTHES WASHER BRANCH
 DRAIN IS REQUIRED TO BE 3" PER FBC-2004
 PLUMBING SEC. 406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-20 Cont ID  
Sent By mmclean Date 2006-04-20 Time 16:12 Rev Time 0.00
Received By mmclean Date 2006-04-20 Time 16:12 Sent To E
Notes
2006-04-20 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 WALL/FENCE/GATE WITH UTILITY EASMENT
 APPROVAL FROM THE CITY OF WEST PALM
 BEACH.