Plan Review Details - Permit 06040674
Plan Review Stops For Permit 06040674
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-03-23 Cont ID  
Sent By shill Date 2007-03-23 Time 18:13 Rev Time 0.00
Received By shill Date 2007-03-23 Time 18:12 Sent To  
Notes
2007-03-02 18:58:47NEW BLDG SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-15 Cont ID  
Sent By shill Date 2006-12-15 Time 14:57 Rev Time 0.00
Received By shill Date 2006-12-15 Time 14:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-11 Cont ID  
Sent By shill Date 2006-09-11 Time 10:54 Rev Time 0.00
Received By shill Date 2006-09-11 Time 10:54 Sent To  
Notes
2006-09-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 IS TO BE ON EACH SHEET
 (TITLE BLOCK FOR E. POULIN, PE).THE
 ADDRESS ON DBPR WEBSITE DOES NOT MATCH
 ANY OF THE ADDRESSES ON THE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-15 Cont ID  
Sent By shill Date 2006-05-15 Time 15:17 Rev Time 0.00
Received By shill Date 2006-05-15 Time 15:17 Sent To  
Notes
2006-05-15 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 2.)THE VALUE IS TOO LOW.PROVIDE A
 REASONABLE VALUE OR AN ESTIMATED VALUE
 WILL BE DONE FOR YOU USING MARSHALL &
 SWIFT.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 4.)NOTE FLOOD ZONE DESIGNATION ON THE
 PLAN.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-02 Cont ID  
Sent By dpalmer Date 2007-03-02 Time 18:57 Rev Time 0.00
Received By dpalmer Date 2007-03-02 Time 18:47 Sent To  
Notes
2007-03-02 18:58:13VOIDED OLD E-2 AS IT WAS REVISED.
 STAMPED NEW SHEETS FOR ELECTRICAL. NEEDS NEW STAMP
 FROM MECHANICAL

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-18 Cont ID  
Sent By dpalmer Date 2006-08-18 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2006-08-18 Time 20:06 Sent To  
Notes
2006-08-18 00:00:00STAMPED ELECTRICAL PLANS, GEN SPECS, WP
 HOUSING, AND ATS SPECS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-09 Cont ID  
Sent By dpalmer Date 2006-05-09 Time 17:53 Rev Time 0.00
Received By dpalmer Date 2006-05-09 Time 17:17 Sent To  
Notes
2006-05-09 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS DETAIL FOR SLAB. COULD NOT LOCATE ON
 PLANS.
  
 2)NOTE: PLEASE SEE CURRENT CODES NEED TO
 BE REFERENCED ON PLANS. PLEASE SEE THAT
 WE ARE CURRENLTY UNDER THE 2004 FBC,
 2003 NFPA-101, 2002 NFPA-110, 2002
 NFPA-70
  
 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 WITH RESPECT TO BFE IF IN A FLOOD ZONE.
 PLEASE SEE NFPA-110 7.2.3*
 PLEASE NOTE AND VERIFY THE LOCATION OF
 GENERATOR.
  
 4)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR GEN, ATS, SUB BASE
 FUEL TANK, WP HOUSING.
 PLEASE SEE THE SPECS SUBMITTED DO NOT
 CORRELATE WITH PLANS. ATS, GEN
 PLEASE ALSO "HIGHLIGHT" AND INDICATE
 UNITS BEING INSTALDLLED ON SPECS.
  
 5)NOTE: PLEASE SEE EXISTING MCB IS SHOWN
 ON ROOF???
 PLEASE VERIFY AS THIS IS NOT READILY
 ACCESSIBLE AS REQUIRED PER 230.70,PLEASE
 SEE MAINS ARE NOT GROUPED PER 230.72,
 225.34, 225.31-225.39
 PLEASE SHOW AND INDICATE THE LOCATION OF
 EXISTING SERVICE FOR BUILDING AND MAINS.
  
 6)NOTE: PLEASE SEE VALUATION IS BASED ON
 COMPLETE SCOPE PF WORK WHICH IS TO
 INCLUDE ALL LABOUR AND MATERIALS, EVEN
 OF ANY EQUIPMENT IS OWNER SUPPLIED.
 VALUE AS SHOWN IS WAY LOW AND MAY BE
 ADJUSTED BY THIS OFFICE IF AN
 APPROPRIATE VALUE IS NOT INCREASED.
 THIS IS TO BE INCREASED WHEN
 RESUBMITTING PLANS AFTER ALL REVIEWS ARE
 COMPLETED.
  
 7)NOTE: PLEASE SUBMIT THE INTENDED LOADS
 FOR GENERATOR. GEN MUST BE SIZED FOR
 LOADS SERVED. PLEASE SEE LOAD SUMMARY
 PROVIDED IS REQUIRED TO BE SIGNED, DATED
 AND SEAL BY SIAD ENGINEER OF RECORD.
 220, 215.5
  
 ***
 8) NOTE: PLEASE SEE PLANS CONTAIN A
 "RAISED SEAL" ON PLANS WHICH CONTAIN A
 "PHOTO-COPIED" SIGNATURE. PLEASE SEE
 THISH HAS BEEN NOTED ON SOME OTHER
 PROJECTS AND PLANS ARE STILL BEING THE
 SAME WAY. PLEASE SEE FS 471.025 AND FAC
 61G15-23.002 WHICH REQUIRES THE
 "ORIGINAL" SIGNATURE. PLEASE KNOW, ONE
 COPY OF PLANS ARE BEING RETAINED BY THIS
 OFFICE.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-03-21 Cont ID  
Sent By mawillia Date 2007-03-21 Time 18:42 Rev Time 0.00
Received By mawillia Date 2007-03-21 Time 18:40 Sent To  
Notes
2007-03-21 18:41:51*****APPROVED******
  
  
 PLAN SHEET E1 WAS STAMPED, INITIALED, AND DATED ON
 09/05/2006.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-05 Cont ID  
Sent By mawillia Date 2006-09-05 Time 15:40 Rev Time 0.00
Received By mawillia Date 2006-09-05 Time 15:40 Sent To  
Notes
2006-09-05 00:00:00*****APPROVED*****
  
  
  
  
 THE NOTES/CONCERNS OF 06/08/2006'S FIRE
 PLAN REVIEW HAVE BEEN RECOGNIZED AND
 ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIES
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-08 Cont ID  
Sent By mwennerg Date 2006-06-08 Time 09:39 Rev Time 0.00
Received By mwennerg Date 2006-06-08 Time 09:39 Sent To  
Notes
2006-06-08 00:00:00***DENIED***
  
 1) PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING FS AND FAC REQUIREMENTS.
  
 2) PLEASE ILLUSTRATE LOCATION OF AND
 MORE DETAILS REGARDING LOCATION OF
 GENERATOR TO STRUCTURE AND ANY OPENINGS.
  
  
 3) PLEASE PROVIDE ALL MANUFACTURER SPEC
 SHEETS FOR GENERATOR AND ASSOCIATED
 EQUIPMENT.
  
 4) WORK SHALL COMPLY WITH APPLICABLE
 BUILDING CODES, AND NFPA 101, 2003
 EDITION AS WELL AS NFPA 110, 2002
 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 09:37 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 09:37 Sent To  
Notes
2007-02-26 11:35:57TO "COMM" BD#6
2007-02-15 09:37:56WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-22 Cont ID  
Sent By adarroug Date 2007-01-22 Time 15:26 Rev Time 0.00
Received By adarroug Date 2007-01-22 Time 15:26 Sent To Z
Notes
2007-01-22 15:27:02TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-27 Cont ID  
Sent By adarroug Date 2006-11-27 Time 14:32 Rev Time 0.00
Received By adarroug Date 2006-11-27 Time 14:32 Sent To B
Notes
2006-11-27 14:33:02TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 08:37 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 08:37 Sent To Z
Notes
2006-11-17 08:37:42TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 11:51 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 11:51 Sent To  
Notes
2006-08-18 00:00:00TO "COMM" BD#61
2006-08-08 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-06-18 Time 11:49 Rev Time 0.00
Received By adarroug Date 2006-04-20 Time 12:17 Sent To  
Notes
2006-05-08 00:00:00TO "COMM" BD#12
2006-04-20 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-07 Cont ID  
Sent By tgordon Date 2007-03-07 Time 09:39 Rev Time 0.25
Received By tgordon Date 2007-03-07 Time 09:39 Sent To  
Notes
2007-03-07 09:42:58*** PROVISO ***
 1) INSTALLATION OF OUTSIDE ABOVEGROUND TANKS. 7.9.2 A
 TANK OR TANKS WHOSE CAPACITY DOES NOT EXCEED 660 GAL
 (2500 L) SHALL BE PERMITTED TO BE INSTALLED OUTSIDE OF
 AND ADJACENT TO A BUILDING, PROVIDED THEY ARE SEPARATED
 FROM THE NEAREST LINE OF ADJOINING PROPERTY BY THE
 FOLLOWING MINIMUM DISTANCE:
 (1)5 FT (1.5 M) FOR TANKS NOT
 EXCEEDING 275 GAL (1040 L) CAPACITY
 (2)10 FT (3 M) FOR TANKS GREATER
 THAN 275 GAL (1040 L) CAPACITY, BUT NOT
 EXCEEDING 660 GAL (2500 L) CAPACITY.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
2007-03-02 18:59:18NEW SHEETS, NEEDS MECH STAMP.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-21 Cont ID  
Sent By tgordon Date 2006-08-21 Time 13:39 Rev Time 0.20
Received By tgordon Date 2006-08-21 Time 13:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-23 Cont ID  
Sent By tgordon Date 2006-05-23 Time 11:12 Rev Time 1.30
Received By tgordon Date 2006-05-23 Time 11:12 Sent To  
Notes
2006-05-23 00:00:00*** DENIED ***
 1) PLEASE SEE ELECTRICAL REVIEW NOTE #8.
  
 2) PLEASE SHOW IF BUILDING WALL NEXT TO
 GENERATOR IS MADE OF COMBUSTIBLE
 MATERIALS OR NOT. IF SO PLEASE COMPLY
 WITH NFPA 37 (4.1.4).
  
 3) PLEASE SHOW LOCATION OF GENERATOR AND
 ADJOINING PROPERTY LINES ON PLANS.
  
 4) PLEASE BE ADVISED, INSTALLATION OF
 OUTSIDE ABOVEGROUND TANKS.
 7.9.2 A TANK OR TANKS WHOSE CAPACITY
 DOES NOT EXCEED 660 GAL (2500 L) SHALL
 BE PERMITTED TO BE INSTALLED OUTSIDE OF
 AND ADJACENT TO A BUILDING, PROVIDED
 THEY ARE SEPARATED FROM THE NEAREST LINE
 OF ADJOINING PROPERTY BY THE FOLLOWING
 MINIMUM DISTANCE:
 (1)5 FT (1.5 M) FOR TANKS NOT
 EXCEEDING 275 GAL (1040 L) CAPACITY
 (2)10 FT (3 M) FOR TANKS GREATER
 THAN 275 GAL (1040 L) CAPACITY, BUT NOT
 EXCEEDING 660 GAL (2500 L) CAPACITY
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-18 Cont ID  
Sent By pschmitz Date 2006-06-18 Time 10:48 Rev Time 0.00
Received By pschmitz Date 2006-06-18 Time 10:48 Sent To  
Notes
2006-06-18 00:00:00DIESEL FUEL, PALN REVIEW BY MECHANICAL.

Review Stop Z ZONING
Rev No 5 Status P Date 2007-03-02 Cont ID  
Sent By kdfreema Date 2007-03-02 Time 17:27 Rev Time 0.00
Received By kdfreema Date 2007-03-02 Time 17:27 Sent To  
Notes
2007-03-02 17:29:27PROVISO: THE WOOD FENCE SHALL BE EXTENDED TO SCREEN THE
 FULL LENGTH OF THE GENERATOR ON ITS WEST SIDE.
 FURTHERMORE, CHAIN LINK FENCING WITH SLATS SHALL NOT BE
 PERMITTED.

Review Stop Z ZONING
Rev No 4 Status F Date 2007-02-03 Cont ID  
Sent By mmclean Date 2007-02-03 Time 07:37 Rev Time 0.00
Received By kdfreema Date 2007-03-02 Time 17:27 Sent To I
Notes
2007-02-03 07:08:56DENIED,
 1. LOCATION OF THE PROPOSED GENERATOR IS LOCATED ON THE
 FEC RY PROPERTY, WHICH IS NOT ALLOWED.
 2. NEED TO PROVIDE A CURRENT SURVEY OF THE PROPERTY
 SHOWING THE COMPLETE PROPERTY, THE VINICITY MAP
 SUBMITTED DOES NOT PROVIDE ALL INFORMATION NEEDED TO
 REVIEW PLANS (NOT A SURVEY).
 3. NEED TO PROVIDE A UNITY OF TITLE, UNIFYING THE
 COMPLETE PROPERTY (IF PUTTING THE GENERATOR ON THE PALM
 BEACH POST PROPERTY).
 4. PLEASE PROVIDE A COPY OF THE LEASE AGGREEMENT FOR
 THE PROPERTY.
 5. THE VINICITY MAP SHOWS THE PROPOSED GENERATOR ON THE
 FEC RY PROPERTY AND E2 SHOWS THE PROPOSED GENERATOR
 WITHIN A 10FT REAR SETBACK (GENERATOR 5FT FROM REAR
 PROPERTY LINE AND 3FT FROM STRUCTURE). PLEASE CLARIFY.
 6. THE PROPOSED BARBWIRE FENCING SHALL BE TO CODE NOTE:
 NO MORE THAN THREE STRANDS OF BARBED WIRE MAY BE USED
 AT THE TOP OF A
 FENCE OR WALL.THE STRANDS MUST BE LOCATED AT LEAST
 SIX FEET ABOVE GRADE OR MOUNTED VERTICALLY OR AT AN
 ANGLE
 PROJECTING INTERIOR TO THE PROPERTY AND MUST NOT
 ENCROACH BEYOND THE PROPERTY LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 3 Status F Date 2006-11-21 Cont ID  
Sent By mmclean Date 2006-11-21 Time 13:21 Rev Time 0.00
Received By mmclean Date 2006-11-21 Time 13:21 Sent To I
Notes
2006-11-21 15:01:59DENIED,
 1. NO SURVEY WAS SUBMITTED IN RESUB PACKET.
 2. PLEASE SUBMIT TWO COPIES OF CURRENT SURVEY OF THE
 COMPLETE PROPERTY SHOWING THE LOCATION OF THE PROPOSED
 GENERATOR WITH SETBACKS.
 3. THE SITEPLAN DOES NOT PROVIDE A COMPLETE VIEW OF THE
 WHOLE PROPERTY, DOES NOT GIVE DIMENSION OF THE LOT AND
 SETBACK OF THE STRUCTURE ON THE PROPERTY AND SHOW ANY
 EASEMENT ON PROPERTY. THAT'S WHY SURVEYS ARE NEEDED.
  
 NOTE; OUTDOOR GENERATORS ARE SUBJECT TO SCREENING
 REQUIREMENTS, SEC 94-444(B) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 NOTE:NOTE: NO MORE THAN THREE STRANDS OF BARBED WIRE
 MAY BE USED AT THE TOP OF A FENCE OR WALL.THE STRANDS
 MUST BE
 LOCATED AT LEAST SIX FEET ABOVE GRADE OR MOUNTED
 VERTICALLY OR AT AN ANGLE PROJECTING INTERIOR TO THE
 PROPERTY AND
 MUST NOT ENCROACH BEYOND THE PROPERTY LINE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  

Review Stop Z ZONING
Rev No 2 Status F Date 2006-09-01 Cont ID  
Sent By kdfreema Date 2006-09-01 Time 08:13 Rev Time 0.00
Received By kdfreema Date 2006-08-31 Time 17:18 Sent To  
Notes
2006-09-01 00:00:00BARBED WIRE MUST BE MOUNTED VERTICALLY
 OR AT AN ANGLE PROJECTING INTERIOR TO
 THE PROPERTY.
  
 A SURVEY SHOWING THE LOCATION OF THE
 GENERATOR MUST STILL BE PROVIDED.
  
 CHAINLINK FENCING IS NOT PERMITTED.
  
 OUTDOOR GENERATORS ARE SUBJECT TO THE
 SCREENING REQUIREMENTS FOUND IN SEC.
 94-444(B) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS. THIS SECTION
 READS AS FOLLOWS:
  
 (B)OUTDOOR STORAGE FOR NONRESIDENTIAL
 AND MULTIFAMILY USES; STORAGE AND
 DISPOSAL FACILITIES.OUTDOOR
 INCINERATORS, GARBAGE OR TRASH
 RECEPTACLES, FUEL OIL OR PROPANE TANKS,
 AND STORAGE RACKS SHALL NOT BE PERMITTED
 UNLESS APPROPRIATE SCREENING IS
 PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE
 LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. A
 FOUR-SIDED ENCLOSURE WITH AN OBSCURING
 GATE MAY BE REQUIRED AS A CONDITION FOR
 SITE PLAN APPROVAL. PLANS FOR THE LAYOUT
 OF TRASH RECEPTACLESSHALL BE IN
 ACCORDANCE WITH THE MINIMUM REQUIREMENTS
 SET FORTH IN FIGURE XIV-3. THE
 PROVISIONS OF THIS SECTION SHALL NOT
 APPLY TO LITTER CONTAINERS PROVIDED FOR
 THE CONVENIENCE OF PEDESTRIANS. ALL
 AREAS FOR THE STORAGE AND DISPOSAL OF
 TRASH AND GARBAGE SHALL BE PAVED WITH
 CONCRETE SURFACE AS REQUIRED BY THE CITY
 DEPARTMENT OF ENGINEERING AND PUBLIC
 WORKS.
  
 PLEASE CALL KELLY FREEMAN, PLANNER, AT
 (561) 822-1435 WITH ANY QUESTIONS.
2006-08-31 00:00:00 
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By mmclean Date 2006-06-13 Time 12:41 Rev Time 0.00
Received By mmclean Date 2006-06-13 Time 12:41 Sent To  
Notes
2006-06-13 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF SITEPLAN & 1
 COPY OF SURVEY SHOWING THE LOCATION OF
 THE PROPOSED GENERATOR.
 2. MUST SHOW THE LOCATION OF GENERATOR
 AND PROVIDE THE SETBACK FROM SIDE/REAR
 PROPERTY LINE OR THE LOCATION OF THE
 PROPOSED GENERATOR (UNKNOWN AT THE TIME
 OF PERMIT).
 3. IF GENERATOR IS LOCATED IN A REQUIRED
 PARKING SPACE, MUST PROVIDE PLANS FOR
 THE REQUIRED PARKING & WHAT IS APPROVED.
  
 NOTE: GENERATOR MUST BE BUFFERED FROM
 VIEW AND SEC 94-303 MECHANICAL/POOL EQUIPMENT/GENERATOR
 MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720