Plan Review Details - Permit 06040623
Plan Review Stops For Permit 06040623
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-04-06 Cont ID  
Sent By amorse Date 2007-04-06 Time 10:52 Rev Time 0.00
Received By amorse Date 2007-04-06 Time 10:52 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-09 Cont ID  
Sent By lmartine Date 2007-02-09 Time 17:22 Rev Time 0.00
Received By lmartine Date 2007-02-09 Time 17:22 Sent To  
Notes
2007-02-09 17:23:02ROOF ENGINEERING APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-15 Cont ID  
Sent By jleech Date 2007-02-05 Time 10:48 Rev Time 0.00
Received By amorse Date 2006-09-15 Time 08:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-26 Cont ID  
Sent By amorse Date 2006-07-26 Time 09:13 Rev Time 2.00
Received By amorse Date 2006-07-26 Time 09:13 Sent To PC
Notes
2006-07-26 00:00:00 
  
 DENIED
  
 THE FOLLOWING NOTES WERE NOT ADDRESSED
 ON THE FIRST REVIEW
  
 5) PROVIDE SIGNED AND DATED ENERGY
 CALC'S BE SURE THEY ARE SIGNED AND DATED
 BY PREPARER AND OWNER/AGENT
 ***(OWNER/AGENT HAS NOT SIGNED)***
  
 15) PROVIDE WOOD CONNECTORS THAT TIE
 TRUSSES TO GIRDERS AT VARIOUS LOCATIONS
 AND STRAPS TO BE USED AT VALLEY SETS
 ***(TRUSS DRAWINGS TO BE REVIEWED AND
 APPROVED BY DESIGNER OF RECORD PLEASE
 NOTE THAT THE DRAWINGS FOR TRUSS TO
 TRUSS AND VALLEY ATTACHMENT IS BY
 OTHERS)PLEASE PROVIDE ATTACHMENT THAT
 MEETS REQUIRED UPLIFTS***
  
 1) ONLY ONE COPY OF SOIL REPORT WAS
 SUBMITTED
  
 2) SEE ZONING COMMENTS SITE PLAN TO
 MATCH SETBACKS ON SURVEY
  
 3) PRODUCT APPROVAL FOR HORIZNTAL
 SLIDERS HAVE A MAXIMUM WIDTH OF 74"
 WINDOW TYPE #5 ON SCHEDULE IS 106 1/4"
 WIDE.
  
 4) PLEASE STATE TYPE OF GLASS ON THE
 HORIZONTAL SLIDER AS THE MIN GLASS TYPE
 DOES NO MEET THE REQUIRED PRESSURE ON
 THE SCHEDULE (SEE PAGE 1 OF 6 IN PRODUCT
 APPROVAL DRAWING)
  
 5) WINDOW PRESSURES FROM PRODUCT
 APPROVALS DO NOT MATCH SCHEDULE ON 5/12
 PLEASE MATCH OR DELETE THIS INFORMATION
  
 6) WINDOW SIZE SKETCH FOR SH25 (WINDOW
 #4 ON SCEDULE) SHOWS A SH24 PLEASE
 CLARIFY
  
 7) NO PRODUCT APPROVALS WERE SUBMITTED
 FOR REGULAR PANEL DOORS (#8 & #9 ON
 SCHEDULE)
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-23 Cont ID  
Sent By jleech Date 2006-05-23 Time 10:28 Rev Time 3.00
Received By amorse Date 2006-05-23 Time 10:28 Sent To PC
Notes
2006-05-23 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. PERMIT FEES
 WILL BE INCREASED ACCORDINLY
  
 3) A DESIGN PROFESSIONAL THAT IS
 REGISTERED TO PRACTICE UNDER CHAPTER 481
 OR 471 OF THE FLORIDA STATUTES SHALL
 AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS
 PER 106.1 FBC 2004. THE DATE IS MISSING
 ALSO THERE IS A MISTAKE ON THE LICENCE#
  
 4) PROVIDE UNDER ROOF SQ FT OF ADDITION,
 CARPORT AND FRONT PORCH. THESE ARE
 REQUIRED FOR COUNTY IMPACT FEES AND
 STATE RADON FEE
  
 5) PROVIDE SIGNED AND DATED ENERGY
 CALC'S BE SURE THEY ARE SIGNED AND DATED
 BY PREPARER AND OWNER/AGENT
  
 6) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 7) PROVIDE COPY OF SURVEY THAT IS LESS
 THAN 1 YR OLD
  
 8) PROVIDE PRODUCT APPROVAL FOR WOOD
 CONNECTORS/HURRICANE STRAPS (SEE
 ATTACHED SHEETS, THIS METHOD WHERE THE
 FL# AND THE CONNECTORS USED ARE MARKED
 IS ADEQUATE)
  
 9) PRODUCT APPROVALS DO NOT MATCH
 DRAWINGS, NOSH WINDOW APPROVALS BUT ALL
 OPENING WINDOWS ON DRAWING SPECIFY SH.
 APPROVALS FOR CASEMENT AND HORIZONTAL
 SLIDERS BUT NONE SPECIFIED ON DRAWINGS.
 FIXED WINDOW APPROVALS ARE NON-IMPACT AS
 SUCH WILL REQUIRE OPENING PROTECTIVES,
 SUBMIT PRODUCT APPROVALS. ALL PRODUCT
 APPROVAL DRAWINGS ARE MISSING DATA AS
 PRINTING SEEMED TO CUT OF TOP OF DRWGS
  
 10) IF THESE PRODUCTS ARE TO BE USED
 UPDATE WINDOW SCHEDULE AND DRAWINGS TO
 REFLECT CHANGES
  
 11) CORRECT BLDG DESIGN DATA ON PAGE 1
  
 12) FOUNDATION SHALL BE A MINIMUM OF 12"
 BELOW GRADE PER R403.1.4 FBC (SEE DETAIL
 1/8 ON PG.8
  
 13) PROVIDE DETAILS ON PORCH BEAM AND
 RAFTER ATTACHMENT TO BEAM AND TIE IN TO
 EXISTING ROOF.
  
 14) PROVIDE DETAILS ON CARPORT BEAMS
  
 15) PROVIDE WOOD CONNECTORS THAT TIE
 TRUSSES TO GIRDERS AT VARIOUS LOCATIONS
 AND STRAPS TO BE USED AT VALLEY SETS
  
 16) PERMIT APPLICATION STATES
 REPLACEMENT OF WINDOWS AND ROOF IN
 EXISTING STRUCTURE, PLEASE CLARIFY, IF
 SHINGLE ARE TO BE RELACED ON ENTIRE ROOF
 SPECIFY ON DRAWING. LIKEWISE FOR WINDOWS
 AS ONLY A FEW ARE TO BE REMOVED AS PER
 DEMO PLAN
  
 17) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-06-07 Cont ID  
Sent By dpalmer Date 2007-06-07 Time 11:53 Rev Time 0.00
Received By dpalmer Date 2007-06-07 Time 10:43 Sent To PC
Notes
2007-06-07 11:54:32CORRECTED NOTES FOR SMOKE ALARMS/ DETECTORS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-05-16 Cont ID  
Sent By dpalmer Date 2007-05-16 Time 10:25 Rev Time 0.00
Received By dpalmer Date 2007-05-15 Time 16:51 Sent To PC
Notes
2007-05-16 10:25:42** UNSAT**
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE PLANS ARE NOT INDICATING ANY
 REVISIONS BY CLOUDS/TRIANGLES OR DATES IN TITLE BLOCK.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE THE PLANS ARE NOT DATED BY THE
 DESIGNER OF RECORD AS REQUIRED UNDER PER FS 481.221.
  
 3) NOTE: PLEASE SEE THE RISER DIAGRAM IS NOW REVISED
 SHOWING NO MAIN, YET PLANS STILL INDICATE A MAIN
 DISCONNECT OUTSIDE?
 PLEASE CLARIFY AND KNOW THAT NO MORE THAN 8FT OF
 UNPROTECTED CONDUCTORS ARE PERMITTED INSIDE BUILDING.
 230.70.
  
 4) NOTE: PLEASE SEE 250.6, 250.24 AS EQUIPMENT
 GROUNDING CONDUCTORS ARE BEING BEFORE THE FIRST MEANS
 OF DISCONNECT AS THE RISER DOES NOT INDICATE ANY MAIN
 BEFORE THE PANEL?
 * EQUIPMENT GROUNDS ARE ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT*
  
 5) NOTE: PLEASE SEE THE PLANS HAVE BEEN REVISED
 REMOVING THE PREVIOUS BATHS 2 AND 3, HOWEVER THE NEW
 PLANS INDICATE ONLY ONE BATH AND RECEPTACLE AS
 EXISTING. HOW IS THIS RECEPTACLE EXISTING WHEN THE
 WALLS/LAYOUT/ AND BATH IS NEW. PLEASE SEE PREVIOUS
 PLANS WHICH DID NOT INDICATE THIS.
 PLEASE COORDINATE AND CLARIFY THIS.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE
 DETECTION DEVICES. IF THESE ARE 120V DEVICES WHICH
 DETECT AND SOUND AN ALARM, THEY ARE SMOKE ALARMS AND
 SHOULD BE SHOWN AS SA. IF THESE ARE INDEED SMOKE
 DETECTORS WHICH ARE SHOWN AS SD, THEN THESE ONLY DETECT
 AND PLANS NEED TO SHOW SOUNDING DEVICES AND PANEL FOR
 CONTROL.
  
 7) NOTE: PLEASE SEE PREVIOUS ISSUED PLANS REDLINED THE
 REQUIRED CODE FOR PLANS.
 PLEASE BE SURE THE FOLLOWING CODES ARE LISTED ON
 ELECTRICAL PLANS.
 2004 FBC, 2002 NFPA-70 (NEC) AND THE 2002 NFPA-72.
  
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-24 Cont ID  
Sent By dpalmer Date 2006-08-24 Time 16:24 Rev Time 0.00
Received By dpalmer Date 2006-08-24 Time 16:08 Sent To M
Notes
2006-08-24 00:00:00***** REDLINED PLANS.
  
  
 1)PLEASE SEE MINIMUM CONDUIT SIZE SHALL
 BE 2" FOR THE SEC'S AND THE FEEDERS FROM
 MAIN DISCONNECT TO SUB PANEL.
 PLEASE SEE CHAPTER 9,TABLES.
  
 2) PLEASE SEE REDLINED NFPA-72 2002,
 NFPA-70 2002 ON ELECTRICAL PLANS.
  
 3) PLEASE SEE REDLINED MIN CLEARENCES
 FOR THE AHU DISCONNECT AS SHOWN.
 110.26
  
  
 ** PLEASE REVISE NOTE #1 WHEN REVISING
 PLANS BEFORE ROUGH ALONG WITH ANY OTHER
 REVISIONS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 16:03 Rev Time 0.00
Received By dpalmer Date 2006-07-23 Time 15:25 Sent To M
Notes
2006-07-23 00:00:00******** UNSAT 2ND REVIEW *********
  
 ** IMPORTANT **
 ONCE ALL REVIEWS ARE COMPLETE PLANS WILL
 BE PICKED UP FOR CORRECTIONS.
 BEFORE RESUBMITTING PLANS, PLEASE
 COMPLETELY "REMOVE" ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY "INSERT NEW"
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STMAPING. ONLY ONE COPY OF THE
 OLD/VOIDED REMOVED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE SEPARATELY.
 THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 *************************************
  
 1) NOTE: PLEASE CORRELATE RISER AND
 PANEL, PLEASE SEE ONE SHOWS 200A AND THE
 OTHER 150A.
 106.1.2 FBC
  
 2) NOTE: PLEASE SEE LOCATIONS FOR
 FAN/LTS IN BEDRMS AND LIVING RMS ARE
 BEING SHOWN AS A "J" BOX ONLY. PLEASE
 CLARIFY AS FIXTURES OF SOME SORT IS
 REQUIRED FOR EGRESS LTS.
 210.70 LS 101 7.8
  
 3) NOTE: PLEASE SEE COVER SHEET SHOWS
 2000 LS 101, PLEASE KNOW, AS OF JAN 05,
 THE STATE ADOPTED THE 2003 LS 101.
 PLEASE ALSO PLACE THE FOLLOWIGN CODES ON
 THE ELECTRICAL PLANS AS REQUIRED.
 2002 NFPA-70, 2002 NFPA-72
  
 4) NOTE: PLEASE INDICATE THE REQUIRED
 LICENSE INFORMATION FOR MARK ROBINSON
 DESIGN , LLC.
 PLEASE SEE FS 481.219, FS 471.023 FOR
 MISSING CERTIFICATE OF AUTHORIZATION #.
 WHAT TYOE OF BUSINESS IS THIS? IF
 ARCHITECT WORKS FOR THIS DESIGN FIRM,
 PLEASE INCLUDECA #.
 61G1-16.004
  
 5) NOTE: PLEASE SEE MAX OCP FOR AHU IS
 TYPICALL 150% , HOWEVER PANEL SCHEDULE
 SHOWS 60A OCP FOR 5KW HEAT IN AHU?
 PLEASE SEE 424.3B FOR MIN @125%.
 PLEASE ALSO SEE #6, SHOWN WHICH IS OK,
 HOWEVER IF SHOWN ON PLANS, #6 WILL BE
 REQUIRED. PLEASE ALSO KNOW, IF THE 5KW
 UNTI CONTAINS THE TYPICAL 30A OCP, #6
 WILL NOT INSERT INTO A 30A BRKR.
 PLEASE ADJUST.
 106.1.2
  
 6) NOTE: PLEASE SEE 250.50, AS THE NEW
 "FOOTER STEEL" SHALL BE PART OF THE
 GROUNDING ELECTRODE SYSTEM.
 PLEASE ALSO CLARIFY THE "STRUCTURAL
 STEEL" AS NOTED.??
  
 7) NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARENCES FOR THE CU/ AHU DISC'S.
  
 8) NOTE: PLEASE SEE MISSING GFI RECEPTS
 FOR CU'S. (BOTH)
 210.63, 210.8A3
  
 9) NOTE: PLEASE VERIFY CIRCUITING OF LT
 OUTSIDE BATH #3, AS LTS IN THE SAME SW
 BOX ARE ON 19, HOWEVER LT FOR THE LT
 ADJACENT IS ON THE MASTER BEDRM/EXT
 RECEPT CIRCUIT. THIS IS OK, HOWEVER IF
 SHOWN, THIS IS REQUIRED. THIS IS ONLY
 NOTED FOR INFORMATIONAL PURPOSE AND THIS
 DOES NOT REQUIRE CHANGE.
 THIS CAN BE REVISED AT A LATER DATE, AS
 OTHER REVISIONS WILL MOST LIKELY TAKE
 PLACE.
  
 10) NOTE: PLEASE SEE SOME ELECTRICAL
 DEVICES ON PLANS ARE MISSING CIRCUITING.
 408.4.
  
 11) NOTE: PLEASE LIST ALL THE REQUIRED
 ARC FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PLEASE SEE ARC FAULT IS ONLY
 SHWON FOR THE SD/LTS CIRCUIT AND ARC
 FUALT IS ONLY NOTED ON PLANS FOR RECEPTS
 NOT ALL AS REQUIRED PER 2002 NEC 210.12B
 PLEASE LIST ON SCHEDULE. 408.4.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-05 Cont ID  
Sent By btrobaug Date 2006-05-05 Time 13:10 Rev Time 0.50
Received By btrobaug Date 2006-05-05 Time 12:27 Sent To P
Notes
2006-05-05 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE 1/0 SERVICE CONDUCTORS SHOWN ON
 THE RISER DIAGRAM ARE NOT LARGE ENOUGH
 FOR A 200 AMP SERVICE. SEE 310.15(B)(6).
  
 2} PLEASE LOCATE THE 200 AMP MAIN
 DISCONNECT ON THE PLAN .
  
 3} PLEASE SEE THAT SMOKE DETECTORS MUST
 BE ON AN ARC FAULT CIRCUIT PER 210.12.
  
 4} A RECEPTACLE MUST BE ADDED TO THE
 REAR OF THE HOUSE PER 21.52(E).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-10-19 Cont ID  
Sent By jleech Date 2007-11-05 Time 08:18 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 16:54 Sent To G
Notes
2007-10-19 16:54:50TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-12 Time 13:01 Rev Time 0.00
Received By adarroug Date 2007-09-12 Time 13:01 Sent To P
Notes
2007-09-12 13:02:02TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-06-05 Cont ID  
Sent By adarroug Date 2007-06-05 Time 13:28 Rev Time 0.00
Received By adarroug Date 2007-06-05 Time 13:28 Sent To E
Notes
2007-06-05 13:29:17TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 10:07 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 10:07 Sent To E
Notes
2007-05-14 10:07:22TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-01-10 Cont ID  
Sent By adarroug Date 2007-01-10 Time 16:10 Rev Time 0.00
Received By adarroug Date 2007-01-10 Time 16:10 Sent To P
Notes
2007-01-10 16:11:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-12-20 Cont ID  
Sent By adarroug Date 2006-12-20 Time 16:12 Rev Time 0.00
Received By adarroug Date 2006-12-20 Time 16:12 Sent To P
Notes
2006-12-20 16:13:06TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 15:05 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 15:05 Sent To E
Notes
2006-08-22 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 11:49 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 11:49 Sent To  
Notes
2006-08-18 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-19 Cont ID  
Sent By adarroug Date 2006-07-19 Time 13:52 Rev Time 0.00
Received By adarroug Date 2006-07-19 Time 13:52 Sent To E
Notes
2006-07-19 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-13 Cont ID  
Sent By adarroug Date 2006-07-13 Time 11:36 Rev Time 0.00
Received By adarroug Date 2006-07-13 Time 11:36 Sent To Z
Notes
2006-07-13 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-04 Cont ID  
Sent By adarroug Date 2006-05-04 Time 10:43 Rev Time 0.00
Received By adarroug Date 2006-05-04 Time 10:43 Sent To E
Notes
2006-05-04 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-05-23 Time   Rev Time 0.00
Received By adarroug Date 2006-04-18 Time 09:01 Sent To  
Notes
2006-04-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-25 Cont ID  
Sent By tgordon Date 2006-08-25 Time 08:27 Rev Time 0.45
Received By tgordon Date 2006-08-25 Time 14:51 Sent To P
Notes
2006-08-24 00:00:00NEW SHEETS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-07-24 Cont ID  
Sent By tgordon Date 2006-07-24 Time 11:28 Rev Time 0.30
Received By tgordon Date 2006-07-24 Time 11:28 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By jleech Date 2006-05-08 Time 07:12 Rev Time 0.30
Received By tgordon Date 2006-05-08 Time 08:23 Sent To B
Notes
2006-05-08 00:00:00*** DENIED ***
 1) ARCHITECT PRINTED NAME, LICENSE
 NUMBER, ADDRESS, AND PHONE NUMBER, PER
 TITLE BLOCK,FAC 61G1-16.004.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 3) PLEASE SUBMIT A MANUAL J CALCULATION,
 PER 2004 FBC 13-607.1.ABC.1 .
  
 4) DRYER VENT EXHAUST MUST TERMINATE A
 MIN. OF FOUR FEET FROM THE A/C CONDENSER
 UNIT, PER 2004 FBC/M 401.5.2 .
  
 5) ELECTRICAL PLANS ARE CALLING FOR A 10
 KW HEATER, AND MECHANICAL PLANS ARE
 CALLING FOR A 5 KW HEATER, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 7 Status F Date 2007-11-05 Cont ID  
Sent By jleech Date 2007-11-05 Time 08:19 Rev Time 0.00
Received By jleech Date 2007-11-05 Time 08:03 Sent To  
Notes
2007-11-05 08:18:46DENIED;
 1. STILL NO GAS PERMIT.
 2. POOL PERMIT SPECS OUT A GAS POOL HEATER. NOT SHOWN
 ON GAS PLAN.
 3. WITH A 2# GAS SYSTEM A SHUTOFF VALVE A REGULATOR AND
 A UNION ARE REQUIRED. SEE ONE PLAN MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 6 Status F Date 2007-10-01 Cont ID  
Sent By jleech Date 2007-10-01 Time 07:52 Rev Time 0.00
Received By jleech Date 2007-10-01 Time 07:52 Sent To  
Notes
2007-10-01 08:33:11DENIED;
 1.SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 4. GAS APPIANCE NOT LISTED ON PLANS.
 5. SEPARATE GAS PERMIT REQUIRED. ( NO PERMIT ON FILE )
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-02-05 Cont ID  
Sent By jleech Date 2007-02-05 Time 10:47 Rev Time 0.00
Received By jleech Date 2007-02-05 Time 10:47 Sent To B
Notes
2007-02-05 10:48:10REVISED FLOOR PLAN AND PLUMBING PIPE LAYOUT.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-01-20 Cont ID  
Sent By jleech Date 2007-01-20 Time 12:47 Rev Time 0.00
Received By jleech Date 2007-01-20 Time 12:47 Sent To B
Notes
2007-01-20 12:49:06CHANGED SANITARY UNDER GROUND AS-BUILT

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-09-13 Cont ID  
Sent By tgordon Date 2006-08-25 Time 14:52 Rev Time 0.00
Received By jleech Date 2006-09-13 Time 07:53 Sent To B
Notes
2006-08-24 00:00:00NEW SHEETS

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-24 Cont ID  
Sent By jleech Date 2006-07-24 Time 13:44 Rev Time 0.00
Received By jleech Date 2006-07-24 Time 13:44 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-05-08 Cont ID  
Sent By jleech Date 2006-05-08 Time 07:12 Rev Time 0.00
Received By jleech Date 2006-05-08 Time 07:12 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-08-21 Cont ID  
Sent By mmclean Date 2006-08-21 Time 18:02 Rev Time 0.00
Received By mmclean Date 2006-08-21 Time 18:02 Sent To I
Notes
2006-08-21 00:00:00NOTE: THE PROPOSED A/C PAD ON THE SOUTH
 EAST SIDE SHALL NOT BE CLOSER THAN 1FT
 FROM SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-18 Cont ID  
Sent By mmclean Date 2006-07-18 Time 15:46 Rev Time 0.00
Received By mmclean Date 2006-07-18 Time 15:46 Sent To I
Notes
2006-07-18 00:00:00DENIED,
 1. THE MINIMUM FRONT SETBACK FOR
 STRUCTURE IS 25FT, SITEPLAN SHOWS
 24.9FT.(SURVEY SHOWS THE EXISTING
 CARPORT AT 30.03FT)
 2. THE CARPORT MUST SIT BACK 25FT.
 PLEASE PROVIDE TWO COPY OF CORRECTED
 SITEPLAN.
  
  
 NOTE:THE PROPOSED A/C PAD ( ON EAST
 SIDE) SHALL NOT BE CLOSER THAN 1FT FROM
 SIDE PROPERTY LINE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-05 Cont ID  
Sent By mmclean Date 2006-05-03 Time 15:49 Rev Time 0.00
Received By mmclean Date 2006-05-03 Time 15:49 Sent To I
Notes
2006-05-03 00:00:00DENIED,
 1. PLEASE CLARIFY COMMENT ON DEMOLITION
 PLAN(3 OF 12) "REMOVE EXISTING
 CONCRETE CARPORT IN ORDER TO PREPARE FOR
 ADDITION CONSTRUCTION".
 2. PLEASE SUBMIT 1 COPY OF CURRENT
 SURVEY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720