Plan Review Details - Permit 06040598
Plan Review Stops For Permit 06040598
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-15 Cont ID  
Sent By alange Date 2006-08-15 Time 09:32 Rev Time 0.50
Received By alange Date 2006-08-15 Time 09:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-19 Cont ID  
Sent By alange Date 2006-06-19 Time 14:03 Rev Time 1.50
Received By alange Date 2006-06-19 Time 13:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-17 Cont ID  
Sent By alange Date 2006-05-17 Time 14:43 Rev Time 2.75
Received By alange Date 2006-05-17 Time 14:43 Sent To  
Notes
2006-05-17 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 3.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 4.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.CHECK CODE
 SECTIONS REFERENCED THROUGH OUT PLANS.
 ESPECIALLY ON THE "M" PAGES.
  
 5.OCCUPANCY TYPE SHOULD BE A-2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-09 Cont ID  
Sent By btrobaug Date 2006-06-09 Time 16:12 Rev Time 0.50
Received By btrobaug Date 2006-06-09 Time 15:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-28 Cont ID  
Sent By btrobaug Date 2006-04-28 Time 14:33 Rev Time 2.00
Received By btrobaug Date 2006-04-27 Time 17:35 Sent To  
Notes
2006-04-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THAT IN THE ELECTRICAL
 SPECIFICATIONS(NOTES) THE 2001 FBC IS
 INCORRECTLYREFERENCED, PLEASE
 REFERENCE THE 2004 FBC. THE "LATEST
 EDITION OF THE NEC" IS MENTIONED IN PART
 3 C. THE 2002 EDITION IS THE ADOPTED
 CODE FOR THE STATE OF FLORIDA, THE
 CURRENT NEC IS 2005. ALSO SEE
 "DESIGN CODES" ON SHEET T1 ARE ALL
 CORRECT EXCEPT THE 2003 NEC.
  
 PLEASE REFERENCE THE ADOPTED EDITIONS OF
 ALL CODE USED IN NOTES OR REFERENCES.
  
 2} CIRCUIT "B1-34" IS MISLABLED AS A
 SPARE, SHOULD BE ROOF RECEPTACLE.
  
 3} THE #1/0 GEC SHOULD BE INCREASED FOR
 A 600 AMP SERVICE. SEE 250.66.
  
 4} FORM 400A WAS SUBMITTED FOR ENERGY
 CODE REQUIREMENTS. PLEASE SHOW CAUSE WHY
 THE PRESCRIPTIVE REQUIREMENTS PER
 13-101.1.3 SHOULD NOT BE MET AND FORM
 400C SUBMITTED, AS THIS IS A RENOVATION.
  
 5} SUBMIT THE AIC RATING OF THE NEW
 SERVICE DISCONNECT PER 110.9.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-05-04 Cont ID  
Sent By mwennerg Date 2006-05-04 Time 14:24 Rev Time 0.00
Received By mwennerg Date 2006-05-04 Time 14:24 Sent To  
Notes
2006-05-04 00:00:00******APPROVED******
  
 1) IF FIRE ALARM SYSTEM IS PROVIDED,
 DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS. VISUAL/AUDIBLE
 DEVICES WILL BE REQUIRED.
  
 2) AS INDICATED ON PLANS, SEPARATE SHOP
 DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM, AND IF APPLICABLE FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 11:07 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 11:07 Sent To M
Notes
2006-08-11 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 11:05 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 11:05 Sent To  
Notes
2006-08-11 00:00:00WAITING FOR "BOB"/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-27 Cont ID  
Sent By adarroug Date 2006-05-27 Time 13:42 Rev Time 0.00
Received By adarroug Date 2006-05-27 Time 13:42 Sent To  
Notes
2006-05-27 00:00:00TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-17 Cont ID  
Sent By alange Date 2006-05-17 Time 14:47 Rev Time 0.00
Received By alange Date 2006-04-19 Time 16:28 Sent To  
Notes
2006-04-25 00:00:00TO "BOB"#16
2006-04-19 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 13:58 Rev Time 0.20
Received By tgordon Date 2006-08-11 Time 13:58 Sent To  
Notes
2006-08-11 00:00:00REVISION TO MECH. PLAN PAGE M2.1 .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-06-02 Cont ID  
Sent By tgordon Date 2006-06-02 Time 13:51 Rev Time 0.20
Received By tgordon Date 2006-06-02 Time 13:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-05-31 Cont ID  
Sent By tgordon Date 2006-05-31 Time 16:40 Rev Time 0.30
Received By tgordon Date 2006-05-31 Time 16:40 Sent To  
Notes
2006-05-31 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 4-26-06
 NOTE #1, PAGE KH-1 REQUIRES AN
 ARCHITECT'S SEAL ON IT, AS IT HAS THE
 ARCHITECT'S COMPANY LISTED IN THE TITAL
 BLOOK. PLEASE SEE FAC 61.003 USE OF
 SEAL.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-26 Cont ID  
Sent By tgordon Date 2006-04-26 Time 16:15 Rev Time 1.30
Received By tgordon Date 2006-04-26 Time 16:15 Sent To  
Notes
2006-04-26 00:00:00*** DENIED ***
 1) PLEASE SEE PLANS PAGE KH-1, NO
 ARCHITECT OR ENGINEER SEAL, PLEASE
 CORRECT PER FAC 61G1-16.003 .
  
 2) PLEASE SEE PLANS PAGE M0.1 OUTSIDE
 AIR CAL'S. RTU-2 10 CFM'S. SEE 2004
 FBC/M TABLE 403.3 FAST FOOD 20 CFM'S PER
 PERSON, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-10 Cont ID  
Sent By jleech Date 2006-06-10 Time 12:54 Rev Time 0.00
Received By jleech Date 2006-06-10 Time 12:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-27 Cont ID  
Sent By jleech Date 2006-04-27 Time 14:57 Rev Time 0.00
Received By jleech Date 2006-04-27 Time 14:57 Sent To  
Notes
2006-04-27 00:00:00DENIED;
 1.PAGE A-7; (4) INTERIOR ELEVATION. SHOW
 MEASUREMENTS OFF WALL FOR HANDICAP
 TOILET, 18" AND 5" TO THE EDGE OF
 LAVATORY OFF WALL. SHOW GRAB BARSON
 DETAIL DRAWING AND FLOOR PLAN.
 2.PAGE PO.1 WATER HEATER DETAIL; A MEANS
 OF THERMAL EXPANSION CONTROL IS REQUIRED
 PER FBC-2004 PLUMBING SEC.607.3. SHOW ON
 PLAN.
 3.GREASE TRAP NOT PERMITED IN FOOD PREP
 AREA. GREASE TRAP TO BE SIZED BY THE
 UTILITY DEPARTMENT. WASTE ORDENANCE
 #3434. PLEASE CONTACT;
 LYNN MASSON
 (561) 822-2271
 (561) 822-2279
 E-MAIL [email protected].
 4. MOP SINK AND FLOOR DRAIN IN FOOD PREP
 AREA TO GO TO GREASY WASTE.
 5.WATER RISER PAGE P5.1 WATER HAMMER
 ARRESTORS TO BE INSTALLED AS CLOSE TO
 THE SOURE OF HAMMER AS POSSIBLE. PLEASE
 SHOW ON DRAWING TO COMPLY WITH YOUR NOTE
 #13 ON PAGE P0.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695