Plan Review Details - Permit 06040586
Plan Review Stops For Permit 06040586
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-04-18 Cont ID  
Sent By jgomez Date 2006-04-18 Time 10:31 Rev Time 0.00
Received By rmcdouga Date 2006-07-28 Time 08:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-07-28 Cont ID  
Sent By rmcdouga Date 2006-07-28 Time 08:20 Rev Time 0.00
Received By rmcdouga Date 2006-07-28 Time 08:20 Sent To  
Notes
2006-07-28 00:00:00RESTAMP PRODUCT APPROVALS AND PRINT
 PERMIT CARD

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-23 Cont ID  
Sent By jgomez Date 2006-05-16 Time 07:47 Rev Time 0.50
Received By jgomez Date 2006-05-16 Time 07:47 Sent To  
Notes
2006-05-23 00:00:00RECEIVED CALCULATIONS WITH ORIGINAL
 SEAL.
2006-05-16 00:00:00TALKED TO ENGINEER TO CLARIFY DESIGN
 PRESSURES CALCS. HE'LL SEND REVISED
 CALCS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-10 Cont ID  
Sent By jgomez Date 2006-05-10 Time 19:24 Rev Time 0.50
Received By jgomez Date 2006-05-10 Time 19:24 Sent To  
Notes
2006-05-10 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- WIND LOAD CALCULATIONS SUBMITTED ARE
 FOR GABLE ROOFS. THIS BUILDING HAS A
 FLAT ROOF. ENGINEER TO REVISE
 CALCULATIONS AS REQUIRED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 AND CHAPTER
 16 FBC 2004.
  
 2- ENGINEER TO REVISE RAS 117
 CALCULATIONS TO REFLECT THE REVISED
 DESIGN PRESSURES. SEE ITEM #1.
  
 3- A) EVERY DOCUMENT PREPARED BY THE
 PROFESSIONAL ENGINEER NEED TO HAVE
 ORIGINAL SEAL, SIGNATURE AND DATE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 AND FLORIDA ADMINISTRATIVE CODE. PROVIDE
 2 COPIES OF EVERY DOCUMENT.
 B) ENGINEER TO PROVIDE HIS NAME AND
 LICENSE # ON EVERY SIGNED AND SEALED
 SHEET AS REQUIRED BY 61G15-23.002 OF
 DEPARTMENT OF COMMUNITY AFFAIRS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-17 Cont ID  
Sent By jgomez Date 2006-04-17 Time 17:56 Rev Time 0.40
Received By jgomez Date 2006-04-17 Time 17:56 Sent To  
Notes
2006-04-17 00:00:00BUILDING REVIEW CHECKLIST:
 1- A) CLEARLY IDENTIFY WHICH APPROVED
 FLAT ROOF SYSTEM IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH
 GENERAL LIMITATION #7 OR #9. SEE CITY
 ATTACHED COPY OF CITY POLICY FOR
 RE-ROOFING PERMIT REQUIREMENTS.
 B) CLEARLY SPECIFY TYPE OF MEMBRANE
 AND FASTENERS TO BE USED ON SELECTED
 APPROVED ASSEMBLY.
  
 2- WIND UPLIFT PRESSURE CALCULATIONS TO
 BE SIGNED AND SEALED BY ENGINEER WHO DID
 THE CALCULATIONS AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE.
  
 3- ROOF DIMENSIONS SHOWN ON WIND UPLIFT
 CALCULATIONS DON'T MATCH ACTUAL BUILDING
 DIMENSIONS AND BUILDING SHAPE. REVISE AS
 REQUIRED.
  
 4- PROVIDE COMPLETE PROJECT ADDRESS AND
 CONTRACTOR INFORMATION ON TOP OF FORM.
  
 5- GENERAL LIMITATION #7 ON LAST PAGE OF
 DADE COUNTY NOA REPORT REQUIRES
 CALCULATIONS TO BE DONE USING RAS 117.
 PROVIDE SUCH CALCULATIONS. SEE GENERAL
 LIMITATION #7.
  
 6- A) WIND UPLIFT PRESSURES CALCULATIONS
 SHEET IS MISSING WHICH DADE COUNTY NOA
 ARE CALCULATIONS DONE FOR. SEE BOTTOM OF
 SHEET AND PROVIDE INFORMATION AS REQ'D.
 B) WIND UPLIFT CALCULATIONS ARE
 REFERING TO FLORIDA FL1599-R3 SYSTEM
 R-2. UNABLE TO FIND THIS INFORMATION IN
 THE FLORIDA WEBSITE. SEE BOTTOM OF SHEET
 AND REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712