Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-16 Cont ID  
Sent By jgomez Date 2006-05-16 Time 15:11 Rev Time 0.50
Received By jgomez Date 2006-05-16 Time 15:11 Sent To  
Notes
2006-05-16 00:00:00PERMIT UNDER "R".

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-02 Cont ID  
Sent By jgomez Date 2006-05-02 Time 13:23 Rev Time 0.40
Received By jgomez Date 2006-05-02 Time 07:51 Sent To  
Notes
2006-05-02 00:00:00BUILDING REVIEW SECOND CHECKLIST:
 1- HIGHLIGHTED FLAT ROOF SYSTEMS (PAGES
 31 AND 31 OF THE DADE COUNTY NOA
 #03-0827.02) ARE LIMITED BY GENERAL
 LIMITATION #9. THIS LIMITATION DOESN'T
 ALLOW CALCULATIONS FOR NAIL ENHANCING.
 THEREFORE IT CAN NOT BE USED. SELECTED
 SYSTEM MUST MEET OR EXCEED THE DESIGN
 PRESSURES OF TABLE R301.1(2) OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 2- A) IF ANOTHER SYSTEM IS SELECTED AND
 LIMITED BY GENERAL LIMITATION #7, THEN
 PROVIDE SIGNED AND SEALED CALCULATIONS
 DONE BY ANY OF THE PROFESSIONALS LISTED
 IN GENERAL LIMITATION #7.
 B) QUALIFIER PERSON FOR RE ROOF
 AMERICA IS NOT A REGISTERED ROOF
 CONSULTANT. SEE GENERAL LIMITATION #7
 TO SEE WHO IS QUALIFIED TO PROVIDE SUCH
 CALCULATIONS.
 C) SELECT ONLY ONE APPROVED ASSEMBLY.
 PULL OUT THE REST OF THE ASSEMBLIES FROM
 THE DADE COUNTY NOA. SEE CITY POLICY FOR
 RE-ROOF PERMITS AND REQUIREMENTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (5610805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-17 Cont ID  
Sent By jgomez Date 2006-04-17 Time 15:15 Rev Time 0.50
Received By jgomez Date 2006-04-17 Time 15:15 Sent To  
Notes
2006-04-17 00:00:00BUILDING REVIEW CHECKLIST:
 1- FLAT ROOF SYSTEM:
 A) NEED TO SPECIFY SPECIFIC APPROVED
 ASSEMBLY TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH GENERAL LIMITATION #7 OR
 #9 ON LAST PAGE OF DADE COUNTY NOA
 REPORT. REQUIRED BY THE CITY POLICY FOR
 RE-ROOF PERMITS. SEE ATTACHED COPY.
 B) PROVIDE SIGNED AND SEALED
 CALCULATIONS BY ANY OF THE PROFESSIONALS
 LISTED IN GENERAL LIMITATION #7.
  
 2- SPECIFY MEAN ROOF HEIGHT AS REQUIRED
 BY CITY POLICY FOR RE-ROOF PERMITS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712