Plan Review Details - Permit 06040510
Plan Review Stops For Permit 06040510
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-12 Cont ID  
Sent By btrobaug Date 2006-05-12 Time 07:54 Rev Time 0.33
Received By btrobaug Date 2006-05-12 Time 07:42 Sent To PC
Notes
2006-05-12 00:00:00 
 PROVISO
  
  
 VERTICAL CLEARANCE MUST COMPLY WITH
 230.24(A):
  
 230.24(A)
 ABOVE ROOFS. CONDUCTORS SHALL HAVE A
 VERTICAL CLEARANCE OF NOT LESS THAN 2.5
 M (8 FT) ABOVE THE ROOF SURFACE. THE
 VERTICAL CLEARANCE ABOVE THE ROOF LEVEL
 SHALL BE MAINTAINED FOR A DISTANCE OF
 NOT LESS THAN 900 MM (3 FT) IN ALL
 DIRECTIONS FROM THE EDGE OF THE ROOF.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-17 Cont ID  
Sent By btrobaug Date 2006-04-17 Time 17:23 Rev Time 0.50
Received By btrobaug Date 2006-04-17 Time 17:17 Sent To PC
Notes
2006-04-17 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 230.24(B) VERTICAL CLEARANCE FROM
 GROUND. SERVICE-DROP CONDUCTORS, WHERE
 NOT IN EXCESS OF 600 VOLTS, NOMINAL,
 SHALL HAVE THE FOLLOWING MINIMUM
 CLEARANCE FROM FINAL GRADE:
 (1) 3.0 M (10 FT) ? AT THE ELECTRIC
 SERVICE ENTRANCE TO BUILDINGS, ALSO AT
 THE LOWEST POINT OF THE DRIP LOOP OF THE
 BUILDING ELECTRIC ENTRANCE, AND ABOVE
 AREAS OR SIDEWALKS ACCESSIBLE ONLY TO
 PEDESTRIANS, MEASURED FROM FINAL GRADE
 OR OTHER ACCESSIBLE SURFACE ONLY FOR
 SERVICE-DROP CABLES SUPPORTED ON AND
 CABLED TOGETHER WITH A GROUNDED BARE
 MESSENGER WHERE THE VOLTAGE DOES NOT
 EXCEED 150 VOLTS TO GROUND
  
 2} PERSON TAKING RESPONSIBILITY FOR THE
 PLAN PLEASE PRINT AND SIGN NAME.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-05 Cont ID  
Sent By adarroug Date 2006-05-05 Time 13:15 Rev Time 0.00
Received By adarroug Date 2006-05-05 Time 13:15 Sent To E
Notes
2006-05-05 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-17 Cont ID  
Sent By btrobaug Date 2006-04-17 Time 17:17 Rev Time 0.00
Received By btrobaug Date 2006-04-17 Time 09:26 Sent To E
Notes
2006-04-17 00:00:00TO "E" BOX