Plan Review Details - Permit 06040434
Plan Review Stops For Permit 06040434
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-09-11 Cont ID  
Sent By lursu Date 2006-09-11 Time 08:16 Rev Time 0.00
Received By lursu Date 2006-09-11 Time 08:16 Sent To  
Notes
2006-09-11 00:00:00EXT#0001 WAS ADDED FOR THE ADDRESS OF
 5816 GEORGIA AVE

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-12-04 Cont ID  
Sent By rmcdouga Date 2006-12-04 Time 11:25 Rev Time 0.00
Received By rmcdouga Date 2006-12-04 Time 11:25 Sent To FIRE
Notes
2006-12-04 11:29:59PER TELEPHONE CONVERSATION WITH HENRY KREH, P.E., I
 CHANGED THE STANDARDS REFERENCED FOR CONCRETE AND
 MASONRY (ACI, ASCE & TMS) TO THE 2002 EDITIONS AS
 REFERENCED IN THE 2004 FBC.
 REVISED SHEETS A-1, S-1 AND S-2 ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-11 Cont ID  
Sent By rmcdouga Date 2006-10-11 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2006-10-11 Time 11:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-27 Cont ID  
Sent By rmcdouga Date 2006-09-27 Time 12:36 Rev Time 0.00
Received By rmcdouga Date 2006-09-27 Time 07:12 Sent To  
Notes
2006-09-27 00:00:00DENIED
  
 1) PRODUCT APPROVAL FOR FIXED WINDOWS
 WAS SUBMITTED AND THE PLANS SPECIFY
 SINGLE HUNG WINDOWS.
  
 2) BUILDING OCCUPANCY WAS CHANGED TO F-1
 BUT THE HEIGHT AND AREA LIMITATIONS WERE
 NOT REVISED.
  
 3) VALUE OF THE JOB NEEDS TO BE REVISED
 TO REFLECT THE SCOPE OF THE WORK.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-07 Cont ID  
Sent By rmcdouga Date 2006-09-07 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2006-09-07 Time 16:21 Sent To  
Notes
2006-09-08 00:00:00DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. THE NOC THAT WAS
 SUBMITTED DOES NOT HAVE THE RECORDING
 STAMP ON IT.
  
 2) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. SUBMIT PRODUCT APPROVALS FOR
 THE NEW EXTERIOR WINDOWS AND DOORS. IF
 GLAZING IS NOT IMPACT RESISTANT, STORM
 PANEL PRODUCT APPROVALS ARE REQUIRED
 ALONG WITH AN INSTALLATION SCHEDULE AND
 KEY PLAN.
  
 3) THE DESCRIPTION OF WORK ON THE PERMIT
 APPLICATION DOES NOT REFLECT THE SCOPE
 OF WORK SPECIFIED ON THE PLANS. PLEASE
 REVISE AND INCREASE THE VALUE OF THE
 WORK LISTED ON THE PERMIT APPLICATION
 ACCORDINGLY.
  
 4) SPECIFY THE LEVEL OF ALTERATION FOR
 THE PROJECT THE ON THE PLANS, AS
 SPECIFIED IN THE 2004 FBC EXISTING
 BUILDING CODE.
  
 5) THE BUILDINGS OCCUPANCIES ARE LISTED
 AS BUSINESS ON SHEET CS. HOWEVER,
 OCCUPANT LOADS ARE GIVEN FOR BUSINESS
 AND WAREHOUSE(STORAGE). IT APPEARS TO BE
 MIXED OCCUPANCIES (STORAGE, BUSINESS AND
 POSSIBILY FACTORY OCCUPANCIES). SPECIFY
 THE OCCUPANCY AND OCCUPANT LOAD OF EACH
 TENANT SPACE. SPECIFY THE TYPE OF
 STORAGE(FBC 311).SEE FBC 302 & 302.3.
  
 6) SPECIFY THE REQUIRED FIRE-RESISTANCE
 RATINGS OF THE TENANT SEPARATION WALLS.
 SEE FBC 302.3.2 AND TABLE 302.3.2.
  
 7) SPECIFY THE FIRE RATING OF THE TENANT
 SEPARATION WALL BETWEEN SUITES 3 AND 4
 IN BUILDING #2.
  
 8) SPECIFY THE FIRE RATING OF THE TENANT
 SEPARATION WALL (NEW AND EXISTING)
 DIVIDING THE AREA OF BUILDING #1 INTO
 TWO SEPARATE SPACES.
  
 9) A FIRE BARRIER IS REQUIRED TO
 SEPARATE THE ACCESSORY USE AREA OF THE
 BUSINESS AREA FROM THE LARGE
 STORAGE/WAREHOUSE AREA IN BUILDING #1.
 THE BUSINESS AREA IS MORE THAN 10 PER
 CENT OF THE AREA IN WHICH IT IS LOCATED.
 SEE FBC 302.2.
  
 10) PROVIDE DETAILS OF THE EXTERIOR WALL
 PATCHES. INDICATE MATERIAL, ATTACHMENTS,
 ETC.
  
 11) THE TENANT BATHROOMS ARE REQUIRED TO
 BE ACCESSIBLE. FBC EXISTING BUILDING
 CODE SECTION 606.1.
  
 12) INDICATE THE REQUIRED CLEAR FLOOR
 SPACE AT THE ACCESSIBLE FIXTURES ON THE
 PLANS. FBC 11-4.16.2, 11-4.19.3 AND
 11-4.23.3.
  
 13) DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 SEE FBC 11-4.23.2.
  
 14) THE GRAB BAR AT THE REAR OF THE
 WATER CLOSET IN THE DETAIL ON A1 IS
 REQUIRED TO EXTEND A MINIMUM OF 12" PAST
 THE CENTER LINE OF THE FIXTURE ON BOTH
 SIDES. SEE FBC FIGURE 11-29(A).
  
 15) FBC TABLE 602 REQUIRES EXTERIOR
 WALLS WITHIN 5' OF THE PROPERTY LINE TO
 HAVE A ONE HOUR FIRE RESISTANCE RATING.
 FBC TABLE 704.8 SPECIFIES THAT NO
 OPENINGS ARE ALLOWED IN EXTERIOR WALLS
 WITHIN 5' OF THE PROPERTY LINES IF THE
 WALLS ARE REQUIRED TO BE FIRE RATED.
 THEREFORE THE OPENINGS IN THESE WALLS
 ARE REQUIRED TO BE ENCLOSED WITH ONE
 HOUR RATED CONSTRUCTION. ONE HOUR FIRE
 RATED GLASS BLOCK MAY BE USED.
  
 NOTE: SEE NOTES AND MARKINGS ON PLAN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-27 Cont ID  
Sent By rmcdouga Date 2006-04-27 Time 09:42 Rev Time 0.00
Received By rmcdouga Date 2006-04-27 Time 09:42 Sent To  
Notes
2006-04-27 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT PLANS DRAWN TO A MINIMUM 1/8"
 SCALE AS REQUIRED BY FBC*106.1.3 CITY
 AMENDMENTS. INDICATE ON THE PLANS THE
 AREAS THAT WILL HAVE THE DRYWALL
 REPLACED. INDICATE IF INSULATION WILL BE
 REPLACED AND SPECIFY THE R-VALUE.
 SPECIFY THE WALLS THAT WILL BE REMOVED.
  
 3)FBC 106.1.1 INDICATE THE SCOPE OF THE
 WORK ON THE PLANS. PROVIDE A COMPETE
 DESCRIPTION OF ALL THE WORK TO BE
 PERFORMED.
  
 4) ADDRESSING ISSUES WILL NEED TO BE
 RESOLVED BEFORE A PERMITS IS ISSUED.
 HAVING TWO SEPARATE BUILDINGS ON ONE
 PERMIT MAY BE A PROBLEM FOR INSPECTIONS
 AND BEFORE A C.O. OR C.C. CAN BE ISSUED
 THE WORK IN BOTH BUILDINGS WILL BE
 REQUIRED TO BE COMPLETED. CONTRACTOR MAY
 WISH TO PERMIT WORK IN EACH BUILDING
 SEPARATELY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-02-05 Cont ID  
Sent By btrobaug Date 2007-02-05 Time 07:49 Rev Time 1.00
Received By btrobaug Date 2007-02-05 Time 06:48 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-12-20 Cont ID  
Sent By btrobaug Date 2006-12-20 Time 15:20 Rev Time 1.00
Received By btrobaug Date 2006-12-20 Time 14:32 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-04 Cont ID  
Sent By btrobaug Date 2006-10-04 Time 07:26 Rev Time 1.00
Received By btrobaug Date 2006-10-04 Time 06:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-11 Cont ID  
Sent By btrobaug Date 2006-09-05 Time 13:42 Rev Time 1.00
Received By btrobaug Date 2006-09-05 Time 07:57 Sent To  
Notes
2006-09-05 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH INSPECTION. ALLOW
 AT LEAST ONE WEEK IN REVIEW. SHEET E-01
 IS THE ONLY REVISION REQUIRED FOR THIS
 REVIEW. OTHER SHEETS NEED ONLY BE
 REVISED FOR FIELD CHANGES.
  
 THE GROUNDING ELECTRODE CONDUCTOR SHOULD
 BE CONNECTED TO THE GROUNDED (NEUTRAL)
 CONDUCTOR IN THE GUTTER, AHEAD OF THE
 INDIVIDUAL METERS, COMMON TO ALL FEEDS,
 BOTH SERVICES. SEE ILLISTRATION 250.10,
 2002 NEC HANDBOOK.
  
 THE GROUNDING ELECTRODE CONDUCTOR MUST
 BE 3/0 CU. ON BUILDING "A" TO COMPLY
 WITH 250.66.
  
 THERE SHOULD NOT BE A GROUND WIRE IN THE
 RISER. 250.6, BOTH SERVICES.
  
 THE NOTE "TYPICAL BEFORE AND AFTER
 METER", AND THE GROUND FROM THE GUTTER
 TO THE METER SHOWN IN BUILDING "B"
 SERVICE, SHOULD BE REMOVED. 250.6,
 OBJECTIONABLE CURRENTS, PARALLELING
 PATHS.
  
 SEE BUILDING PLAN REVIEW NOTES AND
 REVISE ELECTRICAL PLANS AS NEEDED.
 INCORPORATE ELECTRICAL PLANS INTO THE
 SUBMITTED SET, REMOVE OLD SHEETS,
 SUBMIRT ONE SET OF OLD SHEETS TO AID
 REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-03 Cont ID  
Sent By btrobaug Date 2006-08-03 Time 09:29 Rev Time 0.75
Received By btrobaug Date 2006-08-03 Time 06:25 Sent To  
Notes
2006-08-03 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PLEASE SHOW COMPLIANCE WITH CHAPTER 13
 FBC ENERGY CODE. INDICATE SENSORS AND
 TIMER LOCATION ON THE PLAN.
  
 SHEET E-1 BUIULDING"A" DOES NOT SHOW
 EMERGENCY CIRCUITS ON WITH LOCAL
 CIRCUITS PER 701.11(F).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-14 Cont ID  
Sent By btrobaug Date 2006-04-14 Time 07:26 Rev Time 0.75
Received By btrobaug Date 2006-04-14 Time 07:26 Sent To  
Notes
2006-04-14 00:00:00 
 THERE IS NOT SUFFICIENT CLARITY TO
 REVIEW THE PLANS SUBMITTED. PLEASE HAVE
 PLANS REDRAWN AND RESUBMIT SAME. 106.1.3
 FBC ADMINISTRATIVE SECTIION.
  
 THERE APPEARS TO BE ELECTRICAL SYMBOLS
 ON THE PLAN, PLEASE INDICATE IF ALL IS
 NEW WORK OR CLARIFY THE PORTION THAT IS.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN OF THE PLAN MUST PRINT NAME AND
 SIGN SAME. IF AN ARCHITECT OR ENGINEER,
 MUST BE IN COMPLIANCE WITH 481 AND 471
 FS. THE PLAN SUBMITTED HAS AN ENGINEERS
 TITLE BLOCK.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-05 Cont ID  
Sent By mawillia Date 2006-10-05 Time 17:10 Rev Time 0.00
Received By mawillia Date 2006-10-05 Time 17:09 Sent To  
Notes
2006-10-05 00:00:00*****APPROVED W/REMINDERS*****
  
  
  
  
 1.) NUMERICAL ADDRESS OF NO LESS THAN 6"
 IN HEIGHT AND 1" IN WIDTH TO BE ON THE
 BUILDING VISIBLE FROM GEORGIA AVENUE.
 IDENTIFYING NUBERS OR ALPHABETS OF 3" IN
 HEIGHT ARE REQUIRED FOR SUITES OR TENANT
 SPACES. IF TENANT SPACES ARE EQUIPPED
 WITH A REAR DOOR, A NUMBER IS REQUIRED
 ON THE DOOR.
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-03 Cont ID  
Sent By mawillia Date 2006-08-03 Time 15:58 Rev Time 0.00
Received By mawillia Date 2006-08-03 Time 15:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-21 Cont ID  
Sent By mwennerg Date 2006-04-21 Time 11:01 Rev Time 0.00
Received By mwennerg Date 2006-04-21 Time 11:01 Sent To  
Notes
2006-04-21 00:00:00******DENIED******
  
 PLEASE NOTE THAT NOT ENOUGH INFORMATION
 SUBMITTED FOR FIRE REVIEW AT THIS TIME.
 PLEASE INDICATE IF WORK WILL IMPACT
 EXISTING FIRE PROTECTION EQUIPMENT, EXIT
 SIGNS/EMERGENCY LIGHTING ETC.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-01-30 Cont ID  
Sent By adarroug Date 2007-01-30 Time 17:39 Rev Time 0.00
Received By adarroug Date 2007-01-30 Time 17:39 Sent To  
Notes
2007-01-30 17:39:40TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-12-20 Cont ID  
Sent By adarroug Date 2006-12-20 Time 11:54 Rev Time 0.00
Received By adarroug Date 2006-12-20 Time 11:54 Sent To E
Notes
2006-12-20 11:54:58TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-12-04 Cont ID  
Sent By rmcdouga Date 2006-12-04 Time 11:46 Rev Time 0.00
Received By rmcdouga Date 2006-12-04 Time 11:46 Sent To  
Notes
2006-12-04 11:47:53ROUTED TO FIRE AND PLUMBING FOR REVIEWS.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-29 Cont ID  
Sent By spalmer Date 2006-11-29 Time 20:01 Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 20:01 Sent To B
Notes
2006-11-29 20:02:19REV/TO RMCDOUGAL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 17:19 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 17:19 Sent To  
Notes
2006-09-26 00:00:00TO "BOB"#8
2006-09-23 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 11:49 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 11:49 Sent To  
Notes
2006-08-28 00:00:00TO "BOB"#5
2006-08-16 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-17 Cont ID  
Sent By adarroug Date 2006-07-17 Time 16:17 Rev Time 0.00
Received By adarroug Date 2006-07-17 Time 16:17 Sent To  
Notes
2006-07-20 00:00:00TO "BOB"#15
2006-07-17 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-27 Cont ID  
Sent By rmcdouga Date 2006-04-27 Time 09:42 Rev Time 0.00
Received By rmcdouga Date 2006-04-13 Time 15:57 Sent To  
Notes
2006-04-13 00:00:00TO "BOB"#9

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-04-14 Cont ID  
Sent By tgordon Date 2006-04-14 Time 09:12 Rev Time 0.20
Received By tgordon Date 2006-04-14 Time 09:12 Sent To  
Notes
2006-04-14 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-12-04 Cont ID  
Sent By jleech Date 2006-12-04 Time 12:18 Rev Time 0.00
Received By jleech Date 2006-12-04 Time 12:18 Sent To  
Notes
2006-12-04 12:20:44REVISION;
 CHANGED FROM HI-LOW DRINKING FOUNTAINS TO SINGLE D/F'S
 WITH CUP DISPENSOR.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-10-10 Cont ID  
Sent By jleech Date 2006-10-10 Time 14:40 Rev Time 0.00
Received By jleech Date 2006-10-10 Time 14:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-09 Cont ID  
Sent By jleech Date 2006-09-09 Time 09:20 Rev Time 0.00
Received By jleech Date 2006-09-09 Time 09:01 Sent To  
Notes
2006-09-09 00:00:00DENIED;
 1.BATHROOMS TO BE HANDICAP ACCESSIBLE.
 FBC-2004 EXISTING BUILDING CODE SECTION
 606.1. SHOW SIZE OF BATHROOM, CLEAR
 FLOOR SPACE, AND TURNING RADIUS IN ALL
 BATHROOMS. BATHROOM DOORS CAN NOT SWING
 INTO THE CLEAR FLOOR SPACE OF THE
 LAVATORY.
 2.EXISTING BUILDING CODE SECTION 810.1,
 IF THERE IS AN OCCUPANCY CHANGE THE NEW
 OCCUPANCY IS SUBJECT TO DIFFERENT
 PLUMBING FIXTURE REQUIREMENTS. SEE
 FBC-2004 PLUMBING TABLE 403.1. DRINKING
 FOUNTAINS WOULD BE REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By jleech Date 2006-04-14 Time 13:33 Rev Time 0.00
Received By jleech Date 2006-04-14 Time 13:33 Sent To  
Notes
2006-04-14 00:00:00NO PLUMBING SHOWN ON PAPER WORK
 SUBMITED.