| Plan Review Stops For Permit 06040370 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-05-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-05-15 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-05-15 |
Time |
14:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-05-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-05-04 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-05-04 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2006-05-04 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2004 | | | | | | 1.)PROVIDE ANCHORING INFORMATION TO | | | COMPLY WITH FBC1609.1.3; STRUCTURAL | | | MEMBERS AND SYSTEMS, AND COMPONENTS AND | | | CLADDING IN A BUILDING OR STRUCTURE | | | SHALL BE ANCHORED TO RESIST WIND-INDUCED | | | OVERTURNING, UPLIFT AND SLIDING AND TO | | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | | FORCES TO THE FOUNDATION.WHERE A | | | PORTION OF THE RESISTANCE TO THESE | | | FORCES IS PROVIDED BY DEAD LOAD, THE | | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE | | | USED. | | | | | | YOU HAVE PROVIDED INFORMATION IN REGARDS | | | TO THE SLAB, AND PRODUCT INFORMATION WAS | | | PROVIDED FOR TAPCONS, BUT THERE ARE | | | SEVERAL DIFFERENT PRODUCTS ON THE SHEETS | | | SUBMITTED WITH DIFFERENT VALUES. | | | SPECIFY WHICH ANCHOR YOU ARE USING | | | (CIRCLE) AND THE NUMBER OF ANCHORS TO BE | | | USED. | | | | | | 2.)PROVIDE WIND DESIGN CRITERIA | | | FBC1603.1.4. | | | | | | 3.)DOCUMENTS PREPARED BY AN ARCHITECT | | | AND SUBMITTED FOR PUBLIC RECORD ARE TO | | | BE SIGNED, SEALED, DATED ORIGINALS (SITE | | | PLAN).NOTE THAT A SEALED SITE PLAN FOR | | | THIS JOB IS NOT REQUIRED, BUT SINCE IT | | | WAS PREPARED BY AN ARCHITECT IT IS | | | REQUIRED TO BE SEALED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2006-09-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-17 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-17 |
Time |
11:10 |
Sent To |
PC |
|
| Notes |
| 2006-09-17 00:00:00 | REV OK, REDLINED THE 70A DISCONNECT | | | WHICH IS REQUIRED TO HAVE OCP. | | | 240.21 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2006-08-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-31 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-31 |
Time |
12:41 |
Sent To |
PC |
|
| Notes |
| 2006-08-31 00:00:00 | ** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE OCP ON TH GENERATOR | | | SIZE IS AT 200A'S WHICH IS FEEDING #3'S. | | | PLEASE SEE 240.21, AS TAPPED CONDUCTORS | | | MUST TERMINATE IN OCP WHICH PROTECTS THE | | | CONDUCTORS. | | | PLEASE ALSO SEE AS THE EXISTING SUB | | | PANELS DOES NOT INDICATE ANY SIZES , NOR | | | DO THEY INDICATE A MCB WHICH WOULD ALSO | | | LIMIT THE LOAD. | | | PLEASE REVISE RISER. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE QUESTIONS, PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2006-08-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-09 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-09 |
Time |
11:52 |
Sent To |
PC |
|
| Notes |
| 2006-08-09 00:00:00 | APPLS ROUTED TO ADRIANNA M. | | | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE ELECTRICAL RISER NOW | | | INDICATES TWO NEW ATS'S WHICH WERE NEVER | | | SUBMITTED FOR REVIEW. | | | PLEASE SUBMIT SPECS/MANUFACTURES CUT | | | SHEETS. | | | 110.3,90.8 | | | PLEASE ALSO CALRIFY RISER. PLEASE SEE | | | RISER DOES NOT INDICATE WHERE FEEDERS GO | | | TO LOADS. IT APPEARS THEY RUN BACK | | | THROUGH THE MLO PANEL AND USING PANEL AS | | | A RACEWAY. | | | 408.16. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-06-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-01 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-01 |
Time |
09:38 |
Sent To |
PC |
|
| Notes |
| 2006-06-01 00:00:00 | MAINS GROUPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-05-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-05-15 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-05-15 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2006-05-15 00:00:00 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE NOTE #2 FROM | | | PREVIOUS REVIEW. PLEASE SEE MISSING | | | DISCONNECT FOR FEEDERS FROM GEN. | | | PLEASE SEE THIS DISCONNECT SHALL BE | | | GROUPED WITH EXISTING MAIN. | | | THIS DISICONNECT DOES NOT NEED TO | | | CONTAIN OCP, ONLY A DISCONNECTING MEANS | | | RATED FOR THE LOAD SERVED. | | | PLEASE SEE 225.31-225.39 | | | | | | 2) NOTE: PLEASE SEE EXISTING GE SYSTEM | | | IS NOW ONLY SHOWING A SINGLE GROUND ROD, | | | HOWEVER IT IS KNOW TO THIS OFFICE THAT | | | THE CWP SYSTEM IN THIS BUILDING IS | | | METAL. PLEASE SEE 250.50, 250.52 ETC. | | | | | | 3) NOTE: PLEASE HIGH LIGHT ATS BEING | | | INSTALLED, AS THE SPECS SUBMITTED | | | INDICATE MORE THAN ONE UNIT. | | | | | | | | | ** PLEASE SUBMIT TWO COMPLETE SETS WITH | | | ALL NEW SHEETS INSERTED INTO THE | | | COMPLETED SETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-04-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-19 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-19 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2006-04-19 00:00:00 | ********** UNSAT *********** | | | | | | 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS | | | FOR EXISTING LOADS INTENDED FOR USE. | | | SINCE THE GEN WILL BE FEEDING THE ENTIRE | | | SERVICE, PLEASE SUBMIT LOAD CALCS | | | ACCORDINGLY. | | | PLEASE KNOW, AUTOMATIC LOAD SHEDDING IS | | | PERMITTED. | | | 702,220,215.5 | | | | | | 2) NOTE: PLEASE SEE EXISTING 400 MLO IS | | | SHOWN AS A DISCONNECT? THIS IS NOT | | | CLEAR, IS THIS A MLO PANEL? | | | IN EITHER CASE PLEASE INCLUDE A DISC'S | | | GROUPED AND NOT MORE THAN 6 IS PERMITTED | | | OR 6 SPACES ARE PERMIITED. | | | 230.76,230.76,230.70,230.72, | | | 225.31-225.39 | | | PLEASE KNOW, ALL MAINS AND DISCONNECTING | | | MEANS SHALL BE GROUPED. | | | (BRKR ON GEN IS NOT INCLUDED WITH THE | | | MEANS OF DISC.) | | | PLEASE PROVIDE A LAY OUT FOR SERVICE AND | | | LOCATION ON SITE. | | | | | | 3)NOTE: PLEASE PROVIDE THE OCP ON RISER | | | FOR GEN. (IT IS NOTED IN SPECS AT | | | 200A'S). | | | | | | 4) NOTE: PLEASE VERIFY THE GROUNDING | | | ELECTRODE SYSTEM AT SERVICE AS ONE | | | GROUND ROD IS NOT SUFFICIENT. | | | 250.50,250.56, CWP? 2 GRND ROD? | | | | | | 5) NOTR: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT/MAINS. PLEASE SEE THAT | | | NEW MAIN AND EXISTING SERVICE MUST BE | | | RATED FOR THE AVAILABLE FUALT CURRENT | | | FROM FPL AND FROM GENERATOR. | | | 110.9, 215.5, NFPA-110 CHAPTER 7 | | | | | | | | | PLEASE SEE ANY OTHER COMMENTS FROM OTHER | | | TRADES WHICH MAY AFFECT PLANS. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2006-04-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-04-21 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-04-21 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2006-04-21 00:00:00 | ******PROVISO****** | | | | | | 1) PLEASE SEE MECHANICAL REVIEW COMMENTS | | | REGARDING EXHAUST LOCATION REQUIREMENTS. | | | | | | 2) WORK SHALL COMPLY WITH NFPA 110 AND | | | NFPA 1, 2003 EDITIONS. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
1 |
Status |
N |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-04-29 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-04-29 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2006-05-17 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-05-17 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-05-17 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2006-05-17 00:00:00 | RE SUB APPROVEDOK TO PRINT PERMIT PES |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-04-29 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-04-29 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2006-04-29 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | ENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | UNSAT | | | | | | 1)IF THIS IS AN EXISTING GAS METER | | | ,PROVIDE THE TOTAL BTU LOAD, AND TOT. | | | DEVELOPED LENGTH TO THE FURTHEST | | | APPLIANCE. | | | 2) SHOW LOCATION OF GAS REGULATOR AND | | | PROVIDE A MANFACTURE CUT SHEET, ALSO | | | PURPOSE OF REGULATOR. | | | 3) 720 ISBTU'S / CU FT.TOTAL BTU'S IN | | | ONE CU.FT. 1050 X 720 = 756 BTU'S /HR IS | | | THE TOTAL BTU'S. | | | 4)FBC FUEL GAS 2004 TAB. 402.4 (20) FOR | | | POLYETHYLENE PLASTIC PIPE, FOR 756- K | | | BTU'S SHOULD BE 1-1/2" PE PIPE. | | | 5) SHOW THE LOCATION OF THE GAS METER ON | | | SITE PLAN. | | | END OF COMMENTS QUESTIONS 561-805-6692 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-09-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-11 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-11 |
Time |
11:46 |
Sent To |
E |
|
| Notes |
| 2006-09-11 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-08-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-23 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-23 |
Time |
09:32 |
Sent To |
E |
|
| Notes |
| 2006-08-23 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-08-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-23 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-23 |
Time |
09:03 |
Sent To |
P |
|
| Notes |
| 2006-08-23 00:00:00 | TO "PSHMITZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-07 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-07 |
Time |
09:39 |
Sent To |
E |
|
| Notes |
| 2006-08-07 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-05-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-24 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-24 |
Time |
16:31 |
Sent To |
E |
|
| Notes |
| 2006-05-24 00:00:00 | TO "BTROBAUG" DESK/RESUB-EXPEDITED PLANS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-05-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-15 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-15 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2006-05-15 00:00:00 | TO "BOB"#1--EXPEDITED PLANS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-05-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-05-08 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-04-11 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2006-04-11 00:00:00 | TO "COMM" BD#30--EXPIDITED PLAN PER | | | "RBROWN" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-04-20 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-04-20 |
Time |
08:21 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2006-04-20 |
Time |
08:21 |
Sent To |
|
|
| Notes |
| 2006-04-20 00:00:00 | *** PROVISO *** | | | 1)GENERATOR EXHUST MUST BE TEN FEET AWAY | | | FROM ANY BUILDING OPENINGS (WINDOWS, | | | DOORS, ROOF & EAVE VENTS), AND TEN FEET | | | AWAY FROM ADJECENT BUILDING OPENS. PER | | | 2004 FBC/M 401.5.1 . | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-04-29 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-04-29 |
Time |
11:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-05-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-05-08 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-05-08 |
Time |
14:46 |
Sent To |
|
|
| Notes |
|
|