Plan Review Details - Permit 06040370
Plan Review Stops For Permit 06040370
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By shill Date 2006-05-15 Time 14:43 Rev Time 0.00
Received By shill Date 2006-05-15 Time 14:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-04 Cont ID  
Sent By shill Date 2006-05-04 Time 09:38 Rev Time 0.00
Received By shill Date 2006-05-04 Time 09:38 Sent To  
Notes
2006-05-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1609.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 YOU HAVE PROVIDED INFORMATION IN REGARDS
 TO THE SLAB, AND PRODUCT INFORMATION WAS
 PROVIDED FOR TAPCONS, BUT THERE ARE
 SEVERAL DIFFERENT PRODUCTS ON THE SHEETS
 SUBMITTED WITH DIFFERENT VALUES.
 SPECIFY WHICH ANCHOR YOU ARE USING
 (CIRCLE) AND THE NUMBER OF ANCHORS TO BE
 USED.
  
 2.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4.
  
 3.)DOCUMENTS PREPARED BY AN ARCHITECT
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS (SITE
 PLAN).NOTE THAT A SEALED SITE PLAN FOR
 THIS JOB IS NOT REQUIRED, BUT SINCE IT
 WAS PREPARED BY AN ARCHITECT IT IS
 REQUIRED TO BE SEALED.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 11:10 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 11:10 Sent To PC
Notes
2006-09-17 00:00:00REV OK, REDLINED THE 70A DISCONNECT
 WHICH IS REQUIRED TO HAVE OCP.
 240.21

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-08-31 Cont ID  
Sent By dpalmer Date 2006-08-31 Time 12:41 Rev Time 0.00
Received By dpalmer Date 2006-08-31 Time 12:41 Sent To PC
Notes
2006-08-31 00:00:00** UNSAT ***
  
 1) NOTE: PLEASE SEE OCP ON TH GENERATOR
 SIZE IS AT 200A'S WHICH IS FEEDING #3'S.
 PLEASE SEE 240.21, AS TAPPED CONDUCTORS
 MUST TERMINATE IN OCP WHICH PROTECTS THE
 CONDUCTORS.
 PLEASE ALSO SEE AS THE EXISTING SUB
 PANELS DOES NOT INDICATE ANY SIZES , NOR
 DO THEY INDICATE A MCB WHICH WOULD ALSO
 LIMIT THE LOAD.
 PLEASE REVISE RISER.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE QUESTIONS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-09 Cont ID  
Sent By dpalmer Date 2006-08-09 Time 16:49 Rev Time 0.00
Received By dpalmer Date 2006-08-09 Time 11:52 Sent To PC
Notes
2006-08-09 00:00:00APPLS ROUTED TO ADRIANNA M.
 ** UNSAT **
  
 1) NOTE: PLEASE SEE ELECTRICAL RISER NOW
 INDICATES TWO NEW ATS'S WHICH WERE NEVER
 SUBMITTED FOR REVIEW.
 PLEASE SUBMIT SPECS/MANUFACTURES CUT
 SHEETS.
 110.3,90.8
 PLEASE ALSO CALRIFY RISER. PLEASE SEE
 RISER DOES NOT INDICATE WHERE FEEDERS GO
 TO LOADS. IT APPEARS THEY RUN BACK
 THROUGH THE MLO PANEL AND USING PANEL AS
 A RACEWAY.
 408.16.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-01 Cont ID  
Sent By dpalmer Date 2006-06-01 Time 09:38 Rev Time 0.00
Received By dpalmer Date 2006-06-01 Time 09:38 Sent To PC
Notes
2006-06-01 00:00:00MAINS GROUPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-15 Cont ID  
Sent By dpalmer Date 2006-05-15 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2006-05-15 Time 12:07 Sent To  
Notes
2006-05-15 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE NOTE #2 FROM
 PREVIOUS REVIEW. PLEASE SEE MISSING
 DISCONNECT FOR FEEDERS FROM GEN.
 PLEASE SEE THIS DISCONNECT SHALL BE
 GROUPED WITH EXISTING MAIN.
 THIS DISICONNECT DOES NOT NEED TO
 CONTAIN OCP, ONLY A DISCONNECTING MEANS
 RATED FOR THE LOAD SERVED.
 PLEASE SEE 225.31-225.39
  
 2) NOTE: PLEASE SEE EXISTING GE SYSTEM
 IS NOW ONLY SHOWING A SINGLE GROUND ROD,
 HOWEVER IT IS KNOW TO THIS OFFICE THAT
 THE CWP SYSTEM IN THIS BUILDING IS
 METAL. PLEASE SEE 250.50, 250.52 ETC.
  
 3) NOTE: PLEASE HIGH LIGHT ATS BEING
 INSTALLED, AS THE SPECS SUBMITTED
 INDICATE MORE THAN ONE UNIT.
  
  
 ** PLEASE SUBMIT TWO COMPLETE SETS WITH
 ALL NEW SHEETS INSERTED INTO THE
 COMPLETED SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-19 Cont ID  
Sent By dpalmer Date 2006-04-19 Time 12:13 Rev Time 0.00
Received By dpalmer Date 2006-04-19 Time 11:38 Sent To  
Notes
2006-04-19 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 FOR EXISTING LOADS INTENDED FOR USE.
 SINCE THE GEN WILL BE FEEDING THE ENTIRE
 SERVICE, PLEASE SUBMIT LOAD CALCS
 ACCORDINGLY.
 PLEASE KNOW, AUTOMATIC LOAD SHEDDING IS
 PERMITTED.
 702,220,215.5
  
 2) NOTE: PLEASE SEE EXISTING 400 MLO IS
 SHOWN AS A DISCONNECT? THIS IS NOT
 CLEAR, IS THIS A MLO PANEL?
 IN EITHER CASE PLEASE INCLUDE A DISC'S
 GROUPED AND NOT MORE THAN 6 IS PERMITTED
 OR 6 SPACES ARE PERMIITED.
 230.76,230.76,230.70,230.72,
 225.31-225.39
 PLEASE KNOW, ALL MAINS AND DISCONNECTING
 MEANS SHALL BE GROUPED.
 (BRKR ON GEN IS NOT INCLUDED WITH THE
 MEANS OF DISC.)
 PLEASE PROVIDE A LAY OUT FOR SERVICE AND
 LOCATION ON SITE.
  
 3)NOTE: PLEASE PROVIDE THE OCP ON RISER
 FOR GEN. (IT IS NOTED IN SPECS AT
 200A'S).
  
 4) NOTE: PLEASE VERIFY THE GROUNDING
 ELECTRODE SYSTEM AT SERVICE AS ONE
 GROUND ROD IS NOT SUFFICIENT.
 250.50,250.56, CWP? 2 GRND ROD?
  
 5) NOTR: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT/MAINS. PLEASE SEE THAT
 NEW MAIN AND EXISTING SERVICE MUST BE
 RATED FOR THE AVAILABLE FUALT CURRENT
 FROM FPL AND FROM GENERATOR.
 110.9, 215.5, NFPA-110 CHAPTER 7
  
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT PLANS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-04-21 Cont ID  
Sent By mwennerg Date 2006-04-21 Time 11:30 Rev Time 0.00
Received By mwennerg Date 2006-04-21 Time 11:30 Sent To  
Notes
2006-04-21 00:00:00******PROVISO******
  
 1) PLEASE SEE MECHANICAL REVIEW COMMENTS
 REGARDING EXHAUST LOCATION REQUIREMENTS.
  
 2) WORK SHALL COMPLY WITH NFPA 110 AND
 NFPA 1, 2003 EDITIONS.
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-04-29 Cont ID  
Sent By pschmitz Date 2006-04-29 Time 10:34 Rev Time 0.00
Received By pschmitz Date 2006-04-29 Time 10:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-05-17 Cont ID  
Sent By pschmitz Date 2006-05-17 Time 10:48 Rev Time 0.00
Received By pschmitz Date 2006-05-17 Time 10:48 Sent To  
Notes
2006-05-17 00:00:00RE SUB APPROVEDOK TO PRINT PERMIT PES

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-04-29 Cont ID  
Sent By pschmitz Date 2006-04-29 Time 10:34 Rev Time 0.00
Received By pschmitz Date 2006-04-29 Time 10:34 Sent To  
Notes
2006-04-29 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 ENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1)IF THIS IS AN EXISTING GAS METER
 ,PROVIDE THE TOTAL BTU LOAD, AND TOT.
 DEVELOPED LENGTH TO THE FURTHEST
 APPLIANCE.
 2) SHOW LOCATION OF GAS REGULATOR AND
 PROVIDE A MANFACTURE CUT SHEET, ALSO
 PURPOSE OF REGULATOR.
 3) 720 ISBTU'S / CU FT.TOTAL BTU'S IN
 ONE CU.FT. 1050 X 720 = 756 BTU'S /HR IS
 THE TOTAL BTU'S.
 4)FBC FUEL GAS 2004 TAB. 402.4 (20) FOR
 POLYETHYLENE PLASTIC PIPE, FOR 756- K
 BTU'S SHOULD BE 1-1/2" PE PIPE.
 5) SHOW THE LOCATION OF THE GAS METER ON
 SITE PLAN.
 END OF COMMENTS QUESTIONS 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-11 Cont ID  
Sent By adarroug Date 2006-09-11 Time 11:46 Rev Time 0.00
Received By adarroug Date 2006-09-11 Time 11:46 Sent To E
Notes
2006-09-11 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-23 Cont ID  
Sent By adarroug Date 2006-08-23 Time 09:32 Rev Time 0.00
Received By adarroug Date 2006-08-23 Time 09:32 Sent To E
Notes
2006-08-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-23 Cont ID  
Sent By adarroug Date 2006-08-23 Time 09:03 Rev Time 0.00
Received By adarroug Date 2006-08-23 Time 09:03 Sent To P
Notes
2006-08-23 00:00:00TO "PSHMITZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-07 Cont ID  
Sent By adarroug Date 2006-08-07 Time 09:39 Rev Time 0.00
Received By adarroug Date 2006-08-07 Time 09:39 Sent To E
Notes
2006-08-07 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-05-24 Time 16:31 Rev Time 0.00
Received By adarroug Date 2006-05-24 Time 16:31 Sent To E
Notes
2006-05-24 00:00:00TO "BTROBAUG" DESK/RESUB-EXPEDITED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-15 Cont ID  
Sent By adarroug Date 2006-05-15 Time 08:31 Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 08:31 Sent To  
Notes
2006-05-15 00:00:00TO "BOB"#1--EXPEDITED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-08 Cont ID  
Sent By mmclean Date 2006-05-08 Time 14:46 Rev Time 0.00
Received By mmclean Date 2006-04-11 Time 14:46 Sent To  
Notes
2006-04-11 00:00:00TO "COMM" BD#30--EXPIDITED PLAN PER
 "RBROWN"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-04-20 Cont ID  
Sent By tgordon Date 2006-04-20 Time 08:21 Rev Time 0.15
Received By tgordon Date 2006-04-20 Time 08:21 Sent To  
Notes
2006-04-20 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-04-29 Cont ID  
Sent By pschmitz Date 2006-04-29 Time 11:12 Rev Time 0.00
Received By pschmitz Date 2006-04-29 Time 11:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-05-08 Cont ID  
Sent By mmclean Date 2006-05-08 Time 14:46 Rev Time 0.00
Received By mmclean Date 2006-05-08 Time 14:46 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved