| 2006-08-01 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | NOTE - NEW PLAN SUBMITTED | | | | | | 1.)ROOMS/AREAS ARE TO BE LABELED AS TO | | | USE. | | | | | | 2.)THE SCOPE OF WORK IS NOT CLEAR. | | | ARE ALL OF THE WALLS AND DOORS SHOWN | | | NEW?NO WALL LEGEND WAS PROVIDED.ARE | | | THE INDIVIDUAL SPACES WALLS OR CUBICLES? | | | | | | 3.)PROVIDE DOOR DIMENSIONS, | | | FBC1008.1.1. | | | | | | 4.)ARE THE BATHROOMS NEW?IF THEY ARE | | | NEW OR ARE BEING RENOVATED, PROVIDE ALL | | | DETAILS FOR ACCESSIBILITY.FBC11-4.1.6. | | | | | | 5.)NO NOTES WERE MADE ON THE FLOOR | | | PLAN AS TO NEW OR EXISTING.IF THIS IS | | | A NEW FLOOR PLAN, THIS IS NOT A LEVEL I | | | ALTERATION.SEE FBC EB 303 AND 304. | | | SCOPE OF WORK IS NOT CLEAR. | | | | | | 6.)DOORS ARE TO COMPLY WITH | | | FBC11-4.13.6.THERE ARE SEVERAL DOORS | | | SHOWN WHICH DO NOT MEET THE MANEUVERING | | | CLEARANCE REQUIREMENT, SEE ALSO FBC11 | | | FIGURE 19. | | | | | | 7.)TENANT SEPARATION IS NOT CLEAR. | | | SHOW ANY REQUIRED FIRE RESISTANCE ON THE | | | PLAN. | | | | | | 8.)PROVIDE EXITING INFORMATION.THERE | | | ARE TWO DOORS AND A HALLWAY LEADING INTO | | | THE AREA SHOWN AS OPEN SPACE, BUT WHICH | | | IS PROBABLY A SECTION OF THE FLOOR WHICH | | | IS NOT UNDER THIS PERMIT. | | | | | | 9.)NEW COMMENTS WERE TRIGGERED DUE TO | | | NEW PLANS SUBMITTED.THE ARCHITECTURAL | | | PLANS WHICH WERE PREVIOUSLY REVIEWED | | | WERE NOT SUBMITTED, ONLY AN OLD FLOOR | | | PLAN FROM 1997.THE PREVIOUS PLAN | | | INDICATED A SCOPE OF WORK.THIS PLAN | | | SHOWS ONLY WALLS AND DOORS, AND SOME | | | DIMENSIONS, BUT DOES NOT GIVE | | | INFORMATION AS TO THE WORK TO BE DONE. | | | | | | 10.)FROM PREVIOUS REVIEW #4, SIGN | | | OWNER/AGENT LINE OF THE ENERGY CALCS, | | | FBC13-103.1. | | | | | | 11.)FROM PREVIOUS REVIEW #5, ON PAGE 5 | | | OF THE ENERGY CALC, EITHER INDICATE THAT | | | THESE ITEMS HAVE BEEN CHECKED OR WRITE | | | NA. | | | | | | 12.)SEE THE NOTE ON THE BOTTOM OF THE | | | ENERGY CALC, INPUT REPORT PRINTOUT FROM | | | ENERGY GUAGE COM MUST BE SUBMITTED WITH | | | THE COMPLIANCE REPORT. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-07-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-07-07 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-07-07 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2006-07-07 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)PLANS ARE NOT SIGNED AND SEALED. | | | | | | 2.)DECLARE GOVERNING CODE. | | | | | | 3.)DECLARE LEVEL OF ALTERATION FBC EB | | | CHAPTER 3. | | | | | | 4.)SIGN OWNER/AGENT LINE OF THE ENERGY | | | CALCS, FBC13-103.1. | | | | | | 5.)ON PAGE 5 OF THE ENERGY CALC, | | | EITHER INDICATE THAT THESE ITEMS HAVE | | | BEEN CHECKED OR WRITE NA. | | | | | | 6.)PROVIDE HALLWAY DIMENSION AT THE | | | NEW OFFICES (NEW PARTITION WALL TO | | | EXISTING WALL), FBC10. | | | | | | 7.)PROVIDE A CODE SUMMARY.INCLUDE | | | BUILDING SIZE, HEIGHT, MINIMUM BUILDING | | | TYPE FBC6 (INCLUDING A OR B), SPRINKLED | | | OR UNPRINKLED, OCCUPANCY FBC3. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-05-05 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2006-05-05 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2006-05-05 |
Time |
09:21 |
Sent To |
R |
|
| Notes |
| 2006-05-05 00:00:00 | A PRE-INSPECT WAS PERFORMED BY DN ON | | | 5/4/06.IT WAS OBSERVED THAT THE INTERIOR | | | DEMOLITION WAS COMPLETED WITH NO | | | PERMITS:PARTIAL FLOOR PLAN SECTION/PHASE | | | ONE.ALSO IT WAS NOTED THAT EXISTING | | | WALLS WERE REMOVED:4X FEE FOR COMMENCING | | | WORK PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT,FBC 105.1/109.3.WE HAVE | | | DETERMINED, UPON THE COMPLETION OF THE | | | PREINSPECT, THAT THE SUBJECT PERMIT | | | APPLICATION/PLAN BE REVIEWED FOR A LEVEL | | | 2 ALTERATION AND ALL WORK SHALL CONFORM | | | TO FBC SECTION 601/EXISTING BUILDING | | | CODE.THE CONTRACTOR WAS ALSO ADVISED | | | THAT ENERGY CALCULATIONS SHALL BE | | | SUBMITTED FOR PLAN REVIEW AND MECHANICAL | | | /ELECTRICAL PERMITS ARE | | | REQUIRED.THERFORE, THE | | | PRE-INSPECT/PERMIT ISSUANCE IS DENIED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-08-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-08-09 |
Time |
12:26 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-08-09 |
Time |
12:07 |
Sent To |
REV |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-07-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-22 |
Time |
20:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-22 |
Time |
18:49 |
Sent To |
|
|
| Notes |
| 2006-07-22 00:00:00 | ** UNSAT ** | | | | | | ** PLEASE SEE SOME INFORMATION FROM | | | PREVIOUS REVIEW STILL NEEDS TO BE | | | ADDRESSED ALONG WITH NEW COMMENT(S). | | | | | | 1) NOTE: PLEASE SEE COMPLIANCE WITH FBC | | | CHAPTER 13 AS PREVIOUSLY NOTED. PLEASE | | | SEECOMPLIANCE WITH FBC CHAPTER 13 THEN | | | PLEASE SEE THE FOLLOWING: | | | 13-415.1.ABC.1.1, .1.2, AND .1.3 | | | PLEASE PROVIDE OVER-RIDES LOCATED AT THE | | | ENTRANCE INTO SPACE WHERE OCCUPANT CAN | | | CLEARLY SEE LIGHTING IN WHICH IS BEING | | | CONTROLLED. | | | PLEASE SEE SOME SYMBOLS ARE BEING SHOWN | | | AT DOORS HOWEVER THESE ARE NOT CLEAR AS | | | THEY COULD NOT BE LOCATED ON SYMBOL | | | LIST? | | | PLEASE SEE THAT TIME OF DAY SCHEDULING | | | CAN BE CHOSEN BY OCCUPANT. ALL OVER | | | RIDES IF ONMANUAL TIMED DEVICES MAY | | | ONLY A MAX OF 4HRS AND OCCUPANT TYPE | | | SENSORS MAY ONLY BE 30MINS. | | | PLEASE INDICATE THE MAX 30MINS.' | | | PLEASE SEE .1.3, AS SEPARATE SPACES | | | CONTAINING FLOOR TO CEILING HEIGHT | | | PARTITIONS REQUIRES CONTROLS AS NOTED. | | | PLEASE SEE PREVIOUS NOTE WHICH THE | | | ALLOWANCE AND DESIGN WATTAGE WAS IN | | | QUESTION. PLEASE CLARIFY AS WATTAGE IS | | | SHOWN OVER ALLOWANCE. | | | 13-415.2.ABC.1, 415.2.C.1, 415.2.B.1 | | | | | | 2) NOTE: PLEASE SEE PREVIOUS PLANS | | | INDICATED THE PANEL "D" AS EXISTING | | | ALTHOUGH NOTE MENTIONED NEW FEED FROM | | | EXSTING PANEL "G". PLEASE SEE PANEL "D" | | | IS NOW BEING SHOWN AS NEW. PLEASE SEE NO | | | LOAD CALCUALTIONS WERE SUBMITTED FOR | | | EXISTING PANEL "G" INDICATING NEW AND | | | EXISTING LOADS BEING ADDED. | | | PLEASE SUBMIT LOADS FOR PANEL "G" AND | | | SIZE OF PANEL ETC TO VERIFY NEW ADDED | | | LOADS. | | | 220,215.5,215.3,230.42 ETC. | | | FBC 106.1.2,106.3.5.1.2 | | | | | | 3) NOTE: PLEASE SEE COLOR CODING FOR | | | 277/480V SHALL BE BROWN, PURPLE, YELLOW. | | | SHOWN WITH ORANGE FOR "B" PHASE, YET | | | THISIS 277V NOT A "HIGH-LEG. | | | PLEASE ADJUST. PLEASE SEE THAT THIS CAN | | | BE REDLINED ALSO, AS NO 277V LIGHTING | | | ETC IS BEING SHOWN. | | | | | | 4) NOTE: PLEASE VERIFY LOAD ON RECEPT | | | CIRCUITS. PLEASE SEE SOME SHOWN AS | | | 13.5VA, HOWEVER @180 VA PER KNOW RECEPT | | | AND 9 ON EACH CIRCUIT THIS COMES UP TO | | | 1620VA. | | | PLEASE SEE 1,3,5,9,11, | | | | | | | | | ** PLEASE SEE 605 FOR ALL MODULAR | | | FURNITURE INSTALLATIONS.. | | | | | | ** PLEASE CALL TO GO OVER NOTE #1. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-06-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-06-20 |
Time |
13:13 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-06-20 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2006-06-20 00:00:00 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE IF CIRCUITS SHOWN ARE NEW OR | | | EXISTING. THE PANEL DESIGNATION "A", | | | DOES NOT CORRESPOND TO ANY OF THE PANEL | | | DESIGNATIONS(D G H F) SHOWN ON THE PLAN. | | | LOCATE PANEL "A" ON THE PLAN. | | | | | | 2} THE ENGINEER OF RECORD SHALL INDICATE | | | THE CERTIFICATE OF AUTHORIZATIONNUMBER | | | ALONG WITH OTHER INFORMATION REQUIRED BY | | | 61G15-23.002, FLORIDA ADMINISTRATIVE | | | CODE, IN THE TITLE BLOCK. | | | | | | 3} SHOW DIAGRAMATICALLY COMPLIANCE WITH | | | THE ENERGY CODE AS INDICATED IN THE | | | "LIGHTING KEYNOTES". PLACE THE DEVICES | | | ON THE DRAWING WHERE THE DESIGNER | | | INTENDS FOR THEM TO BE INSTALLED. SEE | | | THE REFERENCE TO THE " TORK #???" IS | | | UNACCEPTABLE. | | | | | | 4} PLEASE SEE PAGE 3, LIGHTING POWER | | | COMPLIANCE, ON FORM 400B, ATTACHED. THE | | | OPEN OFFICE ENTRY WITH EFFECTIVE @ 1960 | | | DOES NOT APPEAR TO COMPLY WITH THE | | | ALLOWANCE , WHICH IS SHOWN @ 1903. | | | | | | 5} AN ELECTRICAL CONTRACTOR IS REQUIRED | | | FOR THIS WORK AND MUST APPLY FOR A | | | SEPERATE PERMIT SINCE NOT SIGNED ON WITH | | | THE GC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/805-6731. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-04-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-04-13 |
Time |
18:16 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-04-13 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2006-04-13 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE PANEL DESIGNATION AND | | | CIRCUIT NUMBERS FOR DEVICES. INDICATE IF | | | NEW OR EXISTING. | | | | | | 2} PER 481.221 THE ARCHIITECT WHOSE NAME | | | APPEARS ON THE PLAN MUST SIGN AND SEAL | | | SAME. | | | | | | 3} AN ELECTRICAL CONTRACTOR IS REQUIRED | | | FOR THIS WORK AND MUST APPLY FOR A | | | SEPERATE PERMIT SINCE NOT SIGNED ON WITH | | | THE GC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/805-6731. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-07-26 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2006-07-26 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2006-07-26 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2006-08-09 00:00:00 | **APPROVED** | | | | | | | | | | | | | | | 1.) RE-SUBMITTED PLANS WERE APPROVED AND | | | RESTAMPED ON 08/09/2006 BY MAW. FIRST | | | APPROVAL ON 07/26/2006 BY NAM. | | | | | | 2.) DUCT SMOKE DETECTORS TO INITIATE A | | | GENERAL FIRE ALARM. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-06-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-06-21 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-06-21 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2006-06-21 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE NOTE THAT THE SAME COMMENT BY | | | MECHANICAL REVIEW APPLIES TO THE | | | ELECTRICAL SHEETS. ONLY (1) SET OF PLANS | | | ARE SEALED BY ENGINEER. | | | | | | 2) DUCT SMOKE DETECTOR SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. IF NO FIRE ALARM, | | | AUDIBLE/VISUAL DEVICE STILL REQUIRED. | | | | | | 3) LIFE SAFETY TO COMPLY WITH NFPA 101, | | | 2003 EDITION. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-04-20 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-04-20 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-04-20 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2006-04-20 00:00:00 | ******DENIED****** | | | | | | 1) MORE INFORMATION AND DETAILS REQUIRED | | | FOR A COMPLETE FIRE REVIEW TO BE DONE. | | | | | | 2) PLEASE SHOW EXISTING OR NEW EXIT SIGN | | | AND EMERGENCY LIGHT LOCATIONS. | | | | | | 3) WILL THIS WORK HAVE AN IMPACT ON FIRE | | | SPRINKLER OR FIRE ALARM EQUIPMENT? IF | | | NOT APPLICABLE, PLEASE ADVISE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-08-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-09 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-09 |
Time |
08:12 |
Sent To |
E |
|
| Notes |
| 2006-08-09 00:00:00 | TO "BTROBAUG" DESK/RESUB--EXPEDITED | | | PERMIT-- |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-07-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-22 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-22 |
Time |
14:27 |
Sent To |
E |
|
| Notes |
| 2006-07-22 00:00:00 | TO "DPALMER" DESK/RESUB--EXPEDITED | | | PERMIT-- |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-06-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-14 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-14 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2006-06-20 00:00:00 | HURRICANE DAMAGE.EXPEDITE PLAN REVIEW. | | | | | 2006-06-19 00:00:00 | TO "BOB"#10 | | 2006-06-14 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-05-08 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-05-05 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-04-13 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2006-04-13 00:00:00 | TO "BOB"#5 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-07-24 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-07-24 |
Time |
08:12 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-07-24 |
Time |
08:12 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-06-20 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-20 |
Time |
16:14 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2006-06-20 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2006-06-20 00:00:00 | *** DENIED *** | | | 1) ONLY ONE SET OF MECHANICAL PLANS HAVE | | | THE ENGINEER'S (MICHAEL A. TEELE) SEAL | | | ON THEM, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-04-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-04-13 |
Time |
10:45 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-04-13 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2006-04-13 00:00:00 | *** DENIED *** | | | 1) PLEASE DESCRIBE THE WORK TO BE DONE | | | AND SHOW WHAT WILL BE REPAIRED AND WHAT | | | WILL BE REPLACED OR ALTERED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2006-06-23 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-06-23 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-06-23 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2006-06-23 00:00:00 | NO PLUMBING SHOWN ON PLANS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-04-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-04-14 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-04-14 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2006-04-14 00:00:00 | DENIED; | | | THERE IS NOT ENOUGH INFORMATION TO DO A | | | PLUMBING REVIEW. SHOW DISCRIPTION OF | | | WORK TO BE DONE ON PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|