Plan Review Details - Permit 06040355
Plan Review Stops For Permit 06040355
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-10 Cont ID  
Sent By shill Date 2006-08-10 Time 08:57 Rev Time 0.00
Received By shill Date 2006-08-10 Time 08:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-01 Cont ID  
Sent By shill Date 2006-08-01 Time 13:52 Rev Time 0.00
Received By shill Date 2006-08-01 Time 13:52 Sent To  
Notes
2006-08-01 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 NOTE - NEW PLAN SUBMITTED
  
 1.)ROOMS/AREAS ARE TO BE LABELED AS TO
 USE.
  
 2.)THE SCOPE OF WORK IS NOT CLEAR.
 ARE ALL OF THE WALLS AND DOORS SHOWN
 NEW?NO WALL LEGEND WAS PROVIDED.ARE
 THE INDIVIDUAL SPACES WALLS OR CUBICLES?
  
 3.)PROVIDE DOOR DIMENSIONS,
 FBC1008.1.1.
  
 4.)ARE THE BATHROOMS NEW?IF THEY ARE
 NEW OR ARE BEING RENOVATED, PROVIDE ALL
 DETAILS FOR ACCESSIBILITY.FBC11-4.1.6.
  
 5.)NO NOTES WERE MADE ON THE FLOOR
 PLAN AS TO NEW OR EXISTING.IF THIS IS
 A NEW FLOOR PLAN, THIS IS NOT A LEVEL I
 ALTERATION.SEE FBC EB 303 AND 304.
 SCOPE OF WORK IS NOT CLEAR.
  
 6.)DOORS ARE TO COMPLY WITH
 FBC11-4.13.6.THERE ARE SEVERAL DOORS
 SHOWN WHICH DO NOT MEET THE MANEUVERING
 CLEARANCE REQUIREMENT, SEE ALSO FBC11
 FIGURE 19.
  
 7.)TENANT SEPARATION IS NOT CLEAR.
 SHOW ANY REQUIRED FIRE RESISTANCE ON THE
 PLAN.
  
 8.)PROVIDE EXITING INFORMATION.THERE
 ARE TWO DOORS AND A HALLWAY LEADING INTO
 THE AREA SHOWN AS OPEN SPACE, BUT WHICH
 IS PROBABLY A SECTION OF THE FLOOR WHICH
 IS NOT UNDER THIS PERMIT.
  
 9.)NEW COMMENTS WERE TRIGGERED DUE TO
 NEW PLANS SUBMITTED.THE ARCHITECTURAL
 PLANS WHICH WERE PREVIOUSLY REVIEWED
 WERE NOT SUBMITTED, ONLY AN OLD FLOOR
 PLAN FROM 1997.THE PREVIOUS PLAN
 INDICATED A SCOPE OF WORK.THIS PLAN
 SHOWS ONLY WALLS AND DOORS, AND SOME
 DIMENSIONS, BUT DOES NOT GIVE
 INFORMATION AS TO THE WORK TO BE DONE.
  
 10.)FROM PREVIOUS REVIEW #4, SIGN
 OWNER/AGENT LINE OF THE ENERGY CALCS,
 FBC13-103.1.
  
 11.)FROM PREVIOUS REVIEW #5, ON PAGE 5
 OF THE ENERGY CALC, EITHER INDICATE THAT
 THESE ITEMS HAVE BEEN CHECKED OR WRITE
 NA.
  
 12.)SEE THE NOTE ON THE BOTTOM OF THE
 ENERGY CALC, INPUT REPORT PRINTOUT FROM
 ENERGY GUAGE COM MUST BE SUBMITTED WITH
 THE COMPLIANCE REPORT.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-07 Cont ID  
Sent By shill Date 2006-07-07 Time 09:12 Rev Time 0.00
Received By shill Date 2006-07-07 Time 09:12 Sent To  
Notes
2006-07-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)PLANS ARE NOT SIGNED AND SEALED.
  
 2.)DECLARE GOVERNING CODE.
  
 3.)DECLARE LEVEL OF ALTERATION FBC EB
 CHAPTER 3.
  
 4.)SIGN OWNER/AGENT LINE OF THE ENERGY
 CALCS, FBC13-103.1.
  
 5.)ON PAGE 5 OF THE ENERGY CALC,
 EITHER INDICATE THAT THESE ITEMS HAVE
 BEEN CHECKED OR WRITE NA.
  
 6.)PROVIDE HALLWAY DIMENSION AT THE
 NEW OFFICES (NEW PARTITION WALL TO
 EXISTING WALL), FBC10.
  
 7.)PROVIDE A CODE SUMMARY.INCLUDE
 BUILDING SIZE, HEIGHT, MINIMUM BUILDING
 TYPE FBC6 (INCLUDING A OR B), SPRINKLED
 OR UNPRINKLED, OCCUPANCY FBC3.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-05 Cont ID  
Sent By kconrad Date 2006-05-05 Time 10:48 Rev Time 0.00
Received By kconrad Date 2006-05-05 Time 09:21 Sent To R
Notes
2006-05-05 00:00:00A PRE-INSPECT WAS PERFORMED BY DN ON
 5/4/06.IT WAS OBSERVED THAT THE INTERIOR
 DEMOLITION WAS COMPLETED WITH NO
 PERMITS:PARTIAL FLOOR PLAN SECTION/PHASE
 ONE.ALSO IT WAS NOTED THAT EXISTING
 WALLS WERE REMOVED:4X FEE FOR COMMENCING
 WORK PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT,FBC 105.1/109.3.WE HAVE
 DETERMINED, UPON THE COMPLETION OF THE
 PREINSPECT, THAT THE SUBJECT PERMIT
 APPLICATION/PLAN BE REVIEWED FOR A LEVEL
 2 ALTERATION AND ALL WORK SHALL CONFORM
 TO FBC SECTION 601/EXISTING BUILDING
 CODE.THE CONTRACTOR WAS ALSO ADVISED
 THAT ENERGY CALCULATIONS SHALL BE
 SUBMITTED FOR PLAN REVIEW AND MECHANICAL
 /ELECTRICAL PERMITS ARE
 REQUIRED.THERFORE, THE
 PRE-INSPECT/PERMIT ISSUANCE IS DENIED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-08-09 Cont ID  
Sent By btrobaug Date 2006-08-09 Time 12:26 Rev Time 0.50
Received By btrobaug Date 2006-08-09 Time 12:07 Sent To REV
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-07-22 Cont ID  
Sent By dpalmer Date 2006-07-22 Time 20:02 Rev Time 0.00
Received By dpalmer Date 2006-07-22 Time 18:49 Sent To  
Notes
2006-07-22 00:00:00** UNSAT **
  
 ** PLEASE SEE SOME INFORMATION FROM
 PREVIOUS REVIEW STILL NEEDS TO BE
 ADDRESSED ALONG WITH NEW COMMENT(S).
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH FBC
 CHAPTER 13 AS PREVIOUSLY NOTED. PLEASE
 SEECOMPLIANCE WITH FBC CHAPTER 13 THEN
 PLEASE SEE THE FOLLOWING:
 13-415.1.ABC.1.1, .1.2, AND .1.3
 PLEASE PROVIDE OVER-RIDES LOCATED AT THE
 ENTRANCE INTO SPACE WHERE OCCUPANT CAN
 CLEARLY SEE LIGHTING IN WHICH IS BEING
 CONTROLLED.
 PLEASE SEE SOME SYMBOLS ARE BEING SHOWN
 AT DOORS HOWEVER THESE ARE NOT CLEAR AS
 THEY COULD NOT BE LOCATED ON SYMBOL
 LIST?
 PLEASE SEE THAT TIME OF DAY SCHEDULING
 CAN BE CHOSEN BY OCCUPANT. ALL OVER
 RIDES IF ONMANUAL TIMED DEVICES MAY
 ONLY A MAX OF 4HRS AND OCCUPANT TYPE
 SENSORS MAY ONLY BE 30MINS.
 PLEASE INDICATE THE MAX 30MINS.'
 PLEASE SEE .1.3, AS SEPARATE SPACES
 CONTAINING FLOOR TO CEILING HEIGHT
 PARTITIONS REQUIRES CONTROLS AS NOTED.
 PLEASE SEE PREVIOUS NOTE WHICH THE
 ALLOWANCE AND DESIGN WATTAGE WAS IN
 QUESTION. PLEASE CLARIFY AS WATTAGE IS
 SHOWN OVER ALLOWANCE.
 13-415.2.ABC.1, 415.2.C.1, 415.2.B.1
  
 2) NOTE: PLEASE SEE PREVIOUS PLANS
 INDICATED THE PANEL "D" AS EXISTING
 ALTHOUGH NOTE MENTIONED NEW FEED FROM
 EXSTING PANEL "G". PLEASE SEE PANEL "D"
 IS NOW BEING SHOWN AS NEW. PLEASE SEE NO
 LOAD CALCUALTIONS WERE SUBMITTED FOR
 EXISTING PANEL "G" INDICATING NEW AND
 EXISTING LOADS BEING ADDED.
 PLEASE SUBMIT LOADS FOR PANEL "G" AND
 SIZE OF PANEL ETC TO VERIFY NEW ADDED
 LOADS.
 220,215.5,215.3,230.42 ETC.
 FBC 106.1.2,106.3.5.1.2
  
 3) NOTE: PLEASE SEE COLOR CODING FOR
 277/480V SHALL BE BROWN, PURPLE, YELLOW.
 SHOWN WITH ORANGE FOR "B" PHASE, YET
 THISIS 277V NOT A "HIGH-LEG.
 PLEASE ADJUST. PLEASE SEE THAT THIS CAN
 BE REDLINED ALSO, AS NO 277V LIGHTING
 ETC IS BEING SHOWN.
  
 4) NOTE: PLEASE VERIFY LOAD ON RECEPT
 CIRCUITS. PLEASE SEE SOME SHOWN AS
 13.5VA, HOWEVER @180 VA PER KNOW RECEPT
 AND 9 ON EACH CIRCUIT THIS COMES UP TO
 1620VA.
 PLEASE SEE 1,3,5,9,11,
  
  
 ** PLEASE SEE 605 FOR ALL MODULAR
 FURNITURE INSTALLATIONS..
  
 ** PLEASE CALL TO GO OVER NOTE #1.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-20 Cont ID  
Sent By btrobaug Date 2006-06-20 Time 13:13 Rev Time 1.00
Received By btrobaug Date 2006-06-20 Time 11:39 Sent To  
Notes
2006-06-20 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE IF CIRCUITS SHOWN ARE NEW OR
 EXISTING. THE PANEL DESIGNATION "A",
 DOES NOT CORRESPOND TO ANY OF THE PANEL
 DESIGNATIONS(D G H F) SHOWN ON THE PLAN.
 LOCATE PANEL "A" ON THE PLAN.
  
 2} THE ENGINEER OF RECORD SHALL INDICATE
 THE CERTIFICATE OF AUTHORIZATIONNUMBER
 ALONG WITH OTHER INFORMATION REQUIRED BY
 61G15-23.002, FLORIDA ADMINISTRATIVE
 CODE, IN THE TITLE BLOCK.
  
 3} SHOW DIAGRAMATICALLY COMPLIANCE WITH
 THE ENERGY CODE AS INDICATED IN THE
 "LIGHTING KEYNOTES". PLACE THE DEVICES
 ON THE DRAWING WHERE THE DESIGNER
 INTENDS FOR THEM TO BE INSTALLED. SEE
 THE REFERENCE TO THE " TORK #???" IS
 UNACCEPTABLE.
  
 4} PLEASE SEE PAGE 3, LIGHTING POWER
 COMPLIANCE, ON FORM 400B, ATTACHED. THE
 OPEN OFFICE ENTRY WITH EFFECTIVE @ 1960
 DOES NOT APPEAR TO COMPLY WITH THE
 ALLOWANCE , WHICH IS SHOWN @ 1903.
  
 5} AN ELECTRICAL CONTRACTOR IS REQUIRED
 FOR THIS WORK AND MUST APPLY FOR A
 SEPERATE PERMIT SINCE NOT SIGNED ON WITH
 THE GC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/805-6731.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-13 Cont ID  
Sent By btrobaug Date 2006-04-13 Time 18:16 Rev Time 0.50
Received By btrobaug Date 2006-04-13 Time 17:16 Sent To  
Notes
2006-04-13 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE PANEL DESIGNATION AND
 CIRCUIT NUMBERS FOR DEVICES. INDICATE IF
 NEW OR EXISTING.
  
 2} PER 481.221 THE ARCHIITECT WHOSE NAME
 APPEARS ON THE PLAN MUST SIGN AND SEAL
 SAME.
  
 3} AN ELECTRICAL CONTRACTOR IS REQUIRED
 FOR THIS WORK AND MUST APPLY FOR A
 SEPERATE PERMIT SINCE NOT SIGNED ON WITH
 THE GC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/805-6731.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-07-26 Cont ID  
Sent By nmccray Date 2006-07-26 Time 13:54 Rev Time 0.00
Received By nmccray Date 2006-07-26 Time 13:54 Sent To  
Notes
2006-08-09 00:00:00**APPROVED**
  
  
  
  
 1.) RE-SUBMITTED PLANS WERE APPROVED AND
 RESTAMPED ON 08/09/2006 BY MAW. FIRST
 APPROVAL ON 07/26/2006 BY NAM.
  
 2.) DUCT SMOKE DETECTORS TO INITIATE A
 GENERAL FIRE ALARM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-06-21 Cont ID  
Sent By mwennerg Date 2006-06-21 Time 09:42 Rev Time 0.00
Received By mwennerg Date 2006-06-21 Time 09:42 Sent To  
Notes
2006-06-21 00:00:00***DENIED***
  
 1) PLEASE NOTE THAT THE SAME COMMENT BY
 MECHANICAL REVIEW APPLIES TO THE
 ELECTRICAL SHEETS. ONLY (1) SET OF PLANS
 ARE SEALED BY ENGINEER.
  
 2) DUCT SMOKE DETECTOR SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS. IF NO FIRE ALARM,
 AUDIBLE/VISUAL DEVICE STILL REQUIRED.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-20 Cont ID  
Sent By mwennerg Date 2006-04-20 Time 10:46 Rev Time 0.00
Received By mwennerg Date 2006-04-20 Time 10:46 Sent To  
Notes
2006-04-20 00:00:00******DENIED******
  
 1) MORE INFORMATION AND DETAILS REQUIRED
 FOR A COMPLETE FIRE REVIEW TO BE DONE.
  
 2) PLEASE SHOW EXISTING OR NEW EXIT SIGN
 AND EMERGENCY LIGHT LOCATIONS.
  
 3) WILL THIS WORK HAVE AN IMPACT ON FIRE
 SPRINKLER OR FIRE ALARM EQUIPMENT? IF
 NOT APPLICABLE, PLEASE ADVISE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-09 Cont ID  
Sent By adarroug Date 2006-08-09 Time 08:12 Rev Time 0.00
Received By adarroug Date 2006-08-09 Time 08:12 Sent To E
Notes
2006-08-09 00:00:00TO "BTROBAUG" DESK/RESUB--EXPEDITED
 PERMIT--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 14:27 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 14:27 Sent To E
Notes
2006-07-22 00:00:00TO "DPALMER" DESK/RESUB--EXPEDITED
 PERMIT--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 13:36 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 13:36 Sent To  
Notes
2006-06-20 00:00:00HURRICANE DAMAGE.EXPEDITE PLAN REVIEW.
  
2006-06-19 00:00:00TO "BOB"#10
2006-06-14 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-08 Cont ID  
Sent By lmartine Date 2006-05-05 Time 12:16 Rev Time 0.00
Received By lmartine Date 2006-04-13 Time 10:09 Sent To  
Notes
2006-04-13 00:00:00TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-07-24 Cont ID  
Sent By tgordon Date 2006-07-24 Time 08:12 Rev Time 0.20
Received By tgordon Date 2006-07-24 Time 08:12 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-06-20 Cont ID  
Sent By tgordon Date 2006-06-20 Time 16:14 Rev Time 0.25
Received By tgordon Date 2006-06-20 Time 16:13 Sent To  
Notes
2006-06-20 00:00:00*** DENIED ***
 1) ONLY ONE SET OF MECHANICAL PLANS HAVE
 THE ENGINEER'S (MICHAEL A. TEELE) SEAL
 ON THEM, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-13 Cont ID  
Sent By tgordon Date 2006-04-13 Time 10:45 Rev Time 0.20
Received By tgordon Date 2006-04-13 Time 10:45 Sent To  
Notes
2006-04-13 00:00:00*** DENIED ***
 1) PLEASE DESCRIBE THE WORK TO BE DONE
 AND SHOW WHAT WILL BE REPAIRED AND WHAT
 WILL BE REPLACED OR ALTERED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-06-23 Cont ID  
Sent By jleech Date 2006-06-23 Time 08:54 Rev Time 0.00
Received By jleech Date 2006-06-23 Time 08:54 Sent To  
Notes
2006-06-23 00:00:00NO PLUMBING SHOWN ON PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-14 Cont ID  
Sent By jleech Date 2006-04-14 Time 10:37 Rev Time 0.00
Received By jleech Date 2006-04-14 Time 10:37 Sent To  
Notes
2006-04-14 00:00:00DENIED;
 THERE IS NOT ENOUGH INFORMATION TO DO A
 PLUMBING REVIEW. SHOW DISCRIPTION OF
 WORK TO BE DONE ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695