Plan Review Details - Permit 06040350
Plan Review Stops For Permit 06040350
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-05-11 Cont ID  
Sent By alange Date 2006-05-11 Time 08:12 Rev Time 0.50
Received By alange Date 2006-05-11 Time 08:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-06 Cont ID  
Sent By btrobaug Date 2006-06-06 Time 16:36 Rev Time 0.50
Received By btrobaug Date 2006-06-06 Time 14:33 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-04 Cont ID  
Sent By btrobaug Date 2006-05-04 Time 13:07 Rev Time 0.50
Received By btrobaug Date 2006-05-04 Time 12:45 Sent To M
Notes
2006-05-04 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 A GENERATOR (GEN-RES) PERMIT TYPE
 REQUIRES THAT THE TOTAL COST OF LABOR
 AND MATERIAL BE INCLUDED IN THE
 VALUATION. THIS WOULD BE ALL THE SERVICE
 EQUIPMENT AND THE PAD.
  
 THE LOAD AT 103 AMPS EXCEEDS THE
 GENERATOR OUTPUT AT 54 AMPS. SEE 702.5,
 NEC. IF LOAD SHEDDING IS INTENDED AS
 INDICATED, PLEASE SHOW HOW THIS IS TO BE
 ACCOMPLISHED WITH AN AUTOMATIC TRANSFER
 SWITCH.
  
 IT IS UNCLEAR HOW THE FEED FROM THE
 GENERATOR TO THE TRANSFER SWITCH IS
 BEING ROUTED. PLEASE SHOW THE LOCATION
 OF ALL SERVICE AN DGENERATOR EQUIPMENT
 ON A RISER DIAGRAM. SEE ARTICLE
 225.31-39 FOR DISCONNECT REQUIREMENTS.
  
 THE CONTRACTOR DOES NOT NEED TO SUBMIT
 THE ENTIRE OWNERS MANUAL.THE FOUR PAGE
 SPEC SHEETS CONTAIN ALL THE INFORMATION
 REQUIRED FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-05-05 Cont ID  
Sent By mperson Date 2006-05-05 Time 10:11 Rev Time 0.15
Received By mperson Date 2006-05-05 Time 10:11 Sent To B
Notes
2006-05-05 00:00:00NOTE: GAS PERMIT REQUIRED. GAS
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APLICATION. ALL GAS ISPECTIONS TO BE
 COMPLETE BEFORE FINAL GEN/RES
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-06 Cont ID  
Sent By adarroug Date 2006-06-06 Time 12:06 Rev Time 0.00
Received By adarroug Date 2006-06-06 Time 12:06 Sent To E
Notes
2006-06-06 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-01 Cont ID  
Sent By adarroug Date 2006-06-01 Time 14:33 Rev Time 0.00
Received By adarroug Date 2006-06-01 Time 14:33 Sent To Z
Notes
2006-06-01 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-24 Cont ID  
Sent By adarroug Date 2006-04-24 Time 10:17 Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 10:17 Sent To E
Notes
2006-04-24 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-11 Cont ID  
Sent By alange Date 2006-05-11 Time 08:12 Rev Time 0.00
Received By alange Date 2006-04-13 Time 11:23 Sent To  
Notes
2006-04-13 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-07 Cont ID  
Sent By tgordon Date 2006-06-07 Time 09:26 Rev Time 0.30
Received By tgordon Date 2006-06-07 Time 09:26 Sent To  
Notes
2006-06-07 00:00:00*** PROVISO ***
 1)PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT
 TERMINATE UNDER STRUCTURES OR WHERE THE
 EXHAUST MIGHT BE DRAWN INTO THE
 VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE SETBACK, GENERATORS SHALL
 MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY
 STRUCTURES, I.E. FENCE, BUILDING,
 WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-05 Cont ID  
Sent By tgordon Date 2006-05-05 Time 08:45 Rev Time 0.15
Received By tgordon Date 2006-05-05 Time 08:45 Sent To G
Notes
2006-05-05 00:00:00*** DENIED ***
 1) PLEASE SEE ZONING NOTES.
  
 2) PLEASE BE ADVISED,GENERATOR EXHUST
 MUST BE TEN FEET AWAY FROM ANY BUILDING
 OPENINGS (WINDOWS, DOORS, ROOF & EAVE
 VENTS), AND TEN FEET AWAY FROM ADJECENT
 BUILDING OPENS. PER 2004 FBC/M 401.5.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2006-06-04 Cont ID  
Sent By mmclean Date 2006-06-04 Time 10:23 Rev Time 0.00
Received By mmclean Date 2006-06-04 Time 10:23 Sent To I
Notes
2006-06-04 00:00:00SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
 GENERATOR WILL BE AT LEAST 3FT FROM SIDE
 PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-21 Cont ID  
Sent By mmclean Date 2006-04-21 Time 10:39 Rev Time 0.00
Received By mmclean Date 2006-04-21 Time 10:39 Sent To AD
Notes
2006-04-21 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE LOCATION OF GENERATOR
 WITH SETBACKS AND PROVIDE THE DIMENISON
 OF GENERATOR
 2. ONLY ONE COPY OF SURVEY WAS SUBMITTED
 WTIHOUT THE LOCATION OF GENERATOR.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720