| Plan Review Stops For Permit 06040346 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-01-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-15 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-15 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2008-01-15 15:47:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.PLEASE PROVIDE ADDITIONAL VALUE AS REQURESTED IN | | | THE PREVIOUS CORRECTION LIST.THIS MAY BE DONE BY | | | TELEPHONE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-03 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-03 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2007-12-03 11:36:16 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING | | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | | BEDROOMS, FBC R310, FBC EB 505.1.SEE FBC R310, FBC EB | | | 505.1.THE CLEAR OPENING CANNOT BE REDUCED BY MORE | | | THAN 5%. | | | | | | 2.THREE PRODUCT APPROVALS FOR DOORS WERE SUBMITTED. | | | WHERE ARE YOU INSTALLING DOORS, AND WHICH DOOR ARE YOU | | | USING? | | | | | | 3.FOR THE SHUTTERS, COMPLETE THE ATTACHED | | | INSTALLATION SCHEDULE OR PROVIDE ALL INFORMATION IN | | | ANOTHER FORMAT. | | | | | | 4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN | | | ADDITION TO THE NOAS PROVIDED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG | | | | | | 5.PROVIDE A VALUATION FOR THE ADDITIONAL SCOPE OF | | | WORK. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-05-22 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-05-22 |
Time |
09:27 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2006-05-22 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-12-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2006-12-18 |
Time |
06:54 |
Rev Time |
0.45 |
| Received By |
jleahy |
Date |
2006-12-18 |
Time |
06:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2006-04-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-04-24 |
Time |
08:17 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-04-24 |
Time |
07:37 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2008-01-11 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2008-01-11 |
Time |
10:33 |
Sent To |
B |
|
| Notes |
| 2008-01-11 10:34:09 | TO SAMANTHA HILLS DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-10-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-24 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-24 |
Time |
14:21 |
Sent To |
B |
|
| Notes |
| 2007-10-24 14:22:18 | TO "LMARTINEZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-05-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-26 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-26 |
Time |
12:09 |
Sent To |
M |
|
| Notes |
| 2006-05-26 00:00:00 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-05-22 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-05-22 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-04-13 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2006-04-13 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2006-06-01 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-01 |
Time |
10:28 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-06-01 |
Time |
10:28 |
Sent To |
P |
|
| Notes |
| 2006-06-01 00:00:00 | MECHANICAL PLANS WERE REMOVED FROM | | | BUILDING PLANS SO BUILDING PERMIT MAY | | | BY-PASS A MECH. REVIEW, E-CAL'S. ARE | | | STILL WITH BUILDING PERMIT. MECHANICAL | | | CONTRACTOR WILL SUBMIT MECH. PLANS WHEN | | | APPLYING FOR PERMIT (PER ARNOLD | | | ABRAMSON)TG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-04-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-04-25 |
Time |
14:37 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-04-25 |
Time |
14:37 |
Sent To |
P |
|
| Notes |
| 2006-04-25 00:00:00 | *** DENIED *** | | | 1) MECHANICAL PLANS MUST SHOW THE DUCT | | | LAY-OUT WITH THE DUCT SIZES. | | | | | | 2) SHOW RETURN AIR TRANSFER GRILL SIZES | | | FOR EACH BEDROOM. | | | | | | 3) 18X18 RETURN AIR GRILL IS TO SMALL | | | FOR A 2 1/2 TON A/C SYSTEM. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-06-05 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-06-05 |
Time |
11:46 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2006-06-05 |
Time |
11:46 |
Sent To |
PC |
|
| Notes |
| 2006-06-05 00:00:00 | NOTE: EXACT FIXTURE CHANGEOUT | | | | | | ******PROVISO****** | | | A PLUMBING PERMIT IS REQUIRED, PLUMBING | | | CONTRACTOR TO APPLY AT LATER DATE AND | | | SHALL REFERENCE PERMIT #06040346 ON | | | PERMIT APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-05-01 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-05-01 |
Time |
14:35 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2006-05-01 |
Time |
14:35 |
Sent To |
B |
|
| Notes |
| 2006-05-01 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 PLUMBING, CITY OF | | | WEST PALM BEACH, AMENDMENTS TO FBC-2004, | | | CHAPTER 1, ADMINISTRATION: | | | | | | PLEASE ADJUST YOUR DRAWINGS TO REFLECT | | | THE FOLLOWING INFORMATION REQUIRED FOR | | | PLAN REVIEW: | | | | | | 1. MORE INFORMATION REQUIRED. PLEASE | | | INDICATE ON DRAWING EXISTING PLUMBING | | | LAYOUT, AND INDICATE ON DRAWING PROPOSED | | | PLUMBING LAYOUT. IF NEW PROPOSED | | | PLUMBING LAYOUT IS DIFFERENT FROM | | | EXISTING PLEASE FOLLOW WHAT IS REQUIRED | | | IN #2. IF LAYOUT IS THE SAME PLEASE | | | INDICATE ON DRAWING, FIXTURE CHANGE OUT | | | ONLY. | | | 2. PER CHAPTER 1, SECTION 106.3.5.4 | | | RESIDENTIAL (ONE AND TWO FAMLY) SUBMIT A | | | PLUMBING SANITARY ISOMETRIC RISER | | | DIAGRAM INDICATING ALL WASTE, VENTS, AND | | | TRAPS WITH SIZES. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|