Plan Review Details - Permit 06040346
Plan Review Stops For Permit 06040346
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-01-15 Cont ID  
Sent By shill Date 2008-01-15 Time 15:46 Rev Time 0.00
Received By shill Date 2008-01-15 Time 15:46 Sent To  
Notes
2008-01-15 15:47:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PLEASE PROVIDE ADDITIONAL VALUE AS REQURESTED IN
 THE PREVIOUS CORRECTION LIST.THIS MAY BE DONE BY
 TELEPHONE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By shill Date 2007-12-03 Time 11:32 Rev Time 0.00
Received By shill Date 2007-12-03 Time 11:32 Sent To  
Notes
2007-12-03 11:36:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.SEE FBC R310, FBC EB
 505.1.THE CLEAR OPENING CANNOT BE REDUCED BY MORE
 THAN 5%.
  
 2.THREE PRODUCT APPROVALS FOR DOORS WERE SUBMITTED.
 WHERE ARE YOU INSTALLING DOORS, AND WHICH DOOR ARE YOU
 USING?
  
 3.FOR THE SHUTTERS, COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE OR PROVIDE ALL INFORMATION IN
 ANOTHER FORMAT.
  
 4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO THE NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 5.PROVIDE A VALUATION FOR THE ADDITIONAL SCOPE OF
 WORK.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-05-22 Cont ID  
Sent By alange Date 2006-05-22 Time 09:27 Rev Time 0.50
Received By alange Date 2006-05-22 Time 09:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-18 Cont ID  
Sent By jleahy Date 2006-12-18 Time 06:54 Rev Time 0.45
Received By jleahy Date 2006-12-18 Time 06:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-04-24 Cont ID  
Sent By btrobaug Date 2006-04-24 Time 08:17 Rev Time 0.50
Received By btrobaug Date 2006-04-24 Time 07:37 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 10:33 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 10:33 Sent To B
Notes
2008-01-11 10:34:09TO SAMANTHA HILLS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 14:21 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 14:21 Sent To B
Notes
2007-10-24 14:22:18TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 12:09 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 12:09 Sent To M
Notes
2006-05-26 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-22 Cont ID  
Sent By alange Date 2006-05-22 Time 09:27 Rev Time 0.00
Received By alange Date 2006-04-13 Time 11:26 Sent To  
Notes
2006-04-13 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-06-01 Cont ID  
Sent By tgordon Date 2006-06-01 Time 10:28 Rev Time 0.30
Received By tgordon Date 2006-06-01 Time 10:28 Sent To P
Notes
2006-06-01 00:00:00MECHANICAL PLANS WERE REMOVED FROM
 BUILDING PLANS SO BUILDING PERMIT MAY
 BY-PASS A MECH. REVIEW, E-CAL'S. ARE
 STILL WITH BUILDING PERMIT. MECHANICAL
 CONTRACTOR WILL SUBMIT MECH. PLANS WHEN
 APPLYING FOR PERMIT (PER ARNOLD
 ABRAMSON)TG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-25 Cont ID  
Sent By tgordon Date 2006-04-25 Time 14:37 Rev Time 0.30
Received By tgordon Date 2006-04-25 Time 14:37 Sent To P
Notes
2006-04-25 00:00:00*** DENIED ***
 1) MECHANICAL PLANS MUST SHOW THE DUCT
 LAY-OUT WITH THE DUCT SIZES.
  
 2) SHOW RETURN AIR TRANSFER GRILL SIZES
 FOR EACH BEDROOM.
  
 3) 18X18 RETURN AIR GRILL IS TO SMALL
 FOR A 2 1/2 TON A/C SYSTEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-05 Cont ID  
Sent By mperson Date 2006-06-05 Time 11:46 Rev Time 0.33
Received By mperson Date 2006-06-05 Time 11:46 Sent To PC
Notes
2006-06-05 00:00:00NOTE: EXACT FIXTURE CHANGEOUT
  
 ******PROVISO******
 A PLUMBING PERMIT IS REQUIRED, PLUMBING
 CONTRACTOR TO APPLY AT LATER DATE AND
 SHALL REFERENCE PERMIT #06040346 ON
 PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-01 Cont ID  
Sent By mperson Date 2006-05-01 Time 14:35 Rev Time 0.33
Received By mperson Date 2006-05-01 Time 14:35 Sent To B
Notes
2006-05-01 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING, CITY OF
 WEST PALM BEACH, AMENDMENTS TO FBC-2004,
 CHAPTER 1, ADMINISTRATION:
  
 PLEASE ADJUST YOUR DRAWINGS TO REFLECT
 THE FOLLOWING INFORMATION REQUIRED FOR
 PLAN REVIEW:
  
 1. MORE INFORMATION REQUIRED. PLEASE
 INDICATE ON DRAWING EXISTING PLUMBING
 LAYOUT, AND INDICATE ON DRAWING PROPOSED
 PLUMBING LAYOUT. IF NEW PROPOSED
 PLUMBING LAYOUT IS DIFFERENT FROM
 EXISTING PLEASE FOLLOW WHAT IS REQUIRED
 IN #2. IF LAYOUT IS THE SAME PLEASE
 INDICATE ON DRAWING, FIXTURE CHANGE OUT
 ONLY.
 2. PER CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO FAMLY) SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER
 DIAGRAM INDICATING ALL WASTE, VENTS, AND
 TRAPS WITH SIZES.
  
 END OF COMMENTS:
  