Plan Review Details - Permit 06040305
Plan Review Stops For Permit 06040305
Review Stop AD ADDRESSING
Rev No 1 Status   Date 2006-11-15 Cont ID  
Sent By lursu Date 2006-11-15 Time 15:47 Rev Time 0.00
Received By lursu Date 2006-11-15 Time 15:47 Sent To  
Notes
2006-11-15 15:48:22PERMIT ATTACHED TO PCN = TEMP7442430208101

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-28 Cont ID  
Sent By lmartine Date 2006-04-28 Time 15:56 Rev Time 0.00
Received By lmartine Date 2006-04-28 Time 15:11 Sent To  
Notes
2006-04-28 00:00:00 
  
  
 BUILDING COMMENTS
 -------- --------
  
  
  
  
 1)
 VERTICAL ACCESSIBILITY IS REQUIRED TO
 THE SECOND STORY SPACE, SEE 11-4.1.3
 FBC.
  
 2)
 SUBMIT DATA SHOWING COMPLIANCE FOR THE
 SECOND FLOOR EXIT REQUIREMENTS, SEE
 1018.2 MAXIMUM TRAVEL DISTANCE OF 75'.
  
 3)
 PROVIDE COMPLETE CONSTRUCTION DETAILS
 FOR REVERSING THE STAIRS.
  
 4)
 AT NEW WALL AND DOORS DETAIL ON FIRST
 FLOOR, IS THERE A STOREFRONT SYSTEM AT
 THE EXTERIOR WALL?
  
 5)
 EXPLAIN DOUBLE DOORS DETAIL ON SHEET 2
 OF 4, WHERE DOES IT GO?
  
 6)
 NEW DOOR AT STORAGE ROOM SHALL COMPLY
 WITH 11-4.13.6.
  
 7)
 PROVIDE CLEAR COPIES OF DRAWINGS,
 UNABLE TO READ ALL DETAILS.
  
  
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-12 Cont ID  
Sent By btrobaug Date 2006-04-12 Time 14:23 Rev Time 0.50
Received By btrobaug Date 2006-04-12 Time 13:42 Sent To  
Notes
2006-04-12 00:00:00 
 DENIED
  
 THE PROPOSED ALTERATIONS MAY NOT BE MADE
 UNTILL THE CO IS ISSUED OR A REVISION IS
 APPLIED FOR BY THE CONTRACTOR WITH THE
 CURRENT PERMIT.
  
 1} PLEASE INDICATE PANEL DESIGNATION AND
 CIRCUIT NUMBERS AT THE DEVICES OR HOME
 RUNS IF COMMON.
  
 2} SHOW ALL EXIT AND EMERGENCY LIGHTING
 IN COMPLIANCE WITH ARTICLE 7.8 AND 7.9
 NFPA-101 (2003).
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-20 Cont ID  
Sent By mwennerg Date 2006-04-20 Time 10:23 Rev Time 0.00
Received By mwennerg Date 2006-04-20 Time 10:22 Sent To  
Notes
2006-04-20 00:00:00******DENIED******
 PLAN REVIEW ONLY
 1) PLEASE PROVIDE LOCATIONS OF ALL
 REQUIRED EXIT SIGNS AND EMERGENCY
 LIGHTING.
  
 2) MORE INFORMATION REQUIRED FOR BAY
 AREA REGARDING USAGE, AS THE PROPOSAL
 WOULD MAKE THIS PART OF THE MEANS OF
 EGRESS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 4) DO THE STAIRS MEET THE REQUIREMENTS
 FOR EXISTING STAIRS IN ACCORDANCE WITH
 NFPA 101, 2003 EDITION, SECTION
 7.2.2.2.1(B)?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-28 Cont ID  
Sent By lmartine Date 2006-04-28 Time 16:46 Rev Time 0.00
Received By lmartine Date 2006-04-12 Time 11:15 Sent To  
Notes
2006-04-12 00:00:00TO "BOB"#10

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-13 Cont ID  
Sent By tgordon Date 2006-04-13 Time 10:13 Rev Time 0.30
Received By tgordon Date 2006-04-13 Time 10:13 Sent To  
Notes
2006-04-13 00:00:00*** DENIED ***
 1) FOR REVIEW PURPOSES ONLY NOT FOR
 PERMIT.
  
 2) SEE ELECTRICAL COMMENT #1.
  
 3) NEED TO SHOW ON MECHANICAL PLANS DUCT
 SIZES AND CFM'S TO EACH SUPPLY AIR
 GRILL.
  
 4) PLEASEE SHOW ANY EXISTING A/C DUCTS
 AND GRILLS IN THE WORK AREA AND LIST IF
 THEY WILL BE RELOCATED OR REMOVED.
  
 5) PROVIED FOR RETURN AIR TO EACH
 ENCLOSED AREA, SEE NOTE #6.
  
 6)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.