| Plan Review Stops For Permit 06040272 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-05-09 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-05-09 |
Time |
06:50 |
Rev Time |
0.75 |
| Received By |
amorse |
Date |
2006-05-09 |
Time |
06:50 |
Sent To |
PC |
|
| Notes |
| 2006-05-09 00:00:00 | | | | | | | DENIED | | | | | | 1) NOT ENOUGH INFORMATION: PLEASE SUBMIT | | | HOW MANY WINDOWS GO INTO EACH OPENING | | | AND THE SIZES OF THE WINDOWS | | | | | | 2) STACKING WINDOWS TOGETHER IN AN | | | OPENING REQUIRES MULLIONS BETWEEN THEM | | | TO TRANSFER PRESSURES TO THE STRUCTURE | | | PLEASE SUBMIT PRODUCT APPROVALS FOR | | | MULLIONS. | | | | | | 3) REPLACEMENT OF OVER 25% OF THE | | | WINDOWS IN ONE CALENDER YEAR REQUIRES | | | THAT THEY ARE PROTECTED WITH SHUTTERS | | | PLEASE SUBMIT PRODUCT APPROVALS OR PROOF | | | OF EXISTING SHUTTERS FOR INSPECTOR AT | | | TIME OF FINAL INSPECTION | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|