| 2006-06-21 00:00:00 | BUILDING REVIEW CHECKLIST FOR PLAN |
| | REVIEW ONLY: |
| | 1- PROVIDE THE FOLLOWING WHEN APPLYING |
| | FOR BUILDING PERMITS: |
| | A)NOTICE OF COMMENCEMENT FOR EACH |
| | BUILDING. |
| | B) RECEIPT OF PAID IMPACT FEES AND |
| | PLANS STAMPED WITH IMPACT FEES STAMP BY |
| | PALM BEACH COUNTY FOR EACH BUILDING. |
| | C) DRAWINGS ARE 90% COMPLETE. NEED |
| | DRAWINGS COMPLETE TO 100%. |
| | D) ARCHITECT TO PROVIDE ALL INFORMATION |
| | IN THE TITLE BLOCK AS REQ'D BY CHAPTER |
| | 481 FLORIDA STATUTE AND 61G1-16.004 FAC. |
| | E) ENGINEER'S TO PROVIDE ALL INFORMATION |
| | AS REQUIRED BY CHAPTER 471 FLORIDA |
| | STATUTE AND 61G15-23.002 FAC. |
| | F) SOIL TEST REPORT FOR EACH BUILDING. |
| | G) ENERGY CALCULATIONS FOR EACH BLDG. |
| | H) SIGNED AND SEALED SURVEYS. |
| | |
| | 2- PROVIDE INTERIOR FINISHES SCHEDULE |
| | INDICATING TYPE OF FINISH. SEE TABLE |
| | 803.5 FBC 2004. |
| | |
| | 3- PROVIDE COMPLETE SITE PLAN WITH |
| | DIMENSIONS SHOWING BUILDING SEPARATION |
| | TO VERIFY COMPLIANCE WITH TABLES 601, |
| | 602 FBC FOR FIRE RESISTANCE AND TABLE |
| | 704.8 FBC 2004 FOR OPENINGS ALLOWED. |
| | |
| | 4- SHEET A100: A) CIVIL DRAWINGS ARE |
| | DONE BY ISBELL ENGINEERING OR EAST BAY |
| | GROUP. SEE GENERAL NOTE #1 AND FOR |
| | REFERENCE ONLY NOTE. REVISE AS REQUIRED. |
| | B) NEED NORTH ARROW. |
| | C) SHOW H/C TOTAL NUMBER OF PARKING |
| | SPACES AND SIZE FOR EACH BUILDING |
| | ACCORDING TO FAIR HOUSING ACT & CHAPTER |
| | 11 OF FBC. |
| | D) BUILDING TYPE IV FOOTPRINT DOESN'T |
| | MATCH PLANS. REVISE AS REQUIRED. CHECK |
| | FOOTPRINT OF ALL OTHER BUILDING TYPES. |
| | E) SHOW ACCESSIBLE ROUTE FROM PARKING |
| | SPACE TO ENTRANCE TO EACH UNIT, LEASING |
| | OFFICE AND COMMUNITY BUILDING. PROVIDE |
| | DETAILS. |
| | |
| | 5- SHEET A101: A) REVISE CODE |
| | INFORMATION. THERE IS NOT ENERGY CODE |
| | 2004 FLORIDA BUILDING CODE (CHAPTER 27). |
| | SEE CHAPTER 13 FBC 2004. |
| | B) THERE IS NOT 1982 CITY OF ATLANTA |
| | ZONING ORDINACE. CHECK WITH CITY OF WEST |
| | PALM BEACH ZONING DEPARTMENT FOR CORRECT |
| | ZONING REFERENCE. |
| | C) FLORIDA ACCESSIBLE REFERENCES ARE |
| | FLORIDA BUILDING CODE CHAPTER 11 AND |
| | FAIR HOUSING ACT REVISED IN APRIL OF |
| | 1998. |
| | D) THERE IS NOT PARKING INFORMATION |
| | SUBMITTED. NEED GENERAL PARKING AND H/C |
| | PARKING. SEE FAIR HOUSING AND CHAPTER 11 |
| | FBC 2004 FOR REQ'D H/C SPACES AND SIZES. |
| | E) REVISE TYPE IV AND TYPE VI BUILDING |
| | TO MATCH WHICH ONE IS USED FOR COMMUNITY |
| | ROOM AND WHICH ONE FOR LEASING OFFICE. |
| | F) PROVIDE CALCULATIONS SHOWING AREA |
| | INCREASE. |
| | G) ALLOWABLE AREA/HEIGHT CALCULATIONS: |
| | CLARIFY NOTE FOR R-2: NO INCREASE BASED |
| | ON SPRINKLER PROTECTION?. ONLY BUILDING |
| | TO HAVE SPRINKLER IS THE MIXED BUILDING |
| | TYPE VI, WHICH HAVE THE LEASING OFFICE |
| | AND APARTMENTS AT BOTH SIDES. THE OTHER |
| | BUILDING TYPES ARE NOT SPRINKLERED. |
| | H) SPECIFY TOTAL BUILDING AREA FOR EACH |
| | COMPLETE BUILDING TYPE. BRAKE DOWN INTO |
| | A/C AREAS AND NON A/C AREAS (EG: |
| | BALCONIES AND ENTRY PORCHES) TO VERIFY |
| | BUILDING AREAS AND FOR PERMIT VALUATION. |
| | D) ACCESSIBILITY NOTES: THERE IS NOT |
| | SECTION 1107.5.4, EX 1. REVISE AS REQ'D. |
| | I) REVISE DWELLING UNIT TYPES CALCS. ALL |
| | UNITS IN GROUND FLOOR NEED TO COMPLY |
| | WITH FAIR HOUSING ACT. |
| | J) PROVIDE VENTILATION CALCULATIONS AND |
| | PLANS TO SHOW DETAILS & VENTS LOCATION. |
| | K) FIRE RATING REQUIREMENTS: PROVIDE |
| | ONLY THE INFORMATION THAT PERTAINS TO |
| | THIS PROJECT TO AVOID CONFUSION AND |
| | FACILITATE THE REVIEW PROCESS. |
| | L) PROVIDE CALCULATIONS FOR OCCUPANT |
| | LOAD IN ASSEMBLY BUILDING USING 5 SF, |
| | WHICH IS THE WORST CASE SCENARIO. TABLE |
| | 1004.1.2 FBC 2004. |
| | |
| | |
| | 6- SHEET A103: A) PROVIDE ONLY THE |
| | DETAILS THAT APPLY TO THIS PROJECT TO |
| | AVOID CONFUSIONS AND TO FACILITATE |
| | REVIEW PROCESS. |
| | B) DETAIL 19: WHERE DOES THIS DETAIL |
| | APPLY TO.SEE FIGURE 38 OF CHAPTER 11 |
| | FBC 2004 FOR MAX. REACH HEIGHT. |
| | |
| | 7- SHEET A104: A) PROVIDE ONLY THE |
| | DETAILS THAT APPLY TO THIS PROJECT. |
| | B) WHERE ARE THE DRINKING FOUNTAINS AND |
| | WATER COOLERS IN PLANS. |
| | C) COMMON USE FACILITIES NOTE #2A): |
| | CLARIFY MAX. LOW PROFILE. |
| | |
| | 8- SHEET A110: UL FIRE ASSEMBLY -L528. |
| | THERE ARE 13 DIFERENT SYSTEMS. |
| | INDICATE WHICH SPECIFIC SYSTEMIS THE |
| | ONE GOING TO BE INSTALLED TO CHECK |
| | COMPLIANCE IN PLANS. |
| | |
| | 9- SHEET A201: A) SPECIFY SAFETY GLASS |
| | AS REQUIRED BY SEC. R308.4 2004 FOR: |
| | * BATHROOM WINDOW. |
| | ** WINDOWS BY THE STAIRWAY ON END UNITS |
| | (NOTE: THIS APPLIES TO ALL UNIT TYPES |
| | THAT ARE AT THE END OF THE BUILDING AND |
| | HAVE WINDOWS BY THE STAIRWAY). |
| | *** WINDOW NEXT TO ENTRY DOOR AND |
| | WINDOW NEXT TO BALCONY DOOR. |
| | B) CLARIFY WHAT ARE THE GRAY SHADED |
| | WALLS FOR? |
| | C) CLEARLY IDENTIFY AREAS TO HAVE GRAB |
| | BARS REINFORCEMENT. DIMENSIONS ETC. |
| | |
| | 10- A) SPECIFY ATTIC ACCESS FOR ALL 2ND |
| | FLOOR UNITS. SEC. R807 2004. |
| | B) SPECIFY ATTIC ACCESS FOR 2ND FLOOR |
| | LEASING OFFICE. SEC. 1209 FBC 2004. |
| | |
| | 11- SHEET A202: A)PLANS ARE NOT LEGIBLE. |
| | THEY HAVE OVERLAPPING INFORMATION. |
| | REVISE AS REQUIRED. |
| | B) UNIT PLAN GENERAL NOTES: REVISE NOTE |
| | #6. ALL GROUND UNITS MUST COMPLY WITH |
| | THE FAIR HOUSING ACT. |
| | C) REVISE NOTE #17. OUTLETS TO BE NOT |
| | "LOWER" THAN 15", NOT "HIGHER" THAN 15". |
| | D) WHAT ARE THE GRAY SHADED WALLS FOR? |
| | THERE IS NOT LEGEND FOR THIS WALLS. |
| | (NOTE: THIS APPLIES TO ALL UNIT TYPES |
| | THROUGHOUT ALL DRAWINGS). |
| | E) SPECIFY SAFETY GLASS FOR ALL D |
| | WINDOWS. |
| | |
| | 12- SHEET A203: A) THE ACCESSIBLE UNIT |
| | IS THE LOWER ONE, NOT THE UPPER UNIT. |
| | REVISE AS REQUIRED. |
| | B) CLEARLY SPECIFY ALL AREAS TO HAVE |
| | REINFORCEMENT FOR GRAB BARS IN ALL |
| | BATHROOMS AND PROVIDE REINFORCEMENT |
| | DETAIL. (NOTE: THIS APPLIES TO ALL |
| | BATHROOMS IN ALL UNIT TYPES THROUGHOUT |
| | ALL DWGS). SPECIFY DIMENSIONS ETC. |
| | C) SPECIFY SILL HEIGHT OF WINDOW B TO |
| | VERIFY COMPLIANCE WITH SAFETY GLAZING. |
| | D) SPECIFY SAFETY GLAZING FOR WINDOW |
| | NEXT TO THE ENTRY DOOR AND WINDOW NEXT |
| | TO THE BALCONY DOOR. (NOTE: THIS APPLIES |
| | TO ALL UNIT TYPES SHOWN THROUGHOUT ALL |
| | DRAWINGS). SEC. R308.4 2004. |
| | E) SHOW DETAIL AT GROUND UNIT ENTRANCE |
| | SHOWING COMPLIANCE WITH ACCESSIBLE ROUTE |
| | AND ENTRY THRESHOLD HEIGHT. (NOTE: THIS |
| | APPLIES TO ALL GROUND UNITS AND TO |
| | ENTRANCE TO LEASING OFFICE AND COMMUNITY |
| | ROOMS). SEE FAIR HOUSING ACT AND CHAPTER |
| | 11 FBC 2004. |
| | |
| | 13- SHEET A204: CLOSET DOORS FOR |
| | SECONDARY BEDROOMS DON'T COMPLY WITH |
| | FAIR HOUSING ACT. SEE PAGE 3.15 FAIR |
| | HOUSING ACT. AND COMMENTS ON PLANS. |
| | |
| | 14- SHEET A205: A) SHOW THE 60"X60" |
| | CLEAR FLOOR SPACE AT UNIT ENTRY DOORS AS |
| | SPECIFIED ON H/C ACCESSIBLE UNIT NOTE |
| | #13. (NOTE: THIS APPLIES TO ALL UNIT |
| | TYPES SHOWN THROUGHOUT ALL DRAWINGS). |
| | B) UNIT C1: CLOSET DOORS FOR SECONDARY |
| | BEDROOMS DON'T COMPLY WITH FAIR HOUSING |
| | ACT. SEE PAGE 3.15 FHA. |
| | |
| | 15- PROVIDE SECTION DETAIL AND SPECS FOR |
| | 1HR FIRE RATED ASSEMBLY AT STAIRWAY FOR |
| | HORIZONTAL TENANT SEPARATION. |
| | |
| | 16- A) ALL ROOF PLANS TO SHOW |
| | FIREBLOCKING BETWEEN UNITS. |
| | B) ALL ROOF PLANS TO SHOW ATTIC |
| | VENTILATION CALCULATIONS AND VENTS SIZE |
| | AND LOCATION. |
| | |
| | 17- SHEET A302 ROOF FRAMING PLAN: |
| | SPECIFY 2 LAYERS OF UNDERLAYMENT FOR |
| | ROOF PITCH OF 2.25:12 AS REQUIRED BY |
| | SEC. R905.2.7 2004. |
| | |
| | 18- SHEET A304: A) ROOF PLAN: SHOW ROOF |
| | DRAINS. |
| | B) PROVIDE COMPLETE DETAILS/SPECS FOR |
| | WOOD TRELLIS. |
| | C) UPPER FLOOR PLAN IS NOT LEGIBLE. |
| | |
| | 19- SHEET A404: A) REVISE ELEVATION |
| | ORIENTATION. SEE SURVEY OR SITE PLAN FOR |
| | CORRECT ORIENTATION. NORTH, SOUTH ETC. |
| | B) ELEVATION #19 TO MATCH FLOOR PLAN. |
| | SEE COMMENTS ON PLANS. |
| | C) ELEVATIONS 04 AND 09: PROVIDE MORE |
| | INFORMATION TO DESCRIBE MATERIALS ON 2ND |
| | FLOOR OPENINGS BY STAIRWAY. SEE COMMENTS |
| | |
| | 20- SHEET A406: A) MISSING ONE |
| | ELEVATION. |
| | B) ELEVATION 09 IS MISSING INFORMATION. |
| | EG: LEASING OFFICE BEHIND. |
| | C) ELEVATION 11 AND 16 DON'T MATCH. |
| | CHECK TIE BEAM ELEVATION FOR SECOND |
| | FLOOR AT LEASING OFFICE AREA. |
| | D) SHINGLES CAN'T BE INSTALLED OVER 33' |
| | MEAN ROOF HEIGHT BUILDING. SEE |
| | LIMITATIONS ON PRODUCT APPROVAL. |
| | THEREFORE, LEASING OFFICE CAN'T HAVE |
| | SHINGLES. |
| | E) SPECIFY SIZE OF WINDOWS AT "DORMER" |
| | WITH CLERESTORY WINDOWS. SEE COMMENTS. |
| | F) CHECK TIE BEAM ELEVATION FOR STAIRS |
| | #2 AT LEASING OFFICE. |
| | |
| | 21- SHEET A500: A) DETAIL 06 AND 17 NEED |
| | TO MATCH. CHECK # OF GYP. BD. LAYERS. |
| | B) DETAIL 11 AND 17 NEED TO MATCH. T&G |
| | OR PLYWOOD DECKING. REVISE AS REQUIRED. |
| | C) DETAIL 17: FLOOR ASSEMBLY L-528 |
| | DOESN'T INCLUDE BATT INSULATION AS SHOWN |
| | ON DETAIL. REVISE AS REQUIRED. PROVIDE |
| | UL ASSEMBLY THAT INCLUDES INSULATION. |
| | D) WHERE IS ASSEMBLY UG05 SPECIFIED ON |
| | DETAIL 17. SEE COMMENTS ON PLANS. |
| | E) ROOF ASSEMBLY RC-2601 SPECIFIED ON |
| | DETAIL 17 DOESN'T INCLUDE INSULATION. |
| | REVISE AS REQUIRED. NEED ASSEMBLY THAT |
| | IS TESTED WITH INSULATION. |
| | F) PROVIDE DETAIL/SPECS FOR FIRE RATED |
| | ASSEMBLY UNDER STAIRS. |
| | G) SHOW FIREBLOCKING WHERE REQUIRED BY |
| | SEC. R602.8 2004. |
| | |
| | 22- SHEET A501: A) WALL SECTIONS TO |
| | MATCH STRUCTURAL PLANS. SEE STRUCTURAL |
| | PLANS FOR TRUSSES ORIENTATION. |
| | B) WALL SECTION 19: |
| | * BALCONY IS BUILD WITH CONCRETE. SEE |
| | STRUCTURAL DRAWINGS. |
| | ** SEE STRUCTURAL DWGS FOR RAKED BEAM |
| | SPECS. AND REVISE AS REQUIRED. |
| | C) PROVIDE COMPLETE DETAILS, SPECS AND |
| | DIMENSIONS FOR BALCONY HANDRAIL. SECTION |
| | R312 2004 RESIDENTIAL CODE. |
| | D) SPECIFY FIREBLOCKING MATERIAL AND |
| | LOCATION WHERE REQUIRED BY SEC. R602.8 |
| | |
| | 23- SHEET A502: A) PROVIDE COMPLETE |
| | STRUCTURAL DETAILS FOR ROOF OVERHAND ON |
| | WALL SECTION 16. |
| | B) SPECIFY FIREBLOCKING LOCATION AND |
| | MATERIAL IN ALL WALL SECTIONS. |
| | C) WALL SECTION 18: |
| | * BALCONY CONSTRUCTION TO MATCH |
| | STRUCTURAL DRAWINGS. |
| | ** NOTE REFERING TO FLOOR ASSEMBLY IS |
| | CALLING FOR ROOF. REVISE TYPO. |
| | *** PROVIDE COMPLETE STRUCTURAL DETAILS |
| | AND SPECS FOR CONSTRUCTION OF |
| | OVERLAPPING "DORMER" WITH CLERESTORY |
| | WINDOWS. |
| | **** PROVIDE COMPLETE DETAIL/SPECS FOR |
| | ROOF BEAM AT BALCONY. NOTE: STRUCTURAL |
| | DWGS CALL FOR RAKED BEAM. THIS IS NOT A |
| | RAKED BEAM. REVISE BOTH DRAWINGS TO |
| | MATCH. |
| | |
| | 24- SHEET A510: A) SPECIFY FIREBLOCKING |
| | MATERIAL AND LOCATION IN ALL SECTIONS. |
| | B) WHERE IS DETAIL 11/A500 SPECIFIED |
| | ON WALL SECTION 19? |
| | C) PROVIDE COMPLETE DETAILS/SPECS FOR |
| | BALCONY GUARDRAIL AS REQUIRED BY SEC. |
| | 1012 FBC 2004. |
| | D) PROVIDE SPECIFICATIONS FOR WINDOWS |
| | IN BALCONY AREA. PLANS DON'T PROVIDE ANY |
| | OF THIS INFORMATION. |
| | E) PROVIDE COMPLETE DETAIL/SPECS FOR |
| | WOOD BRAKET. SEE WALL SECTION 19. |
| | |
| | 25- SHEET A520: A) NEED TO PROVIDE 2 HR |
| | FIRE RATED FLOOR ASSEMBLY AS REQUIRED BY |
| | TABLE 302.3.2 FBC 2004. |
| | B) PROVIDE COMPLETE DETAILS/SPECS FOR |
| | WOOD TRELLIS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 26- SHEET A601: A) REVISE RISER AND |
| | TREAD DIMENSIONS TO COMPLY WITH SEC. |
| | R311.5.3.2 2004 RESIDENTIAL CODE. |
| | B) PROVIDE DETAILS/SPECS FOR |
| | INSTALLATION OF CANOPY AB0VE ENTRY DOOR. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| | |
| | 27- SHEET A602: A) DWGS ARE INCOMPLETE. |
| | ALSO, SHOW HANDRAILS AND TREAD AND |
| | RISER DIMENSIONS. |
| | B) DRAWINGS TO MATCH STRUCTURAL DWGS. |
| | C) CLARIFY CONSTRUCTION STAIRS. WOOD |
| | OR CONCRETE. SEE STRUCTURAL DRAWINGS. |
| | |
| | 28- SHEET A603: A) REVISE TREAD AND |
| | RISER DIMENSIONS TO COMPLY WITH SECTION |
| | R311.5.3.2. |
| | B) PROVIDE COMPLETE DIMENSIONS. EG: |
| | STAIR WIDTH. |
| | |
| | 29- SHEET A604: A) NEED ALL DIMENSIONS |
| | TO CHECK COMPLIANCE WITH CHAPTER 11 FBC |
| | 2004. |
| | B) REVISE NOSING ON DETAIL 02 TO COMPLY |
| | WITH SEC. 11-4.9.3 FBC 2004. |
| | C) HANDRAILS ENDS TO COMPLY WITH |
| | SECTION 11-4.9.4 FBC 2004. |
| | |
| | 30- SHEET A700.1: A) DETAIL 02: SEE |
| | FIGURE 38 CHAPTER 11 FBC 2004 AND REVISE |
| | AS REQUIRED. |
| | B) ROOM FINISH SCHEDULE: CLARIFY WHERE |
| | ARE THE MIRRORS ON STAIR #1. |
| | |
| | 31- SHEET A701.1: A) DETAIL 01: SPECIFY |
| | MULLION FASTENERS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | B) WINDOW DETAILS: SPECIFY FASTENERS |
| | FOR 2X BUCK. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | C) WINDOW SCHEDULE: CLARIFY WHICH |
| | BUILDING HAS WINDOW G?. SEE PLANS. ALSO, |
| | SIZE DOESN'T MATCH SIZE SHOWN ON WINDOW |
| | ELEVATIONS AT BOTTOM OF PAGE. |
| | |
| | 32- SHEET A702.1: A) SPECIFY FASTENERS |
| | FOR MULLION ABOVE DOOR. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | B) REVISE THRESHOLD DETAILS TO COMPLY |
| | WITH CHAPTER 11 FBC 2004 AND FAIR |
| | HOUSING ACT FOR ACCESSIBLE UNITS. |
| | |
| | 33- SHEET A703: DETAIL 03: WHERE IS |
| | DETAIL XX/XXXX?. |
| | B) DETAIL 13: WHERE IS DETAIL XX/XXXX. |
| | |
| | 34- SHEET A704: REVISE DETAIL 18. SEE |
| | STRUCTURAL PLANS FOR TYPE OF FLOOR |
| | CONSTRUCTION. |
| | |
| | 35- SHEET A705: A) DETAIL 02: REVISE |
| | FASTENER SPACING. |
| | B) DETAIL 03: REVISE SHINGLES |
| | INSTALLATION. SEE PRODUCT APPROVAL. |
| | C) REVISE DETAIL 17. SEE RIDGE VENT |
| | PRODUCT APPROVAL. |
| | D) DETAIL 18: SPECIFY THICKNESS OF OSB |
| | DRAFTSTOP. |
| | E) SPECIFY ATTIC VENTILATION SIZE AND |
| | LOCATION. SEC. R806. |
| | |
| | 36- SHEET A706.1: REVISE CLEARANCE |
| | REQUIRED BETWEEN HOOD AND RANGE ON |
| | DETAIL 08. SEE HOOD SPECIFICATIONS. |
| | |
| | 37- SHEET A707: A) PROVIDE DIMENSIONS ON |
| | ELEVATIONS WHERE REINFORCING IS |
| | REQUIRED FOR GRAB BARS. |
| | B) PROVIDE COMPLETE BLOCKING |
| | DETAILS/SPECS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 38- SHEET A801: A) SPECIFY SAFETY GLASS |
| | FOR WINDOW NEXT TO DOOR IN THEATRE. |
| | SEC. 2406 FBC 2004. |
| | B) PROVIDE ATTIC ACCESS. SEC. 1209.2 |
| | FBC 2004. |
| | C) STAIR #1: WIDTH OF STAIRS CAN'T BE |
| | REDUCED. REVISE AS REQUIRED. |
| | D) SHOW WINDOWS ON 2ND FLOOR PLAN BY |
| | MULTI-PURPOSE ROOM. |
| | E) PROVIDE COMPLETE DETAILS/SPECS FOR |
| | ELEVATOR. SEC 106.1.2 CITY AMENDMENTS TO |
| | FBC AND CHAPTER 11 FBC 2004. |
| | F) COMPLETE INFORMATION AT BALCONY |
| | AREA. MISSING GUARDS, ETC. |
| | G) NEED MAX. OCCUPANT LOAD SIGN. |
| | |
| | 39- SHEET A802: A) COMPLETE DRAWINGS TO |
| | 100%. PROVIDE DIMENSIONS, THRESHOLD,ETC. |
| | B) COMPLETE DETAIL 04. GRAB BARS, ETC. |
| | C) HANDRAIL DON'T COMPLYWITH SEC. |
| | 11-4.9.4 FBC 2004. |
| | D) PROVIDE CORRECT NAME FOR EACH STAIR. |
| | STAIR #1 ND #2. BOTH ARE NAMED STAIR #1. |
| | REVISE AS REQUIRED. |
| | |
| | 40- SHEET A810: A) NEED MAX. OCCUPANT |
| | LOAD SIGN. |
| | B) SPECIFY SAFETY GLASS FOR WINDOWS |
| | NEXT TO DOORS. SEC. 2406.3 FBC 2004. |
| | C) SHOW THRESHOLD FOR H/C ACCESS. |
| | D) DETAIL 09: PROVIDE COMPLETE |
| | INFORMATION INCLUDING, GRAB BARS SIZES, |
| | LOCATION AND REINFORCEMENT. |
| | E) WHERE IS THE DOOR SCHEDULE FOR ENTRY |
| | DOORS. |
| | |
| | 41- SHEET S-1.1: A) 90% COMPLETE |
| | DRAWINGS. PROVIDE 100%COMPLETE DWGS. |
| | THIS COMMENT APPLIES TO ALL STRUCTURAL |
| | DRAWINGS. |
| | B) GROUND UNITS NEED TO BE ACCESSIBLE. |
| | REVISE DROP AT ENTRY OF UNITS. |
| | COORDINATE WITH ARCHITECTURAL DRAWINGS. |
| | ***NOTE: THIS COMMENT APPLIES TO ALL |
| | BLDG TYPES. REVISE ALL DRAWINGS WITH |
| | GROUND UNITS AS REQUIRED. |
| | C) 2ND FLOOR FRAMING PLAN: REVISE |
| | CONNECTOR SPECIFIED ON NOTE #1 FOR |
| | GIRDER TRUSS. NEED TO SPECIFY A WOOD TO |
| | MASONRY CONNECTOR. CONNECTOR SPECIFIED |
| | IS A WOOD TO WOOD CONNECTOR. |
| | ***NOTE: THIS COMMENT APPLIES TO ALL 2ND |
| | FLOOR FRAMING PLANS IN ALL BUILDING |
| | TYPES. REVISE THIS NOTE IN ALL DRAWINGS |
| | AS REQUIRED. |
| | |
| | 42- SHEET S-1.2. ROOF FRAMING PLAN. |
| | REVISE TYPE OF BEAM SPECIFIED FOR LITTLE |
| | FLAT ROOF ABOVE SOME ENTRY AREAS. FLAT |
| | ROOF DON'T HAVE RAKED BEAM TB-1. THIS |
| | COMMENT APPLIES TO ALL BUILDING TYPES |
| | WITH FLAT ROOF INSTEAD OF GABLE ROOFS. |
| | |
| | 43- SHEET S-1.4: A) SPECIFY CONNECTORS |
| | FOR ROOF TRUSSES. |
| | B) WOOD EXTERIOR STAIRS OR CONCRETE |
| | STAIRS. ARCHITECTURAL DWGS AND |
| | STRUCTURAL DRAWINGS TO MATCH AND PROVIDE |
| | COMPLETE STRUCTURAL DETAILS/SPECS. |
| | C) FOOTING F20.12 FOR STAIRS IS NOT IN |
| | THE FOOTING SCHEDULE. PROVIDE INFO. |
| | D) GROUND FLOOR NEEDS TO BE ACCESSIBLE |
| | TO COMPLY WITH CHAPTER 11 FBC 2004. |
| | |
| | 44- SHEET S-1.5: MISSING COLUMN SCHEDULE |
| | AND TOP AND BOTTOM COLUMN CONNECTIONS |
| | FOR INTERIOR COLUMNS. THIS COMMENT |
| | APPLIES TO ALL BUILDING TYPES. |
| | |
| | 45- SHEET S-1.6: A) LEASING OFFICE AND |
| | GOUND UNITS NEED TO BE ACCESSIBLE TO |
| | COMPLY WITH CHAPTER 11 FBC 2004 AND FAIR |
| | HOUSING ACT. FOUNDATION PLAN NEED TO BE |
| | REVISED ACCORDINGLY TO SHOW |
| | ACCESSIBILITY. |
| | B) STAIR #2 TO MATCH ARCHITECTURAL |
| | DWGS. CHECK LOCATION OF FIRST RISER |
| | GOING DOWN FROM 2ND FLOOR. |
| | C) PROVIDE COMPLETE 2ND FLOOR FRAMING |
| | PLAN. SHOW TRUSS GIRDERS AROUND STAIR |
| | OPENINGS. |
| | D) SPECIFY ALL LIVE AND DEAD LOADS. |
| | |
| | 46- SHEET S-2.1: A) TRUSS TIE DOWN |
| | SCHEDULE. REVISE SPECS FOR CONNECTORS C |
| | AND G TO MATCH MANUFACTURER'S PUBLISHED |
| | VALUES. EG CONNECTOR TYPE, EMBEDMENT AND |
| | UPLIFT VALUES. OTHERWISE, PROVIDE |
| | COMPLETE ENGINEERING ANALYSIS TO SHOW |
| | WHY SPECS WERE CHANGED. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | ***NOTE: THIS COMMENT APPLIES TO ALL |
| | STRUCTURAL DRAWINGS WITH THE TRUSS TIE |
| | DOWN SCHEDULE. REVISE ALL OF THEM. |
| | B) REVISE DESIGN LOAD SCHEDULE FOR |
| | LEASING OFFICE. SEE TABLE 1607.1 FBC |
| | 2004. MAKE SURE CLEAR SPECIFICATIONS ARE |
| | DONE FOR MULTIFAMILY UNITS AND FOR |
| | LEASING OFFICE AND COMMUNITY BUILDING. |
| | |
| | 47- SHEET S-2.6: A) REVISE TIE BEAM |
| | ELEVATION FOR LEASING OFFICE AREA. |
| | ARCHITECTURAL DRAWINGS AND STRUCTURAL |
| | DRAWINGS TO MATCH. |
| | B) PROVIDE TIE BEAM ELEVATION FOR STAIR |
| | #2. CHECK ARCHITECTURAL DRAWINGS. |
| | |
| | 48- SHEETS S-4.1 THRU S-4.4: DRAWINGS |
| | ARE NOT LEGIBLE. ELEVATION ARE TOO |
| | LIGHT. SAME COMMENT APPLIES TO SHEETS |
| | S-5.6, S-5.8, S-6.5, S-6.7 AND S-6.10. |
| | |
| | 49- LEASING OFFICE: SPECIFY FIRE RATING |
| | ON INTERIOR DOOR AND WINDOWS AND PROVIDE |
| | PRODUCT APPROVALS AS REQUIRED. |
| | |
| | 50- BEFORE APPLYING FOR BUILDING PERMITS |
| | COORDINATE WITH HAROLD PISKURA, |
| | INSPECTION SERVICES MANAGER, IF SPECIAL |
| | INSPECTOR WILL BE REQUIRED/DESIRED TO |
| | MAKE SURE THERE IS NOT CONFLICT BETWEEN |
| | INSPECTIONS AND PROGRESS OF WORK. IF |
| | SPECIAL INSPECTOR IS REQUESTED, THEN 3 |
| | COMPLETE SETS OF CONSTRUCTION DOCUMENTS |
| | ARE REQUIRED TO BE SUBMITTED. |
| | |
| | 51- PROVIDE COMPLETE SET OF TRUSS |
| | DRAWINGS FOR REVIEW. TRUSS PACKAGE TO BE |
| | REVIEWED AND APPROVED BY ENGINEER OF |
| | RECORD PRIOR TO SUBMITTAL. |
| | |
| | 52- ALL APPARTMENT UNITS WITH WINDOW |
| | TYPE B NEED TO SPECIFY WINDOW SILL TO |
| | VERIFY COMPLIANCE WITH SAFETY GLASS. |
| | |
| | 53- TYPE VI IS AN SPRINKLERED BUILDING. |
| | NEED SEPARATE PERMIT APPLICATION FOR |
| | SPRINKLER SYSTEM. BUT, NEED TO PROVIDE |
| | SPRINKLER HEAD LAYOUT FOR REVIEW ALONG |
| | WITH PERMIT APPLICATION FOR THIS BLDG. |
| | |
| | 54- ALL PRODUCT APPROVALS NED TO BE |
| | REVIEWED AND APPROVED IN WRITTING BY |
| | DESIGNER OF RECORD AS REQUIRED BY SEC. |
| | 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | TYPICALLY THIS IS DONE USING THE |
| | STANDARD REVIEW AND APPROVE STAMP. |
| | |
| | 55- PROVIDE ALL FLORIDA OR LOCAL PRODUCT |
| | APPROVALS AS REQUIRED BY RULE 9B-72. GO |
| | TO WWW.FLORIDABUILDING.ORG TO REVIEW AND |
| | DOWNLOAD ALL PRODUCT APPROVALS. PROVIDE |
| | FLORIDA COVER PAGE AND SPECIFIC DADE |
| | COUNTY NOA OR DRAWINGS THAT WERE |
| | SUBMITTED TO OBTAIN THE FLORIDA PRODUCT |
| | APPROVAL. |
| | ***NOTE: PROVIDE ONLY PRODUCT APPROVALS |
| | FOR PRODUCT TO BE USED. EG: THERE ARE |
| | NOT SLIDING GLASS DOORS IN THESE PLANS. |
| | A) FLAT ROOF SYSTEM. CLEARLY IDENTIFY |
| | SPECIFIC APPROVED ASSEMBLY TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH |
| | GENERAL LIMITATION #7 OR #9. SEE GENERAL |
| | LIMITATION ON LAST PAGE OF NOA. ALSO, |
| | SEE ATTACHED COPY OF CITY POLICY FOR |
| | ROOFING PERMITS. |
| | NOTE: GENERAL LIMITATION #7 REQUIRES |
| | CALCULATIONS FOR PERIMETER AND CORNER |
| | AREAS NAIL ENHANCEMENT. PROVIDE THEM. |
| | B) SHINGLES. PROVIDE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE. GO TO WEBSITE |
| | WWW.FLORIDABUILDING.ORG TO DOWNLOAD IT. |
| | ALSO, REVISE ARCHITECTURAL DETAIL TO |
| | MATCH PRODUCT APPROVAL. |
| | C) 2HR FIRE RATED CONCRETE BLOCK. |
| | D) STRUCTURAL MULLIONS SPECIFIED FOR |
| | WINDOWS AND DOORS. SEE PLANS. AND |
| | CLEARLY IDENTIFY SPECIFIC ANCHORS TO BE |
| | USED. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | E) STORM SHUTTERS WITH KEY PLAN AND |
| | COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE. (WHY SUBMITTING 2 |
| | DIFFERENT MANUFACTURER'S). |
| | F) ALL STRUCTURAL CONNECTORS SPECIFIED |
| | ON PLANS. SEE TRUSS ANCHOR SCHEDULE AND |
| | ALL SECTIONS AND DETAILS. |
| | G) TYPE OF SIDING SPECIFIED ON PLANS. |
| | H) APARTMENT UNITS ENTRY DOORS. |
| | I) LEASING OFFICE ENTRY DOORS. |
| | J) LEASING OFFICE STAIR #2 EXT. DOOR. |
| | K) COMMUNITY ROOM ENTRY DOORS. |
| | L) COMMUNITY ROOM FIXED WINDOWS. |
| | M) ALL OTHER FIXED WINDOWS. |
| | N) FRENCH DOORS AT LEASING BUILDING. |
| | O) FRENCH DOORS ON BALCONIES AT 2ND |
| | STORY APARTMENT BUILDINGS. |
| | P) SINGLE HUNG WINDOWS. |
| | Q) ROOF RIDGE VENT. AND REVISE |
| | ARCHITECTURAL DETAIL TO MATCH PRODUCT |
| | APPROVAL). |
| | |
| | NOTES: * PROVIDE ONLY PRODUCT APPROVALS |
| | THAT APPLY TO EACH BUILDING WHEN |
| | APPLYING FOR BUILDING PERMIT. |
| | ** CLEARLY IDENTIFY PRODUCT APPROVALS. |
| | EG: LEASING OFFICE DOOR. TO EXPEDITE |
| | REVIEW PROCESS. |
| | *** COORDINATE SHUTTERS INSTALLATION |
| | WITH ITEM #56. SOME WINDOW/DOOR PRODUCT |
| | APPROVALS WILL REQUIRE IMPACT GLASS. |
| | |
| | 56- INSTALLATION OF STORM PANELS FOR |
| | LARGE BUILDINGS NEED THE APPROVAL IN |
| | WRITTING BY THE BUILDING OFFICIAL. SEE |
| | ITEMS 13 AND 14 OF ATTACHED COPY OF CITY |
| | IMPLEMENTATION STANDARD FOR WIND-BORNE |
| | DEBRIS IMPACT PROTECTION. |
| | |
| | 57- PROVIDE SPECIFICATIONS FOR DOOR |
| | HARDWARE AT ACCESSIBLE UNITS, LEASING |
| | OFFICE AND COMMUNITY ROOM. |
| | |
| | 58- PROVIDE COMPLETE DETAILS AND SPECS |
| | SHOWING COMPLIANCE WITH SEC. 1207 FBC |
| | 2004 FOR SOUND TRANSMISSION. |
| | |
| | 59- PROVIDE COMPLETE DETAILS/SPECS AND |
| | STRUCTURAL DETAILS FOR LEASING OFFICE |
| | ELEVATOR. |
| | |
| | 60- PLEASE RETURN REVIEWED SET AFTER |
| | CORRECTIONS ARE DONE TO ORIGINAL |
| | DRAWINGS TO EXPEDITE REVIEW PROCESS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |