| 2006-06-05 00:00:00 | |
| | *** PROVISO *** |
| | PER 2004 FBC, FUEL GAS - POWERED |
| | EQUIPMENT - PERMANENTLY INSTALLED |
| | EQUIPMENT POWERED BY INTERNAL COMBUSTION |
| | ENGINES SHALL BE INSTALLED IN ACCORDANCE |
| | WITH MANUFACTURE'S INSTALLATION |
| | INSTRUCTIONS AND NFPA 37. |
| | |
| | NFPA 37 INSTALLATION & USE OF STATIONARY |
| | COMBUSTION ENGINES & GAS TURBINES: |
| | 4.1.4ENGINES (GENERATORS) LOCATED |
| | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM |
| | OPENINGS IN WALLS & AT LEAST 5 FT FROM |
| | STRUCTURES HAVING COMBUSTIBLE WALLS.A |
| | MINIMUM CLEARANCE IS NOT REQUIRED WHEN |
| | (1) THE ADJACENT WALL HAS A MINIMUM FIRE |
| | RESISTANCE RATING OF 1 HOUR OR (2) THE |
| | WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| | NON-COMBUSTIBLE MATERIALS, AND IT HAS |
| | BEEN DEMONSTRATED THAT A FIRE WITHIN THE |
| | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| | MATERIALS OUTSIDE THE ENCLOSURE. |
| | A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT |
| | TERMINATE UNDER STRUCTURES OR WHERE THE |
| | EXHAUST MIGHT BE DRAWN INTO THE |
| | VENTILATION INTAKES. |
| | |
| | 2004 FMC 804.3.5 #3, WHERE THE |
| | TERMINATION IS LOCATED BELOW AN ADJACENT |
| | ROOF STRUCTURE, THE TERMINATION POINT |
| | SHALL BE LOCATED AT LEAST 3 FT FROM THE |
| | ROOF STRUCTURE. |
| | |
| | PLEASE NOTE, WHILE ZONING ALLOWS |
| | MECHANICAL EQUIPMENT TO ENCROACH 4 FT |
| | INTO THE SETBACK, GENERATORS SHALL |
| | MAINTAIN THE REQUIRED ABOVE MENTIONED |
| | CLEARANCES TO THE ADJACENT PROPERTY |
| | STRUCTURES, I.E. FENCE, BUILDING, |
| | WINDOWS, DOORS, OR OPENINGS. |
| | |
| | PROVIDE MANUFACTURE'S INSTALLATION |
| | INSTRUCTIONS AT THE JOBSITE FOR THE |
| | FIELD INSPECTOR. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |